Pagliawan (Electrical)
Pagliawan (Electrical)
BSCE
Notes:
1. Description (read Philippine electrical code volume 1)
a. Lighting outlet
b. Convenience outlet
c. Others or Spare
2. No of Outlet
a. (Refer to floor plan or electrical layout plan) or assume
b. Count the number of lighting outlet likewise the convenience outlet
3. Volts; use 230 volts
4. L.O 100W per outlet the C.O 180W per outlet usually 2gang (x2) use 360 W
5. Ampere per circuit; compute using ohms law (actual show your solution)
6. Protection: use the available in commercial, above your computed amp (10, 15, 20, &30amp)
7. As PEC requires, refer to table AWG in LO no. 14, CO no.12 if case aircon 1 HP use no.10
8. Conduit ; 15 mm OD,1/2” dia. in 2wires, 20 mm or ¾” dia. in 4 wires, PVC orange