Metering Unit Test Report Make Type CT Ratio VT Ratio Serial No. Burden Expected Insulation Resistance
Metering Unit Test Report Make Type CT Ratio VT Ratio Serial No. Burden Expected Insulation Resistance
Metering Unit Test Report Make Type CT Ratio VT Ratio Serial No. Burden Expected Insulation Resistance
MAKE VISHAL
TYPE OUTDOOR GROUND MOUNTED
CT RATIO 300-150/1A, CLASS 0.5
VT RATIO 11000/110 ,CLASS 1.0
SERIAL NO. VTS/JUN/1/3/2017/30
BURDEN 10VA (CT) , 50VA(VT)
Expected insulation > 66 MΩ
resistance
CT RATIO TEST
PHASES CT ratio Results Half Dev Results Full Dev Remarks
tap (%) tap (%)
Red(R) 300-150/1A 150:1.0015 0.15 300:0.9994 -0.06 pass
VT RATIO TEST.
PHASES VT RATIO TEST RESULT DEVIATION REMARK
(%)
R-Y 11000/110 11000:110.5435 0.49 Pass
R-B 11000/110 11000:110.5383 0.49 Pass
Y-B 11000/110 11000:110.5488 0.50 Pass
INSULATION RESISTANCE TEST
TEST TEST TEST TEST RESULTS (Ω) REMARK
VOLTAGE(KV) TIME(S) R Y B
HV-E 5 60 10.9M 11.2M 12.5M FAIL
HV-LV 5 60 26.5M 52.8M 18.12M FAIL
LV-E 2.5 60 11.6M 16.5M 18.8M FAIL
General assessment:
Metering Unit passed the CT – VT ratio tests, but failed insulation resistance tests.
It needs to be opened up for further checks.
Tested by: Hussein Adrac.
Signature: ……………………………………. Date: …………………………..
Ddungu Henry
Signature: ……………………………………. Date: …………………………..
Recommended by: Expedite Kiggundu.
Principal protection Engineer.