change the details shown on this data sheet without prior notice. The contents are intended for guidance only.

This data sheet is printed on 9lives 55 Silk, which is produced with 55% recycled fibre
from both pre and post-consumer sources, together with 45% virgin ECF fibre.
055-057/01/16 (3)
®

DSEMARINE
®

ON-BOARD
WITH
CONFIDENCE.
DSE5510M SPECIFICATION
AUTO & MANUAL START CONTROL MODULE (ELECTRONIC ENGINE ENABLED)

DC SUPPLY
8V to 35V continuous

CRANKING DROPOUTS
Able to survive 0V for 50mS, providing supply
was at least 10V before dropout and supply
recovers to 5V. This is achieved without the
need for internal batteries

MAXIMUM OPERATING CURRENT


460mA at 12V. 245mA at 24V

MAXIMUM STANDBY CURRENT


375mA at 12V. 200mA at 24V

ALTERNATOR INPUT RANGE


15V(L-N) to 333V AC (L-N) absolute maximum

ALTERNATOR INPUT FREQUENCY


50Hz - 60Hz at rated engine speed (Minimum:
15V AC L-N)

TYPE MAGNETIC PICK-UP VOLTAGE RANGE


+/- 0.5V to 70V Peak
APPROVED
PRODUCT MAGNETIC INPUT FREQUENCY
10,000 Hz (max)
Certificate no:
A-10081 START RELAY OUTPUT
16A DC at supply voltage

The DSE5510M is an Automatic generator short circuit protection, • Magnetic pick-up FUEL RELAY OUTPUT
16A DC at supply voltage
Engine Control Module, designed reverse power, generator phase
to provide advanced load share rotation error, earth fault protection, LOAD SHARE FEATURES AUXILIARY RELAY OUTPUTS
functionality for diesel and gas loss of speed signal, fail to open, • ROCOF & vector shift Three outputs 5A DC at supply voltage
generating sets that include non- fail to close, out of sync, MPU • Automatic starting & stopping of Two outputs volt free 8A at 250V AC

electronic and electronic engines. open circuit failure, negative phase generator on load demand
DIMENSIONS
The module also provides sequence and loss of excitation. • Automatic hours run balancing of 240mm x 172mm x 57mm
generator sets 9.4” x 6.8” x 2.2”
excellent engine monitoring and
• Dead bus sensing
protection features. FEATURES PANEL CUTOUT
• Module has the ability to interface
• Electronic engine capability with existing load share lines
220mm x 160mm
• RS232 or RS485 remote 8.7” x 6.3”
The modules load share functions • Direct communication from the
include, automatic synchronising communications module to the governor and AVR CHARGE FAIL/EXCITATION RANGE
with built in synchroscope and • Modbus RTU • Link up to 16 generators 0V to 35V
closing onto dead bus. Direct and • Pin number protected front panel • Volts & frequency matching
programming BUILT IN GOVERNOR CONTROL
flexible outputs from the module • KW and Kvar load sharing with Fully Isolated
are provided to allow connection • Engine exercise timer multiple generators Minimum Load Impedence:
• Back-lit LCD 4-line text display 1000Ω
to the most commonly used speed
• Multiple display languages BENEFITS
Gain Volts 0V - 10V DC
governors and automatic voltage Offset Volts + / - 10V DC
• Voltage measurement • Sends SMS messages to
regulators (AVRs). • Configurable inputs (9) engineers to notify specific BUILT IN AVR CONTROL
• Configurable outputs (5) engine problems (GSM Modem Fully Isolated
The module has been designed to • Automatic start Minimum Load Impedence:
combine a maximum of 16 and SIM card required) 1000Ω
• Manual start • On-site and remote module Gain Volts 0V - 10V DC
generators and 16 mains (utility) • Audible alarm configuration Offset Volts + / - 10V DC
supplies up to a maximum of 20 in • LED indicators • In-built engine diagnostics
one system, e.g. 16 generators and • Built-in governor and AVR control removes the requirement for
ENCLOSURE PROTECTION
• Engine history event log (front of module)
4 mains (utility) supplies (DSE5560 service equipment IP55 (with optional gasket)
required to synchronise with the • Engine protection • Full engine protection & IP42 (without gasket)
mains). • Fault condition notification to a instrumentation without the need
designated PC for additional senders (Electronic
The module has the ability to • Front panel mounting engines only)
monitor under/over generator • PC configuration • Remote monitoring of the module
• Bus failure detection using comprehensive DSE PC
volts, over current, under/over
• Configurable alarm timers software
generator frequency, under speed,
• Configurable start & stop timers • License free PC software
over speed, charge fail, emergency • Automatic load transfer
stop, low oil pressure, high engine • SMS alert messaging
temperature, fail to start, low/high • Front panel mounting
DC battery volts, fail to stop, • Remote monitoring ELECTRONIC ENGINE CAPABILITY
OPERATION TELEMETRY
ENVIRONMENTAL TESTING The module is operated using the front STOP/RESET, MANUAL, AUTO and The module gives the user full
STANDARDS START push buttons. Three of these push buttons include an LED indicator. telemetry facilities when using the
Additional push buttons provide LCD display scroll, lamp test, mute optional communications software.
ELECTRO MAGNETIC CAPABILITY functionality and breaker control. The module can be connected to a
BS EN 61000-6-2 PC using the DSE810 PC interface
EMC Generic Emission Standard for the
Industrial Environment
TIMERS & INPUT FUNCTIONS or by using a suitable modem.
BS EN 61000-6-4 The module has been designed to include the following timers and input functions:
EMC Generic Emission Standard for the The PC software is Microsoft
Industrial Environment • Start delay timer Windows™ based. All access into
ELECTRICAL SAFETY
• Stop delay timer the module can be configured to
BS EN 60950 • Crank timer become password protected to
Safety of Information Technology Equipment, • Crank rest timer prevent unauthorised entry. The PC
including Electrical Business Equipment • Engage attempt & manual crank limit timers software allows the module to be
TEMPERATURE
• Safety on delay timer controlled from a remote location.
BS EN 60068-2-2 • Warm up timer
Test Ab to +70oC 60067-2-2 Hot • Cooling timer COMMUNICATIONS
Test Ab to -30oC 60068-2-1 Cold • Energise to stop hold timer The DSE5510M has a number of
VIBRATION
• Pre-heat timer different communication capabilities.
BS EN 60068-2-6 • Pre-heat bypass timer
Ten sweeps in each of three major axes • Smoke limiting control timer SMS Messaging
5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn • Fail to stop timer When the module detects an alarm
HUMIDITY
• Over speed over shoot timer condition, it has the ability to send
BS 2011 part 2.1 60068-2-30 • Breaker pulse control timers an SMS message to a dedicated
Test Cb Ob Cyclic • DC battery alarm delay timers mobile number, notifying an engineer
93% RH @ 40oC for 48 hours • Sync/fail to sync timer of the problem. (GSM Modem and
SHOCK SIM Card required).
BS EN 60068-2-27 BUILT-IN FUNCTIONS
Three shocks in each of three major axes • Alternator under/over volts Remote Communications
15gn in 11mS • Alternator under/over frequency When the module detects an alarm
• Warning or shutdown on engine temperature, over/under speed, oil condition, it dials out to a PC notifying
pressure the user of the exact alarm condition.
• Warning, shutdown or electrical trip on battery volts or over current
TYPICAL LOAD SHARE • Shutdown or electrical trip on reverse power, phase rotation or short Vessel Management
APPLICATION circuit fault The module has been designed to
• Earth fault shutdown be integrated into new and existing
• Adjustable crank cycle/attempts vessel management systems.
• Full remote control and telemetry
G1
• 9 configurable digital inputs PC Software
• 5 configurable and 2 fixed relay outputs The module has the ability to be
• System lock input configured and monitored from a
• Load switching control push-button inputs remote PC, using the DSE810
G2 • ROCOF/vector shift (mains/utility decoupling) interface (modem required).
• Negative phase sequence
• Loss of excitation EVENT LOG
The module includes a
G3 LOAD INSTRUMENTATION AND ALARMS comprehensive event log that
The DSE5510M module provides advanced metering and alarm functionality shows the 25 most recent alarm
via the LCD display. The information can be accessed using the display scroll conditions and the date and time
push buttons. The table below shows the instrumentation and alarm features that they occurred.
the module provides.
This function assists the user when
Generator Volts L1-N, L2-N, L3-N fault finding and maintaining the
Generator Volts L1-L2, L2-L3, L3-L1 generating set.
Generator Amps L1, L2, L3
Generator Frequency Hz EXPANSION MODULES
Generator kVA L1, L2, L3, Total DSE123 Load Share Lines Interface
Generator kW L1, L2, L3, Total Module
Generator pf L1, L2, L3, Average DSE157 Relay Input Expansion
Generator kVAr L1, L2, L3, Total Module
Generator KWh DSE545 & DSE548 Remote
Generator KVAh Annunciation Expansion Module
Generator KVArh DSE130 Input Expansion Module
Generator Phase Sequence
Synchroscope Display ELECTRONIC ENGINE
Engine Speed RPM COMPATIBILITY
Engine Oil Pressure • Cummins
Engine Temperature • Deutz
Plant Battery Volts • John Deere
Engine Hours Run • MTU
Number of Start Attempts • Perkins
Maintenance Display • Scania
Engine ECU diagnostics information via industry standard CAN interface • Volvo
Enhanced metering via CAN when connected to an electronic engine • Generic
• Plus additional manufacturers
®

DSE5510M
AUTOMATIC MCCB
AUTOMATIC ACB
or CONTACTOR
CTs MUST BE 5 AMP
CONNECT TO 3 or 4 POLE
SECONDARY
BATTERY NEGATIVE
P1 P2
L1 L1
S1 S2

L2 L2

FROM
GENERATOR L3 L3 TO LOAD

N N

2 AMP 2 AMP
FUSES

SCREEN EARTHED AT
SCREEN EARTHED AT

FUSES

SCREEN TO ENGINE
SCREEN TO ENGINE
TO MAG PICK UP IF

DO NOT CONNECT
DO NOT CONNECT
TO GEN SWITCHING

TO ENGINE ECU

THIS END ONLY


DEVICE CIRCUITRY

THIS END ONLY


USED

49 50 51 52 53 45 46 47 48 39 40 20 21 22 37 38 54 55 56 29 30 31 23 24 25 41 42 43 44

CT1 CT2 CT3 CT4 COM L1 L2 L3 N SCR SCR B A SCR B L L1 L2 L3 N


UNUSED

L151 L251 L351 N52 MPU RS485 J1939


BUS VOLTS
GEN VOLTS CLOSE OUTPUT
GEN CURRENT GEN 5
OUTPUT
4
P810 TO OTHER 5510M’s
SCR 26 MSC CONNECTIONS
MAX 250 METERS
RS232

MODULE 5510M MSC H 27


120 OHM SCREEN CABLE
COMMON GROUND

L 28
CRANK
FUEL

OIL PRESSURE

WATER TEMP

CHARGE ALT

157

UNUSED
BATTERY 3 OUTPUTS THE FIRST AND LAST UNITS
PLANT +VE
GOVERNOR AVR
MSC MUST BE FITTED WITH A
FUEL

9 INPUTS
O/P O/P
+VE

-VE

B A B A 120 OHM RESISTOR ACROSS


2 1 3 4 5 57 58 59 60 9 10 11 12 13 14 15 16 17 18 6 7 8 19 32 33 34 35 36 H(27) AND L(28)
TO BATTERY NEGATIVE
TO CRANK SOLENOID MAX 16AMP
TO FUEL SOLENOID MAX 16AMP

CHARGE ALTERNATOR
FOR REMOTE EM STOP
REMOVE LINK FOR

USER CONFIGURATION INPUT 1

USER CONFIGURATION INPUT 2

USER CONFIGURATION INPUT 3

USER CONFIGURATION INPUT 4

USER CONFIGURATION INPUT 5

USER CONFIGURATION INPUT 6

USER CONFIGURATION INPUT 7

USER CONFIGURATION INPUT 8

USER CONFIGURATION INPUT 9

USER CONFIGURATION INPUT +VE OUTPUT

USER CONFIGURATION INPUT +VE OUTPUT

USER CONFIGURATION INPUT +VE OUTPUT


FUEL TEMP
HIGH COOLANT TEMP
LOW OIL PRESSURE

TO TO
GOVERNOR AVR
CONECT SCREEN AT

CONECT SCREEN AT
GENERATOR ONLY

GENERATOR ONLY
TO BATTERY NEGATIVE

SCREEN EARTHED
AT THIS END ONLY
ANTI-SURGE FUSE

UPTO32 AMPS
MAX 20 AMP
MIN 2 AMPS

FUSE

BATTERY +VE
(12 OR 24 VDC ) BATTERY -VE

ALL BATTERY NEGATIVES MUST BE CONNECTED TOGETHER

RELATED MATERIALS
TITLE PART NO’S
DSE5510M Manual 057-080
DSE123 Data Sheet 055-044
Load Share Design & Commissioning 057-047
Guide to Synchronising and 057-045/6
Load Sharing
55xx Software manual 057-007
CAN & DSE wiring guide 057-004