Professional Documents
Culture Documents
Transformer Protection RET670: Exercise 3 - Differential Protection Open CT and OLTC Adjustment
Transformer Protection RET670: Exercise 3 - Differential Protection Open CT and OLTC Adjustment
1MRG004960
Exercise 3 - Open CT and OLTC adjustment
Copyright
This document and parts thereof must not be reproduced or copied without
written permission from ABB, and the contents thereof must not be imparted to
a third party, nor used for any unauthorized purpose.
Trademarks
ABB is a registered trademark of ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their
respective holders.
ABB AB
Substation Automation Products
SE-721 59 Västerås
Sweden
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
www.abb.com/substationautomation
This exercise is based on the configuration in figure 1, i.e., a three winding transformer protection.
Transformer Data:
80 / 80 / 30 MVA
145±9*1,67% / 22 / 11 kV
318 / 2099 / 1574 A
YNd5d11
140 kV Bus
RET670
140kV/110V Meter.
CV MMXU
300/1 84 ↑↓
TCM YLTC
11 kV Bus W1 87N IdN/I 87T 3Id/I
W3 W2 REF PDIF T3W PDIF
1500/1
Meter. Mont.
CV MMXU DRP RDRE
Function Function
configured not configured
Figure 1: A protection application for a three winding transformer in single breaker arrangement
Figure 1 shows all included functionality in the configuration. Function blocks in black are configured and the
rest indicate possible additions.
Prerequisite
Exercise 1 is finished and the IED is ready for testing (configuration, parameters, signal matrix
and eventually the graphical display is written into the IED).
Test set with 6 current outputs and milliAmpere source are available.
Open CT detection
Open CT detection
5. What happed.
It is possible to detect and avoid tripping due to an open current circuit (one phase out of three). This function is
only active after a certain time (1 min after energization) and during normal load (10-110% IBias).
6. Set OpenCTEnable On
The tap changer position is simulated by a milliampere signal so we need to include a SMMI-function block in
the configuration.
You have updated the Signal Matrix, since you did the connection between the SMAI-block and the MIM_6
We cannot connect the mA-signal direct to the differential function block. It must pass the Tap-changer control
and supervision function block. The function block gives tap commands to the tap changer, when used for
OLTC-control, and supervises that the commands are carried out correctly.
Here we are only using information from the tap changer (position and error messages). Thus YLTCIN is
GRP_OFF (connection to voltage control function block).
The measurement of the tap changer position via MIM module is based on the principle that the specified mA
input signal range (usually 4-20 mA) is divided into N intervals corresponding to the number of positions
available on the tap changer.
RatedTapOLTC1 defines the rated position. This tap position shall correspond to the values for rated current and
voltage set for that winding.
TapHighVoltTC1 defines the end position for OLTC1 where highest no-load voltage for that winding is
obtained.
Differential protection
IDL1MAG: .......... A
IDL2MAG: .......... A
IDL3MAG: .......... A
IDL1MAG: .......... A
IDL2MAG: .......... A
IDL3MAG: .......... A
I LV = 1.25∙2099 ~ 1.25∙Irated
IDL1MAG: .......... A
IDL2MAG: .......... A
IDL3MAG: .......... A
43. Use the GDE and add OLTC information on the screen to be written into the IED