Introduction
This supplement to the L1000A Technical Manual describes features or functions that are changed
with an L1000A software upgrade, and should be read to ensure proper usage. Read this supplement
together with the L1000A Technical Manual.
Observer all safety messages and precautions to prevent injury to personnel and to ensure correct
application of the product.
Figure 2
Figure 3
The PTC thermistor must have the following characteristics for one motor phase. The drives motor overload
detection requires three PTC thermistors to be connected in series.
Overheat detection using a PTC thermistor is configured with parameters L1-03, L1-04, and L1-05 as
explained below.
0: English
1: Japanese
2: German
3: French
4: Italian Default: <1>
A1-00
Language Selection 5: Spanish Min: 0
(100H)
6: Portuguese Max: 12 <2>
7: Chinese
8: Czech
9: Russian
10: Turkish
11: Polish
12: Greek
<1> Default setting value is dependent on Initialization Specification Selection (o2-09).
<2> Language setting 8 to 12 can be selected from an LCD operator with software version 0102 or later. The version number of the LCD
operator's PRG software is shown on the back of the LCD operator.
◆b: Application
No. (Addr.) Name Description Setting
b1: Operation Mode Selection
Default: 0
b1-03
Stopping Method Selection 0: Ramp to stop Min: 0
(182H)
1: Coast to stop Max: 4 <3>
4: Elevator Emergency Stop
<3> V/f Control and Open Loop Vector Control: Max setting = 1
Default: 0.00 Hz
d1-27
Motor 2 Speed Reference Min: 0.00 Hz
(2C9H)
Sets the speed reference for motor 2. Max: 200.00 Hz
Default: <1>
E3-04 Motor 2 Maximum Output
Min: 10.0 Hz
(31AH) Frequency
Max: 200.0 Hz
Default: <1>
E3-06
Motor 2 Base Frequency These parameters are only applicable when E1-03 is set Min: 0.0 Hz
(31CH)
to F. Max: 200.0 Hz
To set linear V/f characteristics, set the same values for
Default: <1>
E3-07 Motor 2 Mid Output E3-07 and E3-09. In this case, the setting for E3-08 will be
Min: 0.0Hz
(31DH) Frequency disregarded. Ensure that the four frequencies are set
Max: 200.0 Hz
according to these rules or an oPE10 fault will occur:
E3-09 ≤ E3-07 < E3-06 ≤ E3-04 Default: <1>
E3-09 Motor 2 Minimum Output
Min: 0.0 Hz
(31FH) Frequency
Max: 200.0 Hz
E5: PM Motor Settings
Default: 12
E5-04
Number of Motor Poles Min: 2
(32CH)
Sets the number of motor poles. Max: 120 <6>
<1> Default setting value is dependent on Initialization Specification Selection (o2-09).
<4> Default setting is determined by the control mode (A1-02).
<5> Setting range depends on the type of motor being used. CLV allows a setting range of 10.0 to 200.0 Hz, while CLV/PM allows a
setting range of 4.0 to 200.0 Hz.
<6> When PG-E3 option connected: Max setting = 48
F1-66 to
Default: 0
F1-81 PG-E3 Encoder Adjust
Sets encoder offsets 1 to 16 for the PG-E3 option card. Min: 0
(B9AH to 1 to 16
These parameters are automatically set by the execution Max: FFFF
BA9H)
of Auto-Tuning of PG-E3 encoder characteristics.
5B Brake Feedback 2
Open: Brake open (N.C.)
Closed: Brake closed
H2-
Function Description
Setting
H2: Multi-Function Digital Outputs
Default: 0
L4-07 Speed Agree Detection
Min: 0
(470H) Selection 0: No detection during baseblock. Max: 1
1: Detection always enabled.
L8: Drive Protection
Default: 0
L8-89 Current Monitoring
Enables or disables the Current Monitoring function. Min: 0
(B97H) Selection
0: Disabled Max: 1
1: Enabled
Default: 0
o1-06 User Monitor Selection 0: 3 Monitor Sequential (Displays the next 2 sequential Min: 0
(517H) Mode monitors) Max: 1
1: 3 Monitor Selectable (o1-07 and o1-08 selected
monitor is displayed)
Default: 102
o1-07 Second Line Monitor
(518H) Selection Min: 101
Selects the monitor displayed on the second line. Max: 699
Default: 103
o1-08 Third Line Monitor
(519H) Selection Min: 101
Selects the monitor displayed on the third line. Max: 699
Default: 0
S1-12 Motor Contactor Control Determines the state of the output contactor control
Min: 0
(6E0H) During Auto-Tuning command (H2- = 51) during Auto-Tuning.
Max: 2
0: Disabled
1: Enabled
2: Enabled during Auto-Tuning and HBB
Default: 10.0%
S1-26 Emergency Stop Start
Min: 0.0%
(6D7H) Level Sets the Emergency Stop Start Level as a percentage of Max: 100.0%
the Maximum Output Frequency.
Default: 0.0 Hz
S3-14 Torque Compensation Sets the speed level for torque compensation to diminish Min: 0.0 Hz
(69FH) Fade Out Speed during the time determined by S3-15. Sets as a Max: 200.0 Hz
percentage of the maximum output frequency (E1-04). A
setting of 0.0% disables this function.
S6: Error Detection
Default: 25%
S6-03
SE2 Detect Current Level Sets the level of current applied to the motor when the Min: 0%
(6B5H)
Brake Control command is activated, as a percentage of Max: 100%
the Motor No-load Current (E2-03).
Default: 60.0 Hz
T1-05
Motor Base Frequency Min: 0.0 Hz
(705H) Sets the rated frequency of the motor as specified on the Max: 200.0 Hz
motor nameplate.
T2: PM Motor Auto-Tuning
Default: 6
T2-08
Number of Motor Poles Min: 2
(32CH) Enter the number of motor poles for the motor as indicated Max: 120 <6>
on the motor nameplate.
Rotation Direction for Sets the direction of motor rotation for execution of Default: 0
T2-19
Auto-Tuning of PG-E3 Auto-Tuning of PG-E3 encoder characteristics (T2-01 = Min: 0
(BB1H)
Encoder Characteristics 12). Max: 1
0: Forward (Up)
1: Reverse (Down)
<6> When PG-E3 option connected: Max setting = 48
<7> Auto-Tuning of PG-E3 encoder characteristics requires a PG-E3 option with software version 1102 or later. To identify the PG-E3
software version, refer to the PG-E3 labeling on the option, in the field designated “C/N” (S + four digit number).
Chapter 1 Receiving
* ■: Added or Changed in software version PRG: 72.
Note: Set parameters S1-02 and S1-04 as follows when setting L8-07 to 3. An incorrect setting may result in
poor performance or nuisance faults or alarms.
y Set S1-02 (DC Injection Current at Start) to a value greater than 15%.
y Set S1-04 (DC Injection/Position Lock Time at Start) to a value greater than 100 ms.
◆ C: Tuning
No.(Addr.) Name Description Setting
C5: Speed Control Loop
0: Disabled
1: Enabled (triggered by a single phase loss)
2: Enabled (triggered when two phases are lost)
3: Enabled (triggered at phase loss at start or when two Default: 0
L8-07 Output Phase Loss
phases lost mid-operation) <2> Min: 0
(4B3H) Protection
Output phase loss fault (LF) is triggered when the Max: 3
output current falls below 5% of the drive’s rated output
current.
Output phase loss fault can mistakenly be triggered if
the motor’s rated current is very small compared to the
drive rating. Disable this parameter in such cases.
<2> Only V/f and OLV allow the setting 3.
Default: 0
n1-08 Leakage Current Vibration 0: Method 1 Min: 0
(1105H) Control Selection 1: Method 2 Max: 1
Parameter n1-08 does not typically require adjustment
from it's default value.
Default: 3
o1-05
LCD Contrast Control Min: 0
(504H) Adjusts the brightness and contrast in the LCD screen of Max: 5
the digital operator.
Default: Determined by
o1-22 A1-02
Mechanical Gear Ratio
(577H) Sets the ratio of the gear installed for display unit Min: 0.10
calculations. Max: 100.00
Default: 0
o1-23 0: Shows HBB
HBB Non Display Select Min: 0
(174H) 1: Hide HBB Max: 1
Shows or hides HBB on the digital operator while the
safety signal is being input.