PD6800 Explosion-Proof Loop-Powered Process Meter: Instruction Manual
PD6800 Explosion-Proof Loop-Powered Process Meter: Instruction Manual
Instruction Manual
Disclaimer
The information contained in this document
Introduction
is subject to change without notice. Precision The PD6800 is a rugged, explosion-proof loop-
Digital Corporation makes no representations powered meter fully featured for demanding
or warranties with respect to the contents hereof; applications in hazardous areas or in the harshest
and specifically disclaims any implied warranties environmental conditions. The meter derives all its
of merchantability or fitness for a particular power from the 4-20 mA loop. It is programmed using
purpose. the four SafeTouch through-glass buttons, without
removing the cover, and can be scaled with or without
a calibration signal. The numeric display will read up
to 99999 and the alphanumeric display can be
• Read complete instructions prior to installation programmed to show any combination of numbers
and operation of the meter. and letters up to seven characters long for use as
engineering units, the process identification tag or a
display for the calculated volume when using for level
• Risk of electric shock or personal injury. applications. The backlight lets you see the display
• This product is not recommended for life support under any lighting condition and can be powered from
applications or applications where malfunctioning either the 4-20 mA loop or from a separate DC power
could result in personal injury or property loss. supply.
Anyone using this product for such applications The enclosure is provided with two threaded conduit
does so at his/her own risk. Precision Digital holes and integrated pipe or wall mounting slotted
Corporation shall not be held liable for damages flanges.
resulting from such improper use.
• Failure to follow installation guidelines could
result in death or serious injury. Make sure only
Ordering Information
qualified personnel perform the installation. Model Description
• Never remove the meter cover in explosive Explosion-Proof Loop-Powered Process
PD6800-0K0
environments when the circuit is live. Meter with Backlight
• Cover must be fully engaged to meet Accessories
flameproof/explosion-proof requirements.
Model Description
PDA0001 3/4" M-NPT to F-M20 Reducer
WARNING PDA0002 3/4" M-NPT to 1/2" F-NPT Reducer
Cancer and Reproductive Harm - www.P65Warnings.ca.gov
PDA1024-01 24 VDC Power Supply for DIN Rail
Steel 2" U-Bolt Kit. All Material: Zinc
Plated Steel; (1) U-Bolt for 2" Pipe with
Limited Warranty PDA6846
(2 each) Washers, Lock Washers, and
Precision Digital Corporation warrants this Nuts.
product against defects in material or Stainless Steel 2" U-Bolt Kit. All
workmanship for the specified period under Material: Stainless Steel; (1) U-Bolt for
“Specifications” from the date of shipment from PDA6846-SS
2" Pipe with (2 each) Washers, Lock
the factory. Precision Digital’s liability under this Washers, and Nuts.
limited warranty shall not exceed the purchase Custom Stainless Steel Tag (see
value, repair, or replacement of the defective unit. PDA-SSTAG
website for convenient ordering form)
See Warranty Information and Terms &
Conditions on www.predig.com for complete
details.
2
PD6800 Explosion-Proof Loop-Powered Process Meter Instruction Manual
Table of Contents
Introduction......................................................................................................... 2
Ordering Information.......................................................................................... 2
Specifications ..................................................................................................... 5
General ............................................................................................................ 5
Input ................................................................................................................ 5
Product Ratings and Approvals .................................................................... 6
Electromagnetic Compatibility ...................................................................... 6
Safety Information .......................................................................................... 6
Installation........................................................................................................... 7
Unpacking ....................................................................................................... 7
Pre-Installed Conduit Plug ............................................................................ 7
Mounting ......................................................................................................... 7
Dimensions ..................................................................................................... 7
Cover Jam Screw ........................................................................................... 8
Connections ................................................................................................... 8
Wiring Diagrams ............................................................................................. 9
Setup and Programming .................................................................................. 10
Overview ....................................................................................................... 10
SafeTouch Buttons ...................................................................................... 10
SafeTouch Button Tips and Troubleshooting ............................................. 10
Buttons and Display..................................................................................... 11
Main Menu Display Functions & Messages ............................................... 12
Main Menu..................................................................................................... 12
Setting Up the Meter (SETUP) ....................................................................... 12
Setting Numeric Values ............................................................................. 13
Setting the Decimal Point (Dec.Pt) ............................................................. 13
Programming the Meter (Prog) .................................................................. 13
Scaling the Meter (SCale) .......................................................................... 13
Calibrating the Meter (Cal) ........................................................................ 14
Minimum Input Span .............................................................................. 14
Re-Calibrating the Internal Calibration Reference (ICaL) ...................... 14
Setting the Tag Display (tag) ................................................................ 14
Setting Up the Password (PASSWRD) ........................................................... 15
Locking the Meter ...................................................................................... 15
Making Changes to a Password Protected Meter ...................................... 15
Disabling Password Protection .................................................................. 15
Service Feature (SERVICE) ........................................................................... 15
Advanced Features Menu ............................................................................ 16
Advanced Features Menu & Display Messages......................................... 16
Indication (INDICAT) .................................................................................. 17
Alarm (alrnm) ............................................................................................ 17
Advanced Function Selection (FUNCTN) ....................................................... 17
Multi-Point Linearization (lnear)................................................................ 17
Multi-Point Scaling (SCALE) ........................................................................ 18
Multi-Point Calibration (CAL)....................................................................... 18
Square Root Linearization (Squar) ............................................................ 18
Low-Flow Cutoff (CUTOFF) .......................................................................... 18
Programmable Exponent Linearization (Prog.E) ......................................... 19
Input Signal Filter (FILTER) ........................................................................ 20
Internal Calibration (ICAL).......................................................................... 20
Error Message (SPAN ERROR) ..................................................................... 20
Information (INFO) ...................................................................................... 20
3
PD6800 Explosion-Proof Loop-Powered Process Meter Instruction Manual
Operation........................................................................................................... 20
Front Panel Buttons Operation ................................................................... 20
Maximum & Minimum Readings (MAXIMUM & MINIMUM) ............................. 20
Reset Meter to Factory Defaults.................................................................. 21
Factory Defaults & User Settings................................................................ 21
Troubleshooting ............................................................................................... 21
Troubleshooting Tips................................................................................... 21
Quick User Interface Reference ...................................................................... 23
EU Declaration of Conformity.......................................................................... 24
Table of Figures
Figure 1. Enclosure Dimensions – Front View ................................................... 7
Figure 2. Enclosure Dimensions – Side Cross Section View ........................... 7
Figure 3. Connector Board .................................................................................. 8
Figure 4. Connections without Backlight ........................................................... 9
Figure 5. Connections with Loop-Powered Backlight ....................................... 9
Figure 6. Connections with Externally-Powered Backlight................................ 9
4
PD6800 Explosion-Proof Loop-Powered Process Meter Instruction Manual
General
Display Five digits 0.70" (17.8 mm) high,
Input
(-9999 to 99999) 7-segment, automatic Input 4-20 mA
lead zero blanking. Accuracy ±0.03% of calibrated span ±1 count,
Seven characters 0.4" (10.2 mm) high, square root & programmable exponent
14-segment. accuracy range:
Symbols High & Low Alarm, 10-100% of calibrated span.
Password Lock
Maximum Without Backlight With Loop-
Display Display may be mounted at 90° increments
Voltage Drop & or with Externally Powered
Orientation up to 270° from default orientation.
Equivalent Powered Backlight Backlight
Display Lower display may be assigned to custom Resistance
Assignment unit or tag. 3.0 VDC @ 20 mA 6.0 VDC @ 20 mA
Display Ambient > -25°C: 2 Updates/Second 150 Ω @ 20 mA 300 Ω @ 20 mA
Update Rate Ambient < -25°C: 1 Update/5 Seconds Temperature 50 PPM/°C from -40 to 75°C ambient
Backlight White; Loop-powered or externally powered. Drift
Backlight can be enabled or disabled via
Multi-Point 2 to 32 points
alternative wiring of terminal block. Loop-
Linearization
powered backlight brightness will increase as
the input signal current increases. Externally Programmable User selectable from 1.0001 to 2.9999
powered backlight has consistent brightness. Exponent for open channel flow
Externally Voltage Maximum Power Low Flow 0-99999 (0 disables cutoff function)
Powered Range: Cutoff Point below at which display always
Backlight 9-36 9 12 24 36 shows zero.
VDC VDC VDC VDC VDC Decimal Point User selectable decimal point
0.2 W 0.25 W 0.5 W 0.75 W Minimum Span Input 1 & Input 2: 0.10 mA
Display Display flashes 99999 Calibration An Error message will appear if input 1
Overrange
Range and input 2 signals are too close together.
Display Display flashes -9999
Underrange Input Minimum Span
Programming Four SafeTouch through-glass buttons when Range Input 1 & Input 2
Method cover is installed. Four internal pushbuttons 4-20 mA 0.10 mA
when cover is removed. Input Over current protection to 2 A max.
Noise Filter Programmable LO, med, HI, or OFF Overload
Recalibration Recalibration is recommended at least every HART The meter does not interfere with existing
12 months. Transparency HART communications; it displays the
Max/Min Max/Min readings reached by the process 4-20 mA primary variable and it allows the
Display are stored until reset by the user or until HART communications to pass through
power to the meter is turned off. without interruption.
Advanced Linear, square root, or programmable The meter is not affected if a HART
Function exponent communicator is connected to the loop.
Password Programmable password restricts The meter does not display secondary
modification of programmed settings. HART variables.
Non-Volatile All programmed settings are stored in non-
Memory volatile memory for a minimum of ten years
if power is lost.
Normal Mode 64 dB at 50/60 Hz
Rejection
Environmental Operating temperature range: -40 to 75°C
Storage temperature range: -40 to 75°C
Relative humidity: 0 to 90% non-condensing
Connections Screw terminals accept 12 to 22 AWG wire
Enclosure Explosion-proof die cast aluminum with glass
window, corrosion resistant epoxy coating,
color: blue. NEMA 4X, 7, & 9, IP68.
Two ¾" NPT threaded conduit openings.
One ¾" NPT metal conduit/stopping plug with
12 mm hex key fitting installed.
Mounting May be mounted directly to conduit.
Two slotted flanges for wall mounting or
NPS 1½" to 2½" or DN 40 to 65 mm pipe
mounting. See Dimensions on page 7.
Overall 5.65" x 5.25" x 4.86" (W x H x D)
Dimensions (144 mm x 133 mm x 124 mm)
Weight 5.00 lbs (80 oz, 2.27 kg)
5
PD6800 Explosion-Proof Loop-Powered Process Meter Instruction Manual
6
PD6800 Explosion-Proof Loop-Powered Process Meter Instruction Manual
Installation Mounting
For Installation in USA: The PD6800 must be in- The PD6800 has two slotted mounting flanges that
stalled in accordance with the National Electrical may be used for pipe mounting or wall mounting.
Code (NEC) NFPA 70. Alternatively, the unit may be supported by the
conduit using the conduit holes provided. Refer to
For Installation in Canada: The PD6800 must be in-
Figure 1 and Figure 2.
stalled in accordance with the Canadian Electrical
Code CSA 22.1. All input circuits must be derived
from a CSA approved Class 2 source.
For European Community: The PD6800 must be in- • Do not attempt to loosen or remove flange bolts
stalled in accordance with the ATEX directive 94/9/EC while the meter is in service.
and the product certificate Sira 10ATEX1116X.
Dimensions
All units: inches [mm]
• Disconnect from supply before opening
enclosure. Keep cover tight while circuits are
alive. Conduit seals must be installed within 5.25 (133.4)
18" (450mm) of the enclosure.
7
PD6800 Explosion-Proof Loop-Powered Process Meter Instruction Manual
8
PD6800 Explosion-Proof Loop-Powered Process Meter Instruction Manual
Wiring Diagrams
Signal connections are made to a four-terminal For installations that use the backlight powered from
connector mounted in the base of the enclosure per the meter, the maximum voltage drop is 6 V and
Figure 3. Connector Board. The enclosure also connections are made per Figure 5.
provides one internal and one external earth For installations that use the backlight powered from
grounding screw. an external source, the maximum voltage drop is 3 V
For installations that don’t use the backlight, the and connections are made per Figure 6.
maximum voltage drop is 3 V and connections are
made per Figure 4.
+SIGNA-L BACKLIGH
+ -T UNLOCK LOCK
+ - + - 9-36 LOOP
UNLOCK LOCK 9-36 LOOP SIGNA L BACKLIGHT
VDC VDC
Slide Switch to
9-36 VDC
Figure 4. Connections without Backlight
Power Supply
SIGNA L BACKLIGHT
UNLOCK LOCK 9-36 LOOP
VDC
Slide Switch to
LOOP
9
PD6800 Explosion-Proof Loop-Powered Process Meter Instruction Manual
10
PD6800 Explosion-Proof Loop-Powered Process Meter Instruction Manual
Enter Button
Button • Press the Enter button to access a menu or to
Description Symbol Status
Symbol accept a setting.
Enter
ENTER
11
PD6800 Explosion-Proof Loop-Powered Process Meter Instruction Manual
12
PD6800 Explosion-Proof Loop-Powered Process Meter Instruction Manual
13
PD6800 Explosion-Proof Loop-Powered Process Meter Instruction Manual
14
PD6800 Explosion-Proof Loop-Powered Process Meter Instruction Manual
3024.7 00000
GALLONS LOCKED LOCKED UNLOCKD
Record the password for future reference. If appropri-
ate, it may be recorded in the space provided.
00000
SETUP PASSWRD
Model: PASSWRD UNLOCKD
Re-Enter
Serial Number: Password Run Mode
Password: __ __ __ __ __
If the correct five-digit password is entered, the meter
displays the message UNLOCKD (unlocked) and the
Additional parameters, not needed for most applica- protection is disabled until a new password is
tions, are programmed with the Advanced Features programmed.
menu; see the Advanced Features Menu on page 16. If the password entered is incorrect, the meter
displays the message LOCKED for about two seconds,
and then it returns to Run Mode. To try again, press
Enter while the Locked message is displayed.
15
PD6800 Explosion-Proof Loop-Powered Process Meter Instruction Manual
16
PD6800 Explosion-Proof Loop-Powered Process Meter Instruction Manual
off
INDICAT
Accept
Setting Multi-Point Linearization (lnear)
Up to 32 linearization points can be selected under
reset 16.000 the Linear function. The multi-point linearization can
ALARM RESET Accept
Enter Setting be used to linearize the display for non-linear signals
Reset Point such as those from level transmitters used to meas-
Alarm (alrnm) ure volume in odd-shaped tanks or to convert level to
flow using weirs and flumes that require a complex
• High alarm trip point: program set point exponent. These points are established via direct en-
above reset point. try (SCALE) or with a live calibration signal source
• Low alarm trip point: program set point (CAL).
below reset point.
• Alarm deadband is determined by the differ-
ence between set and reset points. Minimum
deadband is one display count. If set and
reset points are programmed the same,
output will reset one count below set point.
To acknowledge the alarm, press the Enter button
once for acknowledge prompt and a second time
to confirm.
17
PD6800 Explosion-Proof Loop-Powered Process Meter Instruction Manual
The use of a calibrated signal source is strongly PD6800 Displaying Flow Rate by Extracting Square Root
recommended. from DP Transmitter Signal.
18
PD6800 Explosion-Proof Loop-Powered Process Meter Instruction Manual
Programmable Exponent To display both flow rate and total, consider Precision
Digital’s Model PD6820 Flow Rate Totalizer.
Linearization (Prog.E)
The programmable exponent can be used to linearize
the signal from level transmitters in open-channel flow
applications using weirs and flumes.
Table 12-3
Head CFS GPM MGD
(Feet)
3.00 5.428 2436 3.508
ISCO Open Channel Flow Measurement Handbook, 3rd edition
19
PD6800 Explosion-Proof Loop-Powered Process Meter Instruction Manual
Input Signal Filter (FILTER) Following the information display, the meter will exit
the Advanced features menu and return to run mode.
The noise filter is available for unusually noisy signals
that cause an unstable process variable display. The
noise filter averages the input signal over a certain Operation
period. The filter level can be set to low (LO), medium
(nmed), high (HI), or off (OFF). The higher the filter Front Panel Buttons Operation
setting, the longer the averaging time and so the
longer the display may take to find its final value. Button
Description
The filter contains a noise filter bypass feature so that Symbol
while small variations in the signal will be filtered out,
large, abrupt changes to the input signal are Press to enter or exit
displayed immediately. Programming Mode or exit
Internal Calibration (ICAL) MENU Max/Min readings
RESET
There is no need to recalibrate the meter for milliamps Press to reset Max/Min
when first received from the factory.
readings
The meter is factory calibrated for milliamps prior to
shipment. The calibration equipment is traceable to NIST DISPLAY
standards. Press to display Max/Min
The internal calibration allows the user to scale the readings alternately
meter without applying a signal. The use of a cali-
brated signal source is necessary to perform the Press to display Max or Min
internal calibration of the meter. Check calibration
reading indefinitely while
of the meter at least every 12 months.
ENTER displaying Max or Min
Notes:
The signal source must have a full-scale accuracy of
0.002% or better between 4 and 20 mA in order to main- The meter displays 4.000 mA. Apply a 4.000 mA
tain the specified accuracy of the meter. signal and press Enter. The display flashes for a
Allow the meter to warm up for at least 15 minutes before moment while the meter is accepting the signal.
performing the internal calibration procedure. After the signal is accepted, the meter displays 20.000
mA. Apply a 20.000 mA signal and press Enter. The
The Internal calibration menu is part of the Advanced
display flashes for a moment while the meter is
features menu.
accepting the signal.
Press and hold the MENU button for 5 seconds to
enter the Advanced features menu. Press the Up
arrow button to scroll to the Internal Calibration menu Maximum & Minimum Readings
(ICAL) and press Enter. (MAXIMUM & MINIMUM)
Error Message (SPAN ERROR) The maximum and minimum (peak & valley) readings
An error message indicates that the calibration reached by the process are stored in the meter since
process was not successful. After the error message the last reset or power-up. The meter shows MAXIMUM
is displayed, the meter will revert to input 2 calibration or MINIMUM to differentiate between run mode and
settings. The error message might be caused by max/min display. Press Enter to remain in Max/Min
inadvertently leaving the signal at the previous level display mode. If Enter is not pressed, the Max/Min
or not maintaining the minimum span. Press the Menu display readings will time out after ten seconds. The
button to cancel the current calibration process if meter will return to display the actual reading.
necessary.
Information (INFO)
The Internal calibration menu is part of the Advanced
features menu. It shows software identification num-
ber and version number. To determine the software
version of a meter:
Go to the Information menu (INFO) and press Enter
button.
Continue pressing Enter to scroll through the soft-
ware release number and software version.
20
PD6800 Explosion-Proof Loop-Powered Process Meter Instruction Manual
Troubleshooting
Due to the many features and functions of the meter, it’s possible that the setup of the meter does not agree with
what an operator expects to see. If the meter is not working as expected, refer to the Diagnostics menu and consult
the recommendations described below.
Troubleshooting Tips
Symptom Check/Action
No display or faint display Check input signal connections.
Perform hard reset by shorting S+ and S- terminals.
Rate display unsteady Increase filter setting in Advanced menu.
Meter displays error message during Check signal connections.
calibration (Span eRROR) Verify minimum input span requirements.
Meter flashes 99999 or -9999 Check input signal is within scaled range of 99999 and -9999.
Display stuck displaying MAXIMUM or MINIMUM Press Menu to exit Max/Min display readings.
Display response is too slow Check filter setting to see if it can be lowered to LO or OFF.
If the display locks up or the meter does not Perform hard reset by shorting S+ and S- terminals.
respond at all
Backlight does not appear. Backlight is intended for viewing assistance in dim lighting conditions.
It may not be noticeable under good lighting conditions.
Check connections as shown in Figure 5. Connections with Loop-
Powered Backlight or Figure 6. Connections with Externally-Powered
Backlight on page 9.
21
PD6800 Explosion-Proof Loop-Powered Process Meter Instruction Manual
SafeTouch buttons do not respond Service menu was selected, or mechanical button was pushed.
The SafeTouch buttons will be re-enabled automatically 60 seconds
after the last button push.
If slide switch on connector board is in Lock position, switch to Unlock.
Sunlight can interfere with the sensors. It is recommended to shield the
window from sunlight while operating the buttons by standing so as to
block direct sunlight.
Other symptoms not described above Call Technical Support for assistance.
22
PD6800 Explosion-Proof Loop-Powered Process Meter Instruction Manual
Max/Min Mode
While in Run Mode, pressing Up Arrow will initiate
MAX/MIN Mode. Up Arrow toggles between MAX &
MIN displays, and Right Arrow resets the MAX/MIN
to the current value. Press Menu or wait 10 seconds
to return to Run Mode. Pressing Enter/Ack will disa-
ble the 10 second timeout and continuously display
Max or Min.
23
EU Declaration of Conformity
Issued in accordance with ISO/IEC 17050-1:2004 and ATEX Directive 2014/34/EU.
We,
Precision Digital Corporation
233 South Street
Hopkinton, MA 01748 USA
as the manufacturer, declare under our sole responsibility that the product(s),
Model PD6800 Series Loop Powered Meter
to which this declaration relates, is in conformity with the European Union Directives shown below:
2014/35/EU Low Voltage Directive
2014/34/EU ATEX Directive
2014/30/EU EMC Directive
2011/65/EU RoHS Directive
This conformity is based on compliance with the application of harmonized or applicable technical stand-
ards and, when applicable or required, a European Union notified body certification.
Standards:
EN 55022:2007 EN 61000-6-2:2005
EN 60079-0:2009 EN 61000-6-4:2004
EN 60079-1:2007 EN 61010-1:2001
EN 60079-31:2009 EN 61326:2006
The standards EN 55022:2007, EN 60079-0:2009, EN 60079-1:2007, EN 60079-31:2009, EN 61000-6-
4:2004, EN 61010-1:2001, and EN 61326:2006 are no longer harmonized. The requirements of these
standards have been checked against the harmonized standard EN 55022:2010, EN 60079-0:2018, EN
60079-1:2014, EN 60079-31:2014, EN 61000-6-4:2019, EN 61010-1:2010+A1:2019, and EN
61326:2013 and there were no major technical changes affecting the latest technical knowledge for the
products listed above.
EC Type Examination Certificate: Sira 10ATEX1116X
Product Markings: II 2 G D
Ex d IIC T6 Gb
Ex tb IIIC T85°C Db IP68
Tamb = -40°C to +75°C
ATEX Notified Body for EC Type Examination Certificate: CSA Group Netherlands B.V., NB 2813
Utrechtseweg 310
6812 AR, Arnhem, Netherlands
ATEX Quality Assurance Notification No.: SIRA 10 ATEX M462
ATEX Notified Body for Quality Assurance: CSA Group Netherlands B.V., NB 2813
Utrechtseweg 310
6812 AR, Arnhem, Netherlands
Signed for and on behalf of Precision Digital Corporation:
Sales Support
Call: (800) 343-1001 or (508) 655-7300
Fax: (508) 655-8990
Email: sales@predig.com
Place Orders
Email: orders@predig.com