Calculation Size of Neutral Earthing Transformer (NET) : Generator Details
Calculation Size of Neutral Earthing Transformer (NET) : Generator Details
Calculation Size of Neutral Earthing Transformer (NET) : Generator Details
Generator Details:
Generator Voltage (VL) (L-L) 11 KV
Maximum Over Voltage 14.3 KV
Frequency 50 Hz
Generator Transformer Details:
Transformer Primary Voltage 33 KV
Transformer Secondary Voltage 11 KV
Capacitance Per Phase:
Generator Winding Capacitance / Phase 0.22 µ Farad
Generator Connection Capacitance / Phase 0.001 µ Farad
Generator Transformer Capacitance / Phase 0.006 µ Farad
Generator Transformer Connection Capacitance / Phase 0 µ Farad
Transformer Cabale Capacitance / Phase 0.0003 µ Farad
Surge Arrestor Capacitance / Phase 0.25 µ Farad
Other Capacitance / Phase µ Farad
Total Zero Sequence Capacitance (C): 0.47730 µ Farad
Total Zero Sequence Capacitance Reactance to Ground (Xc): 6672.35 Ω/Phase
Neutral Earthing Transformer Size:
Primary Voltage of the Grounding Transformer (Vp) 11 KV
Secondary Voltage of the Grounding Transformer (Vs) 240 Volt
Turns Ratio of the Grounding Transformer (N) 45.83
Neutral Earthing Transformer % Reactance (X%) 4% 0.04
Neutral Earthing Transformer Reactance in PU (Xpu) 0.04 PU
Neutral Earthing Transformer Base KV (Bv) 0.24 KV
1
al Earthing Transformer (NET)