1. Please read the instruction carefully before you use, please retain it for reference.
2. The picture is only for reference , please prevail in kind
Contents
1. Introduction…….…………………………...……………………..……...1
2. Product overview...……….…………………….….………….…….….2
3. Installation and dimension ……………….…….………....……….….3
3.1 Installation………..………………………………………………………3
3.2 DPT63 …………....……………………………………….…...….…….3
3.3 DPT160……..………......…………………….….……….…….……….4
3.4 DPT250………..………….………………….……..………...…..….....5
4. Operating…….………………….……………..………….….………….7
4.1 Manual operation……………………………………...……..……...….7
4.2 Electrical operating/Manual Mode………………………….......…….8
4.3 Electrical operating/Automatic Mode …..……………………….…....8
4.4 Locking………………………….……………………....….………..…..9
5. Control Unit……………….….………………………....…….......…...10
5.1 Function introduction…….…..………………..……..………....…….10
5.2 Interface ………………..…………….….……….……..……....…….10
5.3 Operation Mode setting....... ……………...................……....……..11
5.4 Function and threshold setting….………………….....…….…..…..12
6. Connections.………………………………………………...…………15
6.1 Main circuit connections.………………….…..………….……...…...15
6.2 Control circuit connections.………….……………….….…..…....….15
7. Maintenance and Troubleshooting…….………...……….……....…15
7.1 Maintenance………………..…...….………………..….………....….15
7.2 Troubleshooting….………...……………………….….…..……...…..16
1.Introduction
This manual describes the installation and the basic operation of the automatic
transfer switches.
Use of symbols
Hazardous voltage: warns about a situation where a hazardous voltage may cause
physical injury to a person or damage to equipment.
General warning: warns about a situation where something other than electrical
equipment may cause physical injury to a person or damage to equipment.
-1-
2. Product overview
Automatic transfer switch (class CB)is used to ensure power supply for different
occasions . You can operate the automatic transfer switch either electrically or
manually.
1. primary line
2. changeover switch
3. handle for manual operation
4. secondary line
5. control unit
6. control unit connecting wiring
You can choose Type CB010 or CB011 control unit for each type of changeover
switch.
-2-
3. Installation and dimension
3.1 Installation
The recommended mounting positions for automatic transfer are horizontal, wall
mounted or table mounted.
Do not install the Automatic transfer switches in any position than those described
above.
M6×50
3.5...4Nm
×
139
129
113
120
102
80
215
195
185
37.5
122
= =
4- 6.5
144 186
435
455
-3-
3.3 Type DPT160
M6×50
3.5...4Nm
M6 ×4
0
148
138
131
122
111
215
195
185
80
37.5
122
=
4- 6.5
165 216
490
510
-4-
3.4 Type DPT250
3.4.1 Installation
M6×50
3.5...4Nm
M6 ×4 0
148
138
131
205
185
80
37.5
122
= =
4- 6.5
205
410
430
-5-
3.4.2 Installation for Control unit
The installation and dimension for control unit CB010 and CB011 are the same.
93 93
83 82
36 35 34 33 32 31 30 29 28 27 26 25 24 23
Q1
Q2
Q1
Q2
197
185
-
+
22 21 20 19 18 17 16 15 14 13
4- 4.5
Avoid to attach or insert terminals when the terminal voltage 380V a.c
13 14 15 16 17 18 19 20 21 22
12 V Q2T Q1T Q2O Q2C Q1O Q1 C Q2 K Q1 K
1 2 3
S W2 SW1 M
-6-
4. Operating
Never open any covers on the product. There may be dangerous external control voltages
inside the automatic transfer switch even if the voltage is turned off.
Never handle control cables when the voltage of the automatic transfer switch or external
control circuits are connected.
You must operate automatic transfer switch manually before the voltage is connected.
c. Attach the handle by pressing it to the changeover switch until it clicks into place
When mechanism is not parked on ON/I,OFF,ON/II position base on severe
abnormalities. You need to tap the handle to make it to the right place, and operate
the switch manually.
Remark: you need to press the handle and the mechanism and motor off.
-7-
4.2 Electrical operation/Manual Mode
Electrical operation is means that turn the knob to sent a signal to operate
changeover switch, U1 colse;U1,U2 open; U2 close.
a.Release the handle from the changeover switch panel by pressing down the
locking latch under the switch panel and pulling the handle off.
-8-
4.4 Locking
4.4.1 Locking the electrical operation
You can lock the electrical operation in all position(I,O,II).
a.Pull up the locking latch under the changeover switch panel.
b.Place the padlock under the latch .
5... 6
-9-
5. Control unit
Control unit must be disconnected from the main circuit during the insulation test.
Base on the difference function configuration, we have CB010 and CB011 for you to
choose.
5.1 Function introduction
CB010 CB011
Under-voltage transfer ×
Over-voltage transfer ×
Phase missing transfer
Delay time setting(s) 1.5 0,3,5,10,15,20,30
Refusing to perform alarm
Release alarm
Phase missing alarm
Over-voltage alarm ×
N pole mistake alarm
Fire fighting
Generator start function ×
5.2 Interface
power state
changeover
switch state
alarm type
alarm alarm
UV
ON
70 90
U1
working mode 1
1 OV
working mode
11 0 130
selection 5
RESET
10
15
UV
selection
3 20 70 90
0 30 U2 OV
T1
10
5 15
3 20
110 130
0 30 Ue%
T2
- 10 -
5.3 Control unit Operation Mode setting
The setting is activated after the botton lasts more than 1 second in the right position.
The function mode setting must be on automatic mode,and the function mode is
activated after pressing reset botton.
No line priority
ON
Knob
U1 priority 1
- 11 -
U1 priority/No line priority U1 priority/Manual back switching
3 20 70 90 3 20 70 90
0 30 U2 OV 0 30 U2 OV
T1 T1
10 10
5 15 5 15
3 20 110 130 3 20 110 130
0 30 Ue% 0 30 Ue%
T2 T2
UV
ON
U1 under-voltage setting
70 90
U1
1 OV
1
110 130
UV
RESET
10
5 15 U2 under-voltage setting
3 20 70 90
0 30 U2 OV
T1
10
5 15
3 20 110 130
0 30 Ue%
T2
2.Over-voltage transfer
When UI has over-voltage fault ,control unit sent a signal to transfer to U2.
The value of over-voltage threshold is adjustable ,the range:110%~130% Ue.
When control unit detects the over-voltage fault of U1 and U2 at the same time,
control unit will sent a signal to transfer to O position.
UV
ON
70 90
U1
1 OV
1 U1 over-voltage setting
110 130
UV
RESET
10
5 15
3 20 70 90
0 30 U2 OV
T1
10
5 15 U2 over-voltage setting
3 20 110 130
0 30 Ue%
T2
- 12 -
3. Phase missing transfer
When UI has phase missing fault,control unit sent a signal to transfer to U2.
When control unit detects phase missing fault of U1and U2 at the same time,control
unit will sent a signal to transfer to O position.
Motor operator is not working when A phase and C phase missing at the same time.
UV
ON
70 90
U1 OV
1
1
110 130
UV
RESET
10
5 15
T1 3 20 70 90
0 30 U2 OV
T1
10
5 15
T2 3 20 110 130
0 30 Ue%
T2
5.Alarm
When control unit sent a conversion signal,the change-over switch execute command
failed,then control unit stops to sent a conversion signal and sent a alarm signal.
Control unit CB010 Fault light and alarm light blink, and has an alarm sound.
Control unit CB011 Refusing to perform light and alarm light blink, and has an alarm
sound.
You need to press the reset botton to reset to automatic mode of control unit after
waiting to the failure relieved.
- 13 -
6.Trip alarm
When the load failure cause breaker tripped:
Control unit CB010 fault light and alarm light blink, and has an alarm sound.
Control unit CB011 tripped light and alarm light blink, and has an alarm sound.
10.Fire fighting
When fire control centre sent a fire signal to control unit, control unit will sent a
conversion signal to transfer the switch to O position.And alarm light blink,has an
alarm sound. Connections shown in Section 7.
You need to press the reset botton to reset the automatic mode after fire
fighting relieved.
The signal send by fire control centre should be 24V d.c., more than 1
second.
- 14 -
6. Connection
6.1 Main circuit connections
2P 3P 4P
- +
Terminals 36 35 34 33 32 31 30 29 28 27 26 25 24 23 *terminal 23,24 for customers connecting 24V d.c. fire signal that lasts more than 1 second is activate.
terminal 25~36:passive contacts for customers connecting, Control unit CB010 do not have generator start function.
for (3A/250V a.c.,3A/28V d.c.)
customers
24V d.c.
SW2 SW1 M U2C U2B U2A U2N U1N U1A U1B U1C
1 2 3 4 5 6 7 8 9 10 11 12
4P
22 21 20 19 18 17 16 15 14 13
22 21 20 19 18 17 16 15 14 13
Terminals
on U2C U2B U2A U2N U1N U1A U1B U1C
3P
DPT
22 21 20 19 18 17 16 15 14 13
SW2 SW1 M U2C U2B U2A U2N U1N U1A U1B U1C
2P
22 21 20 19 18 17 16 15 14 13
1 2 3
U2 connection U1 connection
- 15 -
7.2 Troubleshooting
S/N state analysis action
1.Cables are not connected terminals 1.Check it and connect it again
Power supply normally, the 2.The cable has loosen which it was 2.Check it and plug in again
1
controller without any display connected controller and changeover
switch.
1.Control unit or changeover switch is 1.Change to automatic Mode or
on manual state, or electrical relieve electrical locking or
locking ,or handle mounted. remove the handle
2.Terminal loose 2.Check it and plug in again
3.Fuse is broken 3.Change fuse
4.delay time setting is wrong 4.Modify the delay time setting
Controller is connected, but it 5.Fire fighting signal input to controller 5.Cancel the fire fighting signal
2 6.Voltage is out of the normal range 6.Check voltage, make sure the
can not automatic transfer.
voltage range in 70% ~130%.
1.fire fighting is not 24V d.c. Please input the correct fire
2.fire fighting signal is in wrong polarity fighting signal, it must be
5 Fire fighting fault
3.fire fighting signal lasts less than 1 24V.d.c.and last more than 1
second second.
- 16 -