QUADRUPLEX STACK MOUNTED

"Q" SERIES MEDICAL AIR SYSTEMS


7.5 THROUGH 20 HP
The Amico Alert-2 continuous duty Medical Air system
is a completely packaged NFPA 99 and NEC compliant
assembly featuring 100% oil-less air compressors, a U.L.
listed electrical control cabinet, an ASME receiver and the
necessary accessories required to meet and exceed the
current code requirements. All components are pre-piped
and pre-wired to single-point service connections. The
only field connections are air intake, air discharge and
power connection at the control panel. All interconnect-
ing copper/brass piping as well as wiring is completed and
operationally tested prior to shipment. Liquid tight con-
duit, fittings and junction boxes are provided for all
control and power wiring.
The entire system including the receiver is stack mounted
on a common structural steel base.

The medical air compressors are of the oil-less reciprocat-


ing air-cooled design. The air compressors feature a cast
iron crankcase, teflon-composite compression and rider
rings, lubricated and totally sealed bearings, stainless steel Local audible and visual alarms are provided per NFPA 99
reed valves, non-asbestos gaskets. No oil is used in for compressor thermal malfunction and "Backup in use".
operation of the compressors, so the discharge air is The alarms include indicating lights as well as the horn. In
100% oil-free. Cooling is provided by a fan type com- addition, the thermal malfunction shut-down is provided
pressor pulley with air shroud. with a manual reset. The audible alarm can be acknowl-
Compressors are V-belt driven by 3 phase, 60 cycle, 1750 edged with the "Silence" button. The visual alarm will
RPM, NEMA design B motors. remain energized until the problem has been corrected.
Each alarm function includes a set of dry contacts for
The system includes a pressure storage tank of ASME connection to the master alarm. All control and alarm
construction rated for 200 PSI MWP service. The tank is functions will remain energized while any compressor in
equipped with a pressure gauge, safety relief valve, 3 way the system remains electrically on-line.
by-pass, gauge glass and automatic tank drain with man- Field adjustable control switches are pre-set to operate the
ual override. lead compressor between 80 PSIG and 100 PSIG, the lag
Also included as standard equipment are compressor 1 compressor between 75 PSIG and 100 PSIG and the lag
discharge check valves of bronze construction, safety 2 compressor between 70 PSIG and 100 PSIG. The stand-
relief valves, bronze intake and discharge flexible con- by compressor will automatically start at 65 PSIG if one
nectors, solenoid unloaders for reliable no-load starting, of the other compressors fails to operate.
isolation valves, high discharge temperature shut-down The Medical Air system is guaranteed by the manufac-
switches, pressure control switches as well as copper turer for a period of 12 months from the date of start-up or
tubing with shut-off cock for gauge and switches. 18 months from the date of shipment (whichever comes
first) against defects in design, materials, or construction.
The system includes a UL labeled control panel in a Optional System Accessories
NEMA 12 enclosure. The panel includes the following (only checked options will be supplied)
standard accessories for each pump: externally operable
"Dura-coat" rust protection receiver lining
fusible disconnect switch with a door interlock, control
Galvanized receiver
circuit transformer with fused primary and secondary
Air-cooled aftercoolers
coils, H-O-A switch, run light, hour meter and magnetic
Circuit breakers
starter with 3 leg overload protection and reset switch. The
Dual medical air treatment system
panel is equipped with a multiple position selector switch
with refrigerated air dryers
for selection of normal operation (automatic alternation)
Dual medical air treatment system
or manual selection of lead and lag pumps if one of the
with desiccant air dryers
pumps is taken out of service due to scheduled mainte-
Interface to AIMS (AMICO Information
nance.
Management System)
QUADRUPLEX STACK MOUNTED
"Q" SERIES MEDICAL AIR SYSTEMS
7.5 THROUGH 20 HP
LAYOUT AND PERFORMANCE TABLE

DISCHARGE

INTAKE
(TYP.)

CONTROL
PANEL
RECEIVER
AIR COMPRESSOR

L W

System Horsepower Capacity SCFM (Each Pump) Disch. Tank Dimensions, In. Weight

Model Number Each Total 50 PSIG 100 PSIG Conn. (Gal.) L W H Lbs.

3QOQ7.5S240 7.5 30 32.5 27.6 1.5" 240 118 70 102 4690

3QOQ10S240 10 40 40.8 36.2 1.5" 240 118 70 102 4770

3QOQ15S240 15 60 60.5 51.0 2" 240 118 70 102 5280

3QOQ20S240 20 80 69.0 65.1 2" 240 118 70 102 5670

Note: Maximum ambient temperature: 100°F. For higher ambient temperatures consult factory.

Power Requirements:
(Four) _____ HP Motors, 3 Phase 60 Hertz 208 v 230 v 460 v

Phone 1-800-962-5385, Fax 1-973-471-9331, Web Site: http://www.amico.com October -2002