Professional Documents
Culture Documents
Dash 8 q200 - ATA - 21 - Air - Conditioning
Dash 8 q200 - ATA - 21 - Air - Conditioning
Chapter
21
AIR CONDITIONING
© Jazz Air LP, 2008. All rights reserved. No part of these materials may be reproduced, stored in any material form
(including photocopying or storing on any medium by electronic means) without the prior written permission of the
copyright holder, except in accordance with the provisions of the Copyright Act. The doing of any unauthorized act in
relation to a copyright work may result in a civil claim for damages and/or criminal prosecution.
deHavilland Dash 8 100/300 21 - AIR CONDITIONING
THIS PAGE INTENTIONALLY LEFT BLANK
Selecting the BLEED switch on the air conditioning panel When either engine upstream high pressure bleed air
to BLEED causes the pressure regulator and shut−off reaches 55 + or − 1.5 psig, the associated high pressure
valve to be deenergized open and provides 28 V dc to switch contacts open and disconnects the ground from
the solenoid of time delay relay K3, via the normally time delay relay K3 and (if Mod 8/0496 is embodied) the
closed contacts of the HP bleed control relay K1. On de−ice time delay relay 3010−K2. Time delay relay K3
aircraft with Mod 8/0496, power via the same source is contacts changeover to deenergize both high pressure
also applied to the solenoid of the de−ice time delay relay shut−off valves closed and (if Mod 8/0496 embodied)
Figure 6 – Operation
Oct. 1/2009 - © Jazz Air LP Page 21
Pressure Sensing Control If a high flow rate is desired, as selected on the BLEED
flow control on the air conditioning panel, the torque
The pressure sensing control consists of four pneumatic motor is positioned to vent a large amount of servo
inputs to a summing bar which controls air pressure pressure overboard. The remaining servo pressure
venting to establish the ‘open’ side pressure. These acts on the servo actuator which is positioned to vent
inputs are: a minimum amount of air pressure from the ‘open’ side
●●An actuator sensing pressure downstream of the of the pneumatic actuator. The remaining air pressure
valve. overcomes the spring force to drive the butterfly valve
●●A stabilizer unit, connected via a restricted line. towards the open position.
Figure 8 – PRSOV (1 OF 2)
Oct. 1/2009 - © Jazz Air LP Page 25
Figure 9 – PRSOV (2 OF 2)
Oct. 1/2009 - © Jazz Air LP Page 27
Operation
With both the left and right main gear weight on wheels,
selecting the control switch to FC FAN energizes the fan
control relay K1 to complete the circuit between the 28
V dc right secondary bus and the fan. With either main
gear weight off wheels, the relay is deenergized to open
the circuit to the fan. The ground to the relay is applied or
removed through the proximity switch electronic unit.
NOTE: When Mod 8/1538 is incorporated, the flight
compartment fan is removed.
Figure 18 – Pressurization
Oct. 1/2009 - © Jazz Air LP Page 49
On aircraft incorporating Mod 8/0140 silencers are The condenser/mixer consists of a condenser with a
installed in the supply ducts downstream of the pack water trap, and a mixing box. The condenser extracts
temperature control valves and temperature trim valves moisture from the air where it is collected in the water
to reduce air noise in the ducts. trap and routed, through a filter, to a water nozzle in
the heat exchanger ram air inlet. A second water trap
Temperature of the air supplied by the pack is controlled downstream of the first, collects any moisture missed by
either automatically or manually from the air conditioning the first trap.
panel in the flight compartment.
The mixing box allows for uniform temperature by
In the event the air conditioning pack fails, ram air blending ACM discharge air (along with bypassed hot
is supplied to the cabin and flight compartment for bleed air) with recirculated cabin air.
ventilation.
Pack Temperature Control Valves
Description The pack temperature control valves consist of two
The air conditioning pack consists of an air cycle valves connected in parallel and operated by a single
machine (ACM), a heat exchanger, a condenser/mixer, actuator. One valve is located in a hot air duct from
electrically−operated pack temperature control valves the engine bleed air system and regulates the amount
and a compressor discharge overtemperature switch. of bleed air to bypass the ACM. The second valve is
located in the duct from the primary heat exchanger and
Figure 25 – Cooling
Oct. 1/2009 - © Jazz Air LP Page 63
Figure 31 – Condensor/Mixer
Oct. 1/2009 - © Jazz Air LP Page 75
In the manual mode, the flight compartment manual/ If the cabin or flight compartment supply duct air
auto switch on the air conditioning panel is positioned temperature exceeds 88 degrees C (190 degrees F) a
at MANUAL and the required temperature is duct overtemperature switch closes with the following
obtained by adjusting the flight compartment manual results:
temperature control selector switch between COOL ●●An electrical circuit is completed through the switch
and WARM. Selecting the flight compartment manual/ to the master caution control box and a DUCT HOT
auto switch to MANUAL energizes the auto/manual caution light comes on.
relay K2 to initiate the following functions: ●●The duct overheat relay K3 or K4 is energized.
●●Isolate the hot and cold command signals from the
Energizing the duct overheat relay K3 or K4 initiates the
flight compartment temperature controller to the
following functions:
trim valve actuator in the supply duct.
●●The auto/manual relay K1 or K2 is energized to
●●Complete the COOL and WARM electrical
isolate the automatic hot and cold commands from the
circuits between the flight compartment manual
cabin or flight compartment temperature controller to
temperature control selector switch and the trim
the associated valve actuator.
valve actuator.
●●An electrical circuit is completed to provide a direct
●●With the electrical circuits complete, direct signals
COOL signal to the associated valve actuator. This
are sent to the actuator to position the valves as
signal causes the actuator to reposition its valves to
determined by the selection made at the flight
operate the refrigeration pack in the full cold mode.
compartment manual temperature control selector
switch.
21
AIR CONDITIONING
© Jazz Air LP, 2008. All rights reserved. No part of these materials may be reproduced, stored in any material form
(including photocopying or storing on any medium by electronic means) without the prior written permission of the
copyright holder, except in accordance with the provisions of the Copyright Act. The doing of any unauthorized act in
relation to a copyright work may result in a civil claim for damages and/or criminal prosecution.
deHavilland Dash 8 100/300 21 - AIR CONDITIONING
DHC-8 300 (Differences)
Pressurization
Exhaust air from the cabin and flight compartment is
metered through two outflow valves inthe rear pressure
dome.
Figure 50 – PRSOV
Oct. 1/2009 - © Jazz Air LP Page 119
Figure 52 – Distribution
Oct. 1/2009 - © Jazz Air LP Page 123
Description
The pressurization system consists of two normal and
one safety outflow valves, a control unit with selector
panel, an indicator panel, a cabin pressure controller, a
forward dump manual selector, and a venturi ejector.
Outflow Valves
Two identical normal outflow valves are located on the
rear pressure dome. The right valve is the main or master
valve and is the only valve that has the torque motor
receiving electrical commands from the cabin pressure
controller. The left valve is the auxiliary or slave valve. It
has a torque motor which is not connected to the cabin
controller but the valve is connected pneumatically to
the master valve and instantly follows its positions as
commanded by the cabin pressure controller. Both valves
consist of a torque motor, poppet/diaphragm assembly,
spring, outer dome and differential limiter. The valves are
The cooling system consists of two air conditioning packs Each assembly consists of an annular mixing chamber in
mounted in tandem in the rear fuselage aft of the rear which recirculated air is blended with ACM discharge and
pressure dome. The forward pack is the number 2 pack; bypass bleed air, before flowing accross the condenser
it supplies the flight compartment and gasper systems (low pressure pass). Each condenser high pressure pass
with conditioned air. The rear pack, or number 1, supplies has a water collector in its outlet header.
the cabin system. Both packs are supplied with hot bleed
air from both engines and cool this air as necessary
before distribution to their respective systems. When
heating is required the hot bleed air is allowed to bypass
the refrigeration section of the selected system’s pack.
If cooling is required, the selected system’s temperature
control valves close, routing the hot bleed air through its
refrigeration section.
Silencers are installed in the bypass ducts downstream of
both packs’ temperature control valves to reduce noise in
the ducts.
Temperature of the air supplied by either pack is
controlled automatically or manually from the air
conditioning panel in the flight compartment.
In the event of a single pack failure, the remaining pack
supplies conditioned air for all systems. If both packs fail,
ram air is supplied to the cabin and flight compartment for
ventilation.
Figure 57 – Cooling
Oct. 1/2009 - © Jazz Air LP Page 133
There is a temperature control rotary switch on the The No. 2 pack temperature control valve actuator
forward flight attendant’s panel. This switch gives responds to electrical signals from the controller and
the flight attendant total temperature control of the positions its valve assembly to regulate the flow of
cabin conditioned air when the flight compartment air hot and/or cold air at the desired temperature. The
conditioning panel CABIN/TEMP CONTROL rotary switch temperature limits are the same as for the cabin
is selected to the full counterclockwise F/A position. system.
Thermostatic Switch
There is a thermostatic switch located in the flight
compartment conditioned air supply duct under the
baggage compartment floor. This switch controls the
operation of the gasper fan when the cockpit GASP
FAN−OFF/AUTO/ON switch is selected to the AUTO
position.