Professional Documents
Culture Documents
Overhead Line Galloping. Field Experience During One Event in Belgium On Last February 13TH, 1997
Overhead Line Galloping. Field Experience During One Event in Belgium On Last February 13TH, 1997
Overhead Line Galloping. Field Experience During One Event in Belgium On Last February 13TH, 1997
Abstract Galloping lasted for several hours in the morning and in the
A recorded galloping occurred last winter in the Belgium test afternoon of February 13th, 1997. Large amplitudes (one loop
station on February 13th, 1997. This paper details the mode) , up to the sag, were visually observed.
observation and corresponding measurements. Comparative Compared to the reference twin bundle phase, the galloping
simulations are also detailed so that a clear explanation of the on the span equipped with anti-galloping devices was
phenomena is detailed. Efficiency of some anti-gallopng sensibly reduced (up to 80% reduction in some cases)
devices is also detailed.
Simulation points out that the galloping was a coupled
Keywords. vertical-torsional mode[5] and not a Den-Hartog[1] one, with
overhead lines, galloping, measurement, control devices. the presence of two and one loop modes, with a dominant
one loop.
1. Introduction
Galloping is a main problem for overhead lines in some
climatic conditions[2]. Phase-to-phase flashovers as well as Both measurement and simulation certify the good behaviour
high dynamic stress on towers may lead to power arcs, of anti-galloping « TDD »[6] as designed for that line.
damages to hardware, tower steelwork, fatigue of
conductors, tension strings and jumpers. Galloping is deeply 2. Structural data
investigated in Belgium for many years, in collaboration 2.1 phase arrangement
between university and network utility. span length (dead-ended) : 308 m
The recorded event occurred on a dead-end span (380 kV
Belgium grid) equipped with many different kinds of phases • One phase equipped with tripple conductor
arrangement (twin, tripple, with and without anti-galloping • One phase equipped with twin horizontal conductor,
devices). spacered (reference phase)
Strain gages for tension measurement were located between • One phase equipped with twin horizontal conductors,
anchoring insulators and tower. with pendulum[4] (4 pendulum of 23 kg)
Wind speed were measured in details by climatology • One phase equipped with twin horizontal conductor, with
department of the University of Liège.(including turbulence TDD[6] (3 TDD of 33 kg)
intensity).
2.2 conductor and bundle data
• conductor : 620 mm2 AMS (diameter 32.4 mm, mass 1.8
kg/m, torsional stiffness 300 to 400 Nm2/rad)
• subconductor spacing : 0.45 m Fig.1 Turbulence intensity measured by climatologic
• 6 spacers (with little eccentric massa) department during all the day of February 13th,
• tension at 0°C /subconductor (no wind, no ice) : 1997. Abscissa in GMT+1, given in minutes.
36 kN (sag approximately 6 m)
3.Observations
Fig. 1 and 2 gave informations about meteorological datas
during the day of the galloping event :
wind speed range : 4 to 14 m/s, perpendicular to the test line
with a turbulence intensity close to 25%. It must be noticed
that a vertical wind speed has also been measured in the
range 0 to 0.8 m/s during galloping events.
Rime started suddently, when temperature was going down
through 0°C (about). Icing rain were mentioned in the nearest
meteorological station between 7 and 9 a.m. GMT with slight
positive temperature. Similar rain in the afternoon between
11:30 and 5:00 p.m. GMT with slightly negative temperature.
Icing rain events were simultaneous with strong wind.
Unfortunately, no video was taken, but observers noticed • tripple bundle : 40 kN/ insulator chain (means tower load
very high amplitude (larger than the sag ?). Galloping lasted 80 kN peak-to peak)
for several hours in the morning and in the afternoon of • twin bundle with pendulums : 17 kN (efficiency (25-17)/25
February 13th, 1997. Despite large amplitudes, no short- = 32%)
circuit were re ported, nor any damage. Large amplitude were • twin bundle with TDD : 5 kN (efficiency (25-5)/25 = 80%)
only seen on our test dead-end span, no other lines in the
vicinity seemed to gallop. The dead-end test span was
located near angle towers.
Fig. 3 Recording of tension fluctuations at anchoring level in two phases of the Villeroux test station (Belgium).
Only relative changes are important. Upper oscillogramm (±5kN peak-to-peak) for phase with TDD anti-galloping
device, the other one detail during the same period of observation, the tension fluctuation (± 25 kN peak-to-peak) in
the reference phase (twin bundle at the same vertical position).
Fig. 4 Aerodynamic coefficients used for simulations. Ice thickness 1.1 cm over a subconductor diameter of
32.4 mm (similar as [3])
LIFT positive upwards; Pitching moment and torsional angle positive anti-clockwize. Zero angle when ice
is facing the wind and in horizontal position.
Fig. 7 Vertical displacement at mid-span.
Fig. 5 Galloping ellipse at mid-span (wind speed Fluctuations are related to wind turbulence.
10 m/s with turbulence intensity of 20%).
The galloping is mainly vertical with
peak-to-peak amplitude close to 6 m.
Both measurement and simulation certify the good M. Wolfs, Laborelec,Rodestraat 125, B1630 Linkebeek,
behaviour of TDD as designed for that line. Belgium. Fax : +32-2-3820299
Acknowledgements
The authors from the university would like to thank
the « Communauté Française de Belgique » for their
financial support for research in cable dynamics area.
(Projet ARC 94-99, N°176). Michel Escarmelle from
Laborelec helped a lot for Villeroux tests stations
installation and he also managed all recordings and
data transmission.
References
[1] Den Hartog, J.P., Transmission Line Vibration
due to Sleet, Trans. A.I.E.E., 1930, 49.
[2] Transmission line reference book. Wind
induced conductor motion. Electric Power
Research Institute, Palo Alto,CA, 1980.
[3] Tunstall, M., Koutselos, L.T., Further Studies
of the Galloping Instability & Natural Ice
Accretions on Overhead Line Conductors, 4th Int.
Conf. on Atmospheric Icing of Structures., Paris,
sept.1988.
[4] D.G. Havard, J.C. Pohlman. Field testing of
detuning pendulums for controlling galloping of