METERING UNIT TEST REPORT

MAKE VISHAL
TYPE OUTDOOR GROUND MOUNTED
CT RATIO 300-150/1A, CLASS 0.5
VT RATIO 11000/110 ,CLASS 1.0
SERIAL NO. VTS/JUN/1/3/2017/30
BURDEN 10VA (CT) , 50VA(VT)
Expected insulation > 66 MΩ
resistance

CT RATIO TEST
PHASES CT ratio Results Half Dev Results Full Dev Remarks
tap (%) tap (%)
Red(R) 300-150/1A 150:1.0015 0.15 300:0.9994 -0.06 pass

Blue(B) 300-150/1A 150:1.0015 0.15 300:0.9993 -0.07 pass

VT RATIO TEST.
PHASES VT RATIO TEST RESULT DEVIATION REMARK
(%)
R-Y 11000/110 11000:110.5435 0.49 Pass
R-B 11000/110 11000:110.5383 0.49 Pass
Y-B 11000/110 11000:110.5488 0.50 Pass
INSULATION RESISTANCE TEST
TEST TEST TEST TEST RESULTS (Ω) REMARK
VOLTAGE(KV) TIME(S) R Y B
HV-E 5 60 10.9M 11.2M 12.5M FAIL
HV-LV 5 60 26.5M 52.8M 18.12M FAIL
LV-E 2.5 60 11.6M 16.5M 18.8M FAIL

General assessment:
Metering Unit passed the CT – VT ratio tests, but failed insulation resistance tests.
It needs to be opened up for further checks.
Tested by: Hussein Adrac.
Signature: ……………………………………. Date: …………………………..
Ddungu Henry
Signature: ……………………………………. Date: …………………………..
Recommended by: Expedite Kiggundu.
Principal protection Engineer.
Signature:………………………………. Date: …………………………………