DAMPERS TECHNICAL SUBMITTAL

DATE: FEB 14, 2019


25

  
   

www.airmasteremirates.com
19.0 FIRE
DAMPER

19.0 index

INDEX
SECTION TOPIC PAGE

19.1 Introduction 3

19.2 Curtain Type Fire Damper : AFD-3 6

19.3 Dimensional Details 7


19.4 Motorized Fire Damper : AMFD 8
19.5 Dimensional Details 9

19.6 Motorized Fire & Smoke Damper : AMFSD 10


19.7 Dimensional Details 11

19.8 Motorized Smoke Damper : AMSD 12


19.9 Dimensional Details 13
19.10 Controls 14

2015 Edition.
www.airmasteremirates.com 02 Copyright reserved. Specifications subject to change without notice.
19.1
FIRE
DAMPER
INTRODUCTION

Smoke and Flames rising from residential


buildings, hotels and warehouses have become a
common sight nowadays. Out of 1.2 million fires
reported in the U.S.A in 2013, almost 39% of the
cases were structural fires causing more than 2800
deaths and $9.5 billion in property damage¹. The
‘Center for Disease Control and Prevention’ notes
death from fires and burns are the fifth most
common cause of unintentional injury deaths and
third leading cause of fatal home injury. SMOKE
inhalation during fire accidents is another major
reason for deaths in such cases.

In a case study conducted by NFPA, it was found


that the HVAC system was not linked to smoke
detector system and did not shut off during fire
accident. The air from the operating HVAC system
and Natural ventilation increased the growth of the
fire. It is therefore important to cutoff air supply by
shutting down HVAC system during fire. Various
fire safety equipment are prescribed by national
authorities in their building codes to overcome fire Fire dampers are installed in fire rated walls /
hazards in order to save life and property. One barriers / partitions where the HVAC ductwork
such requirement is the use of FIRE DAMPERS in penetrates ensuring that their integrity is
the HVAC system. maintained. The location and installation procedure
of fire dampers should be in accordance with the
Fire damper is a device installed in an air widely accepted and recommended standard,
distribution system or an air transfer opening NFPA 90A – Standard for the installation of Air-
designed to close automatically upon detection of Conditioning.
heat interrupting airflow and thereby restricting the
passage of fire in the process.

Fire Damper AFD-3


Supply Air duct -Curtain Type Fire damper
Motorized Smoke Damper-AMSD Closed When the Fusible Link
-Electrically Operated Smoke Temperature Reaches 165 Deg Fahrenheit
Horizontally Mounted Vertically Mounted Damper Closed In response to
Signal From Smoke Detector. Breakaway Duct Connection
Air Outlet Smoke Spread Fire Spread Concrete Floor

Fire and Smoke Spread contained 3 Hours Fire Rated UL Approved


by Installing Airmaster Make Dampers Airmaster Fire Protection Dampers

Room 1 Room 2 3 Hour Fire Rated Room 3


Wall barrier

¹SOURCE : NFPA research

2015 Edition.
Copyright reserved. Specifications subject to change without notice.
03 www.airmasteremirates.com
19.1
FIRE
DAMPER

The most prominent testing laboratories for The open/close position can be monitored by
evaluating fire resistive materials and assemblies is introducing a limit switch or Auxiliary switch in the
the Underwriters Laboratory (UL), U.S.A. All damper which communicates the open/close status
Airmaster Fire dampers are tested and certified by to the BMS or a standalone control panel. As a
UL. result, further actions could be programmed like
switching on smoke extract fans or switching off all
Airmaster fire dampers are developed with the HVAC units or informing Fire department and so on.
intention of maximizing the occupant's safety. There
are two basic types of damper operations: a) Curtain UL Testing:
type b) Multiple blade type. Though construction of Airmaster has taken great efforts in developing fire
both dampers are different, the purpose is the same – dampers and getting it certified from UL after passing
to interrupt airflow in order to restrict the passage of their stringent testing procedures successfully. Our
fire & smoke. dampers have withstood the demanding test
requirements of UL 555 and UL 555S standards.
Curtain type: The blades are folded and held under Both these standards call of series of tests like:
spring tension using a bi-metal fusible link. Heat of
165oF (74oC) inside the duct is sufficient for fusible
link to melt and break, thus allowing blades to shut
like a curtain under the force of the springs attached.
The fire damper acts as a barrier between fire and
non-fire zones thus containing the fire in the
compartment from which it originated. This gives
sufficient time for occupants to escape and move into
safety.

Multiple blade type: This model operates mainly


using an electric actuator. Based on the application –
i.e. Fire, Smoke or Combination Fire & Smoke; the
actuator can be configured with the Building
management system (BMS) or a smoke detector.
The electric actuator is energized with power supply
to keep the damper open under normal conditions. Fire Test
When heat/smoke is detected by the thermal
responsive device (TRD) / smoke detector, power
supply to actuator will be disconnected.

Should the BMS be used to close the actuator, it has


to be configured to disconnect power supply to
actuator. Once the circuit is open, the damper closes
automatically by the force of the springs inside the
actuator. Such actuators are otherwise known as
spring return actuators. TRD’s are supplied with a
reset button to re-establish power supply thereby
keeping the damper in open position.

Hose Stream Test

2015 Edition.
www.airmasteremirates.com 04 Copyright reserved. Specifications subject to change without notice.
19.1
FIRE
DAMPER

off-loading and storage at site against any physical


cycling test for operational reliability, salt water
damage. All fire dampers must be stored in a safe
spray test, fire endurance test followed by high
place and must be handled carefully. Dampers
pressure hose stream test, leakage test, dynamic
especially with actuators and electrical accessories
closure test and overall integrity of the damper is
must be stored in a dry enclosed area to avoid
also checked. Quality inspection is carried out on
condensation. Actuators or damper blades should
regular basis by UL representatives to ensure if
not be used for lifting during installation
manufacturing is done be per the mandate.

UL listed products are finally dispatched after UL Maintenance: Regular inspection and maintenance
labels are proudly pasted on each and every fire of fire damper is essential. NFPA 80 – standard for
damper. The installation has to be carried out fire doors and other opening protective states that
strictly as per the installation instructions that is sent fire dampers shall require inspection and testing
along with every shipment. one year after installation. Follow up testing and
inspection shall be done every 4 years except in
hospitals where the frequency shall be 6 years.
Most common installation errors to be avoided:

• Fixing of duct directly to the Fire damper frame is


not allowed.
• Rigid Duct – Sleeve connection without
complying sleeve thickness recommended by
SMACNA (table 5-2). It is important to note that
improper installation procedures could render UL
listing of the damper null and void.

Handling & Storage: Fire dampers are sensitive


products made for the sole purpose of saving life and
property. Therefore extreme care must be taken The Time / Temperature curve achieved during the
while handling fire dampers during loading,
fire test by UL laboratory is as shown above .

2015 Edition.
Copyright reserved. Specifications subject to change without notice.
05 www.airmasteremirates.com
19.2 CURTAIN TYPE
FIRE DAMPER CURTAIN TYPE FIRE DAMPER
Model : AFD-3
3 hrs Fire Rating

CONSTRUCTION:
Frame: High quality galvanized steel sheet of Spring: Constant force stainless steel springs
thickness 16 gauge. on both sides.
Blades: Interlocking type roll formed blades UL listed Fusible Links: 165o F fire rating as
of thickness 20 gauge. standard.
Blade Ramp: 16 gauge thick galvanized steel
with a spring holder.

Description:
• The interlocking type blades are designed with hat shaped reinforcement
ridges ensuring strength and stability.

• The ramp is firmly secured to the frame by S.S rivets.

• The frame is designed to keep blades out of airstream to prevent dust and
contamination.

• All corners of the frame are fully welded (and painted to prevent rust) to
ensure sturdy construction.
• AFD-3 model fire dampers are UL 555
classified & manufactured under Airmaster’s
strict quality control procedures.

• AFD-3 series fire dampers are UL classified


for 3 hours static application only.
• UL approved sizes as are follows:

Maximum Mounting
Section Fire Rating Wall Type
Size W x H Position
Single 42" x 42" Vertical 3 Masonry/Gypsum

Single 36" x 36" Horizontal 1.5 Masonry/Gypsum

Multiple 84" x 84" Vertical 3 Masonry/Gypsum

Multiple 94" x 94" Vertical 1.5 Masonry

Options:
• Frame: Round or Oval Inlet/Outlet.
• Sleeve: Provided only on request with sheet thickness 16 gauge.
• UL listed Fusible link: 212oF fire rating up to 27” x 41”(for vertical application only).
• Micro switch: To know the status of damper’s blade open & close position.
2015 Edition.
www.airmasteremirates.com 06 Copyright reserved. Specifications subject to change without notice.
CURTAIN TYPE 19.3

FIRE DAMPER

Model : AFD-3

Dimensional Details:

Neck Size Outer Size Neck Size Outer Size


W (mm) x H (mm) W (mm) x H (mm) W (mm) x H (mm) W (mm) x H (mm)
100 x 100 140 x 140 550 x 550 590 x 635

150 x 150 190 x 190 600 x 600 640 x 685

200 x 200 240 x 240 650 x 650 690 x 745

250 x 250 290 x 305 700 x 700 740 x 795

300 x 300 340 x 355 750 x 750 790 x 855

350 x 350 390 x 415 800 x 800 840 x 905

400 x 400 440 x 465 850 x 850 890 x 965

450 x 450 490 x 525 900 x 900 940 x 1015

500 x 500 540 x 575 940 x 940 980 x 1065

How to order:
Limit Switch With Sleeve
Size (mm/inch) Quantity (no.)
(Yes/No) (Yes/No)
500 x 500 250 No No

* All the given sizes are considered as neck size

2015 Edition.
Copyright reserved. Specifications subject to change without notice.
07 www.airmasteremirates.com
19.4 MOTORIZED
FIRE DAMPER MOTORIZED FIRE DAMPER
Model : AMFD 1.5 hrs Fire Rating

CONSTRUCTION:
Frame: High quality galvanized steel sheet of T.R.D : Belimo (UL listed), temperature rating -
thickness 16 gauge. 165oF.

Blades: Single skin roll formed from high Jamb Seal: Stainless steel.
quality steel sheet of thickness 16 gauge.

Actuator: Honeywell, 9NM torque (UL listed).

Description:
• All corners of the frame are fully welded (and painted
to prevent rust) to ensure sturdy construction for a
rattle free operation.

• Designed for parallel blade operation. Blades are


linked together externally (out of airstream).

• AMFD model fire dampers are UL 555 classified &


manufactured under Airmaster’s strict quality control
procedures.

• All actuators are externally mounted with 230VAC as


standard and are supplied without inbuilt auxiliary
switch.

• Actuator position will be based on Clockwise (CW)


closure direction as standard.

• TRD’s have an inbuilt manual RESET switch to reopen


the damper after closure.

• All AMFD models are factory fitted with 400mm wide &
1.2mm thick steel sleeve as standard and the entire
assembly can comfortably seat through 8” thick wall.
• All dampers and TRD’s are factory tested before dispatch to ensure smooth operation
in the field.

• Can be used in Masonry and Gypsum walls/partitions of less than 3 hours fire resistance rating as per
NFPA 90-A in accordance with ANSI/UL555 standards.

• Maximum Approved
. Size:
• Multiple section : 70” x 70” (vertical installation / Static application only)
• Single section : 35” x 35” (vertical installation / Static & Dynamic application).

2015 Edition.
www.airmasteremirates.com 08 Copyright reserved. Specifications subject to change without notice.
MOTORIZED 19.5

FIRE DAMPER

Model : AMFD

Options:
• Gasket: UL approved gasket
• Actuator Position: Counter Clockwise direction (CCW)
• Operating Voltage: 24VAC / 120VAC
• Auxiliary Switch: Actuator with inbuilt auxiliary switch

Dimensional Details:

How to order:
Actuator Auxiliary
Size Gasket
Qty (no.) Voltage Position Switch
(mm/inch) (Yes/No)
(CW/CCW) (Yes/No)
400 x 400 100 240VAC CW Yes Yes

500 x 500 250 24VAC CCW No No

2015 Edition.
Copyright reserved. Specifications subject to change without notice.
09 www.airmasteremirates.com
19.6
MOTORIZED FIRE & SMOKE
DAMPER
MOTORIZED FIRE & SMOKE DAMPER
1.5 hrs Fire Rating
Model : AMFSD

CONSTRUCTION:
Frame: High quality galvanized steel sheet of T.R.D : Belimo (UL listed),temperature
thickness 16 gauge. rating -165oF.

Blades: Single skin roll formed from high Jamb Seal: Stainless steel.
quality steel sheet of thickness 16 gauge.
Gasket : UL listed gasket.
Actuator: Honeywell, 9NM torque (UL listed).

Description:
• All corners of the frame are fully welded (and
painted to prevent rust) to ensure sturdy
construction for a rattle free operation.

• Designed for parallel blade operation.

• AMFSD series combination Fire/Smoke dampers


are UL 555/555S classified

• AMFSD Dampers are available with Class II


leakage rating at 2000fpm (10.2m/s) / 4”w.g
(1000pa). Suitable for most of the commercial
smoke management applications in both static and
dynamic systems.

• All actuators are externally mounted with 230VAC


as standard and are supplied without inbuilt
auxiliary switch.
• Actuator position will be based on Clockwise (CW) closure direction as standard.

• TRD’s have an inbuilt RESET switch to reopen the damper.

• All AMFSD models are factory fitted with 400mm wide & 1.2mm thick steel sleeve
as standard and the entire assembly can comfortably seat on 8” thick wall.

• All dampers and TRD’s are factory tested before dispatch to ensure smooth operation
in the field.

• Actuators have to be configured with control panel or BMS system for smoke control
applications before commissioning.

• Can be used in Masonry and Gypsum walls/partitions of less than 3 hours fire resistance
rating as per NFPA 90-A in accordance with ANSI/UL555 standards.

2015 Edition.
www.airmasteremirates.com 10 Copyright reserved. Specifications subject to change without notice.
19.7
MOTORIZED FIRE & SMOKE
DAMPER
Model : AMFSD

• Maximum Approved Size:


• Multiple section : 70” x 35” (vertical installation / Static & Dynamic application).
• Single section : 35” x 35” (vertical installation / Static & Dynamic application).
Options:
• Auxiliary Switch: Actuator with inbuilt auxiliary switch.
• Operating Voltage: 24VAC / 120VAC.
• Actuator Position: Counter Clockwise direction (CCW).

Dimensional Details:

How to order:
Actuator
Quantity Auxiliary Switch
Size (mm/inch) Voltage position
(Nos) (Yes/No)
(CW/CCW)

600 x 600 50 240VAC CW Yes

2015 Edition.
Copyright reserved. Specifications subject to change without notice.
11 www.airmasteremirates.com
19.8
MOTORIZED SMOKE
DAMPER
MOTORIZED SMOKE DAMPER
Model : AMSD 1.5 hrs Fire Rating

CONSTRUCTION:
Frame: High quality galvanized steel sheet of Jamb Seal: Stainless steel.
thickness 16 gauge.
Gasket : UL listed gasket.
Blades: Single skin roll formed from high
quality steel sheet of thickness 16 gauge.

Actuator: Honeywell, 9NM torque (UL listed).

Description:
• Available with Class II leakage, rated at 2000fpm (10.2m/s) / 4”w.g(1000pa).Suitable for most of the
commercial smoke management applications in both static and dynamic systems.

• All corners of the frame are fully welded (and painted to prevent rust) to make construction more sturdy for
a rattle free operation.

• Designed for parallel blade operation. Blades are linked together externally (out of airstream).

• AMSD series is UL 555S classified and manufactured under Airmaster’s strict quality control procedures..

• All actuators are externally mounted with 230VAC as standard and are supplied without inbuilt auxiliary
switch. The actuator can be controlled from command station.

• Factory fitted with 400mm wide & 1.2mm thick steel sleeve and the entire assembly can comfortably seat
on 8” thick wall.
• All dampers are factory tested to ensure smooth
operation before dispatch.

• Actuators have to be configured with smoke


detector/ control panel or BMS system for smoke
control applications before commissioning.

• Can be used in Masonry and Gypsum


walls/partitions of less than 3 hours fire resistance
rating as per NFPA 90-A in accordance with
ANSI/UL555 standards.

• Maximum Approved Size:


• Multiple section : 280” x 35”
(Actuators internally mounted /
vertical installation only)
• Single section : 35” x 35” (vertical
installation only).

2015 Edition.
www.airmasteremirates.com 12 Copyright reserved. Specifications subject to change without notice.
19.9
MOTORIZED SMOKE
DAMPER
Model : AMSD

Options:
• Auxiliary Switch: Actuator with inbuilt auxiliary switch.
• Operating Voltage: 24VAC / 120VAC.
• Actuator Position: Counter Clockwise direction (CCW).

Dimensional Details:

How to order:

Actuator Auxiliary
Quantity TRD
Size (mm/inch) Voltage position Switch
(Nos) (Yes/No)
(CW/CCW) (Yes/No)

700 x 700 15 24VAC CCW Yes Yes

2015 Edition.
Copyright reserved. Specifications subject to change without notice.
13 www.airmasteremirates.com
19.10

FIRE
DAMPER HONEYWELL - CONTROLS

Model - MS4609F1010 :
• Line voltage (230 Vac), 9 (N‫ڄ‬m) torque and without open
& close position-indicating switches.

Model - MS4609F1210 :

• Line voltage (230 Vac), 9 (N‫ڄ‬m) torque and with open & close
position indicating switches.
Model - MS8109F1010:
• Line voltage (24 Vac), 9 (N‫ڄ‬m) torque and without open &
close position-indicating switches.

Model - MS8109F1210 :
• Line voltage (24 Vac), 9 (N‫ڄ‬m) torque and with open & close
position indicating switches.

Temperature Ratings :
• The actuator is designed to meet UL555S standards at 350°F (176°C).

Open & Close Timings:

• Drive Open: 15 seconds typical

• Spring Close: 15 seconds typical.

Environmental Protection Ratings:


• NEMA, IP40.

Operation:
• In case of fire, damper operates on volt free signal to the actuator. i.e spring return
operation.

Mounting:
• Actuator can be used for either clockwise (CW) or counter clockwise (CCW) spring
return.

2015 Edition.
www.airmasteremirates.com 14 Copyright reserved. Specifications subject to change without notice.
3URWHFW \RXU EXLOGLQJ ZLWK ¶$'9$1&(·
)LUHUDWHGVWHHOGRRUV

    

 
    

  !!!
#$%&'()(*)'(*')%&'()(*)(
+$%+;;<#+!#$#<+;#;!#
Non Return Dampers

air master
Non return damper
√ Wall mounted
Model: ANRD-W

Construction:
• Frame: High quality extruded aluminium profile
with 30 mm flange width as standard. 12, 16, 24
mm flange widths are optional.
• Blades: Aluminium sheet as standard. GI sheet
as option.
• Blade supports: Self oiling nylon bushings with
8 mm diameter aluminium rods.
• Blade seals: Foam gasket for air tightness.
• Blade stoper: 20 mm x 20 mm aluminium angle.
• Designed to maintain a constant pressure level
Description: inside pressurized rooms by relieving excess air
• Frame is of high quality extruded aluminium pro- when it exceeds the desired limit.
filed construction with the advantages of corro-
sion resistance and rigidity. • Generally installed on diesel generator, plant
rooms ventilation system and exhaust ducting.
• Air operated damper blades are fixed to the
frame by self oiling nylon bushes with 8 mm dia • Available in square and rectangular sizes.
aluminium pipes.

• Blades are sealed with foam gasket at the bot-


tom to avoid rattling noise and to provide air tight
operation.

• Blades open fully or to any angle depending on


the air velocity. Blades stay in position of opening
with out fluctuating when there is constant air-
flow. Blades closes quietly when the air flow
stops.

Copyright reserved. Specifications subject to change without notice.

18.1
ISO 9002 certified company
Non Return Dampers

air master
Non return damper
√ Duct mounted
Model: ANRD-D

Construction: • Designed to maintain a constant pressure level


• Frame: High quality galvanized steel sheet. inside pressurized rooms. Used at duct outlets to
• Frame size: 125 mm depth and standard flange prevent back draft when air moving devices are
height of 25 mm. switched off.
• Blades: Aluminium sheet as standard. GI sheet
as option. • In a multi fan installation non return dampers pre-
• Blae supports: Self oiling nylon bushings with 8 vent back draft through the operating fans.
mm diameter aluminium rods.
• Blade seals: 20 mm x 20 mm aluminium angle. • Structure is available with flanged edges and are
supplied un drilled as standard.
Description:
• Available in square and rectangular sizes.
• Frame is constructed from galvanized steel
sheet. Welded joints are protected by aluminium
spray coating.

• Air operated damper blades are fixed to the


frame by self oiling nylon bushes with 8 mm dia
aluminium pipes.

• Blades are sealed with foam gasket at the bot-


tom to avoid rattling noise and to provide air tight
operation.

• Blades open fully or to any angle depending on


the air velocity. Blades stay in position of opening
with out fluctuating when there is constant air
flow. Blades close quietly when the air flow stops.

Copyright reserved. Specifications subject to change without notice.

18.2
ISO 9002 certified company
DUCT REGULATING DAMPERS

R E G U L A T I N G
D A M P E R S

DD
SERIES
MANUFACTURERS OF AIR/FIRE/SMOKE CONTROL PRODUCTS
Product Description and Features

Introduction Blades
The DD Series Duct Balancing Damper was designed The 63mm wide extruded aluminium airfoil section
for duct installations to balance/regulate airflows. blades are fitted to 12.5mm diameter spindles, with the
option of galvanised mild steel or Grades 316 and 430
All spindles revolve in low maintenance nylon bushes
stainless steel blades available to order.
which are fitted within pressed inserts. Precise blade
positioning is achieved via a robust dual-purpose All models are available with either opposed or parallel
quadrant and spindle assembly, operating the linkage blades (unless specified, opposed blades will be
mechanism which is located outside of the airstream. supplied as standard).
The quadrant assembly is designed to facilitate simple Fitted to the ends of the aluminium blades are End
conversion to motorisation without the need for Caps to alleviate noise generation.
additional components.

Features
Plain
, Standard case construction is galvanised mild steel Aluminium
, Two airfoil blade designs Blade

, Four casing options


, Out of airflow linkage
, Easy conversion from manual to motorised
or vice versa
, Infinite sizing capability from 100mm to 1000mm and
from 100mm diameter to 800mm diameter
, Variable flange dimensions
, Comprehensive control options
End Cap
, Can be supplied with blades and case in Grades
316 and 430 stainless steel
, Stainless steel side seals to order

Specifications & Testing


, Unless stated otherwise, flange models are suitable
for classes A & B of DW144, with spigot models
suitable for classes A, B & C of DW144
, Conforms to HVCA specification DW144
, Conforms to Eurovent 2/2 classes A-C
, Independent performance tests for pressure loss,
leakage and casing airtightness.
Test reports 143, 145 and 146 refer respectively

Galvanised Mild
Steel or Stainless
Steel Blade

MANUFACTURERS OF AIR/FIRE/SMOKE CONTROL PRODUCTS

1
Dimensions

Flangefit 105
* * W * ‘Tear Drop’ Hole Detail

m
W x H = 100mm to

m
15
1000mm square 5.5 Rad.
Ņ
3.5 Rad.
B = 20mm, 25mm and
30mm to order H

m
Dims

m
(35mm standard)

24
+ 0.25mm

*= 35mm flange - depending


on size of
50mm spindle flange -
30mm flange -
B
A * bolt sizes Ņ
range from 6-10mm dia.
55mm spindle

Spigotfit 40 85 40 55
30 W 30
W x H = 100mm to 30
1000mm square

30

Circular 85 55
* * 30 D 30
Spigotfit See Table Page 3

D = 100mm to 800mm
diameter

D H-D (Equidistant)

* = 40mm
(100-449mm dia.)
See Table Page 3
55mm
(450-800mm dia.)

Flat Oval
Spigotfit
W x H = 100mm to
1000mm spigots

MANUFACTURERS OF AIR/FIRE/SMOKE CONTROL PRODUCTS

2
Circular Spigotfit Dimensions

Depth Width Height


(D) (W) (H)
100 160 140
125 185 195
W
150 210 210
200 260 260
250 310 320
300 360 385
315 375 385
350 410 385
400 460 460 D H

450 510 510


500 560 580
550 610 640
600 660 700
650 710 770
700 760 770
750 810 830
800 860 895

Multiple Assemblies

Illustrated below are several variants to multiple section For applications which necessitate the blades to be
units. Where sizes exceed 1000mm square, multi- installed vertically, BSB’s sales office must be informed
section units will be supplied. so that thrust bearings are fitted to eliminate blade
friction.
All multiple units are shipped as individual sections for
site assembly by others. Unless requested, joining It is recommended that for sizes greater than
strips would not normally be supplied drilled. 1000mm width or height, the HD Series Heavy Duty
Damper is used.

MANUFACTURERS OF AIR/FIRE/SMOKE CONTROL PRODUCTS

3
Control Options

Option E 50
Extended Spindle
When the specification requires the DD Series Damper
to be supplied for motorisation by others, BSB supplies
the damper with a 12.5mm diameter spindle, 50mm in
length, based on a 35mm flanged damper.

Option H
Hand Control
BSB’s unique hand lockable quadrant is supplied
complete from the factory.
When the specification is amended from Option “E” to
Option “H” conversion is easily completed.

Option M
Electric Motor
The DD Series Damper can be supplied with the
following control motors fitted:
Open/Close operation:
A = 70mm, 15Nm.
A = 80mm, 30Nm.
Spring Return operation:
A = 95mm, 15Nm.
For additional technical details, please contact BSB’s sales office for
data sheets to Option “M”.

Option P
Pneumatic Actuator
The model actuator used will be double rack and pinion design with bodies
manufactured of cast aluminium alloy.
The pneumatic actuator operates between 30psi/2bar and 120psi/8bar.
The pneumatic actuator is available as a Spring Return or Double Acting
model and will comply to PED 97/23/EC.
It is supplied fitted to the damper complete with integral threaded 1/4bsp
air-ports to pressurize and vent the actuator. Various accessories are available
including Solenoid Valves and Switch Boxes. ATEX rated models available.
For further information and technical advice, please contact BSB’s sales office.

MANUFACTURERS OF AIR/FIRE/SMOKE CONTROL PRODUCTS

4
Specification Tables

Torque Chart
Differential Damper Size (mm) These values have
been rounded up
Pressure 200 x 200 500 x 500 1000 x 1000 and down to whole
numbers and are
(Pa) Nm lb/ins Nm lb/ins Nm lb/ins illustrated for
500 2.0 18.0 4.0 35.0 7.5 66.0 estimation purposes
only.
1000 4.0 35.0 7.0 62.0 10.0 88.0

Weight Chart (kg) Flangefit and Spigotfit Models - Aluminium Blades


Damper Damper Width (mm) These values
have been
Height (mm) 200 300 400 500 600 700 800 900 1000 rounded up
and down to
100 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 whole numbers
200 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 7.0 and are
illustrated for
300 3.0 4.0 4.5 5.5 6.0 6.5 7.0 8.0 9.0 estimation
purposes only.
400 4.0 5.0 6.0 6.5 7.5 8.5 9.0 10.0 10.5
500 4.5 5.5 6.5 7.5 8.5 9.5 10.5 11.0 12.0
600 5.5 6.5 7.5 9.0 10.0 11.0 12.0 13.0 14.0
700 6.0 7.5 9.0 10.5 12.0 13.0 14.0 15.0 15.5
800 7.0 8.5 9.5 11.0 12.5 13.5 15.0 16.5 17.5
900 7.5 9.0 11.0 12.5 13.5 15.0 15.5 17.0 19.0
1000 8.0 10.0 12.0 13.5 15.5 17.0 17.5 19.0 21.0

Performance Characteristics

Pressure Loss (Report Ref. 143) Leakage (Report Ref. 145)


1000
800 45° 2000
600 Closed
500
400 BSB Flangefit 30°
300 600mm x 600mm 1275 Pa
Closed
200 1000 1000 Pa
900
Static Pressure (Pa)

800
Pressure Loss (Pa)

100
80
15° 700
60 Closed
600 625 Pa
50
40
30 500
20 400
Fully
10
8 Open
300
6 250 Pa
5
4 200
3
BSB Flangefit
2
600mm x 600mm l/sec l/sec/m2
1
1 2 3 4 5 6 7 8 9 10 15 200 300 400
Air Velocity (m/s) Air Leakage (l/s, l/sec/m2)
Max. velocity 15m/s = Measured Calibrations

MANUFACTURERS OF AIR/FIRE/SMOKE CONTROL PRODUCTS

5
Product Specifications

Material Specification Options


Casing Casing
1.2mm (18swg) galvanised mild steel to BS EN 10142 Grades 316 or 430 stainless steel, 1.2mm thick.
1991. Coating Class Fe P02b Z275 Na.
Blades
Blades
Grades 316 or 430 stainless steel or galvanised
Extruded airfoil aluminium to BS 1747 1987, wall coated mild steel, 0.8mm thick.
thickness 1.0mm (20swg) minimum.
Locking Quadrant Brackets
Blade End Caps
Grades 316 or 430 stainless steel, 1.2mm thick.
Injection moulded black polypropylene to BSB’s
recorded design. Oilite Bronze Bushes
Blade Spindles Impregnated with mineral oil to ISO VG 100 (SAE 30).
12.5mm (1/2”) diameter die-cast Mazak alloy to BS Side Seal Gasket
1004 Alloy A DIN 1743, 2400 or engineering quality
thermoplastic nylon dependant on availability, with Grades 302 or 316 stainless steel hard rolled to BS
6mm diameter steel linkage pin pressed in for the 5770 Part 4 1981, 0.345mm (0.010”) thick.
linkage bar to connect to. Paint
Drive Spindles Galvafroid zinc rich paint.
IXEF semi-crystalline polymer polyarylamide as
standard or12.5mm (1/2”) diameter die-cast Mazak
alloy to BS 1004 Alloy A DIN 1743, 2400.
Blade Spindle Bushes
Injection moulded (hoescht) Nylon 66 “Top Hat” design
(melting point 120°C).
Quadrant
1.2mm (18swg) galvanised mild steel chassis with
integral rotation slot and blade position indication.
20mm x 2.5mm (3/4” x 1/8”) high temperature
Masterbatch, to specification PA6.6 Vyoyne 21SP
Compound.
Steel handle available to order.
Drive Bar
22mm x 1.6mm galvanised mild steel flat bar punched
to fit onto zinc plated drive pins.
Rivets
High quality self-sealed rivets are used to European
standards as relevant.
Sealant
All joints and seams are sealed with 3M sealant
conforming to dictates of DW144.
Paint
Aluminium primer is applied to all welds and ground
surfaces.
Operating Temperature
-10°C to +110°C

MANUFACTURERS OF AIR/FIRE/SMOKE CONTROL PRODUCTS

6
Ordering Codes DD Regulating Duct Damper
Example: Model:
F Flange-fit
DD F A - H S
C
Rectangular/Square Spigot-Fit
Circular Spigot-Fit
O Flat Oval Spigot-Fit
D A M P E R S

Blade Material:
Control
A Aluminium Airfoil Blades
Option
G Galvanised Steel Airfoil Blades
Blade Material S Stainless Steel Airfoil Blades (state Grade)

Model Control Options:


E Extended Spindle
Regulating Duct Damper H Hand Control
M Electric Motor (state voltage and model)
P Pneumatic Actuator Fitted
R E G U L A T I N G

BSB Product Range


BD Series DD Series FD Series
Backdraught Damper Duct Damper Fire Damper

FSD Series HD Series SB Series


Fire/Smoke Damper Heavy Duty Control Single Blade
Damper Regulating Damper
SC Series SF Series Control Panel
Smoke Control Damper Slimfit Regulating Fully Addressable or
Damper Electro-Mechanical

BSB Engineering Limited


Unit E, Tribune Drive, Trinity Trading Estate,
Sittingbourne, Kent ME10 2PD
Tel: +44 (0)1795 422609. Fax: +44 (0)1795 429543
Email: sales@bsb-dampers.co.uk
www.bsb-dampers.co.uk

BSB Engineering Services Ltd. reserves the right to modify or withdraw any specification without A Member of The Maico Group
prior notice that may result from continuous product development. The information contained within
this brochure is correct at the time of going to press. BSBDD. Jun. 2008

MANUFACTURERS OF AIR/FIRE/SMOKE CONTROL PRODUCTS


MANTEQ ENGINEERING

ABU RKHAYA
LOUVERS TECHNICAL SUBMITTAL

DATE: FEB 14, 2019


LOUVERS

Page Contents

2 Air Louvers
3 Air Louvers - Performance Data
5 Gravity Shutter
6 Gravity Shutter - Performance Data
7 Sand Trap Louvers
8 Sand Trap Louvers - Performance Data
9 Ordering System
10 Sand Louvers
14 Penthouse Louvers
20 Stationary Stormproof Louvers

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
Air Louvers

Model: CI - Air L - H

CI - Air L - H
CI - Air L - H

Features:

Designed for use as air intakes or air exhaust louvers for commercial or industrial air conditioning systems.
Combines fine architectural design with good performance meets most requirements.

Produced From heavy gauge extruded anodized finish aluminum bars.


Blades and frame are mechanically fastened to provide rigid and mitred joints.

Louvers are completely weather proof and rain proof blade lips.
Can be provided with bird or insect screens, White and anodized aluminum are the standard color,
other colors are available upon request.

2 www.cic-jo.com Cooling Industries Company

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
Air Louvers
Performance Data

Free Area in Sq. Ft.


Width. Inches (CMS)
Height
12 14 16 18 20 24 30 36 42 48 54 60 72
Inches
(30) (36) (41) (46) (51) (61) (76) (91) (107) (122) (137) (152) (183)
(CMS)
12
0.22 0.26 0.30 0.34 0.38 0.46 0.58 0.70 0.82 0.94 1.06 1.18 1.42
(30)

16
0.37 0.43 0.50 0.57 0.64 0.77 0.98 1.18 1.38 1.59 1.79 1.99 2.40
(41)

20
0.52 0.61 0.71 0.80 0.90 1.09 1.38 1.66 1.95 2.24 2.52 2.81 3.38
(51)

24
0.67 0.79 0.91 1.04 1.16 1.41 1.78 2.15 2.52 2.89 3.26 3.63 4.37
(61)

28
0.82 0.79 1.12 1.27 1.42 1.72 2.18 2.63 3.08 3.54 3.99 4.44 5.35
(71)

32
0.97 1.04 1.32 1.505 1.68 2.04 2.58 3.11 3.65 4.18 4.72 5.26 6.33
(81)

36
1.12 1.32 1.53 1.74 1.94 2.36 2.98 3.60 4.22 4.84 5.46 6.08 7.32
(91)

40
1.27 1.50 1.73 1.97 2.20 2.67 3.38 4.08 4.78 5.49 6.19 6.86 8.30
(102)

44
1.41 1.68 1.94 2.20 2.46 2.98 3.78 4.55 5.34 6.12 6.91 7.69 9.26
(112)

48
1.57 1.86 2.15 2.44 2.736 3.31 4.18 5.05 5.92 6.79 7.66 8.53 10.27
(122)

52(
1.72 2.03 2.35 2.67 2.99 3.62 4.58 5.53 6.48 7.44 8.39 9.34 11.25
(132)

56
1.87 2.21 2.56 2.90 2.25 3.94 4.98 6.01 7.05 8.08 9.12 10.16 12.23
(142)

60
2.02 2.39 2.67 3.14 3.51 4.26 5.38 6.50 7.62 8.74 9.86 10.98 13.22
(152)

Cooling Industries Company www.cic-jo.com 3

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
Air Louvers
Performance Data

Note: 1.0
For sizes not shown, the approximate free
area in square feet can be calculated by
using the formula below: 0.5

Free area = (0.5 H-0.26) (W-0.1) 0.4

0.3
W= Width on feet
H= Height on feet 0.2

CFM = Free Area x Face Velocity

Ps)
Ps)

T (+
0.1

E (-
(Sq. Ft.) X (fpm)

US
AK

HA
INT

EX
Pressure Loss Inches w. g.

0.05

0.04

0.03

0.02

0.01

0.005

0.004

0.003

0.002

0.001
100 200 300 400 600 1000 2000 3000 4000 5000

Free Area Velocity (fpm.)

4 www.cic-jo.com Cooling Industries Company

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
Gravity Shutter
Horizontal Operatable Pressure Relief Shutter

Model: CI - Air GS-H

CI - Air GS-H

CI - Air GS-H
Features:

A horizontal operatable shutter which operates to equalize the pressure across it.
The frame and blades are constructed of extruded aluminum anodized as standard painted, powder
coated are available on request.
The frame has a typical wall thickness of 1/16” and separated from the movable blades by an extruded
rigid PVC track which is riveted to and becomes an integral part of the frame. A1/8” thick, 3/8” wide foam
tape is installed on the blades where they overlap to insure a good seal and to reduce noise.

Each shutter is carefully designed to equalize the pressure in such areas as a compressor of fan room with
the outside.
The blades are designed and positioned in such a way that if the pressure in the room increase the blades
automatically lift and open relieving the pressure in the room.
When the room pressure is normalized the blades drop to the closed position by gravity.

These devices are also employed at the end of exhaust ducts where they would open when the exhaust
fan was turned on and would close when the fan was turned off.

Cooling Industries Company www.cic-jo.com 5

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
Gravity Shutter
Performance Data

Technical Data and Listed Sizes Area Factor

Listed Height
(Inches) 12 14 16 18 20 24 30 36 42 48 54 60 72
12 0.81 0.96 1.10 1.25 1.40 1.64 2.08 2.47 2.91 3.30 3.74 4.13 4.96
16 1.08 1.27 1.47 2.66 1.86 2.18 2.77 3.29 3.87 4.44 5.02 5.49 6.60
20 1.36 1.60 1.85 2.09 2.33 2.75 3.48 4.13 4.87 5.52 6.25 6.91 8.30
24 1.62 1.92 2.21 2.50 2.79 3.29 4.16 4.95 5.82 6.61 7.48 8.17 9.93
Listed Height

28 1.89 2.23 2.57 2.91 3.25 3.83 4.85 5.76 6.78 7.69 8.71 9.63 11.56
32 2.16 2.55 2.93 3.32 3.71 4.37 5.53 6.57 7.74 8.78 9.94 10.99 13.19
36 2.44 2.87 3.31 3.75 4.19 4.93 6.24 7.42 8.73 9.91 11.22 12.40 14.89
40 2.70 3.19 3.68 4.16 4.65 5.47 6.93 8.23 9.69 11.00 12.45 13.76 16.52
44 2.97 3.50 4.04 4.57 5.11 6.01 7.61 9.05 10.65 12.08 13.68 15.12 18.16
48 3.25 3.83 4.42 5.00 5.59 6.57 8.32 9.89 11.64 13.21 14.97 16.54 19.86
52 3.52 4.15 4.78 5.41 6.04 7.11 9.01 10.71 12.60 14.30 16.20 17.89 21.49
56 3.78 4.46 5.14 5.82 6.50 7.65 9.69 11.52 13.56 15.39 17.43 19.25 23.12
60 4.06 4.79 5.52 6.25 6.98 8.21 10.40 12.36 14.55 16.52 18.71 20.67 24.82

Note: Pressure Loss

For sizes not shown, the approximate area factor


can be calculated by using the formula below:
0.875 (Height) x (Width - 1.5)
* Area Factor:
144
Pressure Drop Inches w. g.

To calculate the Air Volume (CFM) multiply the area


factor by the face velocity.
CFM = Area Factor x Face Velocity
* Area factor calculation assumes gravity shutter
blades being 100% open.

Face Velocity fpm

6 www.cic-jo.com Cooling Industries Company

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
Sand Trap Louvers

Model: CI - Air SL-H

CI - Air SL-H

Features:

The sand trap louver is made of Aluminum section.


It is composed of two sets of inverted U-channels, mounted vertically on two opposite rows.

The sand trap louver is used to lower the dust loading of conventional filtration as it is designed to separate
large size sand particles at low to medium speeds.

It is also fitted with a bird screen mesh made of galvanized steel to protect against the unwanted objects.
The sand trap louver is a self emptying system, it has a set of holes at the bottom face of the casing to
discharge separated sand particles.

Cooling Industries Company www.cic-jo.com 7

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
Sand Trap Louvers
Performance Data

Effective Pressure Area Ft2

Height Width (inches)


(inches)
12 18 24 30 36 42 48 54 60 66 72 78 84 90
12 0.31 0.47 0.64 0.79 0.96 1.12 1.28 1.44 1.60 1.77 1.93 2.09 2.25 2.41
18 0.47 0.72 0.96 1.21 1.45 1.70 1.94 2.19 2.43 2.68 2.92 3.17 3.41 3.66
24 0.64 0.96 1.29 1.62 1.95 2.78 2.60 2.93 3.26 3.59 3.92 4.24 4.57 4.90
30 0.79 1.21 1.62 2.03 2.44 2.85 3.27 3.68 4.09 4.50 4.91 5.32 5.73 6.15
36 0.96 1.45 1.95 2.44 2.94 3.43 3.93 4.42 4.92 5.41 5.91 6.40 6.89 7.39
42 1.04 1.57 2.11 2.65 3.19 3.72 4.26 4.79 5.33 5.87 6.40 6.96 7.47 8.01
48 1.20 1.82 2.44 3.06 3.68 4.30 4.92 5.54 6.16 6.78 7.40 8.02 8.69 9.26
54 1.36 2.06 2.77 3.47 4.17 4.87 5.58 6.28 6.98 7.69 8.39 9.10 9.80 10.50
60 1.52 2.31 3.09 3.88 4.67 5.45 6.24 7.03 7.81 8.60 9.39 10.17 10.96 11.75
66 1.69 2.55 3.42 4.29 2.16 6.03 6.90 7.77 8.64 9.51 10.38 11.25 12.12 13.00
72 1.85 2.80 3.75 4.71 5.68 6.61 7.57 8.52 9.47 10.42 11.38 12.33 13.28 14.23
78 2.01 3.04 4.08 5.12 6.15 7.19 8.23 9.26 1030 11.33 12.37 13.41 14.44 15.48
84 2.17 3.29 4.41 5.53 6.65 7.77 8.87 10.01 11.13 12.25 13.37 14.49 15.61 16.72
90 2.33 3.53 4.74 5.69 7.14 8.35 9.55 10.75 11.96 13.16 14.36 15.56 16.77 17.97

Performance:

Test results conducted on similar equipment


indicate a typical efficiency of 80% on AC
coarse.
(20 - 200 microns) and 50% on AC Fine test
duct (1 to 70 microns).
Pressure Drop Inches W.G.
Efficiency

Face Velocity Based on W x H, FPM

8 www.cic-jo.com Cooling Industries Company

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
Sand Trap Louvers

Available Types of Finishing: Standard Sizes:


Powder coated (painted to RAL codes). (Use any combination of width & length)

* To convert into Imperial units use Width Length


(1 inch = 25mm). (B) (A)
* Non Standard Sizes are Available Upon (mm) (mm)
Request. 300 300
450 450
600 600
750 750
900 900
1050 1050
1200 1200
1350 1350
1500 1500

Ordering System:

Type Size Finish

Ral : Powder coated Finish as per RAL Codes.

Size : Width x Lenght

STL : Sand trap louver


Example : STL 1050 X 150 RAL 9016

Cooling Industries Company www.cic-jo.com 9

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
Sand Louvers
CI - Air DL - H

General:

CIC Sand Louver CI - Air DL- H are architectural air inlets. They are
widely used for building exteriors and are suitable for different
HVAC and industrial applications to prevent sand entry.

The blades are carefully designed to provide a low resistance to


air flow and a high free area.

Description: Sand Louver (CI - Air DL- H)

CI - Air DL- H louvers have 2 inch deep horizontal fixed blades designed carefully for low pressure drop and
to prevent entry of sand.
The frame is 1.25” wide (flat or curved) flanged type and is mechanically joined to give a rugged
construction to the louver.
These louvers are available as optional with galvanized bird screen, aluminum type air filter in 1”, 2” and 4”
thickness and volume control damper.
They are manufactured in a wide range of standard sizes however, they can be supplied in non-standard
sizes, depths or architectural shapes to suit customers requirements.

Material and Finish:

CI - Air DL- H sand louvers are made of heavy extruded aluminium profiles.
They are available in white polyester powder coated finish or any other RAL standard colour upon
customer’s request.
Bird screens are made of galvanized expanded metal sheets.

10 www.cic-jo.com Cooling Industries Company

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
Sand Louvers
CI - Air DL - H
Product Code

CIC Sand Louver CI - Air DL- H - W - H - C

Width in inch.

Height in inch.

Accessories:
B : Bird screen
D : Volume Control Damper (VCD)
BD : Bird screen & VCD.
I : Insect Screen.
F1 : Aluminium Filter 1” thick.
F2 : Aluminium Filter 2” thick.
F4 : Aluminium Filter 4” thick.

Use the code of CI - Air DL- H to refer to CIC sand louver with flat frame.

Example:
• CI - Air DL- H - 30 - 18 - B:
CIC Sand Louver - size 30” x 18” with bird screen.
• CI - Air DL- H - 24 - 20 BDF1:
CIC Sand Louver - size 24” x 20” with bird screen, volume control damper and 1” thick aluminium filter.

A special assembly of sand louver with a bird screen, volume


control damper and a washable aluminium filter.
(All are enclosed in a galvanized box).

Example: CI - Air DL- H - W - H - BDF2

Cooling Industries Company www.cic-jo.com 11

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
Sand Louvers
CI - Air DL - H
Dimensional Data

CIC Sand Louver with flat frame - (CI - Air DL- H)

Selection Procedure:

To select a suitable size of a sand louver (CI - Air DL- H) for a certain application, follow exactly the same
procedure as been explained previously.

Note:
The approximate effective free area in square feet can be calculated by using the following formula:-

Effective free area (Ak) = (0.45 H-0.08) x (W-0.1)

Where, H is Height in ft and W is Width in ft.

12 www.cic-jo.com Cooling Industries Company

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
Sand Louvers
CI - Air DL - H
Performance Data

Available Standard Sizes


12x12 12x14 12x16 12x18 12x20 12x24 12x30 12x36 12x42 12x48
16x12 16x14 16x16 16x18 16x20 16x24 16x30 16x36 16x42 16x48
20x12 20x14 20x16 20x18 20x20 20x24 20x30 20x36 20x42 20x48
24x12 24x14 24x16 24x18 24x20 24x24 24x30 24x36 24x42 24x48
28x12 28x14 28x16 28x18 28x20 28x24 28x30 28x36 28x42 28x48
32x12 32x14 32x16 32x18 32x20 32x24 32x30 32x36 32x42 32x48
36x12 36x14 36x16 36x18 36x20 36x24 36x30 36x36 36x42 36x48
40x12 40x14 40x16 40x18 40x20 40x24 40x30 40x36 40x42 40x48
44x12 44x14 44x16 44x18 44x20 44x24 44x30 44x36 44x42 44x48
48x12 48x14 48x16 48x18 48x20 48x24 48x30 48x36 48x42 48x48

Table No. 1 CI - Air DL- H standard sizes available (HxW) in inches.

Pressure Requirement
Face Velocity (FPM) 200 300 400 500 600 700 800 900 1000 1200 1400 1600
Intake PD° W.G. 0.007 0.016 0.028 0.044 0.063 0.086 0.112 0.141 0.175 0.252 0.338 0.433

Table No. 2 Intake pressure drop in inches of water as a function of face velocity in FPM for CI - Air DL- H.

Effective Free Area

Height Width (Inches)


(Inches) 12 14 16 18 20 24 30 36 42 48
12 0.33 0.40 0.46 0.52 0.58 0.70 0.89 1.07 1.26 1.45
16 0.47 0.55 0.64 0.73 0.81 0.99 1.25 1.51 1.77 2.00
20 0.60 0.71 0.83 0.94 1.05 1.27 1.61 1.94 2.28 2.61
24 0.74 0.87 1.01 1.15 1.28 1.56 1.97 2.38 2.79 3.20
28 0.87 1.03 1.20 1.36 1.52 1.84 2.33 2.81 3.30 3.78
32 1.00 1.19 1.38 1.57 1.75 2.12 2.69 3.25 3.81 4.37
36 1.14 1.35 1.57 1.78 1.99 2.41 3.05 3.70 4.32 4.95
40 1.28 1.51 1.75 1.99 2.22 2.70 3.41 4.12 4.83 5.54
44 1.41 1.67 1.94 2.20 2.46 2.98 3.77 4.55 5.34 6.12
48 1.55 1.83 2.12 2.41 2.69 3.30 4.13 5.00 5.85 6.71

Table No. 3. Effective free area in ft² factor) for CI - Air DL- H.

Cooling Industries Company www.cic-jo.com 13

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
Penthouse Louvers
CI - Air PHL - H

General:

CIC penthouse louvers CI - Air PHL - H are considered as typical louver units for both air intake and exhaust
applications.
They are designed and built to become a permanent part of the building.
They maintain their pleasant appearance and effective weather protection as a result of their rugged,
durable, extruded aluminium construction and careful workmanship.
They are usually furnished with either mullion or mitered corners and incorporate the normal CIC fresh air
louver blades CI - Air PHL - H as standard. However, any other type of CIC louver blades can also be used
as optional.

Penthouse Louver (CI - Air PHL - H) Penthouse Louvers (CI - Air PHL - H)
With Mullion Corner With Mitered Corner

Description:

CI - Air PHL - H penthouse louvers have as a standard 2” deep fixed horizontal blades.
The blades are carefully designed to get low pressure drop, maximum free area and to prevent rain-water
penetration.
They are available in 1.25” flanged frame and are built and mounted to an internal framing with mullion
corners.
The integral framing mullion structures are furnished with a standard 1.6” x 1.6” extruded aluminium
profiles.
For the other mitered corners type penthouse louvers, blades are beveled and welded internally at the
end.
The top of the penthouses are covered with flat or pitched roofs of aluminium sheets.
All of the four louver sides are of removable type for easy maintenance purposes, Penthouse louvers can
also be supplied as optional with galvanized bird or insect screens and / or aluminium washable air filters
of 1”, 2”, or 4” thickness.

14 www.cic-jo.com Cooling Industries Company

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
Penthouse Louvers
CI - Air PHL - H
Product Code

Material and Finish:

CI - Air PHL - H penthouse louvers are made of heavy gauge extruded aluminium profiles. They are
available in white polyester powder coated finish or any other RAL standard colour upon customer’s
request.
Structural mullion corners are of strong aluminium profiles while roof tops are of aluminium sheets
as a standard.
However, galvanized roofs are also available upon request.
Bird screens are made of galvanized expanded metal sheets.

CIC Penthouse Louver CI - Air PHL - H - W - L - H - C

Width in inch.

Length in inch.

Height in inch.

Accessories:

B : Bird Screen
I : Insect Screen
F : Aluminium Filter 1” thick.
F2 : Aluminium Filter 2” thick.
F4 : Aluminium Filter 4” thick.

Example:

CI - Air PHL - H - 18 - 18 - 24 - B:
CIC penthouse louver with 18” x 18” basement
size, 24” height and bird screen.

CI - Air PHL - H - 24 - 18 - 36 - BF2:


CIC penthouse louver with 24” x 18” basement
size, 36” height, bird screen and 2” thick aluminium air filter.

Cooling Industries Company www.cic-jo.com 15

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
Penthouse Louvers
CI - Air PHL - H
Definitions

Definitions:
: Is the air stream velocity measured at the face of a louver in FPM
Face velocity
and it corresponds to the effective free area.

CFM : Is the air flow rate in cubic feet per minute.

: Is in ft2 , and is related to the other parameters by the equation :


Effective free area CFM = Free Area x Face velocity
= A k x Vk

: Is the inside basement perimeter in feet and is calculated from:


Penthouse louver perimeter P= 2W + 2L, W and L are the horizontal dimensions of the penthouse
louver.

Total pressure drop : Is the sum of static pressure and velocity pressure given in inches W.G

CI - Air PHL - H - F2

16 www.cic-jo.com Cooling Industries Company

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
Penthouse Louvers
CI - Air PHL - H
Dimensional Data

Ci - Air PHL - H (with mullion corners)

Ci - Air PHL - H (with mitered corners)

Cooling Industries Company www.cic-jo.com 17

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
Penthouse Louvers
CI - Air PHL - H
Selection Procedure

Example:

Select a penthouse louver for an exhaust requirements of 3300 CFM with a total pressure drop of 0.1” W.G.

1) From the pressure requirement table 2 it shows that an 800 FPM velocity results an exhaust pressure
drop of 0.1” W.G.
2) Determine the effective free area:

CFM
Effective free area Ak =
Vk
3000
= = 4.125 ft2
800
3) From table 3 the 4.125 ft2 effective free area is suitable for the following penthouse louver’s sizes:
• P = 5 ft, H = 28 inch.
Could be suitable for a penthouse basement dimensions of (WxL) - 12” x 18”.
• P = 6 ft, H = 24 inch.
Could be suitable for a penthouse basement dimensions of (WxL) - 12”x24” or 18” x 18”
depending on the duct size.

Note:
The approximate effective free area in square feet can be calculated by using the following formula:-

Effective free area (Ak) = (H-0.5) x (0.5P-0.25)


Where, H is height in ft and P is Inside Perimeter in ft.

Pressure Requirement:
Free Velocity (FPM) 200 300 400 500 600 700 800 900 1000 1200 1400 1600
Intake PD" W.G. 0.006 0.011 0.023 0.037 0.050 0.066 0.087 0.110 0.142 0.193 0.280 0.390
Exhaust PD" W.G. 0.007 0.014 0.028 0.044 0.059 0.080 0.10 0.128 0.159 0.255 0.310 0.425

Table No. 4 Pressure drop in inches of water as a function of face velocity


through the free area in FPM for CI - Air PHL - H.

18 www.cic-jo.com Cooling Industries Company

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
Inside Perimeter in feet (2W + 2L)
Height
(Inches)
4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

12 0.875 1.125 1.375 1.625 1.875 2.125 2.375 2.625 2.875 3.125 3.375 3.625 3.875 4.125 4.375 4.625 4.875 5.125 5.375 5.625 5.875

16 1.458 1.875 2.292 2.708 3.125 3.542 3.958 4.375 4.792 5.208 5.625 6.042 6.458 6.875 7.292 7.708 8.125 8.542 8.958 9.375 9.792
CI - Air PHL - H

2.042 2.625 3.208 3.792 4.375 4.958 5.542 6.125 6.708 7.292 7.875 8.458 9.042 9.625 10.208 10.792 11.375 11.958 12.542 13.125 13.708

Cooling Industries Company


20
Performance Data
Penthouse Louvers

24 2.625 3.375 4.125 4.875 5.625 6.375 7.125 7.875 8.625 9.375 10.125 10.875 11.625 12.375 13.125 13.875 14.625 15.375 16.125 16.875 17.625

28 3.208 4.125 4.842 5.958 6.875 7.792 8.708 9.625 10.542 11.458 12.375 13.292 14.208 15.125 16.042 16.958 17.875 18.792 19.708 20.625 21.542

32 3.792 4.875 5.958 7.042 8.125 9.208 10.292 11.375 12.458 13.542 14.625 15.708 16.792 17.875 18.958 20.042 21.125 22.208 23.292 24.375 25.458

36 4.375 5.625 6.875 8.125 9.375 10.625 11.875 13.125 14.375 15.625 16.875 18.125 19.375 20.625 21.875 23.125 24.375 25.625 26.875 28.125 29.375

40 4.958 6.375 7.792 9.208 10.625 12.042 13.458 14.875 16.292 17.708 19.125 20.542 21.958 23.375 24.792 26.208 27.625 29.042 30.458 31.875 33.292

44 5.542 7.125 8.708 10.292 11.875 13.458 15.042 16.625 18.208 19.792 21.375 22.958 24.542 26.125 27.708 29.292 30.785 32.458 34.042 35.625 37.208

48 6.125 7.785 9.625 11.375 13.125 14.785 16.625 18.375 20.125 21.875 23.625 25.375 27.125 28.875 30.625 32.375 34.125 35.875 37.625 39.375 41.125

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
52 6.708 8.625 10.542 12.458 14.375 16.292 18.208 20.125 22.042 23.958 25.875 27.792 29.708 31.625 33.542 35.458 37.375 39.292 41.208 43.125 45.042

56 7.292 9.375 11.458 13.542 15.625 17.708 19.792 21.875 23.958 26.042 28.125 30.208 32.292 34.375 36.458 39.542 40.625 42.708 44.792 46.875 48.958

60 7.875 10.125 12.375 14.625 16.875 19.125 21.375 23.625 25.875 28.125 30.375 32.625 34.875 37.125 39.375 41.625 43.875 46.125 48.375 50.625 52.875

64 8.458 10.875 13.292 15.708 18.125 20.542 22.958 25.375 27.792 30.208 32.625 35.042 37.458 39.875 42.292 44.708 47.125 49.542 51.958 54.375 56.792

68 9.042 11.625 14.208 16.792 19.375 21.958 24.542 27.125 29.708 32.292 34.875 37.458 40.042 42.625 45.208 47.792 50.375 52.958 55.542 58.125 60.708

www.cic-jo.com
72 9.625 12.375 15.125 17.875 20.625 23.375 26.125 28.875 31.625 34.375 37.125 39.875 42.625 45.375 48.125 50.875 53.625 56.375 59.125 61.875 64.625

Table No. 5. Effective free area in ft2 (Ak Factor) for CI - Air PHL - H

19
Stationary Stormproof Louvers
CI - Air SSL - H

General:

CIC stationary stormproof louvers CI - Air SSL-H are mainly


designed to protect air intake and exhaust openings in building
exterior walls and are recommended for applications where low
water penetration is required.

They are carefully designed to provide high free area, maximum


resistance to rain and extreme weather conditions with minimum
resistance to airflow.

Description:

CI - Air SSL-H louvers have heavy gauge horizontal blades


of 1.8 mm thick aluminium extruded profile. They are carefully
designed to get low pressure drop, maximum free area and to
prevent rain water penetration with high efficiency to extreme Stationary Stormproof Louver
weather conditions. (CI - Air SSL-H)
They are available in 1.6” flanged curved frame of heavy gauge aluminium extruded profile which in turn
is mechanically joined to give the highest rigidity and strength.

Louvers can be supplied with galvanized bird or aluminium insect screen, volume control damper and
aluminium air filter of 1”, 2” and 4” thickness.

The filters are accessable from the side or backward of the louver depending upon type of installation and
must be specified by the customer.

These louvers are available in standard given sizes, however they can also be supplied in other requested
sizes and architectural shapes upon customers requirements.

Material and Finish:

CI - Air SSL-H louvers are made of heavy gauge extruded aluminium profiles.
They are available in white polyester powder coated finish or any other RAL standard colour upon
customer’s request.
Bird screens are made of galvanized expanded metal sheets.

20 www.cic-jo.com Cooling Industries Company

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
Stationary Stormproof Louvers
CI - Air SSL - H
Product Code & Dimensional Data

CIC Stationary Stormproof Louver CI - Air SSL-H - W - H - C

Width in inch.

Height in inch.

Accessories:

B : Bird Screen
D :Volume Control Damper (VCD)
BD :Bird screen & VCD.
I :Insect Screen
F1 :Aluminium Filter 1” thick.
F2 :Aluminium Filter 2” thick.
F3 :Aluminium Filter 4” thick.
Dimensional Data

Example:

• CI - Air SSL-H - 24 - 36 - BF1:


CIC stormproof louver size 24” x 36” with
bird screen and I” thick aluminium filter.

• CI - Air SSL-H - 48 - 48 - BDF2


CIC stormproof louver size 48”x48” with bird
screen, volume control damper (VCD) and 2” thick
aluminium filter.

CIC Stationary Stormproof Louver


CI - Air SSL-H

Cooling Industries Company www.cic-jo.com 21

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
Stationary Stormproof Louvers
CI - Air SSL - H
Selection Procedure

Example:

Louver size required for an exhaust requirements of 1200 CFM with a total pressure drop of 0.07” W.G.

1) From the pressure requirement table 7 it shows that a 600 FPM velocity results an exhaust pressure
drop of 0.07” W.G.
2) Determine the effective free area:

CFM
Effective free area Ak =
Vk
1200
= = 2.0 ft2
600

3) From table 8 the 2.0 ft2 effective area is mostly suitable for the size 42” x 18”.

Note:
For other louver sizes not shown in table 8. The approximate effective free area in square feet can be
calculated by using the following formula:-

Effective free area (Ak) = (0.58H-0.34) x (W-0.3)


Where, H is Height in ft and W is Width in ft.

Available Standard Sizes:


12x12 12x18 12x24 12x30 12x36 12x42 12x48 12x54 12x60 12x66 12x72 12x78 12x84 12x90
18x12 18x18 18x24 18x30 18x36 18x42 18x48 18x54 18x60 18x66 18x72 18x78 18x84 18x90
24x12 24x18 24x24 24x30 24x36 24x42 24x48 24x54 24x60 24x66 24x72 24x78 24x84 24x90
30x12 30x18 30x24 30x30 30x36 30x42 30x48 30x54 30x60 30x66 30x72 30x78 30x84 30x90
36x12 36x18 36x24 36x30 36x36 36x42 36x48 36x54 36x60 36x66 36x72 36x78 36x84 36x90
42x12 42x18 42x24 42x30 42x36 42x42 42x48 42x54 42x60 42x66 42x72 42x78 42x84 42x90
48x12 48x18 48x24 48x30 48x36 48x42 48x48 48x54 48x60 48x66 48x72 48x78 48x84 48x90
54x12 54x18 54x24 54x30 54x36 54x42 54x48 54x54 54x60 54x66 54x72 54x78 54x84 54x90
60x12 60x18 60x24 60x30 60x36 60x42 60x48 60x54 60x60 60x66 60x72 60x78 60x84 60x90
66x12 66x18 66x24 66x30 66x36 66x42 66x48 66x54 66x60 66x66 66x72 66x78 66x84 66x90
72x12 72x18 72x24 72x30 72x36 72x42 72x48 72x54 72x60 72x66 72x72 72x78 72x84 72x90
78x12 78x18 78x24 78x30 78x36 78x42 78x48 78x54 78x60 78x66 78x72 78x78 78x84 78x90
84x12 84x18 84x24 84x30 84x36 84x42 84x48 84x54 84x60 84x66 84x72 84x78 84x84 84x90
90x12 90x18 90x24 90x30 90x36 90x42 90x48 90x54 90x60 90x66 90x72 90x78 90x84 90x90

Table No. 6 CI - Air SSL-H standard sizes available (HxW) in inches.

22 www.cic-jo.com Cooling Industries Company

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
Stationary Stormproof Louvers
CI - Air SSL - H
Performance Data

Pressure Requirement:
Free Velocity (FPM) 200 300 400 500 600 700 800 900 1000 1200 1400 1600
Intake PD" W.G. 0.007 0.018 0.031 0.047 0.070 0.092 0.112 0.145 0.183 0.271 0.380 0.50

Table No. 7 Total pressure drop in inches of water as a function of face velocity in FPM for CI - Air SSL-H.

Effective Free Area

Height Width (Inches)


(Inches) 12 18 24 30 36 42 48 54 60 66 72 78 84 90
12 0.168 0.288 0.408 0.528 0.648 0.768 0.888 1.008 1.128 1.248 1.368 1.488 1.608 1.728

18 0.371 0.636 0.901 1.166 1.431 1.696 1.961 2.226 2.491 2.756 3.021 3.286 3.551 3.816

24 0.574 0.984 1.394 1.804 2.214 2.624 3.034 3.444 3.854 4.264 4.674 5.084 5.494 5.904

30 0.777 1.332 1.887 2.442 2.997 3.552 4.107 4.662 5.217 5.772 6.327 6.882 7.437 7.992

36 0.980 1.680 2.380 3.080 3.780 4.480 5.180 5.880 6.580 7.280 7.980 8.680 9.380 10.080

42 1.183 2.028 2.873 3.718 4.563 5.408 6.253 7.098 7.943 8.788 9.633 10.478 11.323 12.168

48 1.386 2.376 3.366 4.356 5.346 6.336 7.326 8.316 9.306 10.296 11.286 12.276 13.266 14.256

54 1.589 2.724 3.859 4.994 6.129 7.264 8.399 9.534 10.669 11.804 12.939 14.074 15.209 16.344

60 1.792 3.072 4.352 5.632 6.912 8.192 9.472 10.752 12.032 13.312 14.592 15.872 17.152 18.432

66 1.995 3.420 4.845 6.270 7.695 9.120 10.545 11.970 13.395 14.820 16.245 17.670 19.095 20.520

72 2.198 3.768 5.338 6.908 8.478 10.048 11.618 13.188 14.758 16.328 17.898 19.468 21.038 22.608

78 2.401 4.116 5.831 7.546 9.261 10.976 12.691 14.406 16.121 17.836 19.551 21.266 22.981 24.696

84 2.604 4.464 6.324 8.184 10.044 11.904 13.764 15.624 17.484 19.344 21.204 23.064 24.924 26.784

90 2.807 4.812 6.817 8.822 10.827 12.832 14.837 16.842 18.847 20.852 22.857 24.862 26.867 28.872

Table No. 8. Effective free area in ft² (Ak factor) for CI - Air SSL-H.

CI - Air SSL-H CI - Air SSL-H


(Cross section)
Cooling Industries Company www.cic-jo.com 23

TRIAL MODE − a valid license will remove this message. See the keywords property of this PDF for more information.
 
  