Material Submittal

for
Fire Sprinklers
(Globe-USA)

PROJECT NAME : MODIFICATION AT KHALIFA INTERNATIONAL


STADIUM TERTIARY PUMPS AND OTHER RELATED
WORKS AT ASPIRE ZONE FOUNDATION (SP/C/6089/18)
CONSULTANT NAME : M/S.PROJACS
INDEX

S.NO. DESCRIPTION
1 SUPPLIER’S PROFILE

2 MANUFACTURER’S PROFILE

3 COMPLIANCE STATEMENT

4 MATERIAL SCHEDULE

5 COUNTRY OF ORIGIN CERTIFICATE

6 PRODUCT CATALOGUE / DATA SHEET

7 QCDD & UL CERTIFICATES

8 PREVIOUS PROJECT APPROVALS

9 PROJECT REFERENCE LIST


SUPPLIER’S PROFILE
Chairman

Chief Executive Officer


Managing Director

General Manager

Al Waab Bldg., Block D, 2nd Floor, Salwa Road


P.O. Box 23761, Doha - Qatar

Telephone : +974 4491 7350


Fax : +974 4491 7355
MANUFACTURE’S PROFILE
GLOBE FIRE SPRINKLER CORPORATION
4077 AIRPARK DRIVE
STANDISH MICHIGAN 48658 USA
TEL: 1-989-846-4583 FAX: 1-989-846-9231
www.globesprinkler.com

GLOBE ASIA CORPORATION LTD. GLOBE FIRE SPRINKLER


Unit B, 7F Mow Shing Centre AUSTRALIA PTY LTD
118 Bedford Road 9 Florence Street
Tai Kok Tsui, Kowloon Burwood, Victoria 3125
HONG KONG AUSTRALIA
Tel: (852) 2764 1662 Fax: (852) 2774 6591 Tel: (61) 39 808 7171Fax: (61) 39 808 7293
ABOUT US

Globe Fire Sprinkler Corporation is an independent, privately owned


company that strives to exceed customer expectations, offering top
quality, competitive products, and a high level of customer service.

Since the early 20th century the name GLOBE has been synonymous in supplying quality fire pro-
tection products.

In May of 1988, Mr. Robert C. Worthington, a profes-


sional fire protection engineer, purchased the former
Globe Fire Equipment Company, bringing with him 35
years of experience in the fire sprinkler industry, hav-
ing worked for three other large sprinkler manufactur-
ers in various capacities.

Today the combined business experience of the offi-


cers of Globe totals more than 120 years devoted ex-
clusively to the fire sprinkler industry.

Under Mr. Worthington's leadership, the product line


has been greatly expanded and modernized, and
sales have increased more than 500% since incep-
tion. Globe today is a major manufacturer of sprinklers, valves and associated devices and ships its
products to all corners of the world on a continuing basis. Approximately 50 percent of Globe's net
sales are to overseas customers.

Globe continues to develop new products as the world market demands, and is happy to state that
its relationship with the various approval authorities, such as Underwriters Laboratories Inc, FM Ap-
provals and the Loss Prevention Certification Board (UK), is excellent. Globe has the LPCB (UK)
certification for ISO 9000 series Quality Assurance, therefore exhibiting proof of the quality it con-
tinuously builds into each of its 100% factory-tested products.
Certificate of Management
System Registration
Certificate Number: 147 Issue: 11

Globe Fire Sprinkler Corporation

having complied with the requirements of:

ISO 9001:2008
Quality Management Systems – Requirements

are authorised to use the LPCB Certification Mark on stationery and publications related to the
following products and/or services:

Globe Fire Sprinkler Corporation Scope:


4077 Air Park Drive Design and manufacture of fire sprinklers, fire
Standish protection valves and related products for fire
Michigan 48658 sprinkler systems.
USA

This certificate is maintained and held in force through regular surveillance activities.

Tracie Hunter 26 April 2014 27 April 2017 11 January 1993


Signed for LPCB Technical Manager Date of This Issue Expiry Date Date of First Issue

This certificate and appendix remains the property of BRE Global Limited and is
issued subject to terms and conditions (for details visit
www.redbooklive.com/terms).
To check the validity of this certificate and appendix please scan the QR tag, visit
www.redbooklive.com/check or contact us.
LPCB is part of BRE Global Ltd., Garston, Watford WD25 9XX.
T: +44 (0)1923 664100 F: +44 (0)1923 664603 E: Enquiries@breglobal.com

BF040 Rev 9.5 Page 1 of 1 © BRE Global Ltd, 2013


COMPLIANCE STATEMENT
QCS 2014 Section 23: Fire Fighting and Fire Alarm Systems Page 5
Part 04: Fire Fighting System

12 The Contractor shall install an adequate quantity of additional sprinkler heads of the correct
temperature rating. The number will depend on the size of the installation and number of
sprinkler heads likely to be opened. The following figures are the minimum number of
additional sprinkler heads that should be installed:

(a) for systems not exceeding 300 sprinklers, 6 spare heads shall be installed
(b) for systems exceeding 300 sprinklers but not exceeding 1000, 12 spare heads shall
be installed
(c) for systems exceeding 1000 sprinklers, 24 spare heads shall be installed.

13 All components for sprinkler system packages should be from one single manufacturer with
an approved local agent. The Contractor shall maintain a technical representative from the
manufacturer or the local agent on site for the duration of the Contract in order to supervise
the installation. This representative shall issue a certificate upon completion of the Project
stating that the complete system has been installed, tested and commissioned in accordance
with the Project Documentation, the requirements of the NFPA and the Civil Defence
Department.

.L
4.2.2 Sprinkler Heads

.L
o
1 The glass bulb sprinkler heads should be of the upright pendant type and rated for 68 C.

W
They shall be arranged such that there is not interference with the discharge pattern and
they shall be positioned between 75 and 150 mm below ceilings.
AR
2 The sprinklers and pipelines shall not be spaced too close together in order to prevent an
operating sprinkler from wetting, and thereby delaying the operation of, adjacent sprinklers.
AT

3 In locations where sprinkler heads are liable to be operated or damaged by accidental blow,
they should be protected by stout metal guards. Care shall be taken to ensure that the
normal operation of the sprinkler head in the event of a fire is not impeded by such guards.
Q

4 Sprinklers in false ceilings areas shall be the concealed or recessed type. They shall be the
IX

two-piece design with closure and mounting plate which allows for easy installation and
removal.
R
ET

5 Sprinklers in parking and hardware areas shall be the pendant or upright bulb type with a 12
o
mm diameter orifice and temperature rated to 68 C with a natural brass finishes and
sprinkler guard.
M

4.2.3 Sprinkler System Alarm Devices

1 The system shall be provided with alarm devices consisting of, but not limited to, the items
described in the following clauses.

4.2.4 Alarm Valve

1 Alarm valves shall be UL listed and FM approved. They shall be check type, with a rubber
faced clapper, designed for use in wet pipe systems for automatic actuation. The alarm valve
may be installed vertically or horizontally with inlet and outlet connection in accordance with
the relevant provisions of ANSI B 16.1.

4.2.5 Basic Trip and Retarding Chamber

1 Basic trip and retarding chamber shall be UL listed and FM approved. It shall be used in
order to prevent any false alarm that may be caused by small variation in pressure. The
chamber should consist of a by-pass check valve to permit slow as well as small transient
increases in water supply pressure to be passed through to the system and held at their
highest value, without opening of the water way clapper.
SPECIFICATION REQUIREMENT CONTRACTOR'S PROPOSAL REMARKS

4.2.2 Sprinkler Heads


1. The glass bulb sprinkler heads should be of the pendant type The glass bulb sprinkler heads will be of the Upright or
and rated for 68°C. They shall be arranged such that there is not Sidewall Sprinklers and rated for 68°/ 79 C as per Drawings.
Comply as per Drawings
interference with the discharge pattern and they shall be They will be arranged such that there is not interference with
positioned between 75 and 150 mm below ceilings. the discharge pattern and they will be positioned between 75
The sprinklers and pipelines will not be spaced too close
2. The sprinklers and pipelines shall not be spaced too close
together in order to prevent an operating sprinkler from
together in order to prevent an operating sprinkler from wetting,
wetting, and thereby delaying the operation of, adjacent
and thereby delaying the operation of, adjacent sprinklers.
sprinklers.
3. In locations where sprinkler heads are liable to be operated
or damaged by accidental blow, they should be protected by
stout metal guards. Care shall be taken to ensure that the Comply wherever applicable
normal operation of the sprinkler head in the event of a fire is
not impeded by such guards.
4. Sprinklers in false ceilings areas shall be the concealed or
recessed type. They shall be the two-piece design with closure
Not Applicable for this submittal
and mounting plate which allows for easy installation and
removal.

5. Sprinklers in parking and hardware areas shall be the pendant


or upright bulb type with a 12 mm diameter orifice and
Comply with 79 Deg Upright Sprinklers with Brass Finish
temperature rated to 68°C with a natural brass finishes and
sprinkler guard.
MATERIAL SCHEDULE
MATERIAL LIST/EQUIPMENT LIST

SL. MAKE /
ITEM DESCRIPTION MODEL
NO ORIGIN

UPRIGHT SPRINKLER,QUICK RESPONSE, K5.6,


UPRIGHT
1 3MM BULB, 1/2" NPT, 1/2" ORIFICE, 79°C, 175 PSI, GL-5615 GLOBE/USA
SPRINKLER
BRASS, UL/FM, GLOBE USA

HORIZONTAL SIDEWALL SPRINKLER, EXTENDED


2 SIDE WALL COVERAGE, QUICK RESPONSE, K 8, 3MM BULB, GL-8128 GLOBE/USA
SPRINKLER 3/4" NPT,68°C, 175 PSI, CHROME, UL, GLOBE USA

DRY RECESSED PENDENT SPRINKLER, QUICK


RESPONSE, 68°C - K 5.6, 3MM BULB, 1" NPT,
3 DRY PENDENT GL-5635 GLOBE/USA
17/32" ORIFICE, 155 DEG, 175PSI, CHROME
SPRINKLER
UL/FM GLOBE USA
COUNTRY OF ORIGIN CERTIFICATE
PRODUCT CATALOGUE /
PRODUCT DATASHEET
UPRIGHT SPRINKLER
4077 Airpark Dr. Standish, MI 48658 • 989-846-4583 • www.globesprinkler.com
Technical Support • 989-414-2600 • techservice@globesprinkler.com

SERIES GL-QR STANDARD COVERAGE, QUICK RESPONSE


UPRIGHT, PENDENT & RECESSED PENDENT SPRINKLERS
K-FACTOR: 2.8, 4.2, 5.6, 8.0
GENERAL DESCRIPTION
Globe Series GL-QR sprinklers are Listed Quick Response
sprinklers which utilize a 3mm frangible glass bulb as the
thermosensitive operating element. These sprinklers are
available in upright, pendent, and recessed pendent orien-
tations. They are Listed and Approved as Standard Cover-
age sprinklers and are to be installed in accordance with RECESSED PENDENT
the guidelines of the appropriate Installation Standard being
mandated by the AHJ (i.e. NFPA 13; FM 2-0). These sprin-
klers are available in various K-factors, temperatures and UPRIGHT PENDENT
finishes as shown. Recessed escutcheons with either ½”
or ¾” vertical adjustment are available (See Approvals Ta-
bles for appropriate sprinkler/escutcheon combinations and
Listings). Some pendent models are additionally available
RECESSED PENDENT
with a special “Seismic” escutcheon to meet the IBC-ASCE/ SEISMIC IBC/ASCE/SEI CODES
SEI 7 requirements for use in seismic design categories C,
D & E.

OPERATION FINISHES AND ACCESSORIES


Upon exposure to heat such as from a fire, the fluid in the Finishes
bulb expands, compressing the air bubble within the bulb. • Factory Bronze • Chrome • White Polyester
When the air bubble can no longer compress, the fluid ex- • Black Polyester - special order
pansion causes breakage of the glass bulb, resulting in re- Escutcheons
lease of the water seat assembly, and discharge of water • Brass • Chrome • White Polyester • Black Polyester
from the sprinkler. Wrenches
• Standard • Recess • 1/2” NPT • 3/4” NPT

TECHNICAL DATA NOTE:


Corrosion resistant coatings, where applicable, are utilized to
SIN extend the life of copper alloy sprinklers beyond that which would
• Upright: GL2815, GL4215, GL5615, GL8115, GL8118 otherwise be expected when exposed to corrosive atmospheres.
• Pendent, Recessed Pendent: GL2801, GL4201, Although corrosion resistant coated sprinklers have passed the
GL5601, GL8101, GL8106 standard corrosion tests of the applicable approval agencies,
Approvals the testing is not representative of all possible corrosive atmo-
• cULus • FM • LPCB • CE spheres. Consequently, it is recommended that the end user be
consulted with respect to the suitability of these coatings for any
• See Approval Tables given corrosive environment. The effects of ambient temperature,
Maximum Working Pressure concentration of chemicals, humidity, and gas/chemical velocity,
• 175 psi (12 bar) should be considered, as a minimum, along with the corrosive
• Factory tested to 500 psi (34 bar) nature of the chemical to which the sprinklers will be exposed.
Minimum Operating Pressure
• 7 psi (48 kPa)
Temperature Rating
• See Approval Tables
Materials of Construction
• Frame - bronze • Deflector - brass • Screw - brass NOTE:
• Lodgement Wire - stainless steel • Bulb seat - copper Users should refer to Globe’s web site (www.globesprinkler.com)
to ensure that the most recent technical literature is being utilized.
• Spring - nickel alloy • Seal - teflon
• Bulb - glass with alcohol based solution, 3mm
• Escutcheon Assembly - carbon steel
SEP 2019 GFS-100 PAGE 1 OF 6
TABLE A: UPRIGHT SPRINKLER APPROVALS
SIN GL2815 GL4215 (1) GL5615 (1) GL8115 * GL8118 (1)
ORIENTATION UPRIGHT UPRIGHT UPRIGHT UPRIGHT UPRIGHT
K-FACTOR 2.8 (40 metric) 4.2 (60 metric) 5.6 (80 metric) 8.0 (115 metric) 8.0 (115 metric)
NPT 1/2” (15mm) 1/2” (15mm) 1/2” (15mm) 1/2” (15mm) 3/4” (20mm)
HAZARD L.H. L.H L.H./O.H. L.H./O.H. L.H./O.H.
135°F (57°C) 135°F (57°C) 135°F (57°C) 135°F (57°C) 135°F (57°C)
155°F (68°C) 155°F (68°C) 155°F (68°C) 155°F (68°C) 155°F (68°C)
cULus Listed 175°F (79°C) 175°F (79°C) 175°F (79°C) 175°F (79°C) 175°F (79°C)
200°F (93°C) 200°F (93°C) 200°F (93°C) 200°F (93°C) 200°F (93°C)
286°F (141°C) 286°F (141°C) 286°F (141°C) 286°F (141°C) 286°F (141°C)
135°F (57°C) 135°F (57°C)
155°F (68°C) 155°F (68°C)
FM Approved NA NA 175°F (79°C) NA 175°F (79°C)
200°F (93°C) 200°F (93°C)
286°F (141°C) 286°F (141°C)
135°F (57°C) 135°F (57°C)
155°F (68°C) 155°F (68°C)
LPCB
NA NA 175°F (79°C) NA 175°F (79°C)
Ref. No. 147c/05 200°F (93°C) 200°F (93°C)
286°F (141°C) 286°F (141°C)
135°F (57°C) 135°F (57°C)
155°F (68°C) 155°F (68°C)
CE NA NA 175°F (79°C) NA 175°F (79°C)
200°F (93°C) 200°F (93°C)
286°F (141°C) 286°F (141°C)

* FOR RETROFIT USE ONLY


(1) cULus LISTED CORROSION RESISTANT WITH POLYESTER COATING.

FIGURE 3: SERIES GL-QR UPRIGHT SPRINKLERS


GL2815, GL4215, GL5615, GL8115

FIGURE 4: SERIES GL-QR UPRIGHT SPRINKLERS


GL8118

SEP 2019 GFS-100 PAGE 3 OF 6


EXTENDED COVERAGE
SIDEWALL SPRINKLER K FACTOR-8
EXTENDED COVERAGE
LIGHT HAZARD
AUTOMATIC SPRINKLERS
GL SERIES
HORIZONTAL SIDEWALL

DESCRIPTION AND OPERATION


The Globe GL8128, GL8129 and GL8174 Ex-
tended Coverage Horizontal Sidewall Sprinklers
are a low profile yet durable design which utilizes a
3mm frangible glass ampule as the thermosensitive
element. While the sprinkler provides an aesthetically
pleasing appearance, it serves to protect various area
coverages and should be installed in accordance with
NFPA 13. This sprinkler series is available in various
temperature ratings and several finishes to meet many
varying design requirements.
The heart of Globe's Series GL-ECLH sprinkler proven SERIES GL-ECLH/SW
actuating assembly is a hermetically sealed frangi-
EXTENDED COVERAGE
ble glass ampule that contains a precisely measured HORIZONTAL SIDEWALL
amount of fluid. When heat is absorbed, the liquid with-
in the bulb expands increasing the internal pressure. At
the prescribed temperature the internal pressure within
the ampule exceeds the strength of the glass causing
the glass to shatter. This results in water discharge
which is distributed in an approved pattern.

TECHNICAL DATA
• See reverse side for Approvals and Specifications.
• Temperature Ratings -
135°F (57°C), 155°F (68°C), 175°F (79°C), 200° (93°C)
• Water Working Pressure Rating - 175 psi (12 Bars)
• Factory tested hydrostatically to 500 psi (34 Bars)
• Maximum low temperature glass bulb rating is -67°F (-55°C)
• Frame - bronze • Deflector - brass • Screw - brass SERIES GL-ECLH/SW

• Bulb seat - copper • Spring - nickel alloy • Seal - teflon EXTENDED COVERAGE
RECESSED
• Bulb - glass with alcohol based solution, 3mm size HORIZONTAL SIDEWALL
• Escutcheon Assembly - steel

SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING


AVAILVABLE SPRINKLER N.F.P.A. MAXIMUM CEILING
CLASSIFICATION BULB COLOR
TEMPERATURES TEMPERATURE

ORDINARY 135°F/155°F 57°C/68°C ORANGE/RED 100°F 38°C


INTERMEDIATE 175°F/200°F 79°C/93°C YELLOW/GREEN 150°F 66°C

MAR 2019 GFS-225 (Formerly A-46)


EXTENDED COVERAGE
LIGHT HAZARD AUTOMATIC SPRINKLERS
GL SERIES HORIZONTAL SIDEWALL
SPECIFICATIONS AND APPROVALS
NOMINAL THREAD NYC-DOB MEA
SIN STYLE LENGTH FINISHES cULus
“K” FACTOR SIZE 101-92-E

GL8128 Factory Bronze


HORIZONTAL 8.0 3/4”NPT 3” Chrome
GL8129 X X
SIDEWALL (115 metric) (20mm) (7.6cm) White Polyester2
GL8174 Black Polyester1,2
NOTE: METRIC CONVERSIONS ARE APPROXIMATE.
1
FINISHES AVAILABLE ON SPECIAL ORDER. 2AVAILABLE AS cULus LISTED AS CORROSION RESISTANT WHEN SPECIFIED ON ORDER.

cULus LISTING DESIGN - USE REQUIREMENTS FOR LIGHT HAZARDS ONLY


TEMPERATURES MAX. AREA OF MIN. DEFLECTOR MIN. DISTANCE
MIN.
COVERAGE FLOW TO CEILING BETWEEN
SIN STYLE 135°F 155°F 175°F 200°F PRESSURE
WIDTH X LENGTH G.P.M. DISTANCE SPRINKLERS
(57°C) (68°C) (79°C) (93°C) P.S.I. (bars)
Feet (Meters) (L/min.) Inches (mm) Feet (Meters)

16 (4.9) x 16 (4.9) 10.6 (.73) 26 (98)


HORIZONTAL QR QR QR QR
SIDEWALL 16 (4.9) x 18 (5.5) 13.1 (.90) 29 (110) 4 (101.6)
& to
GL8128 QR SR --- SR 16 (4.9) x 20 (6.1) 17.0 (1.17) 33 (125)
RECESSED 6 (152.4)
HORIZONTAL QR* SR --- --- 16 (4.9) x 22 (6.7) 21.4 (1.48) 37 (140)
SIDEWALL
QR* SR --- --- 16 (4.9) x 24 (7.3) 27.6 (1.90) 42 (159)

QR QR QR --- 16 (4.9) x 16 (4.9) 10.6 (.73) 26 (98)


HORIZONTAL
SIDEWALL QR QR QR --- 16 (4.9) x 18 (5.5) 13.1 (.90) 29 (110)
6 (152.4) 8 (2.4)
&
GL8129 QR SR --- SR 16 (4.9) x 20 (6.1) 17.0 (1.17) 33 (125) to
RECESSED
12 (304.8)
HORIZONTAL QR* SR --- --- 16 (4.9) x 22 (6.7) 21.4 (1.48) 37 (140)
SIDEWALL
QR* SR --- --- 16 (4.9) x 24 (7.3) 27.6 (1.90) 42 (159)
HORIZONTAL 16 (4.9) x 16 (4.9) 12.3 (.85) 28 (106)
SIDEWALL
16 (4.9) x 18 (5.5) 15.0 (1.03) 31 (117) 12 (304.8)
&
GL8174 SR --- --- --- to
RECESSED
16 (4.9) x 20 (6.1) 19.1 (1.32) 35 (132) 18 (457.2)
HORIZONTAL
SIDEWALL 16 (4.9) x 22 (6.7) 21.4 (1.48) 37 (140)
NOTE: METRIC CONVERSIONS ARE APPROXIMATE
SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
FOR COVERAGE AREA DIMENSIONS LESS THAN OR BETWEEN THOSE INDICATED, USE THE MINIMUM FLOW FOR THE NEXT HIGHEST COVERAGE
AREA FOR WHICH HYDRAULIC DESIGN CRITERIA ARE STATED.
* LISTED FOR USE WITH 1/2” ADJUSTABLE RECESSED CUP.
ORDERING INFORMATION
CROSS SECTIONS SPECIFY
• Quantity • SIN • Style • Orifice
• Thread Size • Temperature • Finishes desired
1" x 3/4" REDUCER
CEILING CEILING
• Quantity - Wrenches - P/N 312366
1" x 3/4" REDUCER
WALL 4" to 6" (GL8128)
6" to 12" (GL8129) WALL
4" to 6" (GL8128)
6" to 12" (GL8129)
• Quantity - Recessed Wrenches - P/N 325401
12" to 18" (GL8174)
• Quantity - Protective Caps - P/N 327109-CAP
CUP CUP 12" to 18" (GL8174)
RETAINER
RETAINER
2" DIA. MIN.
HOLE IN WALL 2" DIA. MIN. (Friction Fit Recessed)
2 15/16" DIA. HOLE IN WALL
1 29/32" DIA.

GLOBE® PRODUCT WARRANTY


2 15/16" DIA.
1 29/32" DIA.

1" MIN.
1 3/4" MAX. Globe agrees to repair or replace any of its own manufactured
1/8"
1" MIN.
1 1/2" MAX. products found to be defective in material or workmanship for a
1/8" MIN. 1/8"
period of one year from date of shipment.
For specific details of our warranty please refer to Price List
7/8" MAX.
1/8" MIN.
5/8" MAX.

3/4” ADJUSTMENT 1/2” ADJUSTMENT Terms and Conditions of Sale (Our Price List).
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
1-800-248-0278 www.globesprinkler.com
MAR 2019 PRINTED U.S.A. GFS-225 (Formerly A-46)
DRY PENDENT SPRINKLER
K FACTOR-5.6
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES
DRY TYPE PENDENT
SERIES GL-QR/DRY
DESCRIPTION AND OPERATION
The Globe Quick Response Series GL-QR/DRY Pendent Sprinkler is
designed for use in special applications such as freezing environments
and conditions where sediment or foreign materials might accumulate
in ordinary drop nipples.
The Globe Quick Response Series GL-QR/DRY Pendent Sprinkler
utilizes a 3mm frangible glass ampule as the thermosensitive element.
This provides sprinkler operation approximately six times faster than
ordinary sprinklers. At the ampule's rated temperature, the sprinkler
opens releasing the bulb seat, causing the inner tube assembly to
move, allowing the spring assembly to pivot alongside the inner tube.
At this time, water flows through the sprinkler and is distributed by the
deflector in an approved discharge pattern. It can be installed wherever
standard spray sprinklers are specified but offers the additional feature
of greatly increased safety to life. Quick Response Sprinklers should
be used advisedly and under the direction of approving authorities SURFACE SLEEVE & SKIRT
having jurisdiction. MOUNT
The heart of Globe's Series GL-QR/DRY sprinkler proven actuating
assembly is a hermetically sealed frangible glass ampule that contains
a precisely measured amount of fluid. When heat is absorbed, the
liquid within the bulb expands increasing the internal pressure. At the
prescribed temperature the internal pressure within the ampule exceeds
the strength of the glass causing the glass to shatter. This results in
water discharge which is distributed in an approved pattern.

TECHNICAL DATA
• See reverse side for Approvals and Specifications.
• Temperature Ratings -
135°F (57°C), 155°F (68°C), 175°F (79°C)
200°F (93°C), 286°F (141°C)
• Water Working Pressure Rating - 175 psi (12 Bars)
• Factory tested hydrostatically to 500 psi (34 Bars) EXTENDED RECESSED
• Maximum low temperature glass bulb rating is -67°F (-55°C)
• Frame - bronze • Deflector - brass • Screw - brass
• Bulb Seat - brass • Spring - nickel alloy • Seal - teflon
• Retainer - brass • Pin - stainless steel
• Torsion Spring - stainless steel • Orifice Insert - brass
• Bulb - glass with alcohol based solution, 3mm size
• 3/4”NPT or 1”NPT • Outer Tube - galvanized steel pipe • Inner Tube - stainless steel

SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING


AVAILABLE SPRINKLER N.F.P.A. MAXIMUM CEILING
CLASSIFICATION BULB COLOR
TEMPERATURES TEMPERATURE
ORDINARY 135°F/155°F 57°C/68°C ORANGE/RED 100°F 38°C
INTERMEDIATE 175°F/200°F 79°C/93°C YELLOW/GREEN 150°F 66°C
HIGH 286°F 141°C BLUE 225°F 107°C

DEC 2017 GFS-505a (Formerly A-55)


QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES DRY TYPE
PENDENT
SPECIFICATIONS
NOMINAL
THREAD SIZE LENGTH FINISHES
“K” FACTOR

5.6 (80 metric) 3/4” or 1”NPT Factory Bronze


cULus Variable to 48” Chrome
FM Variable to 36” White Polyester2
8.0 (115 metric) 1”NPT Black Polyester1,2
NOTE: METRIC CONVERSIONS ARE APPROXIMATE.
1
FINISHES AVAILABLE ON SPECIAL ORDER.
2
cULus LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER.

APPROVALS
NYC-DOB
K THREAD 135°F 155°F 175°F 200°F 286°F
STYLE SIN HAZARD1 *FM cULus MEA
FACTOR SIZE (57°C) (68°C) (79°C) (93°C) (141°C)
101-92-E
GL5635 5.6 1”NPT LH/OH X X X X X X X X
PENDENT
RECESSED GL5636 5.6 3/4”NPT LH/OH X X X X X --- X X
PENDENT
GL8135 8.0 1”NPT LH/OH X X X X X --- X X
1
SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
*PENDENT STYLE - FM APPROVED 155°F (68°C), 200°F (93°C), AND 286°F (141°C)
*RECESSED PENDENT STYLE - FM APPROVED 155°F (68°C) AND 200°F (93°C)
LH: LIGHT HAZARD; OH: ORDINARY HAZARD

CROSS SECTIONS IMPORTANT INSTALLATION DATA


TEE FITTING TEE FITTING Globe GL Series Dry Pendent Sprinklers should be installed in
ANSI B16.3 CLASS 15 OR ANSI B16.3 CLASS 15 OR
ANSI B16.4 CLASS 125 ANSI B16.4 CLASS 125
accordance with the requirements set forth in NFPA 13. These
FACE OF
TEE
FACE OF
TEE sprinklers are to be installed using a pipe wrench applied to
FITTING FITTING
2 1/2" MIN. DIA.
HOLE IN CEILING the outer tube. When this is not possible, the proper sprinkler
"A"
1" MIN. 3/4"NPT
3/4" MIN. 1"NPT "A"
head wrench may be used with extreme care for lengths up to
2 1/2" MIN. 3/4"NPT
2 1/4" MIN. 1"NPT approximately 18”. Excessive force may distort the frame thus
FACE OF 1 1/2" MIN. DIA.
3 1/2" DIA.
CEILING HOLE IN CEILING destroying the unit.
When installed in a wet system extending into a freezing
TWO PIECE
3 3/4" MIN.
4 3/4" MAX.
ESCUTCHEON
3" DIA.
FACE OF
area see chart on Dry Caution Sheet for minimum exposed
ESCUTCHEON 1/4"

2"
CEILING
barrel length to prevent ice plugs. Please refer to our Dry
Caution Sheet for further important installation data.
EXTENDED SURFACE MOUNT
ORDERING INFORMATION
TEE FITTING
ANSI B16.3 CLASS 15 OR
TEE FITTING
ANSI B16.3 CLASS 15 OR
SPECIFY
ANSI B16.4 CLASS 125 ANSI B16.4 CLASS 125 • Quantity • SIN • Style • Orifice • Temperature • Finishes
FACE OF
TEE
FACE OF
TEE
• Quantity - Wrenches - P/N 333010
FITTING FITTING
• Quantity Recessed Wrenches - P/N 337014
1 3/4" MIN. DIA.
• Escutcheons Desired
HOLE IN CEILING
"A"
3 1/4" MIN. 3/4"NPT
"A"
1 3/4" MIN. 3/4"NPT
• Quantity - Protective Caps - P/N 327109-cap (Friction Fit Recessed)
2 3/4" MIN. 1"NPT 1 1/2" MIN. 1"NPT
“A” Dimension - Distance from face of fitting to the finished ceiling line
2" MIN. DIA.
HOLE IN CEILING
regardless of escutcheon used.
2 15/16" DIA.
3 7/32" DIA.
FACE OF
CEILING

1/8"
FACE OF
TWO PIECE
ESCUTCHEON
2 1/2" MIN.
4" MAX.
G LOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manufactured
1 1/4" MIN. CEILING
2" MAX. CUP
RETAINER
products found to be defective in material or workmanship for a
RECESSED SLEEVE & SKIRT period of one year from date of shipment.
For specific details of our warranty please refer to Price List
Terms and Conditions of Sale (Our Price List).
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
1-800-248-0278 www.globesprinkler.com
DEC 2017 PRINTED U.S.A. GFS-505a (Formerly A-55)
QCDD & UL CERTIFICATE
‫ﺗﺎﺭﻳﺦ ﺍﻟﻄﺒﺎﻋﺔ ‪2018-12-10 :‬‬ ‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴــــﺔ‬
‫ﻭﻗـﺖ ﺍﻟﻄﺒﺎﻋﺔ ‪ :‬ص ‪6:22‬‬ ‫ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﻪ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬
‫ﺭﻗــﻢ ﺍﻟﻄﻠـﺐ ‪PAC18015105 :‬‬ ‫ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

‫ﺷﻬــــــﺎﺩﺓ ﻋﺪﻡ ﻣﻤﺎﻧﻌﺔ‬


‫ﺍﻋﺘﻤﺎﺩ ﻣﻨﺘﺞ‬ ‫ﻧﻮﻉ ﺍﻟﺸﻬﺎﺩﺓ ‪:‬‬

‫ﺑﻴﺎﻧﺎﺕ ﺍﻟﻤﻨﺸﺄﺓ‬

‫ﺍﻳﺸﻴﻠﺪ ﻟﺤﻠﻮﻝ ﺍﻻﻣﻦ ﻭﺍﻟﺴﻼﻣﻪ‬ ‫ﺍﻻﺳﻢ ﺍﻟﺘﺠﺎﺭﻱ‪:‬‬


‫‪66467‬‬ ‫ﺭﻗﻢ ﺍﻟﺮﺧﺼﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ‪:‬‬ ‫‪58809‬‬ ‫ﺭﻗﻢ ﺍﻟﺴﺠﻞ ﺍﻟﺘﺠﺎﺭﻱ‪:‬‬
‫ﺭﻗﻢ ﺍﻟﻬﺎﺗﻒ‪:‬‬ ‫‪12-8569-01‬‬ ‫ﺭﻗﻢ ﻗﻴﺪ ﺍﻟﻤﻨﺸﺄﺓ‪:‬‬
‫ﺍﻟﺒﺮﻳﺪ ﺍﻹﻟﻜﺘﺮﻭﻧﻲ‪:‬‬
‫‪Fire Fighting systems‬‬ ‫ﺍﻟﺘﺼﻨﻴﻒ ‪:‬‬
‫‪Sprinklers and accessories‬‬ ‫ﺇﺳﻢ ﺍﻟﻤﻨﺘﺞ ‪:‬‬

‫ﺗﻔﺎﺻﻴﻞ ﺍﻟﺸﻬﺎﺩﺓ‬

‫ﺗﻢ ﻣﺮﺍﺟﻌﺔ ﺍﻟﻄﻠﺐ ﺍﻟﻤﻘﺪﻡ ﻭﺍﺗﻀﺢ ﺑﺄﻧﻪ ﻻ ﻣﺎﻧﻊ ﻣﻦ ﺍﻋﺘﻤﺎﺩ ﺍﻟﻤﻨﺘﺞ ‪/‬ﺍﻟﻤﻨﺘﺠﺎﺕ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻰ ﺍﻟﻤﺮﻓﻖ ﺑﻨﺎﺀ ﻋﻠﻰ ﺍﻋﺘﻤﺎﺩﻩ ﻣﻦ‬
‫ﻗﺒﻞ ﺍﻟﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﺭ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ‪.‬‬

‫ﻣﻼﺣﻈﺎﺕ ‪:‬‬

‫‪ .1‬ﻳﺠﺐ ﻋﻠﻰ ﺍﻟﺸﺮﻛﻪ ﺍﻻﻟﺘﺰﺍﻡ ﻭﺍﻟﻌﻤﻞ ﺑﻤﺎ ﺟﺎﺀ ﻓﻲ ﺍﺷﺘﺮﺍﻃﺎﺕ ﻗﺴﻢ ﺃﻧﻈﻤﺔ ﺍﻟﺴﻼﻣﻪ ﺍﻟﺘﻲ ﺗﻢ ﺍﻻﻃﻼﻉ ﻭﺍﻟﻤﻮﺍﻓﻘﺔ ﻋﻠﻴﻬﺎ ﻣﻦ ﺧﻼﻝ ﺍﻟﻤﻮﻗﻊ ‪.‬‬
‫‪ .2‬ﻳﺠﺐ ﺍﻥ ﻳﻘﻮﻡ ﺑﺘﺮﻛﻴﺐ ﻫﺬﺍ ﺍﻟﻤﻨﺘﺞ ﻣﻦ ﻗﺒﻞ ﻣﻬﻨﺪﺳﻴﻦ ﻭﻓﻨﻴﻴﻦ ﻣﻌﺘﻤﺪﻳﻦ ﻣﻦ ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‪.‬‬
‫‪ .3‬ﻳﺠﺐ ﺍﻥ ﻳﺤﻤﻞ ﺍﻟﻤﻨﺘﺞ ﺍﻟﻌﻼﻣﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ ﻟﻠﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻌﺘﻤﺪﺓ ﻭﺍﻟﻤﻮﺿﺤﻪ ﻓﻲ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ ‪.‬‬

‫‪09/12/2020‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻹﻧﺘﻬﺎﺀ ‪:‬‬ ‫‪10/12/2018‬‬ ‫ﺗﺎﺭﻳﺦ ﺍﻻﻋﺘﻤﺎﺩ ‪:‬‬

‫ﻉ‪/‬‬

‫ﻣﺪﻳﺮ ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗـﺎﻳـــــﺔ‬


‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬

‫‪Page 1 of 2‬‬
‫ﺑﺴﻢ ﺍﻟﻠﻪ ﺍﻟﺮﺣﻤﻦ ﺍﻟﺮﺣﻴﻢ‬

DATE : 2018-12-10 : ‫ﺍﻟﺘﺎﺭﻳـــــــﺦ‬ ‫ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴﺔ‬


PERMIT PAC18015105 : ‫ﺭﻗﻢ ﺍﻟﻄﻠﺐ‬ ‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬
‫ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ‬

TECHNICAL REPORT ‫ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ‬

PRODUCT : Sprinklers and accessories : ‫ﺍﻟﻤﻨﺘﺞ‬


PRODUCT APPLICATION : Fire Fighting systems : ‫ﺗﺼﻨﻴﻒ ﺍﻟﻤﻌﺪﺓ‬
APPLICANT / P.O .Box ‫ﺍﻳﺸﻴﻠﺪ ﻟﺤﻠﻮﻝ ﺍﻻﻣﻦ ﻭﺍﻟﺴﻼﻣﻪ‬ : ‫ﻣﻘﺪﻡ ﺍﻟﻄﻠﺐ‬
MANUFACTURER /
GLOBE FIRE SPRINKLER CORP. / USA :‫ ﺑﻠﺪ ﺍﻟﺼﻨﻊ‬/ ‫ﺍﻟﺸﺮﻛﺔ ﺍﻟﻤﺼﻨﻌﺔ‬
LOCATION :

‫ﺍﻟﻮﺻﻒ‬ ‫ﺍﻟﻤﻮﺩﻳﻞ‬
Automatic sprinkler, quick response, Upright type, 5.6 nominal K-factor, 175 psig system
GL5615
working pressure, 135, 155, 175, 200, 286 deg.F. temperature rating.
Automatic sprinkler, quick response, pendent type, 8.0 nominal K-factor, 175 psig system
GL8118
working pressure, 135, 155, 175, 200, 286 deg.F. temperature rating.
Automatic sprinkler, quick response, Pendent type, 8.0 nominal K-factor, 175 psig system
GL5601
working pressure, 135, 155, 175, 200, 286 deg.F. temperature rating.
Automatic sprinkler, quick response, Pendent type, 8.0 nominal K-factor, 175 psig system
GL8106
working pressure, 135, 155, 175, 200, 286 deg.F. temperature rating.
Automatic sprinkler, quick response, HSW, Rec. HSW type, 5.6 nominal K-factor, 175 psig
GL5626
system working pressure, 135, 155, 175, 200, 286 deg.F. temperature rating.
Automatic sprinkler, quick response, HSW type, 8.0 nominal K-factor, 175 psig system
GL8127
working pressure, 135, 155, 175, 200, 286 deg.F. temperature rating.

3RD PARTY ‫ﺷﻬﺎﺩﺓ ﺍﻟﻤﺨﺘﺒﺮﺍﺕ ﺍﻟﻤﺴﺎﻧﺪﺓ‬


CERTIFICATE / - VNIV.EX1085 - Underwriters
APPROVAL : Laboratories : ( ‫)ﻣﻦ ﻫﻴﺌﺎﺕ ﻣﻌﺘﻤﺪﺓ‬
(UL)

RECOMMENDATIONS ‫ﺍﻟﺘﻮﺻﻴﺎﺕ‬
NOTES/STANDARD:

Intended to operate when the temperature of the heat-responsive element exceeds its thermal-response
temperature.
INVESTIGATED TO STANDARD UL 199.

/‫ﻉ‬

‫ﻣﺪﻳﺮ ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗـﺎﻳـــــﺔ‬


‫ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ‬

Page 2 of 2
2019-02-27 ŒÃ†Š¼×…žë¥† ŒNNNNì؟…¢×…‹¥…§å
AM 11:00 ŒÃ†Š¼×…ŽNÏå êߢÜׅÁ†Ë¢Ø×âۆÄׅ‹¥…¡ó…
PAC19002476 ˆNؼׅÚNNÏ¥ Œë†Ïæׅ‹¥…¡

ŒÄ߆ÜÛ٢Ë¡†NNNNNNä¯
–àÛ¡†ÜÃ… ‹¡†ä°×…Áæß

‹|°àÜׅ†ß†ì‰

âÛô¬×…åÞÛó…Õæ؜×¢Øì°ë… 饆˜×…Ú«ó…
66467 Œë¥†˜×…Œ´Ÿ¦×…ÚÏ¥ 09 饆˜×…֘¬×…ÚÏ¥
ʏ†äׅÚÏ¥ 12-69-01 ‹|°àÜׅ¢ìÏÚÏ¥
êß妐Ô×ñ…¢ë¦Š×…
)LUH )LJKWLQJ V\VWHPV Êìഐׅ
6SULQNOHUV DQG DFFHVVRULHV –àÜׅÚ«

‹¡†ä°×…Ö쳆̏

ÞÛᡆܐÅèØÃx†à‰Î˦ÜׅèàÌׅ¦ë¦Ð×…èË✷æÜׅ†˜àÜׅ–àÜׅ¡†ÜÃ…ÞÛÂ߆Ûóâß|‰š¸…åÙ¢ÐÜׅˆØ¼×…ŒÄ—…¦Ûڏ
Î˦ÜׅêàÌׅ¥¦Ð×…èË✷æÜׅŒë¦Š Üׅâ„ìäׅ֊Ï

†À›ôÛ

ÂÏæÜׅÕôŸÞÛ†äìØÃŒÐ˅æÜׅåÁô»ó…ڏê×…âÛô¬×…ŒÜÀß{ڬύ†»…¦¯…êËx†—†Ü‰ÖÜÄׅåم¨×ó…âÓ¦°×…èØȘë
êߢÜׅÁ†Ë¢Ø׌ۆÄׅ‹¥…¡ñ…ÞÛÞë¢ÜÄÛÞììàËåÞì«¢àäÛ֊ÏÞÛ–àÜׅ…¤ãˆìÓ¦‰ÙæÐë݅ˆ˜ë
Î˦ÜׅêàÌׅ¦ë¦Ð×…êË✷æÜׅ勢ܐÄÜׅŒë¦Š Üׅâ„ìäØ׌륆˜×…ŒÛôÄׅ–àÜׅÖܜë݅ˆ˜ë

26022021 x†äßñ…žë¥† 27022019 ¡†ÜÃó…žë¥†

ŒNNNNNë†NÏæׅ‹¥…¡¦ë¢Û
êߢÜׅÁ†Ë¢Ø׌ۆÄׅ‹¥…¡ñ…

Page 1 of 2
Ú웦ׅÞܛ¦×…âØׅÚ¬‰

'A7( : 2019-02-27 žNNNNNNN륆×… Œì؟…¢×…‹¥…§å


P(5M,7 PAC19002476 ˆØ¼×…ÚÏ¥ êߢÜׅÁ†Ë¢Ø׌ۆÄׅ‹¥…¡ñ…
Œë†Ïæׅ‹¥…¡

7(C+1,CA/ 5(P257 ϲϨϔϟ΍ ήϳήϘΘϟ΍


P52'8C7 : 6SULQNOHUV DQG DFFHVVRULHV –àÜׅ
P52'8C7 APP/,CA7,21 : )LUH )LJKWLQJ V\VWHPV ‹¢ÄÜׅÊìഏ
APP/,CA17  P2 %R[ âÛô¬×…åÞÛó…Õæ؜×¢Øì°ë… ˆØ¼×…Ù¢ÐÛ
MA18)AC785(5 
*OREH )LUH 6SULQNOHU CRUS  86A Âà´×…¢Ø‰ŒÄà´ÜׅŒÓ¦°×…
/2CA7,21 :

ϒλϮϟ΍ ϞϳΩϮϤϟ΍
5HVSRQVH 7\SH 65 7\SH +6: 5HF +6: 1RP .-)DFWRU 0
*/12
6\VWHP :RUNLQJ PUHVVXUH SVLJ 17 7HPS 5DWLQJ ) 1 1 17 200
5HVSRQVH 7\SH 65 7\SH +6: 5HF +6: 1RP .-)DFWRU 0
*/129
6\VWHP :RUNLQJ PUHVVXUH SVLJ 17 7HPS 5DWLQJ ) 1 1 17

5' PA57< ‹¢ß†¬Üׅ…¦Š Üׅ‹¡†ä¯


C(57,),CA7(  - 91,9(;10 - 8QGHUZULWHUV
APP529A/ : /DERUDWRULHV  ‹¢ÜÄۍ†„ìãÞÛ 
8/

5(C2MM(1'A7,216 †ì³æ×…
1RWHV: 7KH EDVLF VWDQGDUG XVHG WR LQYHVWLJDWH SURGXFWV LQ WKLV FDWHJRU\ LV A16,8/ 199 AXWRPDWLF 6SULQNOHUV
IRU )LUH PURWHFWLRQ 6HUYLFH

ŒNNNNNë†NÏæׅ‹¥…¡¦ë¢Û
êߢÜׅÁ†Ë¢Ø׌ۆÄׅ‹¥…¡ñ…

Page 2 of 2
2019-01-16 ŒÃ†Š¼×…žë¥† ŒNNNNì؟…¢×…‹¥…§å
6:39 ‫Œ ص‬Ɗ¼×…ŽNÏå êߢÜׅÁ†Ë¢Ø×âۆÄׅ‹¥…¡ó…
PAC19000467 ˆNؼׅÚNNÏ¥ Œë†Ïæׅ‹¥…¡

ŒÄ߆ÜÛ٢Ë¡†NNNNNNä¯
–àÛ¡†ÜÃ… ‹¡†ä°×…Áæß

‹|°àÜׅ†ß†ì‰

âÛô¬×…åÞÛó…Õæ؜×¢Øì°ë… 饆˜×…Ú«ó…
66467 Œë¥†˜×…Œ´Ÿ¦×…ÚÏ¥ 09 饆˜×…֘¬×…ÚÏ¥
ʏ†äׅÚÏ¥ 12- 69-01 ‹|°àÜׅ¢ìÏÚÏ¥
êß妐Ô×ñ…¢ë¦Š×…
Êìഐׅ
–àÜׅÚ«

‹¡†ä°×…Ö쳆̏

ÞÛᡆܐÅèØÃx†à‰Î˦ÜׅèàÌׅ¦ë¦Ð×…èË✷æÜׅ†˜àÜׅ–àÜׅ¡†ÜÃ…ÞÛÂ߆Ûóâß|‰š¸…åÙ¢ÐÜׅˆØ¼×…ŒÄ—…¦Ûڏ
Î˦ÜׅêàÌׅ¥¦Ð×…èË✷æÜׅŒë¦Š Üׅâ„ìäׅ֊Ï

†À›ôÛ

ÂÏæÜׅÕôŸÞÛ†äìØÃŒÐ˅æÜׅåÁô»ó…ڏê×…âÛô¬×…ŒÜÀß{ڬύ†»…¦¯…êËx†—†Ü‰ÖÜÄׅåم¨×ó…âÓ¦°×…èØȘë
êߢÜׅÁ†Ë¢Ø׌ۆÄׅ‹¥…¡ñ…ÞÛÞë¢ÜÄÛÞììàËåÞì«¢àäÛ֊ÏÞÛ–àÜׅ…¤ãˆìÓ¦‰ÙæÐë݅ˆ˜ë
Î˦ÜׅêàÌׅ¦ë¦Ð×…êË✷æÜׅ勢ܐÄÜׅŒë¦Š Üׅâ„ìäØ׌륆˜×…ŒÛôÄׅ–àÜׅÖܜë݅ˆ˜ë

1 01 2021 x†äßñ…žë¥† 16 01 2019 ¡†ÜÃó…žë¥†

ŒNNNNNë†NÏæׅ‹¥…¡¦ë¢Û
êߢÜׅÁ†Ë¢Ø׌ۆÄׅ‹¥…¡ñ…

Page 1 of 2
Ú웦ׅÞܛ¦×…âØׅÚ¬‰

A : 2019-01-16 žNNNNNNN륆×… Œì؟…¢×…‹¥…§å


P PAC19000467 ˆØ¼×…ÚÏ¥ êߢÜׅÁ†Ë¢Ø׌ۆÄׅ‹¥…¡ñ…
Œë†Ïæׅ‹¥…¡

C CA P
P C : –àÜׅ
P C APP CA : ‹¢ÄÜׅÊìഏ
APP CA P âÛô¬×…åÞÛó…Õæ؜×¢Øì°ë… ˆØ¼×…Ù¢ÐÛ
A AC
P C P A Âà´×…¢Ø‰ŒÄà´ÜׅŒÓ¦°×…
CA :

- 6 C P
63
1 17

3 PA ‹¢ß†¬Üׅ…¦Š Üׅ‹¡†ä¯
C CA - 10 -
APP A :  ‹¢ÜÄۍ†„ìãÞÛ 

C A †ì³æ×…
A A

A 199 A P
199 A
A 199 A
C 199
A

ŒNNNNNë†NÏæׅ‹¥…¡¦ë¢Û
êߢÜׅÁ†Ë¢Ø׌ۆÄׅ‹¥…¡ñ…

Page 2 of 2
2/9/2019 SPRINKLERS, AUTOMATIC AND OPEN | UL Product iQ

VNIV.EX1085 - SPRINKLERS, AUTOMATIC AND OPEN

Sprinklers, Automatic and Open


See General Information for Sprinklers, Automatic and Open

GLOBE FIRE SPRINKLER CORP EX1085


4077 AIRPARK DR
STANDISH, MI 48658-9447 USA
Sprinklers are glass bulb type. Decorative sprinklers identified by an unplated brass compression screw. Chrome plated and decorative white paint
coated sprinklers identified by uncoated levers.

UPRIGHT AND PENDENT STANDARD SPRAY SPRINKLERS


NOMINAL 5.6 K-FACTOR
System
Response Working
SIN Type Type Pressure, psig Temp Rating, °F
GL5601 QR Pendent 175 135, 155, 175, 200, 286
GL5602 QR Pendent 300 135, 155, 175, 200, 286
GL5615 QR Upright 175 135, 155, 175, 200, 286
GL5616 QR Upright 300 135, 155, 175, 200, 286
GL5617 QR Upright 175 135, 155, 175, 200, 286
GL5651 SR Pendent 175 135, 155, 175, 200, 286, 360
GL5652 SR Pendent 300 135, 155, 175, 200, 286, 360
GL5661 SR Upright 175 135, 155, 175, 200, 286, 360
GL5662 SR Upright 300 135, 155, 175, 200, 286, 360
GL5663 SR Upright 175 135, 155, 175, 200, 286

NOMINAL 1.4 TO 4.2 K-FACTOR


Response Nom System Working
SIN Type Type K-Factor Pressure, psig Temp Rating, °F
GL2801 QR Pendent 2.8 175 135, 155, 175, 200, 286
GL4201 QR Pendent 4.2 175 135, 155, 175, 200, 286
GL4202 QR Pendent 4.2 175 135, 155, 175, 200, 286
GL2815 QR Upright 2.8 175 135, 155, 175, 200, 286
https://iq.ulprospector.com/en/profile?e=160253 1/13
2/9/2019 SPRINKLERS, AUTOMATIC AND OPEN | UL Product iQ

GL4215 QR Upright 4.2 175 135, 155, 175, 200, 286


GL4221 QR Upright 4.2 175 135, 155, 175, 200, 286
GL2851 SR Pendent 2.8 175 135, 155, 175, 200, 286, 360
GL4251 SR Pendent 4.2 175 135, 155, 175, 200, 286, 360
GL4252 SR Pendent 4.2 175 135, 155, 175, 200, 286, 360
GL2861 SR Upright 2.8 175 135, 155, 175, 200, 286, 360
GL4261 SR Upright 4.2 175 135, 155, 175, 200, 286, 360
GL4262 SR Upright 4.2 175 135, 155, 175, 200, 286, 360

NOMINAL 8.0 K-FACTOR


Response Inlet System Working
SIN Type Type Thread NPT Pressure, psig Temp Rating, °F
GL8101 QR Pendent 1/2 175 135, 155, 175, 200, 286
GL8106 QR Pendent 3/4 175 135, 155, 175, 200, 286
GL8102 QR Pendent 1/2 300 135, 155, 175, 200, 286
GL8107 QR Pendent 3/4 300 135, 155, 175, 200, 286
GL8115 QR Upright 1/2 175 135, 155, 175, 200, 286
GL8118 QR Upright 3/4 175 135, 155, 175, 200, 286
GL8116 QR Upright 1/2 300 135, 155, 175, 200, 286
GL8119 QR Upright 3/4 300 135, 155, 175, 200, 286
GL8151 SR Pendent 1/2 175 135, 155, 175, 200, 286, 360
GL8156 SR Pendent 3/4 175 135, 155, 175, 200, 286, 360
GL8152 SR Pendent 1/2 300 135, 155, 175, 200, 286, 360
GL8157 SR Pendent 3/4 300 135, 155, 175, 200, 286, 360
GL8161 SR Upright 1/2 175 135, 155, 175, 200, 286, 360
GL8164 SR Upright 3/4 175 135, 155, 175, 200, 286, 360
GL8162 SR Upright 1/2 300 135, 155, 175, 200, 286, 360
GL8165 SR Upright 3/4 300 135, 155, 175, 200, 286, 360

STANDARD SIDEWALL SPRAY SPRINKLERS


Response Nom System Working
SIN Type Type K-Factor Pressure, psig Temp Rating, °F
GL8127** QR HSW 8.0 175 135, 155, 175, 200, 286
GL2826 QR HSW, Rec. HSW 2.8 175 135, 155, 175, 200, 286
GL4226 QR HSW, Rec. HSW 4.2 175 135, 155, 175, 200, 286
GL5626* QR HSW, Rec. HSW 5.6 175 135, 155, 175, 200, 286
GL5632 QR VSW, Rec. VSW 5.6 175 135, 155, 175, 200, 286
GL8133 QR VSW, Rec. VSW 8.0 175 135, 155, 175, 200, 286
https://iq.ulprospector.com/en/profile?e=160253 2/13
2/9/2019 SPRINKLERS, AUTOMATIC AND OPEN | UL Product iQ

GL8171** SR HSW 8.0 175 135, 155, 175, 200, 286


GL2870 SR HSW, Rec. HSW 2.8 175 135, 155, 175, 200, 286
GL4270 SR HSW, Rec. HSW 4.2 175 135, 155, 175, 200, 286
GL5670* SR HSW, Rec. HSW 5.6 175 135, 155, 175, 200, 286
GL5675 SR VSW, Rec. VSW 5.6 175 135, 155, 175, 200, 286, 360
GL8176 SR VSW, Rec. VSW 8.0 175 135, 155, 175, 200, 286, 360
* For ordinary hazard occupancy installed 4 to 12 in. below the ceiling.

** For ordinary hazard occupancies.

FLUSH, RECESSED AND CONCEALED SPRINKLERS

Response Nom System Working Temp Rating, °F


SIN Type Type K-Factor Pressure, psig Cover Sprinkler
GL2804 QR Conc. Pendent 2.8 175 135 135, 155
GL2845 QR Conc. Pendent 2.8 175 135 135, 155
GL2804 QR Conc. Pendent 2.8 175 155 155, 200
GL2845 QR Conc. Pendent 2.8 175 155 155, 200
GL4204 QR Conc. Pendent 4.2 175 135 135, 155
GL4245 QR Conc. Pendent 4.2 175 135 135, 155
GL4204 QR Conc. Pendent 4.2 175 155 155, 200
GL4245 QR Conc. Pendent 4.2 175 155 155, 200
GL5604 QR Conc. Pendent 5.6 175 135 135, 155
GL5645 QR Conc. Pendent 5.6 175 135 135, 155
GL5605 QR Conc. Pendent 5.6 300 135 135, 155
GL5604 QR Conc. Pendent 5.6 175 155 155, 175, 200
GL5645 QR Conc. Pendent 5.6 175 155 155, 175, 200
GL5605 QR Conc. Pendent 5.6 300 155 155, 175, 200
GL5609 QR Conc. Pendent 5.6 175 135 135, 155
GL5609 QR Conc. Pendent 5.6 175 155 175, 200
GL5646* QR Adj.Conc.Pendent 5.6 300 135, 155 135, 155, 175, 200
GL8145 QR Conc. Pendent 8.0 175 155 155, 175, 200
GL5650 QR Flush Pendent 5.6 175 — 135, 155, 175, 200
GL2826 QR Rec. HSW 2.8 175 — 135, 155, 175, 200, 286
GL4226 QR Rec. HSW 4.2 175 — 135, 155, 175, 200, 286
GL5626 QR Rec. HSW 5.6 175 — 135, 155, 175, 200, 286
GL2801 QR Rec. Pendent 2.8 175 — 135, 155, 175, 200, 286
GL4201 QR Rec. Pendent 4.2 175 — 135, 155, 175, 200, 286
GL4202 QR Rec. Pendent 4.2 175 — 135, 155, 175, 200, 286

https://iq.ulprospector.com/en/profile?e=160253 3/13
2/9/2019 SPRINKLERS, AUTOMATIC AND OPEN | UL Product iQ

GL5601 QR Rec. Pendent 5.6 175 — 135, 155, 175, 200, 286
GL5602 QR Rec. Pendent 5.6 175 — 135, 155, 175, 200, 286
GL8101 QR Rec. Pendent 8.0 175 — 135, 155, 175, 200, 286
GL8106 QR Rec. Pendent 8.0 175 — 135, 155, 175, 200, 286
GL8107 QR Rec. Pendent 8.0 175 — 135, 155, 175, 200, 286
GL8151 SR Rec. Pendent 8.0 175 — 135, 155, 175, 200, 286
GL8156 SR Rec. Pendent 8.0 175 — 135, 155, 175, 200, 286
GL2854* SR Conc. Pendent 2.8 175 135, 155 135, 155, 175, 200
GL2856* SR Conc. Pendent 2.8 175 135, 155 135, 155, 175, 200
GL4254* SR Conc. Pendent 4.2 175 135, 155 135, 155, 175, 200
GL4256* SR Conc. Pendent 4.2 175 135, 155 135, 155, 175, 200
GL5654* SR Conc. Pendent 5.6 175 135, 155 135, 155, 175, 200
GL5656* SR Conc. Pendent 5.6 175 135, 155 135, 155, 175, 200
GL5657* SR Adj.Conc.Pendent 5.6 175 135, 155 135, 155, 175, 200
GL5655 SR Conc. Pendent 5.6 300 135 135, 155
GL8169 SR Conc. Pendent 8.0 175 135 135, 155
GL8169 SR Conc. Pendent 8.0 175 155 155, 175, 200
GL8173* SR Conc. Pendent 8.0 175 135, 155 135, 155, 175, 200
GL5606 QR Conc. Pendent 5.6 175 135, 155 135, 155, 175, 200
GL5653 SR Conc. Pendent 5.6 175 135, 155 135, 155, 175, 200
GL2870 SR Rec. HSW 2.8 175 — 135, 155, 175, 200, 286
GL4270 SR Rec. HSW 4.2 175 — 135, 155, 175, 200, 286
GL5670 SR Rec. HSW 5.6 175 — 135, 155, 175, 200, 286
GL2851 SR Rec. Pendent 2.8 175 — 135, 155, 175, 200, 286
GL4251 SR Rec. Pendent 4.2 175 — 135, 155, 175, 200, 286
GL4252 SR Rec. Pendent 4.2 175 — 135, 155, 175, 200, 286, 360
GL5651 SR Rec. Pendent 5.6 175 — 135, 155, 175, 200, 286
GL5652 SR Rec. Pendent 5.6 175 — 135, 155, 175, 200, 286
* The 135°F and 155°F sprinklers utilize a 135°F coverplate and the 155°F, 175°F, 200°F sprinklers can utilize a 155°F coverplate.

DRY SPRINKLERS
Max System Nom
Response Length, Working K-
SIN Type Type In. Pressure, psig Factor Temp Rating, °F
GL5637+ QR Conc. Pendent 48 175 5.6 135, 155, 175, 200
GL5649+ QR Conc. Pendent 48 175 5.6 135, 155, 175, 200
GL5638+# QR Conc. Pendent 48 175 5.6 135, 155, 175, 200
GL5622+# QR Conc. Pendent 48 175 5.6 135, 155, 175, 200
https://iq.ulprospector.com/en/profile?e=160253 4/13
2/9/2019 SPRINKLERS, AUTOMATIC AND OPEN | UL Product iQ

GL5634+ QR Conc. Pendent 48 175 5.6 135, 155, 175, 200


GL8137+ QR Conc. Pendent 48 175 8.0 135, 155, 175, 200
GL8149+ QR Conc. Pendent 48 175 8.0 135, 155, 175, 200
GL8134+ QR Conc. Pendent 48 175 8.0 135, 155, 175, 200
GL5641& QR HSW, Rec. HSW 48 175 5.6 135, 155, 175, 200,
286
GL5642#& QR HSW, Rec. HSW 48 175 5.6 135, 155, 175, 200,
286
GL8141*& QR HSW, Rec. HSW 48 175 8.0 135, 155, 175, 200,
286
GL5635 QR Pendent, Rec. 48 175 5.6 135, 155, 175, 200,
Pendent 286
GL5636# QR Pendent, Rec. 48 175 5.6 135, 155, 175, 200,
Pendent 286
GL8135 QR Pendent, Rec. 48 175 8.0 135, 155, 175, 200,
Pendent 286
GL5639++ QR Upright 48 175 5.6 135, 155, 175, 200,
286
GL5640# QR Upright 48 175 5.6 135, 155, 175, 200,
286
GL8139++ QR Upright 48 175 8.0 135, 155, 175, 200,
286
GL5644++#* QR VSW 48 175 5.6 135, 155, 175, 200,
286
GL5643++* QR VSW 48 175 5.6 135, 155, 175, 200,
286
GL8143++* QR VSW 48 175 8.0 135, 155, 200, 286
GL5681+ SR Conc. Pendent 48 175 5.6 135, 155, 175, 200
GL5677+ SR Conc. Pendent 48 175 5.6 135, 155, 175, 200
GL5682+# SR Conc. Pendent 48 175 5.6 135, 155, 175, 200
GL5678+# SR Conc. Pendent 48 175 5.6 135, 155, 175, 200
GL5689+ SR Conc. Pendent 48 175 5.6 135, 155, 175, 200
GL8181+ SR Conc. Pendent 48 175 8.0 135, 155, 175, 200
GL8177+ SR Conc. Pendent 48 175 8.0 135, 155, 175, 200
GL8189+ SR Conc. Pendent 48 175 8.0 135, 155, 175, 200
GL5686# SR HSW, Rec. HSW 48 175 5.6 135, 155, 175, 200,
286
GL5685 SR HSW, Rec. HSW 48 175 5.6 135, 155, 175, 200,
286

https://iq.ulprospector.com/en/profile?e=160253 5/13
2/9/2019 SPRINKLERS, AUTOMATIC AND OPEN | UL Product iQ

GL8185*& SR HSW, Rec. HSW 48 175 8.0 135, 155, 175, 200,
286
GL5679 SR Pendent, Rec. 48 175 5.6 135, 155, 175, 200,
Pendent 286
GL5680# SR Pendent, Rec. 48 175 5.6 135, 155, 175, 200,
Pendent 286
GL8179 SR Pendent, Rec. 48 175 8.0 135, 155, 175, 200,
Pendent 286
GL5683++ SR Upright 48 175 5.6 135, 155, 175, 200,
286
GL5684++# SR Upright 48 175 5.6 135, 155, 175, 200,
286
GL8183++ SR Upright 48 175 8.0 135, 155, 175, 200,
286
GL5688++#* SR VSW 48 175 5.6 135, 155, 175, 200,
286
GL5687++* SR VSW 48 175 5.6 135, 155, 175, 200,
286
GL8187++* SR VSW 48 175 8.0 135, 155, 175, 200,
286
+ The 135°F and 155°F sprinklers utilize a 135°F coverplate and the 155°F, 175°F, 200°F sprinklers can utilize a 155°F coverplate.

++ Upright style with minimum operation pressure of 12 psig.

* For light and ordinary hazard occupancies.

# 3/4 in. N.P.T.

&* For installation 4 to 12 in. below the ceiling.

STANDARD RESPONSE (SR) - EXTENDED COVERAGE SPRINKLER - LIGHT HAZARD


Max Max Min Distance
Width Length Flow Nom Below
SIN Type (A) Ft (B) Ft GPM K-Factor Ceiling In. Temp Rating, °F
GL8174 HSW, Rec. HSW 16 16 28 8.0 12-18 135
GL8174 HSW, Rec. HSW 16 18 31 8.0 12-18 135
GL8128 HSW, Rec. HSW 16 20 33 8.0 4-6 155, 200
GL8129 HSW, Rec. HSW 16 20 33 8.0 6-12 155, 200
GL8174 HSW, Rec. HSW 16 20 35 8.0 12-18 135
GL8128 HSW, Rec. HSW 16 22 37 8.0 4-6 155
GL8129 HSW, Rec. HSW 16 22 37 8.0 6-12 155
GL8174 HSW, Rec. HSW 16 22 37 8.0 12-18 135
GL8128 HSW, Rec. HSW 16 24 42 8.0 4-6 155
GL8129 HSW, Rec. HSW 16 24 42 8.0 6-12 155
GL1112 Pendent 20 20 40 11.2 12-18 155
https://iq.ulprospector.com/en/profile?e=160253 6/13
2/9/2019 SPRINKLERS, AUTOMATIC AND OPEN | UL Product iQ

GL8159 Pendent, Rec. Pendent 16 16 26 8.0 12-18 135, 155, 175, 200
GL8159 Pendent, Rec. Pendent 18 18 33 8.0 12-18 135, 155, 175, 200
GL8159 Pendent, Rec. Pendent 20 20 40 8.0 12-18 135, 155, 175, 200
(A) Dimension of wall on which a sidewall sprinkler is installed.

(B) Dimension perpendicular to wall on which a sidewall sprinkler is installed.

QUICK RESPONSE (QR) - EXTENDED COVERAGE SPRINKLERS - LIGHT HAZARD


Distance
Max Max Min System Nom Below
Width Length Flow Working K- Ceiling, Temp Rating,
SIN Type (A) Ft (B) Ft GPM Pressure, psig Factor In. °F
GL5603+ Conc. Pendent 16 16 26 175 5.6 — 135,155,175
GL5603+ Conc. Pendent 18 18 33 175 5.6 — 135,155,175
GL5603 Conc. Pendent 20 20 40 175 5.6 — 135
GL5613+ Conc. HSW 16 18 29 175 5.6 4-6 135, 155, 175
GL5613+ Conc. HSW 16 18 32 175 5.6 6-12 135, 155, 175
GL5613+ Conc. HSW 16 20 32 175 5.6 4-12 135, 175
GL5614 Pendent, Rec. 16 16 26 175 5.6 — 135, 155, 175,
Pendent 200
GL5614 Pendent, Rec. 18 18 33 175 5.6 — 135, 155, 175,
Pendent 200
GL5614 Pendent, Rec. 20 20 40 175 5.6 — 135
Pendent
GL8113+ Conc. HSW 16 16 26 175 8.0 4-12 135, 155, 175
GL8113+ Conc. HSW 16 18 29 175 8.0 4-6 135, 155, 175
GL8113+ Conc. HSW 16 18 32 175 8.0 6-12 135, 155, 175
GL8113+ Conc. HSW 16 20 32 175 8.0 4-6 135, 175
GL8113+ Conc. HSW 16 20 37 175 8.0 6-12 135, 175
GL8114++ Conc. HSW 16 22 36 175 8.0 4-6 135
GL8114++ Conc. HSW 16 24 39 175 8.0 4-6 135
GL8114++ Conc. HSW 18 20 36 175 8.0 4-12 135
GL8114++ Conc. HSW 18 22 40 175 8.0 4-12 135
GL8104+ Conc. Pendent 16 16 26 175 8.0 — 135, 155, 175,
200
GL8104+ Conc. Pendent 18 18 32 175 8.0 — 135, 155, 175,
200
GL8104+ Conc. Pendent 20 20 40 175 8.0 — 135
GL5628 HSW 16 20 32 175 5.6 4-12 175
GL5628 HSW, Rec. HSW 16 16 26 175 5.6 4-6 200

https://iq.ulprospector.com/en/profile?e=160253 7/13
2/9/2019 SPRINKLERS, AUTOMATIC AND OPEN | UL Product iQ

GL5628 HSW, Rec. HSW 16 16 26 175 5.6 4-12 135, 155, 175
GL5628 HSW, Rec. HSW 16 18 29 175 5.6 4-6 200
GL5628 HSW, Rec. HSW 16 18 29 175 5.6 4-12 135, 155, 175
GL5628 HSW, Rec. HSW 18 18 32 175 5.6 4-6 200
GL5628 HSW, Rec. HSW 18 18 32 175 5.6 4-12 135, 155, 175
GL5628 HSW, Rec. HSW 16 20 32 175 5.6 4-12 135
GL8128 HSW, Rec. HSW 16 16 26 175 8.0 4-6 135, 155, 175,
200
GL8129 HSW, Rec. HSW 16 16 26 175 8.0 6-12 135, 155, 175
GL8128 HSW, Rec. HSW 16 18 29 175 8.0 4-6 135, 155, 175,
200
GL8129 HSW, Rec. HSW 16 18 29 175 8.0 6-12 135, 155, 175
GL8128 HSW, Rec. HSW 16 20 33 175 8.0 4-6 135
GL8129 HSW, Rec. HSW 16 20 33 175 8.0 6-12 135
GL8129 HSW, Rec. HSW 16 22 37 175 8.0 6-12 135
GL8128 HSW, Rec. HSW 16 22 37 175 8.0 4-6 135
GL8129 HSW, Rec. HSW 16 24 42 175 8.0 6-12 135
GL8128 HSW, Rec. HSW 16 24 42 175 8.0 4-6 135
GL8109 Pendent, Rec. 16 16 26 175 8.0 — 135, 155, 175,
Pendent 200
GL8109 Pendent, Rec. 18 18 33 175 8.0 — 135, 155, 175,
Pendent 200
GL8109 Pendent, Rec. 20 20 40 175 8.0 — 135
Pendent
GL1112 Pendent, Rec. 18 18 33 175 11.2 — 135, 155, 200
Pendent
GL1112 Pendent, Rec. 20 20 40 175 11.2 — 135, 175
Pendent
GL1112 Pendent 18 18 33 175 11.2 — 135, 155,175
GL1112 Pendent 20 20 40 175 11.2 — 135, 155, 175
GL1106+ Concealed Pendent 16 16 30 175 11.2 _ 135, 155, 175,
200
GL1106+ Concealed Pendent 18 18 33 175 11.2 _ 135, 155, 175,
200
GL1106+ Concealed Pendent 20 20 40 175 11.2 _ 135, 155, 175,
200
+ The 135°F and 155°F sprinklers utilize a 135°F coverplate and the 175°F, 200°F sprinklers utilize a 155°F coverplate.

++ Utilizes a 135°F cover plate only.

(A) Dimension of wall on which a sidewall sprinkler is installed.

https://iq.ulprospector.com/en/profile?e=160253 8/13
2/9/2019 SPRINKLERS, AUTOMATIC AND OPEN | UL Product iQ
(B) Dimension perpendicular to wall on which a sidewall sprinkler is installed.

STANDARD RESPONSE (SR) EXTENDED COVERAGE SPRINKLERS - ORDINARY HAZARD


Min
Max Ordinary Sprinkler
Width x Length Hazard Flow Rate Nom
SIN Type Ft x Ft Group GPM K-Factor Temp Rating, °F
GL1113 Pendent, Rec. Pendent 16X16 1 39 11.2 155, 175, 200, 286
GL1113 Pendent, Rec. Pendent 16X16 2 51 11.2 155, 175, 200, 286
GL1113 Pendent, Rec. Pendent 18X18 1 49 11.2 155, 175, 200, 286
GL1113 Pendent, Rec. Pendent 18X18 2 65 11.2 155, 175, 200, 286
GL1113 Pendent, Rec. Pendent 20X20 1 60 11.2 155, 175, 200, 286
GL1113 Pendent, Rec. Pendent 20X20 2 80 11.2 155, 175, 200, 286
GL1121 Upright 16X16 1 39 11.2 155, 175, 200, 286
GL1121 Upright 16X16 2 51 11.2 155, 175, 200, 286
GL1121 Upright 18X18 1 49 11.2 155, 175, 200, 286
GL1121 Upright 18X18 2 65 11.2 155, 175, 200, 286
GL1121 Upright 20X20 1 60 11.2 155, 175, 200, 286
GL1121 Upright 20X20 2 80 11.2 155, 175, 200, 286

QUICK RESPONSE (QR)-EXTENDED-COVERAGE SPRINKLERS - ORDINARY HAZARD


Max Min
Width x Ordinary Sprinkler Temp
Length Hazard Flow Rate Nom Rating,
SIN Type ft x ft Group gpm K-Factor °F
GL1113 Pendent, Recessed Pendent 14 x 14 1 30 11.2 155, 200
GL1113 Pendent, Recessed Pendent 14 x 14 2 39 11.2 155, 200
GL1121 Upright 14 x 14 1 30 11.2 155, 200
GL1121 Upright 14 x 14 2 39 11.2 155, 200

CORROSION RESISTANT SPRINKLERS


Nom
SIN Type K-Factor Coating Type Temp Rating, °F
GL5685 Dry HSW 5.6 Lead, Wax, Wax over Lead, Polyester 135, 155, 175, 200, 286
GL5686 Dry HSW 5.6 Lead, Wax, Wax over Lead, Polyester 135, 155, 175, 200, 286
GL5679 Dry Pendent 5.6 Lead, Wax, Wax over Lead, Polyester 135, 155, 175, 200, 286
GL5680 Dry Pendent 5.6 Lead, Wax, Wax over Lead, Polyester 135, 155, 175, 200, 286
GL5683 Dry Upright 5.6 Lead, Wax, Wax over Lead, Polyester 135, 155, 175, 200, 286
GL5684 Dry Upright 5.6 Lead, Wax, Wax over Lead, Polyester 135, 155, 175, 200, 286
GL5687 Dry VSW 5.6 Lead, Wax, Wax over Lead, Polyester 135, 155, 175, 200, 286

https://iq.ulprospector.com/en/profile?e=160253 9/13
2/9/2019 SPRINKLERS, AUTOMATIC AND OPEN | UL Product iQ

GL5688 Dry VSW 5.6 Lead, Wax, Wax over Lead, Polyester 135, 155, 175, 200, 286
GL2826 HSW 2.8 Lead, Polyester 135, 155, 175, 200, 286
GL2870 HSW 2.8 Polyester 135, 155, 175, 200, 286, 360
GL2870 HSW 2.8 Wax, Wax over Lead 155, 200
GL4226 HSW 4.2 Lead, Polyester 135, 155, 175, 200, 286
GL4270 HSW 4.2 Polyester 135, 155, 175, 200, 286, 360
GL4270 HSW 4.2 Wax, Wax over Lead 155, 200
GL5626 HSW 5.6 Lead, Polyester 135, 155, 175, 200, 286
GL5642 DRY HSW 5.6 Lead, Polyester 135, 155, 175, 200, 286
GL5686 DRY HSW 5.6 Lead, Wax, Wax over Lead, Polyester 135, 155, 175, 200, 286
GL5670 HSW 5.6 Polyester 135, 155, 175, 200, 286, 360
GL5670 HSW 5.6 Wax, Wax over Lead 155, 200
GL8127 HSW 8.0 Lead, Polyester 135, 155, 175, 200, 286
GL8143 DRY HSW 8.0 Lead, Polyester over Lead, Polyester 135, 155, 175, 200, 286
GL8171 HSW 8.0 Polyester 155, 200
GL8171 HSW 8.0 Wax, Wax over Lead 155, 200
GL2801 Pendent 2.8 Lead 135, 155, 200, 286, 360
GL2851 Pendent 2.8 Lead, Polyester 135, 155, 175, 200, 286, 360
GL2851 Pendent 2.8 Wax, Wax over Lead 155, 200
GL4201 Pendent 4.2 Lead, Polyester 135, 155, 175, 200, 286
GL4202 Pendent 4.2 Lead, Polyester 135, 155, 175, 200, 286
GL4251 Pendent 4.2 Lead, Polyester 135, 155, 175, 200, 286, 360
GL4251 Pendent 4.2 Wax, Wax over Lead 155, 200
GL4252 Pendent 4.2 Lead, Polyester 135, 155, 175, 200, 286, 360
GL4252 Pendent 4.2 Wax, Wax over Lead 155, 200
GL5601 Pendent 5.6 Lead, Polyester 135, 155, 175, 200, 286
GL5635 DRY Pendent 5.6 Lead, Polyester 135, 155, 175, 200, 286
GL5635 DRY Pendent 5.6 Lead, Polyester 135, 155, 175, 200, 286
GL5651 Pendent 5.6 Lead, Polyester 135, 155, 175, 200, 286, 360
GL5651 Pendent 5.6 Wax, Wax over Lead 155, 200
GL8106 Pendent 8.0 Lead, Polyester 135, 155, 175, 200, 286
GL8139 DRY Pendent 8.0 Lead, Polyester 135, 155, 175, 200, 286
GL8156 Pendent 8.0 Lead, Polyester 135, 155, 175, 200, 286, 360
GL8156 Pendent 8.0 Wax, Wax over Lead 155, 200
GL1112 Rec. Pendent 11.2 Lead, Polyester 135, 155, 175, 200, 286
GL2815 Upright 2.8 Lead 135, 155, 200, 286, 360

https://iq.ulprospector.com/en/profile?e=160253 10/13
2/9/2019 SPRINKLERS, AUTOMATIC AND OPEN | UL Product iQ

GL2861 Upright 2.8 Lead, Polyester 135, 155, 175, 200, 286, 360
GL2861 Upright 2.8 Wax, Wax over Lead 155, 200
GL4215 Upright 4.2 Lead, Polyester 135, 155, 175, 200, 286
GL4221 Upright 4.2 Lead, Polyester 135, 155, 175, 200, 286
GL4261 Upright 4.2 Lead, Polyester 135, 155, 175, 200, 286, 360
GL4261 Upright 4.2 Wax, Wax over Lead 155, 200
GL4262 Upright 4.2 Lead, Polyster 135, 155, 175, 200, 286, 360
GL4262 Upright 4.2 Wax, Wax over Lead 155, 200
GL5615 Upright 5.6 Lead, Polyester 135, 155, 175, 200, 286
GL5639 DRY Upright 5.6 Lead, Polyester 135, 155, 175, 200, 286
GL5640 DRY Upright 5.6 Lead, Polyester 135, 155, 175, 200, 286
GL5661 Upright 5.6 Lead, Polyester 135, 155, 175, 200, 286, 360
GL5661 Upright 5.6 Wax, Wax over Lead 155, 200
GL8118 Upright 8.0 Lead, Polyester 135, 155, 175, 200, 286
GL8135 DRY Upright 8.0 Lead, Polyester 135, 155, 175, 200, 286
GL8164 Upright 8.0 Lead, Polyester 135, 155, 175, 200, 286, 360
GL8164 Upright 8.0 Wax, Wax over Lead 155, 200
GL5642 DRY VSW 5.6 Lead, Polyester 135, 155, 175, 200, 286
GL5675 VSW 5.6 Lead, Polyester 135, 155, 175, 200, 286, 360
GL5688 DRY VSW 5.6 Lead, Wax, Wax over Lead, Polyester 135, 155, 175, 200, 286
GL8143 DRY VSW 8.0 Lead, Polyester 135, 155, 175, 200, 286, 360
GL8187 DRY VSW 8.0 Lead, Polyester 135, 155, 175, 200, 286
GL8133 VSW 8.0 Lead, Polyester 135, 155, 175, 200, 286, 360

INTERMEDIATE LEVEL SPRINKLERS


Response Nom Temp
SIN Type Type K-Factor Rating, F
GL8106 QR Pendent 8.0 135, 155, 175, 200, 286
GL5601 QR Pendent 5.6 135, 155, 175, 200, 286
GL5615 QR Upright 5.6 135, 155, 175, 200, 286
GL5617 QR Upright 5.6 135, 155, 175, 200, 286
GL8101 QR Pendent 8.0 135, 155, 175, 200, 286
GL8115 QR Upright 8.0 135, 155, 175, 200, 286
GL8117 QR Upright 8.0 135, 155, 175, 200, 286
GL8118 QR Upright 8.0 135, 155, 175, 200, 286
GL8120 QR Upright 8.0 135, 155, 175, 200, 286
GL8151 SR Pendent 8.0 135, 155, 175, 200, 286

https://iq.ulprospector.com/en/profile?e=160253 11/13
2/9/2019 SPRINKLERS, AUTOMATIC AND OPEN | UL Product iQ

GL8156 SR Pendent 8.0 135, 155, 175, 200, 286


GL5661 SR Upright 5.6 135, 155, 175, 200, 286
GL5663 SR Upright 5.6 135, 155, 175, 200, 286
GL5651 SR Pendent 5.6 135, 155, 175, 200, 286
GL8161 SR Upright 8.0 135, 155, 175, 200, 286
GL8163 SR Upright 8.0 135, 155, 175, 200, 286
GL8164 SR Upright 8.0 135, 155, 175, 200, 286
GL8166 SR Upright 8.0 135, 155, 175, 200, 286
GL1114 QR Pendent 11.2 155, 175, 200, 286
GL1124 QR Upright 11.2 155, 175, 200, 286
GL1123 QR Upright 11.2 155, 175, 200, 286
GL1160 SR Pendent 11.2 155, 175, 200, 286
GL1167 SR Upright 11.2 155, 175, 200, 286
GL1168 SR Upright 11.2 155, 175, 200, 286

SPRINKLERS FOR STORAGE PROTECTION (CONTROL MODE DENSITY AREA)


Response Nom
SIN Type Type K-Factor Temp Rating, °F
GL1114 QR Pendent 11.2 155, 175, 200, 286
GL1123 QR Upright 11.2 155, 175, 200, 286
GL1160 SR Pendent 11.2 155, 175, 200, 286
GL1167 SR Upright 11.2 155, 175, 200, 286

SPECIFIC-APPLICATION SPRINKLERS
Attic Sprinklers
Response Fire Roof Pitch, Max Width, Max Length, Min Flow Nom Temp
SIN Type Risk in./in. ft ft Rate, gpm K-Factor Rating, °F
GL5620 QR ++ 3/12 to 6/12 8 24 20 5.6 200
GL5621 QR ++ 3/12 to 6/12 8 24 20 5.6 200
++ For protection of light hazard attic spaces of wood truss or open wood joist construction with saddle-type and hip-type roofs in buildings 24 to
72 ft. in width and not exceeding a protection area of 400 sq. ft. per sprinkler when installed in accordance with the Manufacturer's Installation
and Design Parameter Instructions.

SPECIFIC-APPLICATION SPRINKLERS
Concealed-space Sprinklers
Height of Max Temp
Space, in. Coverage Nom Rating,
SIN Response Type Type Min Max Area, ft2 K-Factor °F
GL5608+ ** QR Upright 12 60 256 5.6 175, 200
GL5608++ ** QR Upright 6* 84 256 5.6 175, 200

https://iq.ulprospector.com/en/profile?e=160253 12/13
2/9/2019 SPRINKLERS, AUTOMATIC AND OPEN | UL Product iQ
* Minimum distance between upper and lower joists.

** Wet or Dry pipe systems using steel pipe.

+ For use in light hazard flat concealed spaces incorporating noncombustible or wood truss construction. The Manufacturers Installation and
Design Parameter Instructions should be consulted for specific installation parameters, obstruction criteria and hydraulic design requirements.

++ For use in combustible solid wood and composite wood joist construction.

Last Updated on 2018-10-28

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with
permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the
following format: "© 2019 UL LLC"

https://iq.ulprospector.com/en/profile?e=160253 13/13
PREVIOUS PROJECT APPROVALS
PROJECT REFERENCE LIST
PROJECT LIST OF ISHIELD SECURITY & SAFETY SOLUTIONS

No. Project Name Description Contractor Consultant SCOPE OF WORK

Construction & Maintenance of Supply & Installation Testing & Commisioning of Wet sprinkler
Structurel ACE Consulting
1 Arab Center for Research & Governmenet system, Fire Pump, FM-200 system, Foam system, Anti freeze
Policy Studies
Qatar Engineers sprinkler system & Fire Hydrant.

Supply of Fire Fighting Equipments & Installation of NOVEC &


2 Holiday Inn Hotel Matrix AEB
Aerosol system.

Supply of Fire Fighting Equipments & Supply of Fire Pump set,


3 QSTP-TECH 4 Commercial BUTEC PARSONS
Testing & commissioning.

Al Moayyed James Cubitt &


New Early ChildHood Teachers Supply of Fire Fighting Equipments & Installation Testing &
4 University Air Partner
Training Center Commissioning of Aerosol system & NOVEC system.
Conditioning Consultancy

Souq Wakif Under Ground Car Supply of Fire Fighting Equipments & Installation Testing &
5 Car Park Arabian MEP PARSONS
Park Commissioning of Aerosol system, Foam system & FM-200 system.

Supply Installation Testing & Commissioning of Fire Fighting


6 Lexus Shoroom Commercial Shannon MZ & Partner
Equipments, Fire Pump set, Foam system & FM-200 System.

Souq Ahmad & Souq Najada Supply Installation Testing & Commissioning of Fire Fighting
7 Tunnel UCC Louis Berger
Pedestrain Tunnel Equipments, Fire Pump & NOVEC System.
PROJECT LIST OF ISHIELD SECURITY & SAFETY SOLUTIONS

No. Project Name Description Contractor Consultant SCOPE OF WORK

Residential Supply & Installation Testing & Commisioning of Aerosol Fire


8 Abraj Quartiers Arabian MEP KEO
Appartment Suppression system
Shooting Range at Lehsaynia Phas-
9 Government EMEC Qatar Louis Berger Supply, Installation of Wet sprinkler system, Fire Pump, FM-200
1
Commercial Supply of Wet sprinklers system, Fire Pump, NOVEC-1230,
10 CBQ Laboulevard Arabian MEP AEB
Building Preaction system
Centra Supply & Installation, Testing & Commisioning of Aerosol Fire
11 Barzan Camp Residential AEB
Corporation Suppression system
Shapoorji Supply, Installation, Testing & Commissioning of Wet sprinkler
12 South East Car Park Car Park PARSONS
Paloonji system, Novec-1230, FM-200 system

Vector
Supply, Installation, Testing & Commissioning of Wet sprinkler
13 Le Miarage Appartments 4 Residential Electromechanic LACASA
system, Novec-1230, Aerosol Fire Suppression system.
al

6 km Under Ground Piping with 56 Hydrants.


Sidra Village Staff Housing – Pkg. Residential
14 Millennium AEB
2 (Qatar Foundation) Compound Supply, Installation, Testing & commisioning of Fire Alarm, Wet
sprinklers system, FM-200, Aerosol Fire Suppression system, Foam
System.
Supply, Installation, Testing & commisioning of Fire Alarm, Wet
15 Tawar Mall Commercial Arabian MEP ACG sprinklers system, FM-200, Aerosol Fire Suppression system, Foam
System.
PROJECT LIST OF ISHIELD SECURITY & SAFETY SOLUTIONS

No. Project Name Description Contractor Consultant SCOPE OF WORK

James Cubitt & Supply, Installation Testing & Commisioning of Wet Sprinkler
16 QIB Hotel Commercial Shannon Partner system, Fire Pump, Fire Alarm System, Aerosol Fire Suppression
Consultancy system

Porto Arabia Tower, The Pearl Supply ,Installation, Testing & Commisioning of Wet sprinkler
17 Commercial Bloom EHAF
Qatar system, Fire Pump,Aerosol Fire Suppression system, Foam system

Diversion Work : Modify the current under ground Pipes with new
18 Doha Port Pkg. 2 Commercial Ishield AEB 26 Hydrant (3 Km Under Ground Pipe)
Supply, Installation of Wet sprinkler system, Fire Pump, Novec-1230
system
Development of Land at Ein
Khaled – Commercial Commercial Supply, Installation, Testing & Commisioning of Aerosol Fire
19 HKH EHAF
Development (B+G+ME+2) for Building Suppression system.
Qatar Navigation

Convention Centre – Education Convention


Testing & Commisioning of Wet sprinkler system, Fire Pump,FM-
20 City – Qatar Foundation (Tree Centre and Baytur KEO & Diwan
200 System.
Building ) – Gharafa multipurpose hall

HMC-Hamad Medical Supply ,Installation, Testing & Commisioning of Wet sprinkler


21 Hospital HMC APG
Corporation system, Fire Pump,Aerosol Fire Suppression system, Foam system
PROJECT LIST OF ISHIELD SECURITY & SAFETY SOLUTIONS

No. Project Name Description Contractor Consultant SCOPE OF WORK

Supply, Installation, Testing & Commisioning of Aerosol Fire


22 Messila Compound Residential Villa GET EHAF
Suppression system.
Supply, Installation, Testing & Commisioning of Aerosol Fire
23 Wajba Palace Residential Structurel Qatar GHD
Suppression system.

Qatar Academy Auditorium (Qatar PAT Supply, Installation, Testing & Commisioning of NOVEC-1230
24 Recreational AEB System
Foundation) Engineering

25 Doha Port Pkg. 1 Commercial Ishield AEB Supply, Installation, Testing & Commisioning of Fire Alarm system

Design and Supply, Installation, Testing & Commisioning of Fire Alarm system,
26 Al Hekma International School Education - Fire Pump, wet sprinkler system.
Built

Supply, Installation, Testing & Commisioning of Fire Alarm system,


27 Al Khaliji Bank Commercial Shannon AEB Fire Pump, wet sprinkler system, FM-200 System, Aerosol Fire
Supression system.

United Supply, Installation, Testing & Commisioning of Fire Alarm system,


28 Al Sharq Newspapers HQ Commercial Al Khaleej Fire Pump, wet sprinkler system.
Consultant

Alfardan (Proposed Residential Supply, Installation, Testing & Commisioning Fire Pump, wet
29 Commercial Shannon AEB sprinkler system, FM-200 System, Aerosol Fire Supression system.
Apartment)
PROJECT LIST OF ISHIELD SECURITY & SAFETY SOLUTIONS

No. Project Name Description Contractor Consultant SCOPE OF WORK

Dukhan Tower (B+G+36) Red Line Supply, Installation, Testing & Commisioning of Fire Alarm system,
30 Hotel Apartment AEB Fire Pump, wet sprinkler system.
Dafna Area beside W Hotel Contractor

12 Building each Supply, Installation, Testing & Commisioning of Fire Pump, wet
31 Awqaf Building – Bin Mahmoud Hassanesco ECG
B+G+8 sprinkler system & Fire Alarm system.

Barahaa Tower – Lusail Area Supply of Hose Reel cabinets & Testing Commisioning of Fire
32 Commercial CRC EHAF Pump.
(4B+G+18)

Supply, Installation, Testing & Commisioning of Aerosol Fire


33 CBQ – Al Jazeera Branch Financial How United QEA
Suppression system.
Crown Plaza Staff 7 Buildings each Supply, Installation, Testing & Commisioning of Fire Pump, wet
34 Shannon AEB
Accommodation G+4 sprinkler system, FM-200 System.
Dukhan Tower (Dafna Area ) Supply, Installation, Testing & Commisioning of Aerosol Fire
35 Commercial Shannon Al Aqsa
B+G+32 Suppression system.
36 El Sad Police Station Government Hassensco Al Jazeera Supply, Installation, Testing & Commisioning of Aerosol Fire
GCC – Electricity Head Quarter Supply, Installation, Testing & Commisioning of Fire Pump, wet
37 Government Shannon AEB sprinkler system, FM-200 System.
(2B+G+4)
Supply, Installation, Testing & Commisioning of Fire Pump, wet
38 Gulf Glass Factory Industrial PPE Qatar Design sprinkler system & Fire Alarm system.
Design and Supply, Installation, Testing & Commisioning of Aerosol Fire
39 Hamad Medical Corporation Government - Suppression system.
Built

You might also like