Professional Documents
Culture Documents
Cooling Load Data
Cooling Load Data
Cooling Load Data
15933.877727
17018.877727
33747.068321
9.8906999769
Column1 Column2 Column3 Column4 Column5 Column6 Column7 Column8 Column9
Project KER Room living room-2
location Yangon Lat. 16.8661
DB , °F WB, °F RH, % Daily range Day Time
Design Outdoor 100 80 24 April 3:00 PM
conditons Room 75 65
Roof/ceiling
Floor
Partition 0.585 67.89 16 635.4504
door
8346.3169046
8656.3169046
18832.228997
5.5194106088
Project KER Room Corridor
location Yangon Lat. 16.8661
DB , °F WB, °F RH, % Daily range Day Time
Design Outdoor 100 80 24 April 3:00 PM
conditons Room 75 65
Roof/ceiling
Floor
Partition 0.585 193.212 9 1 1017.2612
door
Solar Dir. SHGF Area,ft² SC CLF
Glass
Lighting Watt BF CLF
84 3.41 1.25 358.05
people HG N CLF RLHG
sensible 250 2 0.05 25 BTU/hr
latent 200 2 400
Equipment HG N
Roof/ceiling
Floor
Partition 0.585 110.492 9 1 581.74038
door
Solar Dir. SHGF Area,ft² SC CLF
Glass
Lighting Watt BF CLF
48 3.41 1.25 204.6
people HG N CLF RLHG
sensible 250 2 0.05 25 BTU/hr
latent 200 2 400
Equipment HG N
hot plate 694.547 1 694.547
Fridge 300.256 1 300.256
infiltration CFM w'/T dif:
sensible 480.6599616 25 1.1 13218.148944
latent 480.6599616 5 0.68 1634.2438694
Subtotal 15024.292324 2034.2438694
RTHG
BTU/hr 17058.536193
KW 4.9995709828