Download as pdf or txt
Download as pdf or txt
You are on page 1of 50

Ref. No.

: m83/om/403 masibus
Issue No.: 22

Operator’s Manual

S C A N N ER - 8 5 X X

Masibus Automation & Instrumentation Pvt. Ltd.


B/30, GIDC Electronics Estate,
Sector-25, Gandhinagar-382044, Gujarat, India.
Ph: 91-079-23287275--79
Fax: 91-079-23287281/82
Email: support@masibus.com
Web: www.masibus.com

Page 1 of 50
Operator’s manual
Date: 07/09/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

CONTENTS

1. TECHNICAL DETAILS.

2. SPECIFICATIONS.

3. KEY OPERATION.

4. CONNECTIONS DETAILS.

5. USER GUIDE.

6. MODE OF OPERATION.

7. RELAY TABLE.

8. AUXILLAY OPTIONS TABLE.

9. TROUBLE SHOOTING.

10. MODBUS DETAIL (OPTIONAL).

11. OPEN COLLECTOR PIN DETAILS.

Page 2 of 50 Operator Manual


Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

if group mode is selected as 1rELy, then


Relay action type ( ON or OFF ) for alarm
limit 1 is only programmable.
1. TECHNICAL DETAILS
Latching for LED Status of alarm limit 1 and
This is a versatile micro-controller based alarm limit 2 is programmable.
Scanner with a very high performance to
price ratio. The features offered in this Scan time is programmable up to 99 seconds.
product are better than any other Scanner Provision for zero and span setting is made to
available in similar price range. restrict range of usage and programming.
The instrument is made in 96x192x208 mm This restricts accidental wrong setting of set
size with standard cut out of 92x188 mm. point beyond the range of interest. Outside
Front is sealed membrane type to withstand this range the unit will indicate data as
dusty environment. On back plate PCB 'OVER' towards span side up to 5% more
soldered flat terminals of very good quality than programmed span and “UNDR” towards
are used. zero side up to 5% less then programmed
The programming, calibration and operation zero. This zero and span setting is more
of the instrument are by nine simple keys useful for linear inputs for setting the range
with two independent displays for channel between -1999 to 9999 counts.
no. and data value for that channel. Channel
display is of two digits to differentiate it from Digital input is mapped on 0-5V input and
data display of four digits, each of 0.56" printing output and display is as “ON “ if input
seven segments LED. Status of Run/ voltage is less than 2.5v DC and “OFF” if
Program/Verify mode, Fault, Auto/Manual input voltage is greater than 2.5v DC. The
mode and status of each channel for reverse feature can be obtained on using
programmed set point limits are displayed by UPSCALE/DOWN SCALE of open sensor.
3 mm red LED’s. Operation of the instrument There is no relay or any output action for
is menu driven with user understandable digital input.
prompts. Provision for PASS WORD is kept for
unauthorized access to critical configuration Number of optional features provided
and program parameters. including Relay output, Open collector output,
The product is made to accept all 7 standard Isolated Retransmission output, which can be
thermocouple, PT100 RTD, CU-53, PT46, easily set through front panel keys under
Linear voltage and current inputs and digital Auxiliary Slot1 and Slot2 configuration.
input. The type of input can be changed in
field also. The calibration of the unit is done • Full relay mapping possible. Any
without trim-pots. The unit can be calibrated channel can be assigned to any
in installed condition itself by front panel keys group.
at any given point i.e. user do not required to • For each group two relays are given
feed a fixed signal. RTD inputs are linear for for one alarm limit 1 and second
0.1 deg. as well as 1 deg. resolution. Also alarm limit 2 if relay group mode is
incorporating Self check feature for stand selected as 2rELy.
alone verification of hardware of the device of • For each group one relay is given for
input section. alarm limit 1 if relay group mode is
selected as 1rELy.
Set point type (LL, HL or HH), abnormal • Isolated Retransmission output (4-
status (Alarm or Trip) for alarm limit1 and 20mA) can be configured for either
alarm limit 2 as well as Minimum or Maximum of channels
selected in a group.
Relay action type (ON or OFF) for alarm limit • Serial Communication with RS 232 /
1 and alarm limit 2 are programmable if RS 485 is also provided for using the
group mode is selected as 2rELy. scanner as backend for Supervisory
Control or for P.C. connectivity.
Relay action type (ON or OFF) for alarm limit Standard protocol for communication
1 are programmable if group mode is used is “MODBUS-RTU”.
selected as 2rELy.

Page 3 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

• Also PC based configuration software 2. SPECIFICATIONS


is available for configuration of data
through PC.

2.1. DISPLAY  CMRR


 2 digit 0.56" Red seven segment LED’s  CMRR > 120 db @ 50Hz.
for channel no.
 4 digit 0.56" Red seven segment LED’s  NMRR
for data of current channel.  NMRR > 40 db @ 50Hz.
 Power ON and Mode Selection discrete
Red LED’s. 2.3. RANGE
 Individual discrete Red LED’s to  E -200 to 1000 Deg C
indicate channel status.  J -200 to 1200 Deg C
 K -200 to 1372 Deg C
2.2. INPUT  T -200 to 400 Deg C
 Universal Input.  B 400 to 1820 Deg C
 No. of inputs 8,16 or 24.  R 0 to 1768 Deg C
 Thermocouple type E, J, K, T, B, R, S  S 0 to 1768 Deg C
(ANSI Standard).  Cu-53 -210 to 210 Deg C
 RTD Pt 100, Pt-46, CU-53 3-wire.  PT46 -200 to 600 Deg. C
 4-20 mA* / 1-5 V DC / 0-20 mA* / 0-  PT100(RTD 1) -199 to 850 Deg. C
5 V DC (*250 ohm/0.1% external  PT100 (RTD 0) -199.9 to 200.0 Deg C
Resistor required).  4-20mA- Field scaleable-1999 to 9999
 Digital I/P wetted internally.  0-5 V - Field scaleable -1999 to 9999
 Digital input is mapped on 0-5V input
and display is as “ON “ if input voltage is 2.4. CALIBRATION
less than 2.5v DC and “OFF” if input  Ambient, Zero and span adjusted by
voltage is greater than 2.5v DC. The digital calibration through front panel
reverse feature can be obtained on using keys. No trim- pots.
UPSCALE/DOWN SCALE of open  Zero Span Calibration of output
sensor. There is no relay or any output through front panel keys.
action for digital input.  One shot Calibration of both input and
 Cold junction compensation automatic output.
for thermocouple types. Three wire
cancellation 2.5. CONTROLS
for RTD I/P automatic by software.  Vfy, Increase, Decrease, Auto/Man,
 Accuracy: +/- 0.1% of full span +/- 1 Next/Group Check, Skip/Self Check,
Count Al1/Al2, Scan Time/Print Time and
 Sampling Speed Enter/ ACK keys for operation,
250 msec per channel for T/C & Linear programming & calibration.
Input.
450 msec per channel for RTD Input. 2.6. Serial Communication
 Display Scan Rate  Isolated RS232/485 Serial
Settable 1 to 99 seconds. Communication Protocol Standard
MODBUS RTU HEX.

Page 4 of 50 Operator Manual


Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

2.7. OPTIONS FOR AUXILLARY OUTPUTS (Maximum Two Auxiliary


Outputs are possible under SLOT-1 and SLOT-2 Input):

Relay card Analog Output Card Open Collector


Card
2relay/1relay(per
group)

3 groups(1 to 3 ) with 2 Two Isolated Retransmission 24 Open Collector


set points/ groups Outputs
Slot 1
6 groups(1 to 6) with 1 (Gr. No.: 1 and 2)
set point

3 groups(4 to 6) with 2 Two Isolated Retransmission 24 Open Collector


set points groups Outputs
Slot 2
6 groups(7 to 12) with (Gr. No.: 3 and 4)
1 set point

2A@230V A.C. with Groups:- MAX or MIN 24V D.C. @ 100mA


N.O./C/N.C. externally wet
Outputs:- 4-20mA Contacts
Relay Mapping possible
Common with number of Accuracy:- 0.25% of Range
Descriptio channels
n Load:- 250 Ohms

NOTE: The possible combinations are explained in the operational manual in Topic no. 8.

Special note 1: 1) For T/C and Linear - 250 mSec.


If “OR” type Logic is selected or 2) For Rtd - 450 mSec.
Scanner Type is 8508 and
“INDIVIDUAL” logic is used, user can
configure SLOT-2 for any other 2.9. PHYSICAL
Output. (Refer to Operation manual
for detail description of “OR” type and  Case - M.S. powder coated with
“INDIVIDUAL” type Logic). If ABS molded bezel
“INDIVIDUAL” Logic is used and  Terminals - Screw type, can accept
Scanner Type 8516 or 8524 both Slots up to 2.5 sq. mm wire
require Open Collector Output by  Bezel size - 96 X 192 mm
default.  Depth behind panel - 208 mm /
250mm (with terminal plate)
2.8. GENERAL  Panel cutout - 92 X 188 mm
 power supply - selectable 85V to
265V AC 50 Hz and 125V to 280 VDC. 2.10. SPECIAL FEATURES:
22V to 30V DC, (optional),90V to
135V DC(optional).  Square Root Extraction.
 Ambient - 0 to 55 deg C.  85xx-WP
 Humidity - up to 95% RH (Non- • Case-Material:- 1.6 MM THK.
condensing) M.S SHEET METAL
 Power consumption - Less than 20 FABBRICATIED. Painted Shade
VA 631,IS:5.
 Scanning time -
Page 5 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

• Dimension-
320 (H) x 350 (W) x 420(D) 3.1.1.2. ENTER/ACK
 85xx-EXP This key is used to enter the value of the
• Case-Material:- Cast Al. LM- selected parameter. After setting the data to
6(A6-M).Paint-Epoxy, Light proper value, if ENTER key is pressed, the data
Grey Shade 631,IS:5. will be permanently stored in non-volatile
memory. On pressing of ENTER key, the
• Dimension- decimal point on last digit disappears to indicate
560 (H) x 275 (W) x 210(D) that data is entered. Now, the data change is
• Key – 9 push button keys for not allowed until ENTER key is pressed once
front access. again. On pressing of ENTER key once again,
 Relay Card with DC contact decimal point on last digit will glow and allow
change in the data.
Rating: 30/110/220VDC @
This key when pressed during RUN MODE will
2/0.3/0.12A be considered as an ACK key which is used to
acknowledge the relays and LED status as per
2.11. OTHER OPTIONS logic selected.
3.1.1.3. INC (▲)
1. Channel to channel online isolation up
This key will increment the selected
to 125V AC and 300V DC and off-line
parameter value by one count in program,
isolation up to 500VDC is available for
configuration or calibration mode. if you keep
Critical Applications.
pressed the key then value will be
incremented by 10 times faster up to the
2. Horizontal Scanner:
maximum value of that particular parameter.
 Bezel size - 192 X 96 mm
 Depth behind panel -208 mm / 3.1.1.4. DEC (▼)
250mm (with terminal plate)
 Panel cutout - 188 X 92 This key will decrement the selected
parameter value by one count in program or
configuration mode. If you keep pressed the
key then value will be decremented by 10
3. CONNECTION DETAILS: times faster up to the minimum value of that
particular parameter.
There are nine keys for operation of the
3.1.1.5. NEXT /GCHK
instrument. For understanding the operation
first let us see the operation of keys. This key is used to move into next parameter
3.1.1.1. VFY in a current mode. In MAN mode it is used to
select next channel for fixed channel display.
This key is used to select desired parameter Also during RUM Mode this key is used as
in configuration, program, verify Relay map check key. On pressing NEXT
configuration and verify program modes. On /GCHK key for at least 3 sec the Relay map
first press of this key, it will display display feature is enabled and display shows
set point type , group number and channels
Md mapped to it is shown by LEDs AL1 and AL2
glowing.
upgm Verify program
hh
mode
By pressing INC or DEC key you can select
the desired mode (VPGM, PRGM, VCFG, and Grp1
CNFG) of operation. Now if you again press Press VFY to exit from this mode or will come
the vfy key then the instrument will come in out after time out of at least 20 seconds.
Run mode. The corresponding mode LED will Check those Leds which are on at this prompt
glow on pressing this key. indicated that the channel is in this group.
Page 6 of 50 Operator Manual
Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

3.1.1.6. AUTO/MAN
3.1.1.8. SKIP / SCHK KEY
This key is used to set the unit in either auto This key is used to skip / un-skip the channel
mode or manual mode. This is a toggle key. in program mode. This is also a toggle key.
i.e. if it is pressed in auto mode, the unit is i.e. if key is pressed while channel is skipped,
switched into MAN mode and channel display it will un-skip the channel. On pressing this
will become fixed. MAN LED will glow in MAN key in program mode, skip / un-skip message
mode to indicate the same. will be displayed in Data window and channel
This key is also used for individual zero/span, no. will be displayed in Channel window. Self
individual input type, individual decimal point check feature can also be invoked by this key
position, Relay mapping, Retransmission during Run Mode.
mapping and Retransmission configuration
setting for each channel. 3.1.1.9. AL1 / AL2

3.1.1.7. SCN /PRN TIME This key is used to change from alarm limit 1
to alarm limit 2 and vice-versa. This is also a
This key is used to set the scan time for toggle key.
display of channels and its reading. It can be
incremented up to 99 using INC key or
decremented up to 1 using DEC key.
This key is also used to enter in calibration
mode from configuration mode.

Page 7 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

4. CONNECTION DETAILS:
Back plate Detail. (Standard back plate)

C C
C C
NO NO
NO RL NO RL
RL NC RELAY RL NC
NC OUTPUT NC
C C
C C
NO NO
RL NO RL
NO RL RL NC
NC
2 4 NC
NC 1 +Ve 3
C +Ve C
C +Ve +Ve C
NO -Ve -Ve NO
NO RL -Ve -Ve RL NO RL
RL NC RL RL NC
NC NC
RL
C RL C
C C
+ + CH
+ CH -
CH + CH -
SENSOR CONNECTION
- - 1. FOR RTD INPUT : 2. FOR T/C : 3. FOR DIGITAL

C
C
C
C - + C - + - C
+ + CH
+ CH -
CH INPUT + CH -
- SIGNAL - 4. FOR VOLT : 5. FOR CURRENT :
C C
C C - + - +
+ + CH
+ CH -
CH + CH -
- - 250Ohms,0.1%,Externally.

C C
C C
+ + CH
+ CH -
CH + CH -
- -
C C
C C
+ + CH
AMB.SENSOR

+ CH
-
CH
PIN 1 + CH
-
- -
C C
C C
+ + CH
+ CH -
CH SERIAL COMMUNICATION + CH -
- -
NC L/+ N/- E POWER CONNECTION
F U SE 1 2 3 4
2 3 4
MAINS
L/+ N/- E

Page 8 of 50 Operator Manual


Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

Back plate Detail of OPEN COLLECTOR (OPTIONAL)

DG OC36
OC13 OC48
OC1 OC35
OC14 OC47
OC2 OC34
OC15 OC3 OC33 OC46
OC16 OC45
OC4 OC32
OC17 OC44
OC5 OC31
OC18 OC6 OC30 OC43
OC19 OC7 OC29 OC42
OC20 OC41
OC8 OC28
OC21 OC40
OC9 OC27
OC22 OC10 OC26 OC39
OC23 OC38
OC11 OC25
OC24 OC37
OC12 DG
OPEN
COLLECTOR
OUTPUT
C C
C C
+ + CH
+ CH -
CH + CH -
SENSOR CONNECTION
- - 1. FOR RTD INPUT : 2. FOR T/C :

C
C
C
C - + C - +
+ + CH
+ CH -
CH INPUT + CH -
- SIGNAL - 3. FOR VOLT : 4. FOR CURRENT :
C C
C C - + - +
+ + CH
+ CH -
CH + CH -
- -
250Ohms,0.1%,Externally.

C C
C C
+ + CH
+ CH -
CH + CH -
- -
C C
C C
+ AMB.SENSOR
+ CH
+ CH
-
CH
PIN 1 + CH
-
- -
C C
C C
+ + CH
+ CH -
CH SERIAL COMMUNICATION + CH -
- -
NC L/+ N/- E POWER CONNECTION
F U SE 1 2 3 4
2 3 4
MAINS
L/+ N/- E

Page 9 of 50
Operator’s manual
Date: 13/7/2011
Date: 07/09/2011
Operator Manual
Back plate Connection Detail of Weather Proof and FLP Scanner

MODBUS SUPPLY
Rx O/P-1 Rx O/P-2 RS-485 MAINS
C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC
D+ D- + - + - RL-11 RL-9 RL-7 RL-5 RL-3 RL-1 L/+N/- E
RL-12 RL-10 RL-8 RL-6 RL-4 RL-2
RL-7 to 12

RL-1 to 6
TOP VIEW

CH-17 to 24
CH-9 to 16
CH-1 to 8
CH-2 CH-4 CH-6 CH-8 CH-10 CH-12 CH-14 CH-16 CH-18 CH-20 CH-22 CH-24
Ref. No.: m83/om/403

CH-1 CH-3 CH-5 CH-7 CH-9 CH-11 CH-13 CH-15 CH-17 CH-19 CH-21 CH-23
masibus
Issue No.: 22

(optional).
C + - C + - C + - C + - C + - C + - C + - C + - C + - C + - C + - C + -

Page 10 of 50
RTD
T/C
VOLTS + -
CURRENT + - 250 ohm 0.1%
MA
Ref. No.: m83/om/403 masibus
Issue No.: 22

 Back plate connection detail of Weather Proof & FLP


SCANNER (25 PIN D TYPE Female) Relay cable (25 pin D type connector)
(Female)

CHANNEL PIN NO CHANNE CHANNEL PIN NO CHANNEL


L 1 C-3
CH-1 16 Common CH-9 CH-17
2 NO-3
14 +/Hi 3 NC-3
15 -/Lo 4 C-4
CH-2 19 Common CH-10 CH-18 12 NO-6
17 +/Hi
13 NC-6
18 -/Lo
CH-3 20 Common CH-11 CH-19 14 C-1
22 +/Hi 15 NO-1
21 -/Lo 16 NC-1
CH-4 23 Common CH-12 CH-20 17 C-2
25 +/Hi 18 NO-2
24 -/Lo
19 NC-2
CH-5 3 Common CH-13 CH-21
1 +/Hi 20 NO-4
2 -/Lo 21 NC-4
CH-6 6 Common CH-14 CH-22 22 C-5
4 +/Hi
23 NO-5
5 -/Lo
CH-7 8 Common CH-15 CH-23 24 NC-5
10 +/Hi 25 C-6
9 -/Lo
CH-8 11 Common CH-16 CH-24
13 +/Hi
12 -/Lo

NC 7 Common

Page 11 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

5. USER GUIDE SCANNER


5.1. INTRODUCTION
MAN
This is a single chip micro-controller based
scanner designed for universal input type. RUN
Instrument is operated by nine user friendly POWER
keys. These keys are used for operation, CHANNEL VFY
programming and calibration.
There are four levels of protections in the PRG
instrument. The four levels decide access to
verify settings (operator level), access to set FLT
points & control parameters (supervisor DATA
level), configuration and calibration.
The manual covers all aspects of operation of AL1
the instrument. Please read instructions 1 2 3 4 5 6 7 8 9 10 11 12
carefully before altering any programming or AL2
configuration information.
AL1
Vertical Scanner: 13 14 15 16 17 18 19 20 21 22 23 24
 Bezel size - 96 X 192 mm AL2
 Depth behind panel - 208 mm /
250mm (with terminal plate)
 Panel cutout - 92 X 188 mm
ENT
ACK

AUTO
VFY NEXT
MAN

SKIP AL1 SCN


SCHK AL2 TIME

masibus 85XX

Page 12 of 50 Operator Manual


Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

Horizontal Scanner:
 Bezel size - 192 X 96 mm
 Depth behind panel -208 mm / 250mm (with terminal plate)
 Panel cutout - 188 X 92 mm

FLP Scanner:

Page 13 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

WEATHER PROOF Scanner:

5.2. OPERATION 6.5 Verify configuration mode


6.6 Verify Program mode
5.2.1. POWER SUPPLY 6.7 Calibration mode

Always be sure that you are connecting right Each are described in detail in individual
input supply voltage to right power terminal chapter
of the instrument. On application of proper
power, the instrument will display Scanner 6.1 RUN MODE
type for 2 seconds and then configuration
type for another two seconds. This mode is indicated by RUN LED glowing.
Now, if the input signal is connected, scanner In this mode, channel window will display
will display value of input in DATA window current channel number and DATA window
and channel no. in channel window on display will show its temperature. In AUTO mode, it
along with appropriate mode LED. will keep on displaying successive un-skipped
channels at the programmed scan rate. In
case of MAN mode, only one channel will be
displayed continuously. For manual mode
separate LED indication of mode is provided
on front.
In RUN mode, alarm status of channels is
indicated by discrete LEDs for both AL1 and
AL2 limits. If the LED is on, the channel has
6. MODES OF OPERATIONS crossed that limit. If the LED is flashing, the
alarm is not acknowledged. When ENTER/ACK
There are seven modes of operations.
key is pressed, the LED will become steady to
indicate acknowledged alarm. The relay of
6.1 Run mode
that channel will be turned OFF, on
6.2 Manual mode
acknowledging the alarm, if the alarm type is
6.3 Program mode
not configured for trip logic, where relay is
6.4 Configuration mode
not turned OFF until it actually comes within
Page 14 of 50 Operator Manual
Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

limit. The type of action and normal status of CHANNEL 1


relay is programmable and described in
Configuration mode. Also refer relay logic 01
table
There is a facility for latching of alarm status.
Even when the channel comes back to normal
500
mode, LED will be ON till acknowledged to First parameter is alarm limit 1 for channel 1.
indicate past alarms. The relay will be self The upper row LED (for AL1) for channel 1
clearing in this mode. will be flashing to indicate channel affected
For currently selected calibration channel by this limit. Also a decimal point on last digit
decimal point on unit’s digit of channel no. of data will glow.
will glow. In this mode self check feature Change the limit as per requirement by INC
through SKIP/SCHK key and Relay map and DEC key and press ENTER. The LEDs will
summary through NEXT/GCHK key are also stop flashing. For changing the entry once
accessible. again, press ENTER key. The decimal point on
last digit of data indicates, whether changing
6.2 MANUAL MODE of data is allowed or not. If decimal point is
off and LEDs are steady data changing is not
Manual mode is same as normal run mode allowed.
except for displaying only one channel Pressing NEXT key will bring display to
continuously. The channel number can be channel 02 limits.
changed by NEXT key. This mode is entered
by pressing AUTO/MAN key in RUN/AUTO CHANNEL 2
mode. Pressing this key once again brings
back to AUTO mode. In this mode self check 02
feature through SKIP/SCHK key and Relay
map summary through NEXT/GCHK key are
also accessible.
600
Alarm limit for 1 for channel 2.
The upper row LED (for AL1) for channel 2
6.3 PROGRAM MODE will be flashing to indicate channels affected
by this limit. Other operations are identical
This mode is used to display / change alarm to channel 1.
limits, scan time, print time and skip status of Pressing NEXT key will bring display to
channels. For entering in this mode, press channel 03 limits.
VFY key in RUN mode and VFY LED will glow
to indicate the mode selection and display will
CHANNEL 3
ask to select the mode. By pressing
increment and decrement key select PRGM 03
option and press ENTER key. By pressing the
ENTER key it will ask for Password. Select
your password by using “INC” and “DEC” 700
keys. If the Password is correct then it will go Alarm limit 1 for Channel 3.
in to Program mode and PRG LED will start The upper row LED (for AL1) for channel 3
glowing to indicate the current mode of will be flashing to indicate channel affected
operation. Then press NEXT key to enter in by this limit. Other operations are identical to
program mode. Pressing VFY key will take channel 1.
you out of this mode. Factory set password is Pressing NEXT key will bring display to
'00'. If the user has programmed password in channel 04 limits. Thus you can set AL1 limit
configuration mode, go to correct password for each individual channel.
using INC key and DEC keys and then press For programming AL2 limit for all channels,
ENT key. press AL1/AL2 key to change to AL2 limits.
Now, the lower row LEDs for AL2 will start
6.3.1 SET ALARM TRIP VALUE flashing for the particular channel. Other
operations are identical to AL1 programming.

Page 15 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

SCAN TIME Configuration mode is used to change basic


For programming Scan Time or Print Time, configuration of unit. The program is same
press SCN/PRN key in program mode. Display for all options and all options are configurable
will show: from front only by using various keys. No
hardware changes are necessary for changing
St input type. It can be changed by just using
front keys.
001 For entering Configuration mode, press VFY
Displays scan time for updating the channel
key in RUN mode and VFY LED will glow to
on display.
indicate the mode selection and display will
Maximum Scan Time is 99 Sec.
ask to select the mode. By pressing
Minimum Scan Time is 1 Sec.
increment and decrement key select CNFG
Change Scan Time by INC and DEC keys and
option and press ENTER key. Now it will ask
press ENTER when correct value is set.
for Password. After setting correct Password
with the help of INC and DEC keys press
6.3.2 SKIPPING / UNSKIPPING OF
ENTER. If the Password is correct then only
CHANNEL
you can enter in Configuration mode. PRG
For changing the skip status of channels,
LED starts glowing which indicates the mode
press SKIP key in program mode. The display
of operation. Then press NEXT key to go
will show channel skip status. If Ch-1 is
ahead in Configuration mode. Pressing VFY
skipped, display will be
key will take you out of this mode. By
1 entering in Configuration mode, the scanner
will display scanner type. The parameters in
sequence are described below. User can go to
S-ch next parameter in sequence by pressing
NEXT key.

If Ch-1 is un-skipped, display will be 6.4.1 SCANNER TYPE

1 No OR No
U-ch 8508 8516
Channel can be selected by pressing NEXT
key. OR
SKIP key works as a toggle key, i.e. if
channel is skipped, by pressing SKIP key
status will change to un-skip and vice-versa.
After changing the skip status, press ENTER
key to store the status.
No
Skipping of all channels is not allowed. At
least one channel has to be un-skipped for
8508
operation of unit. When user tries to skip the There are three options 8508 or 8516 or
last un-skipped channel, it will not allow. 8524 for this parameter. Pressing INC and
In program mode, user can select any DEC key you can make it 8508 or 8516 or
parameter by using NEXT, SKIP, AL1/AL2 and 8524.
SCAN TIME keys and can abort from this
mode by pressing VFY key. For Verify mode 6.4.2 CONFIGURATION TYPE
all the parameter sequences are same except
for password entry and decimal point in last FI OR MI
digit is 'off'.

6.4 CONFIGURATION MODE


CNfg CNfg
There are two options fix or mix type
configuration for this parameter. Pressing INC

Page 16 of 50 Operator Manual


Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

and DEC key you can make it as fix or mix


type. K-tc -
K - type thermocouple -200 to 1372
6.4.3 INPUT TYPE

For changing of input type, no internal T-tc -


hardware changes are required. If input type T - type thermocouple -200 to 400
is 4-20mA then you are required to connect
the 250ohm Resistors supplied between the
INHI and INLOW terminals of the terminal B-tc -
plate. This will be treated as common i/p type B - type thermocouple 400 to 1820
for all the channels.
When an input type is selected its
corresponding zero and span range is R-tc -
automatically adjusted as per its table. R - type thermocouple 0 to 1768
However if user wants to change zero and
span as required he can move to the zero or
span prompt and can change . S-tc -
With this facility if the same input is selected S - Type thermocouple 0 to 1768
(ie.ENTER key is pressed on the same input),
its zero and span range is kept as it is. For
setting the range as per the table one has to CU53 -
change the input first and then change back RTD CU-53, 1 deg. Resolution -210 to 210
to same input as required. Refer
corresponding range as per the inputs.

There is provision for setting input type for


Pt46 -
RTD PT-46, 1 deg. Resolution -200 to 600
each channel individually. By pressing
AUTO/MAN key here, you can enter individual
input type for all the channels provided that
configuration type is selected as “mix”.
Rtd -
Display will show as: RTD PT-100, 1 deg. Resolution -199 to 850

IP Rtd.1 -
E-tc RTD PT-100, 0.1 deg. Resolution -199.0 to
200.0
Discrete LED 1 of AL1 will start flashing .By
pressing INC/DEC keys; you can set the input 4-20 -
type for channel 1. By pressing NEXT key here
4-20 mA or 1-5 V input -1999 to 9999
you can go to next channel and similarly set the
input type of other channels. If you want to
come at channel 1 from any other channel then 0-5v -
use SCN TIME key. VFY key will bring you back 0-5 V input or 0-20 mA -1999 to 9999
to the configuration mode (i.e. one level up) at
common input type setting. From here you can
go to the next parameters setting. Each type
dIgt -
is displayed by prompt as follows. Digital input(0-5 v) on or off

E-tc -
6.4.4 SETPOINT TYPE
E - type thermocouple -200 to 1000

J-tc -
hh OR hL OR LL
J - type thermocouple -200 to 1200

Page 17 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

condition will be treated as normal condition


SPtY in trip type.
This is common for all groups if the relay
Where HH - high, very high group mode is configured as 2rELy.
AL1 – high AL2 - very high
NOTE: If the relay group mode is selected as
HL - high, Low 1rELy, then only AL1 limit will be available
AL1 - low AL2 – high which can be configured as alarm or trip.

LL - low, very low


AL1 - very low AL2 - low 6.4.6 ABNORMAL STATUS OF AL2

This setting is common for all groups if the


relay group mode is configured as 2rELy.
AL OR TR
If the relay group mode is selected as 1rELy, CAL2
then only two set points types will be This is for configuration of abnormal status
available. for AL2. Other description is same as AL1.
i.e. NOTE: This parameter will be available only if
relay group mode is selected as 2rELy.
hi OR Lo
6.4.7 LATCHING OF ALARM
SptY
Y no
OR
Where, hi - high
AL1 – high Ltch
Lo - low AL1 - low This is used to enable latching of discrete
LEDs when alarm limit is crossed. This option
For exact understanding of relay and will keep discrete LEDs latched even after the
LED operation please refers the ‘relay channel has come to normal status until ACK
logic table’ given at the end of manual. key is pressed.
This option can be changed to Yes or no for
enabling and disabling respectively. When
6.4.5 ABNORMAL STATUS OF AL1 CAL1 and CAL2 are of trip type, this
parameter will be skipped from display.

6.4.8 OPEN SENSOR UP/DOWN


AL OR TR
CAL1 UP
Configuration of abnormal status for AL1 OPEN
limit. It will toggle between ALRM and TRIP This is used to define the state of the alarms
by INC and DEC keys. In alarm type, discrete in open sensor condition. It can be configured
LEDs and relays are self-clearing. In trip as UP or DOWN by pressing INC and DEC
type, both are latched. They will go off only keys. If it is configured as UP then open
by pressing ACK key and returning to normal condition will be treated as alarm / abnormal
status. Even if the reading has come to condition. If it is configured as DOWN then
normal, relay will not be turned off until ACK open condition will be treated as normal
key is pressed. This is useful when the relay condition.
is used for tripping the plant or device and it
is not to be started once again until operator 6.4.9 HYSTERESIS
has set up for starting once again. Open
h
Page 18 of 50 Operator Manual
Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

6.4.11 SPAN
010
Hysteresis for relay operation on alarm limits.
S
This parameter is common for all groups.
Minimum value can be '0' and maximum 2000
value can be 100. Use INC or DEC keys for Span value or maximum value for selected
changing the value. Hysteresis is treated as input. Up to 5% above of the total zero and
per count basis depending on display value. span value OVER will be indicated on display.
For RTD Pt100; 0.1 deg. resolution, For out of range value, OPEN will be indicated
maximum setting will be 10.0 deg. on display. Maximum or minimum value is
decided by input type. For linear inputs, this
6.4.10 ZERO is the span setting for range programming.
Ey pressing AUTO/MAN key here, you can
Z enter individual zero/ span values for all the
channels. Display will show as:
-1999 01
Zero value or minimum value for selected
input. Upto 5% below of the total zero and
span value OVER will be indicated on display.
1000
For out of range value, OPEN will be indicated Discrete LED 1 of AL2 will start flashing. All
on display. Minimum value is decided by the functions described in the previous
input type. Maximum value will be span description of zero value setting are
value. For linear inputs, this is the zero applicable here.
setting for range programming. This will be
treated as common Zero value for all the 6.4.12 DECIMAL POINT POSITION
channels.
There is provision for setting zero/ span/ dp dP
position (dp position is zero for t/c’s, 1 for
RTD0.1) for each channel individually. By 000
pressing AUTO/MAN key here, you can enter Decimal point position is applicable only to 4-
individual zero value for all the channels. 20 mA or 0-5V i/p. It can be set 0 to 3 as
Display will show as: per requirement.
01 If i/p type is selected as linear (4 to
20mA, 0 to 5V) then only by pressing
100 AUTO/MAN key here, you can enter individual
dp position value for all the channels. If
Discrete LED 1 of AL1 will start flashing .By configuration type is selected as mix then you
pressing INC/DEC keys; you can set the zero can enter in individual DP position setting but
value for channel 1. If you press AUTO/MAN you can change DP position of channels only
key here then Discrete LED 1 of AL2 will start which has I/P type as 0-5V or 4 –20.
flashing. Now display will show span of Display will show as:
channel 1.By pressing INC/DEC keys, you can
set the span value for channel 1. AUTO/MAN
01
key here works as toggle key between AL1 &
AL2 (i.e. Zero and Span). By pressing NEXT 001
key here you can go to next channel and
similarly set the zero and span values of Discrete LED 1 of AL1 will start flashing .By
other channels. If you want to come at pressing INC/DEC keys; you can set the dp
channel 1 from any other channel then use position value for channel 1. By pressing
SCN TIME key. VFY key will bring you back to NEXT key here you can go to next channel
the configuration mode (i.e. one level up) at and similarly set the dp position values of
common zero value setting. From here you other channels. If you want to come at
can go to the next parameters setting. channel 1 from any other channel then use
SCN TIME key. VFY key will bring you back to
Page 19 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

the configuration mode (i.e. one level up) at This parameter is used to set the BAUD RATE
common DP value setting. From here you can for serial communication. Different baud rates
go to the next parameters setting. For the can be selected by using INC/DEC keys.
channels having input type’s t/c and rtd, dp Baud rate can be set from 9600 and 19.2KB.
position value is fixed (zero). .
If you are using the instrument with
individual scaling of zero/span and dp then 6.4.17 SLOT 1CONFIGURATION:
don’t press ENTER key at the main zero/span 6.4.18 SLOT 2CONFIGURATION:
and dp parameters in the configuration mode
after setting individual values. Main
zero/span and dp values are common values Scanner is equipped with two auxiliary slots
for all the channels. After setting individual whose function of operation can be defined and
values if you will press ENTER key at main configured through Slot 1 and Slot 2
zero/span/dp then this will make zero, span configurations parameters. Each slot is
and dp values same or common for all the programmed independently for required output
channels. and their configurations are configured per slot.
I.e. Slot wise configuration is carried out.
6.4.13 PASSWORD (Refer Auxiliary options table for detail
information)
0
These slots can be configured for number of
PASS outputs and there combinations are as defined
Password for entering to Program mode and in Auxiliary options chart. Five available options
Configuration mode. The value of password are:
can be programmed anywhere between '0' to
'99'. Factory set password is 00. Relay output ----

6.4.14 SERIAL OUTPUT CONFIGURATION: relC Relay Card

This parameter is used for configuration of Open Collector Output ----


Serial Modbus. Display will show:

S0 opeC Open collector card

Modb Retransmission Output ----

rtrC Retransmission card


6.4.15 SERIAL NUMBER

No Output. ----
1
NoNe No card placed in slot
SrNo
This parameter is required while using the 6.4.19 RELAY OUTPUT:
Serial Communication facility. It represents To set Slot 1 or Slot 2 configuration as Relay
the serial number or the ID number of the output, select Relay card on slot 1 prompt,
Unit. It can be configured between 1 and 99 display shows:
by using INC/DEC keys.
S1
6.4.16 BAUD RATE

bd RELC
Press ENTER on this prompt, on pressing next
9600 key a Relay Mapping Menu appears wherein

Page 20 of 50 Operator Manual


Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

channels can be mapped to groups. Relay All relay operations are based on grouping of
configuration menu appears on display as: channels.
On pressing VFY key menu will shift back to
GROUP RELAY: upper level and on pressing NEXT key Relay
configuration parameter appears:

GP RELAY STATUS OF AL1:

1rLy or 2rLy OF OR on
The relay settings can be configured as 1 relay CrL1
(1rELy) for settings of total of 12 groups. Or as
2 relay(2rELy) for settings of total 6 groups. Configures normal relay status as ON or OFF
for AL1 Relay. This is common for all groups.
1rELy – group1 - 6 for Slot1 and group7 –12 for If GP mode is selected as 1rELy, then only
slot2. CrL1 will be displayed.
If GP mode is selected as 2rELy, then both
2rELy – group1 -3 for Slot1 and group4 –6 for CrL1 and CrL2 will be displayed.
slot2.
RELAY STATUS OF AL2:
RELAY MAPPING:
Rl OF OR on
mapp CrL2
Configures normal relay status as ON or OFF
Press Auto/Man key to enter into mapping for AL2 Relay. This is common for all groups.
configuration. Individual channels are If it is configured as ON, relay will remain ON
displayed with there mapping onto groups. If when all channels of that group are in clear
both the slots are selected as Relay card and status. This is useful for specific applications
the group settings are selected as 2rELy in where Scanner ON is used for making a
GP mode, a total of 6 groups are available, 3 contact for failsafe operation, i.e. user wants
groups per card where as if only single slot is to sound buzzer or annunciator when Scanner
configured as Relay card, only 3 groups are is turned OFF or it is not working.
available. If both the slots are selected as
Relay card and the group settings are NOTE: This parameter will be displayed only
selected as 1rELy in GP mode, a total of 12 if 2rELy mode is selected.
groups are available, 6 groups per card where
as if only single slot is configured as Relay Pressing NEXT key displays the configuration
card, only 6 groups are available. Display for Slot 2:
appears as:
01 S2
Grp1 RELC
Discrete LED 1 of AL1 will start flashing .By The Same sequence is followed for Slot 2
pressing INC/DEC keys; you can set the Configuration as Relay card:
required group for channel 1. By pressing NEXT Note:
key here you can go to next channel and Refer the Back plate details for Relay output
similarly the group for any channel can be set. connections.
Also one can select No group prompt for For full fledge details of Relay operation refer
avoiding the channel in any group. the Relay Logic Table attached.

6.4.20 OPEN COLLECTOR CARD:


01 24 open collector outputs are available per card
NGrp and can be configured as:
Page 21 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

• 1 outputs per channel -- Common Retransmission group. (2 in case of one


output of AL1 and Al2 (OR – Type) Retransmission card and 4 in case of two
Retransmission card).
• 2 output per channel -- Individual
output Al1 and Al2 configuration When Output configuration is set as Maximum,
(IND- Type) channel whose output is maximum in that
group will be transmitted as 4-20mA
When the output is selected as OR Type, one equivalent. When Output configuration is set as
open collector output is available per channel Minimum, channel whose output is minimum in
and is activated when any of AL1 or AL2 alarm that group will be transmitted as 4-20mA
limit is crossed. equivalent. Channels those are OPEN or skipped
are not considered for Retransmission output.
When the output is selected as IND Type, two
open collector output is available per channel As for an Example: Analog o/p of 4 to 20mA.
corresponding to AL1 and AL2 limits. Analog O/P will follow as the below indication:

In order to configure Slot 1 as Open collector Set zero = 0. Set span = 500.
output , Select Open collector output on display mA Min/Max 3.2 3.2
prompt, Process open UNDER -25 (5%)
value
on display
S1
mA 4 20 20.8
oPEC Process 0 500 525(5%)
By pressing NEXT key a parameter for Open value
collector output type can be configured (“IND” on display
or “OR” type)
mA 20.8 Min/Max
Process value OVER OPEN
In orOR on display

oCty
Note: In order to select Retransmission output, enter
Open collector type options is common for Retransmission card at display prompt,
both Slot 1 and Slot 2 configuraiton .
An open collector output follows the Led
Indication as seen on Front panel.
S1
Refer back plate details for Open collector RtrC
output connections. On pressing NEXT key a menu for
Retransmission mapping is displayed wherein
6.4.21 RETRANSMISSION OUTPUT: any channel can be mapped to any
Retransmission group.
Two Isolated 4-20mA with 0.25% accuracy of
full scale & Loading up to 250Ω,
Retransmission output is available per card. rt
Slot1 or Slor2 can be configured for
Retransmission output. When both the slots
are configures as Retransmission card, a total
mapp
Press Auto/Man key to enter into mapping
of 4 Isolated Retransmission output is
configuration. Individual channels are
available with two auxiliary cards.
displayed with there mapping onto groups. If
Retransmission output can be configured as
both the slots are selected as Retransmission
either Minimum or Maximum of channels
output a total of 4 Retransmission groups are
mapped to Retransmission groups. Any
available, 2 groups per card where as if only
channel can be mapped to any
Page 22 of 50 Operator Manual
Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

4 - 20 mA input Square root Process By making this prompt yes user can use 4-
calculated Variable 20 Ma or 0-5V as square root input type.
inside These input types will be very much useful in
4.000 ( 0%) 0 0.0 flow measurement application. For example if
8.000 (25%) 0.25 50.0 input type is 4-20 mA with square root yes
12.000 (50%) 0.50 70.7 and zero and span scaling is 0 to 1000 with
16.000 (75%) 0.75 86.6 dp at position one, then at different input
20.000 (100%) 1.00 100.0 process variable will be as under.
single slot is configured as Retransmission
output, only 2 groups are available. Display This parameter can be displayed by prompt
appears as: shown below.

01 y
Rgp1 Sqrt
Discrete LED 1 of AL1 will start flashing .By
pressing INC/DEC keys; you can set the Above example is just for explanation
required group for channel 1. By pressing NEXT purpose only, user can set any value at zero
key here you can go to next channel and and span parameter.
similarly the group for any channel can be set.
Also one can select No group prompt for Basic equation to calculate process variable
avoiding the channel in any group. for 4-20mA square root input type is

Square root ( (input - 4mA )/16)*100


01 %.

NGrp
On pressing VFY key menu will shift back to
upper level and on pressing NEXT key
Retranmission group configuration parameter
appears:

rt
6.5 VERIFY CONFIGURATION
cnfg MODE
Press Auto/Man key to enter into output
configuration. In this Menu output group can be This mode is to verify all the configuration
configured as either Maximum or Minimum parameters like scanner type, input type, no.
output of channels of that group. of groups, no. of channels in each group,
decimal point, zero, span etc. User can view
the data but can’t change the data in this
g1 mode. For entering into verify configuration
mode, press VFY key in RUN mode and VFY
Max OR mIN LED will glow to indicate the mode selection
and display will ask to select the mode. By
Discrete LED 1 of AL1 will start flashing .By
pressing increment and decrement key select
pressing INC/DEC keys; you can set the
VCFG option and press ENTER key. Then
required output configuration for Group1. By
press NEXT key to enter in verify
pressing NEXT key here you can go to next
configuration mode. Pressing VFY key will
output group. Same Menu appears for Slot
take you out of this mode.
2Configuration.

6.4.22 SQUARE ROOT: 6.6 VERIFY PROGRAM MODE

This mode is to verify the alarm limits, scan


time and channel skip information. User can
Page 23 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

view the data but can not change it in this


mode. For entering into verify program If retransmission output is selected then, by
mode, press VFY key in RUN mode and VFY pressing ENT key output calibration is
LED will glow to indicate the mode selection selected. On pressing INC key Retransmission
and display will ask to select the mode. By output Calibration prompt appears:
pressing increment and decrement key select
VPGM option and press ENTER key. Then
press NEXT key to enter in verify program Op
mode. Pressing VFY key will take you out of
this mode. CLch
6.7 CALIBRATION MODE
If retransmission output is not selected then,
You can calibrate instrument after entering in their calibrations prompt will not appear.
configuration mode, press SCN TIME key to
enter into Calibration mode. Here there are 5 For input calibration, On pressing next key
groups of calibration. following prompt appears:

Group 1: E-t/c, Jt/c, Kt/c, Tt/c. I


Group2: Bt/c, Rt/c, St/c.
Group3: RTD0,
Group4: RTD1, PT46, CU53
ChNo
Group4: 0-5V, 4-20mA.
Select your channel for calibration by using
INC/DEC keys. After selecting calibration
Calibration can be done in any one channel
channel press enter to change calibration
only for each group. Calibration done in any
parameter. It is mandatory to press enter if
one channel will hold for all the channels that
you want to change calibration parameter of
has I/P type of that group only. For the first
particular channel.
group the calibration done is of I/P type
“Kt/c”. For the second group the calibration
6.7.1 AMBIENT CALIBRATION
type is “Rt/c”. For the third group the
calibration type is RTD0. For the fourth group CA
the calibration type is RTD1 and for the fifth
group the calibration type is 0-5V. i.e. if you
want to use any channel in Jt/c then first you 027
have to calibrate any channel as per any I/P
type of group: 1. This calibration will hold for It will display current reading of ambient
all the four types of first group. Similar is the temperature. Use INC or DEC key to bring it
case with all the groups. One shot calibration to correct value and press ENTER key to store
feature is implemented for both input as well ambient temperature. To come out of
as output. For one shot calibration calibrate calibration mode press VFY key.
zero and Span sequentially. There is no need 6.7.2 ZERO CALIBRATION
of calibration for digital input.
In calibration mode following values are CZ
displayed and programmed as follows.
When you press SCN TIME key display will be 054
as follows:
It will display current reading of calibration
Ip channel. Use INC or DEC key to bring it to
desired value and press ENTER key to store
CLch zero calibration. Display will shoe Wait
message during calibration. On both sides
This gives selection for Input or Output 10% of total span is allowed for adjustment.
calibration. Press INC or DEC key to select To come out of calibration mode press VFY
the calibration type. key.

Page 24 of 50 Operator Manual


Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

6.7.4 RETRANSMISSION ZERO


6.7.3 SPAN CALIBRATION CALIBRATION

CS CZ
1000 3.200
It will display current reading of calibration
channel. Use INC or DEC key to bring it to
It will display current reading of
desired value and press ENTER key to store
retransmission output. Use INC or DEC key to
span calibration. On both sides 10% of total
set the mA value exactly same as at Ampere-
span is allowed for adjustment. After pressing
meter reading connected at output. Now
ENTER at span, unit under goes one shot
Press ENTER key to calibrate O/P for 4 mA.
Calibration (in case of sequentially calibration
Display will show Wait message during
of zero and span) with a WAIT message on
calibration. On both sides 10% of total span
display. Calibration is completed then after.
is allowed for adjustment. To come out of
calibration mode press VFY key.
If output calibration is selected then,
6.7.5 RETRANMISSION SPAN
On pressing next key following prompt
CALIBRATION
appears:

I Cs
ChNo 2.
Select your channel for calibration by using
0.800
INC/DEC keys. After selecting calibration It will display current reading of calibration
channel press enter to change calibration channel. Use INC or DEC key to set the mA
parameter. It is mandatory to press enter if value exactly same as at Ampere-meter
you want to change calibration parameter of reading connected at output. Now Press
particular channel. ENTER key to calibrate O/P for 20 mA.
Display will show Wait message during
calibration. On both sides 10% of total span
is allowed for adjustment. To come out of
calibration mode press VFY key.

7 Relay logic table


For 2 relay settings:

ALARM AL1
MOMEMTARY ALARM (when in abnormal condition ack not pressed)

CONDITION NORMAL ABNORMAL UP (O/S) DOWN (O/S) ACK ** NORMAL * ACK ***
ALARM LATCH = LAMP OFF FLASH FLASH OFF FLASH OFF
YES RELAY OFF ON ON OFF OFF OFF
HIGH ALARM LATCH = LAMP OFF FLASH FLASH OFF OFF OFF
***** NO RELAY OFF ON ON OFF OFF OFF
TRIP LAMP OFF FLASH OFF OFF FLASH OFF
RELAY OFF ON OFF OFF ON OFF
ALARM LATCH = LAMP OFF FLASH OFF FLASH FLASH OFF
YES RELAY OFF ON OFF ON OFF OFF

Page 25 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

LOW ALARM LATCH = LAMP OFF FLASH OFF FLASH OFF OFF
***** NO RELAY OFF ON OFF ON OFF OFF
TRIP LAMP OFF FLASH OFF OFF FLASH OFF
RELAY OFF ON OFF OFF ON OFF
ALARM LATCH = LAMP OFF FLASH OFF FLASH FLASH OFF
YES RELAY OFF ON OFF ON OFF OFF
VLOW ALARM LATCH = LAMP OFF FLASH OFF FLASH OFF OFF
NO RELAY OFF ON OFF ON OFF OFF
TRIP LAMP OFF FLASH OFF OFF FLASH OFF
RELAY OFF ON OFF OFF ON OFF

ALARM AL2
MOMEMTARY ALARM (when in abnormal condition ack not pressed)

CONDITION NORMAL ABNORMAL UP (O/S) DOWN (O/S) ACK ** NORMAL * ACK ***
ALARM LATCH LAMP OFF FLASH FLASH OFF FLASH OFF
YES RELAY OFF ON ON OFF OFF OFF
VHIGH ALARM LATCH LAMP OFF FLASH FLASH OFF OFF OFF
NO RELAY OFF ON ON OFF OFF OFF
TRIP LAMP OFF FLASH OFF OFF FLASH OFF
RELAY OFF ON OFF OFF ON OFF
ALARM LATCH LAMP OFF FLASH FLASH OFF FLASH OFF
YES RELAY OFF ON ON OFF OFF OFF
HIGH ALARM LATCH LAMP OFF FLASH FLASH OFF OFF OFF
NO RELAY OFF ON ON OFF OFF OFF
TRIP LAMP OFF FLASH OFF OFF FLASH OFF
RELAY OFF ON OFF OFF ON OFF
ALARM LATCH LAMP OFF FLASH OFF FLASH FLASH OFF
YES RELAY OFF ON OFF ON OFF OFF
LOW ALARM LATCH LAMP OFF FLASH OFF FLASH OFF OFF
NO RELAY OFF ON OFF ON OFF OFF
TRIP LAMP OFF FLASH OFF OFF FLASH OFF
RELAY OFF ON OFF OFF ON OFF

ALARM AL1
MAINTAINED ALARM (when in abnormal condition ack is pressed)
DOWN
CONDITION NORMAL ABNORMAL UP (O/S) (O/S) ACK ** NORMAL * ACK ***
ALARM LATCH = LAMP OFF FLASH FLASH OFF STEADY STEADY OFF
YES RELAY OFF ON ON OFF ON OFF OFF
HIGH ALARM LATCH = LAMP OFF FLASH FLASH OFF STEADY OFF OFF
***** NO RELAY OFF ON ON OFF OFF OFF OFF
TRIP LAMP OFF FLASH OFF OFF STEADY STEADY OFF
RELAY OFF ON OFF OFF ON ON OFF
ALARM LATCH = LAMP OFF FLASH OFF FLASH STEADY STEADY OFF
YES RELAY OFF ON OFF ON ON OFF OFF
LOW ALARM LATCH = LAMP OFF FLASH OFF FLASH STEADY OFF OFF
***** NO RELAY OFF ON OFF ON OFF OFF OFF
Page 26 of 50 Operator Manual
Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

TRIP LAMP OFF FLASH OFF OFF STEADY STEADY OFF


RELAY OFF ON OFF OFF ON ON OFF
ALARM LATCH = LAMP OFF FLASH OFF FLASH STEADY STEADY OFF
YES RELAY OFF ON OFF ON ON OFF OFF
VLOW ALARM LATCH = LAMP OFF FLASH OFF FLASH STEADY OFF OFF
NO RELAY OFF ON OFF ON OFF OFF OFF
TRIP LAMP OFF FLASH OFF OFF STEADY STEADY OFF
RELAY OFF ON OFF OFF ON ON OFF
ALARM AL2
MAINTAINED ALARM (when in abnormal condition ack is pressed)
DOWN
CONDITION NORMAL ABNORMAL UP (O/S) (O/S) ACK ** NORMAL * ACK ***
ALARM LATCH LAMP OFF FLASH FLASH OFF STEADY STEADY OFF
YES RELAY OFF ON ON OFF ON OFF OFF
VHIGH ALARM LATCH LAMP OFF FLASH FLASH OFF STEADY OFF OFF
NO RELAY OFF ON ON OFF OFF OFF OFF
TRIP LAMP OFF FLASH OFF OFF STEADY STEADY OFF
RELAY OFF ON OFF OFF ON ON OFF
ALARM LATCH LAMP OFF FLASH FLASH OFF STEADY STEADY OFF
YES RELAY OFF ON ON OFF ON OFF OFF
HIGH ALARM LATCH LAMP OFF FLASH FLASH OFF STEADY OFF OFF
NO RELAY OFF ON ON OFF OFF OFF OFF
TRIP LAMP OFF FLASH OFF OFF STEADY STEADY OFF
RELAY OFF ON OFF OFF ON ON OFF
ALARM LATCH LAMP OFF FLASH OFF FLASH STEADY STEADY OFF
YES RELAY OFF ON OFF ON ON OFF OFF
LOW ALARM LATCH LAMP OFF FLASH OFF FLASH STEADY OFF OFF
NO RELAY OFF ON OFF ON OFF OFF OFF
TRIP LAMP OFF FLASH OFF OFF STEADY STEADY OFF
RELAY OFF ON OFF OFF ON ON OFF
Notes :
* means normal condition after abnormal has occurred
** means ack pressed in abnormal condition
*** means ack pressed in normal condition after abnormal has already occurred.
***** means this logic will also be apply for 1relay settings for HIGH & LOW respectively.

Page 27 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

8 Auxiliary options table

Auxiliary options available for scanner under Slot1 and Slot2 Configuration.

Page 28 of 50 Operator Manual


Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

Sr. Output Type SLOT: 1 SLOT: 2 Remarks


No
1 Relay output (3 Groups) Relay card (RELC) No card (NONE)

2 Relay output (6 Groups) Relay card (RELC) Relay card (RELC)

3 Retransmission output Retransmission card No card (NONE)


2 – channels (RTRC)

4 Retransmission output Retransmission card Retransmission card


4 – channels (RTRC) (RTRC)

5 Relay output (3 Groups) Relay card (RELC) / Retransmission card


Retransmission card (RTRC) /
& Retransmission (RTRC) Relay card (RELC)
output

( 2-channels)

6 Open collector output O/C card (OPEC) O/C card (OPEC) IND type
8516,8524 – IND type configuration

6 Open collector output O/C card (OPEC) No card (NONE) IND type
8508 – IND type configuration

6 Open collector output O/C card (OPEC) No card (NONE) OR type


8508,8516,8524 – OR configuration
type

9 No output No card (NONE) No card (NONE)

Note:
• For different combinations of output slot marked with “No card (NONE)” can be configured for other
outputs as required as explained in above table.

9 Trouble shooting • Check the O/P of sensor is as per


the chart supplied to you by sensor
manufacturer. Measure it with
 Scanner does not Switch ON. instrument with better then 0.1%
accuracy. Standard multi-meter
• Check the Mains Cord. with 3½ digit display may have
• I/P power may be not present. poor accuracy then scanner.
Check power supply voltage is it • For temperature measurements
proper as per order check position of the sensor and
• Check fuse, if blown off replace it check for the problem related to
• Check the Power ON Indication sensor first.
LED. • Calibrate the unit as explained in
the manual. Select the proper
 Calibration of the unit is doubted method according to your scanner
to have drifted. input type.

Page 29 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

 In linear type input the unit shows • If scanner is showing different reading
false reading or ‘OVER’ or in all channels for common I/P type
‘UNDER’. and same Process vale then please
• Check for the polarity of the I/p enter I/P type again.
connections. • Check for AC voltage pick up at
• Check that the 250Ω resistor is the signal at scanner side
connected across the I/P • All low-level input and output
terminals, if the I/P type is 4 – 20 such as T/C, Rtd, Linear I/P and
mA. 250Ω resistor is mandatory for control signal wires must be kept
linear I/P type 4 to 20mA. separate from supply and relay output
• Check the current I/P coming from cabling.
the field, it may be below 4 or over
20 mA.  Communication Problem between
• Check for the proper range the Unit and Host PC/Operator
programmed in that channel. Terminal
• Check the cabling.
 In thermocouple type input the • Check the serial No. and baud rate
reading indicated has got some settings at PC side and scanner
error. side.
• Check for the proper I/p type • Check the RS-485 to RS232
selected. converter for 485 communications.
• Ensure that the compensating • Check the serial port of the
cables used are of proper type and computer by shorting 2 and 3 no
connected in proper direction pin of PC comports with PROCOMM
Positive and negative. or any other available application.
• Check the calibration of the unit. • Check RS 232 –RS 485 connection
• Check that proper zero-span range at PC and scanner side.
is programmed or not. • For RS 485 sometimes terminating
resistor of 120Ω at scanner and
 Reading indicated by scanner is converter side. In most of the
unstable, wrong or open. cases this is not required for
scanner.
• Checks the process input and also
check its connection are as per the  Relay or open collector O/P Action
back-plate supplied. problem
• Ensure the perfect EARTHING to the
unit & also check that neutral should • Check power to the contactor operated
not be floating. by relay from scanner.
• Shielded cables should used for input. • If relay card or open collector card
Shield should be EARTHED near the burns out frequently check for the
unit only. rating of the relay driven by open
• Check any of the sensor is not getting collector card or rating of contactor
EARTHED or having weak insulation driven by relay card.
with respect to earth. If so, remove
that sensor and check the cabling.  General
• Check the lead resistance of all the
three arms of RTD’s. All the three • It is mandatory to reset the
leads should have same lead Instrument by switching off the Power
resistance. If no, change the cables. if the input type is changed.
• Check that Input cables are properly • In Configuration, Program, Verify
tighten with back-plate Configuration, Verify Program and
• Check that back-plate is not Calibration modes, 20 Sec time out is
loose. provided i.e. if no key is pressed for
• Take separate earth wires for separate 20 seconds; it will fall back into
instruments, avoid looping of earth Run/Man mode.
wires.
Page 30 of 50 Operator Manual
Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

• While programming value, if the INC • All supply connections to final control
or DEC key is kept pressed for more devices such as contactors, solenoids
than 10 counts, the etc. must be taken directly from the
Speed of change will be increased by 5 supply and not from the supply
times. It is the dual speed concept for terminals of the instrument.
changing value at faster rate. • An effective earth is mandatory for the
• On power on scanner will first display instrument. I n absence of proper
model (8508/8516/8524), then earthing instrument body will float at
configuration type for some time and half some part of the supply voltage
then it will come to actual Run mode and this may give shock to user.
display. • When power supply LED not glowing
• If there is any error in EEPROM data, change fuse as per table FUSE
it will display error message and halt. selection:-
• FUSE Selection:-
10 Supply Voltage FUSE

-Err 85V to 265V 1A


AC/125V to 280V
• The upper two digit display will show
DC
no. of parameters having errors and
lower 4 digit display will show -err
message. To see the parameter 22V to 30V DC 2A
having error, scan through parameters
• Both in Program mode & Configuration 90V to 135V DC 1A
mode. The decimal point of first digit
of channel no. display will glow, if the
parameter data in EEPROM is
disturbed. This is an electronics instrument it
• If you change any individual I/P type may have problem not listed above,
or common I/P type then please also in case of such fault while reporting
adjust your particular channel span to factory (Masibus area office or
value, Zero value and alarm-trip set- head office), mention exact nature of
points. fault with sequence of events.

 SUPPLY VOLTAGE

• Supply voltage should be given


through a good isolation transformer.
This being a microprocessor based
instrument, a massive voltage spike
can damage it. A good isolation
transformer shields the instrument
from such voltage spikes and surges.
10. Modbus detail

10.1. INTRODUCTION

The scanner 85XX can be connected in RS-485/RS232 communication data link either in multi drop
or repeat mode. Each scanner 85XX must have unique Serial Number. Two scanners may not have
the same address. Entire range of addresses (1 to 99) may be used.
Before starting any communication, choose a baud rate and protocol compatible to the host
computer. Only two-pass protocol is available on scanners and hence when using the scanners,
only two-pass protocol is assumed. This speeds up the total throughput.

Page 31 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

10.2. COMMUNICATION PROTOCOL


The communication protocol is a HEX protocol. The host computer issues the commands to the
scanners that in turn respond to each command. The entire protocol is based on the
command/answer pr
otocol.

10.2.1 How Characters are transmitted serially

When messages are transmitted on standard Modbus serial networks, each character or byte is
sent in this order (left to right):
Least Significant Bit (LSB) ... Most Significant Bit (MSB) With RTU character framing,
the bit sequence is:

i.e. 1 start bit, 2 Stop bit for none parity,


.

10.2.2 MESSAGE QUERY:

Page 32 of 50 Operator Manual


Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

10.2.3 RTU Framing

10.2.4 START DELAY and ADDRESS:

Always contains the start of message with 3.5 null char delay followed by the address of the
scanner to be addressed. The address is represented by a HEX character ranges from 00 to 99.

10.2.5 FUNCTION:

When a message is sent from a master to a slave device the function code field tells the slave
what kind of action to perform.
In scanner 85XX the functions implemented are

01– READ COIL STATUS (REFERENCE - 0x).


05. – FORCE SINGLE COIL (REFERENCE - 0x).
03. – READ HOLDING REGISTERS (REFERENCE- 4x).
06. – PRESET SINGLE REGISTER (REFERENCE - 4x).

Here Same Reference Functions are used for Reading and writing a parameter, so only one
Variable Tag is required for reading and writing a parameter.

10.2.6 DATA FIELD:

Read: The query message specifies the starting register and quantity of registers to be read.
Registers are addressed starting at zero- registers 1 ... 12 are addressed as 0 ... 11.
The quantity of channels must not exceed (total no of channels – starting channel address).
Write: The query message specifies the register address and the data to be written in that
register. Registers are addressed starting at zero- register 1 is addressed as 0.

10.2.7 CHECKSUM COMPUTATION:

Page 33 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

The error-checking field contains a 16-bit value implemented as two eight-bit bytes. The error
check value is the result of a Cyclical Redundancy Check (CRC) calculation performed on the
message contents.

10.2.8 CRC calculation:

The CRC field checks the contents of the entire message. It is applied regardless of any parity
check method used for the individual characters of the message.
The CRC value is calculated by the transmitting device, which appends the CRC to the message.
The receiving device recalculates a CRC during receipt of the message, and compares the
calculated value to the actual value it received in the CRC field. If the two values are not equal, an
error results.
The CRC is started by first pre loading a 16-bit register to all 1's. Then a process begins of
applying successive eight-bit bytes of the message to the current contents of the register. Only the
eight bits of data in each character are used for generating the CRC. Start and stop bits, and the
parity bit, do not apply to the CRC.
During generation of the CRC, each eight-bit character is exclusive ORed with the register
contents. Then the result is shifted in the direction of the least significant bit (LSB), with a zero
filled into the most significant bit (MSB) position. The LSB is extracted and examined. If the LSB
was a 1, the register is then exclusive ORed with a preset, fixed value. If the LSB was a 0, no
exclusive OR takes place.
This process is repeated until eight shifts have been performed. After the last (eighth) shift, the
next eight-bit byte is exclusive ORed with the register's current value, and the process repeats for
eight more shifts as described above. The final content of the register, after all the bytes of the
message have been applied, is the CRC value.
When the CRC is appended to the message, the low-order byte is appended first, followed by the
high-order byte.

10.2.9 MESSAGE RESPONSE:

Page 34 of 50 Operator Manual


Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

10.3 COMMUNICATION PROTOCOL IN SCANNER


10.3.1 Process Value read and Alarm – Trip Set-point value read write
Data read Query = [0 x Sr.No.], [0 x Fun Code], [0 x ADD. High], [0 x ADD. Low], [0 x Data.
High], [0 x Data. Low] [0 x CRC Low] [0 x CRC High]
Fun code = 0X03
Data word - Address word < 73.
Response = [Sr.No.], [0 x Fun Code], [Byte count], [Data High], [Data Low] …... [Data. High],
[Data. Low]
[0 x CRC Low] [0 x CRC High]

Data write Query = [0 x Sr.No.], [0 x Fun Code], [0 x ADD. High], [0 x ADD. Low], [0 x Data.
High], [0 x Data. Low] [0 x CRC Low] [0 x CRC High]
Fun code = 0X06
Data word - Address word < 73.
Response = [Sr.No.], [0 x Fun Code], [ADD High], [ADD Low], [Data. High], [Data. Low] [0 x CRC
Low] [0 x CRC High]

10.3.2. Process value Addresses


Sr.no Analog Parameters Absolute Type of Access Parameter Values
Address Type Applicable
1. CH1 40001 Read only Int NA
2. CH2 40002 Read only Int NA
3. CH3 40003 Read only Int NA
4. CH4 40004 Read only Int NA
5. CH5 40005 Read only Int NA
6. CH6 40006 Read only Int NA
7. CH7 40007 Read only Int NA
8. CH8 40008 Read only Int NA
9. CH9 40009 Read only Int NA
10. CH10 40010 Read only Int NA
11. CH11 40011 Read only Int NA
12. CH12 40012 Read only Int NA
13. CH13 40013 Read only Int NA
Page 35 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

14. CH14 40014 Read only Int NA


15. CH15 40015 Read only Int NA
16. CH16 40016 Read only Int NA
17. CH17 40017 Read only Int NA
18. CH18 40018 Read only Int NA
19. CH19 40019 Read only Int NA
20. CH20 40020 Read only Int NA
21. CH21 40021 Read only Int NA
22. CH22 40022 Read only Int NA
23. CH23 40023 Read only Int NA
24. CH24 40024 Read only Int NA
Note:
Display on scanner will show ‘over’ when process value is higher then 5 % of individual span, at
that time scanner will send process value fed to it to PC.
Same way when process value is lower then 5 % of individual zero scanner will show ‘under’ on its
display but it will send process value fed to it to PC.
If scanner process value is out of limit for particular I/P type then scanner will show ‘Open’ on
display but it will send ‘10000’ to PC
Skipped channel value will be zero, if scanner is restarted after channel is skip. If scanner is not
restarted it will give OLD process value.

10.3.3 Alarm value addresses (AL1)

Sr. No. Analog Absolute Type of Access Parameter Values Applicable


Parameters Address Type

25. ALM1_1 40025 Read/ Write Int Ind. zero to Ind. Span
26. ALM2_1 40026 Read/ Write Int Ind. zero to Ind. Span
27. ALM3_1 40027 Read/ Write Int Ind. zero to Ind. Span
28. ALM4_1 40028 Read/ Write Int Ind. zero to Ind. Span
29. ALM5_1 40029 Read/ Write Int Ind. zero to Ind. Span
30. ALM6_1 40030 Read/ Write Int Ind. zero to Ind. Span
31. ALM7_1 40031 Read/ Write Int Ind. zero to Ind. Span
32. ALM8_1 40032 Read/ Write Int Ind. zero to Ind. Span
33. ALM9_1 40033 Read/ Write Int Ind. zero to Ind. Span
34. ALM10_1 40034 Read/ Write Int Ind. zero to Ind. Span
35. ALM11_1 40035 Read/ Write Int Ind. zero to Ind. Span
36. ALM12_1 40036 Read/Write Int Ind. zero to Ind. Span
37. ALM13_1 40037 Read/ Write Int Ind. zero to Ind. Span
38. ALM14_1 40038 Read/ Write Int Ind. zero to Ind. Span
39. ALM15_1 40039 Read/ Write Int Ind. zero to Ind. Span
40. ALM16_1 40040 Read/ Write Int Ind. zero to Ind. Span
41. ALM17_1 40041 Read/ Write Int Ind. zero to Ind. Span
42. ALM18_1 40042 Read/ Write Int Ind. zero to Ind. Span
43. ALM19_1 40043 Read/ Write Int Ind. zero to Ind. Span
44. ALM20_1 40044 Read/ Write Int Ind. zero to Ind. Span
45. ALM21_1 40045 Read/ Write Int Ind. zero to Ind. Span
46. ALM22_1 40046 Read/ Write Int Ind. zero to Ind. Span
47. ALM23_1 40047 Read/ Write Int Ind. zero to Ind. Span
48. ALM24_1 40048 Read/ Write Int Ind. zero to Ind. Span
10.3.4 Trip Value Addresses (AL2)

Sr. No. Analog Absolute Type of Parameter Values Applicable


Parameters Address Access Type
49. TRIP1_1 40049 Read/ Write Int Ind. zero to Ind. Span
50. TRIP2_1 40050 Read/ Write Int Ind. zero to Ind. Span
51. TRIP3_1 40051 Read/ Write Int Ind. zero to Ind. Span
52. TRIP4_1 40052 Read/ Write Int Ind. zero to Ind. Span
53. TRIP5_1 40053 Read/ Write Int Ind. zero to Ind. Span
Page 36 of 50 Operator Manual
Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

54. TRIP6_1 40054 Read/ Write Int Ind. zero to Ind. Span
55. TRIP7_1 40055 Read/ Write Int Ind. zero to Ind. Span
56. TRIP8_1 40056 Read/ Write Int Ind. zero to Ind. Span
57. TRIP9_1 40057 Read/ Write Int Ind. zero to Ind. Span
58. TRIP10_1 40058 Read/ Write Int Ind. zero to Ind. Span
59. TRIP11_1 40059 Read/ Write Int Ind. zero to Ind. Span
60. TRIP12_1 40060 Read/ Write Int Ind. zero to Ind. Span
61. TRIP13_1 40061 Read/ Write Int Ind. zero to Ind. Span
62. TRIP14_1 40062 Read/ Write Int Ind. zero to Ind. Span
63. TRIP15_1 40063 Read/ Write Int Ind. zero to Ind. Span
64. TRIP16_1 40064 Read/ Write Int Ind. zero to Ind. Span
65. TRIP17_1 40065 Read/ Write Int Ind. zero to Ind. Span
66. TRIP18_1 40066 Read/ Write Int Ind. zero to Ind. Span
67. TRIP19_1 40067 Read/ Write Int Ind. zero to Ind. Span
68. TRIP20_1 40068 Read/ Write Int Ind. zero to Ind. Span
69. TRIP21_1 40069 Read/ Write Int Ind. zero to Ind. Span
70. TRIP22_1 40070 Read/ Write Int Ind. zero to Ind. Span
71. TRIP23_1 40071 Read/ Write Int Ind. zero to Ind. Span
72. TRIP24_1 40072 Read/ Write Int Ind. zero to Ind. Span

10.3.5 Individual Scale Zero Addresses


Sr. Analog Absolute Type of Parameter Values Applicable
No. Parameters Address Access Type
73. SCL_ZERO1_1 40073 Read/ Write Int Particular Ind. I/P type range
74. SCL_ZERO2_1 40074 Read/ Write Int Particular Ind. I/P type range
75. SCL_ZERO3_1 40075 Read/ Write Int Particular Ind. I/P type range
76. SCL_ZERO4_1 40076 Read/ Write Int Particular Ind. I/P type range
77. SCL_ZERO5_1 40077 Read/ Write Int Particular Ind. I/P type range
78. SCL_ZERO6_1 40078 Read/ Write Int Particular Ind. I/P type range
79. SCL_ZERO7_1 40079 Read/ Write Int Particular Ind. I/P type range
80. SCL_ZERO8_1 40080 Read/ Write Int Particular Ind. I/P type range
81. SCL_ZERO9_1 40081 Read/ Write Int Particular Ind. I/P type range
82. SCL_ZERO10_1 40082 Read/ Write Int Particular Ind. I/P type range
83. SCL_ZERO11_1 40083 Read/ Write Int Particular Ind. I/P type range
84. SCL_ZERO12_1 40084 Read/ Write Int Particular Ind. I/P type range
85. SCL_ZERO13_1 40085 Read/ Write Int Particular Ind. I/P type range
86. SCL_ZERO14_1 40086 Read/ Write Int Particular Ind. I/P type range
87. SCL_ZERO15_1 40087 Read/ Write Int Particular Ind. I/P type range
88. SCL_ZERO16_1 40088 Read/ Write Int Particular Ind. I/P type range
89. SCL_ZERO17_1 40089 Read/ Write Int Particular Ind. I/P type range
90. SCL_ZERO18_1 40090 Read/ Write Int Particular Ind. I/P type range
91. SCL_ZERO19_1 40091 Read/ Write Int Particular Ind. I/P type range
92. SCL_ZERO20_1 40092 Read/ Write Int Particular Ind. I/P type range
93. SCL_ZERO21_1 40093 Read/ Write Int Particular Ind. I/P type range
94. SCL_ZERO22_1 40094 Read/ Write Int Particular Ind. I/P type range
95. SCL_ZERO23_1 40095 Read/ Write Int Particular Ind. I/P type range
96. SCL_ZERO24_1 40096 Read/ Write Int Particular Ind. I/P type range

Page 37 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

10.3.6 Individual Scale span Addresses


Sr. Analog Absolute Type of Access Parameter Values Applicable
No. Parameters Address Type

97. SCL_SPAN1_1 40097 Read/Write Int Particular Ind. I/P type Range
98. SCL_SPAN2_1 40098 Read/Write Int Particular Ind. I/P type Range
99. SCL_SPAN3_1 40099 Read/Write Int Particular Ind. I/P type Range
100. SCL_SPAN4_1 40100 Read/Write Int Particular Ind. I/P type Range
101. SCL_SPAN5_1 40101 Read/Write Int Particular Ind. I/P type Range
102. SCL_SPAN6_1 40102 Read/Write Int Particular Ind. I/P type Range
103. SCL_SPAN7_1 40103 Read/Write Int Particular Ind. I/P type Range
104. SCL_SPAN8_1 40104 Read/Write Int Particular Ind. I/P type Range
105. SCL_SPAN9_1 40105 Read/Write Int Particular Ind. I/P type Range
106. SCL_SPAN10_1 40106 Read/Write Int Particular Ind. I/P type Range
107. SCL_SPAN11_1 40107 Read/Write Int Particular Ind. I/P type Range
108. SCL_SPAN12_1 40108 Read/Write Int Particular Ind. I/P type Range
109. SCL_SPAN13_1 40109 Read/Write Int Particular Ind. I/P type Range
110. SCL_SPAN14_1 40110 Read/Write Int Particular Ind. I/P type Range
111. SCL_SPAN15_1 40111 Read/Write Int Particular Ind. I/P type Range
112 SCL_SPAN16_1 40112 Read/Write Int Particular Ind. I/P type Range
113. SCL_SPAN17_1 40113 Read/Write Int Particular Ind. I/P type Range
114. SCL_SPAN18_1 40114 Read/Write Int Particular Ind. I/P type Range
115. SCL_SPAN19_1 40115 Read/Write Int Particular Ind. I/P type Range
116. SCL_SPAN20_1 40116 Read/Write Int Particular Ind. I/P type Range
117. SCL_SPAN21_1 40117 Read/Write Int Particular Ind. I/P type Range
118. SCL_SPAN22_1 40118 Read/Write Int Particular Ind. I/P type Range
119. SCL_SPAN23_1 40119 Read/Write Int Particular Ind. I/P type Range
120. SCL_SPAN24_1 40120 Read/Write Int Particular Ind. I/P type Range

10.3.7 Individual DECIMAL POINT Addresses

Sr. No. Analog Parameters Absolute Type of Parameter Values Applicable


Address Access Type

121. IND_DP_POS1_1 40121 Read/Write Int Refer Note A.


122. IND_DP_POS2_1 40122 Read/Write Int Refer Note A.
123. IND_DP_POS3_1 40123 Read/Write Int Refer Note A.
124. IND_DP_POS4_1 40124 Read/Write Int Refer Note A.
125. IND_DP_POS5_1 40125 Read /Write Int Refer Note A.
126. IND_DP_POS6_1 40126 Read/Write Int Refer Note A.
127. IND_DP_POS7_1 40127 Read/Write Int Refer Note A.
128. IND_DP_POS8_1 40128 Read/Write Int Refer Note A.
129. IND_DP_POS9_1 40129 Read/write Int Refer Note A.
130. IND_DP_POS10_1 40130 Read/Write Int Refer Note A.
131. IND_DP_POS11_1 40131 Read/Write Int Refer Note A.
132. IND_DP_POS12_1 40132 Read/Write Int Refer Note A.
133. IND_DP_POS13_1 40133 Read/Write Int Refer Note A.
134. IND_DP_POS14_1 40134 Read/Write Int Refer Note A.
135. IND_DP_POS15_1 40135 Read/Write Int Refer Note A.
136. IND_DP_POS16_1 40136 Read/Write Int Refer Note A.
137. IND_DP_POS17_1 40137 Read/Write Int Refer Note A.
138. IND_DP_POS18_1 40138 Read/Write Int Refer Note A.

Page 38 of 50 Operator Manual


Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

139. IND_DP_POS19_1 40139 Read/Write Int Refer Note A.


140. IND_DP_POS20_1 40140 Read/Write Int Refer Note A.
141. IND_DP_POS21_1 40141 Read/Write Int Refer Note A.
142. IND_DP_POS22_1 40142 Read/Write Int Refer Note A.
143. IND_DP_POS23_1 40143 Read/Write Int Refer Note A.
144. IND_DP_POS24_1 40144 Read/Write Int Refer Note A.

Note A : For 4 to 20 mA and 0to 5V DP pos value should be 0-1-2-3. For other I/P Type it
should be zero only.

10.3.8 Individual inp type Addresses

Sr. No. Analog Parameters Absolute Type of Access Parameter Values


Address Type Applicable
145. IND_INP_TYPE1_1 40145 Read/Write Int 0 to 11
146. IND_INP_TYPE2_1 40146 Read/Write Int 0 to 11
147. IND_INP_TYPE3_1 40147 Read/Write Int 0 to 11
148. IND_INP_TYPE4_1 40148 Read/Write Int 0 to 11
149. IND_INP_TYPE5_1 40149 Read/Write Int 0 to 11
150. IND_INP_TYPE6_1 40150 Read/Write Int 0 to 11
151. IND_INP_TYPE7_1 40151 Read/Write Int 0 to 11
152. IND_INP_TYPE8_1 40152 Read/Write Int 0 to 11
153. IND_INP_TYPE9_1 40153 Read/Write Int 0 to 11
154. IND_INP_TYPE10_1 40154 Read/Write Int 0 to 11
155. IND_INP_TYPE11_1 40155 Read/Write Int 0 to 11
156. IND_INP_TYPE12_1 40156 Read/Write Int 0 to 11
157. IND_INP_TYPE13_1 40157 Read/Write Int 0 to 11
158. IND_INP_TYPE14_1 40158 Read/Write Int 0 to 11
159. IND_INP_TYPE15_1 40159 Read/Write Int 0 to 11
160. IND_INP_TYPE16_1 40160 Read/Write Int 0 to 11
161. IND_INP_TYPE17_1 40161 Read/Write Int 0 to 11
162. IND_INP_TYPE18_1 40162 Read/Write Int 0 to 11
163. IND_INP_TYPE19_1 40163 Read/Write Int 0 to 11
164. IND_INP_TYPE20_1 40164 Read/Write Int 0 to 11
165. IND_INP_TYPE21_1 40165 Read/Write Int 0 to 11

166. IND_INP_TYPE22_1 40166 Read/Write Int 0 to 11


167. IND_INP_TYPE23_1 40167 Read/Write Int 0 to 11
168. IND_INP_TYPE24_1 40168 Read/Write Int 0 to 11
10.3.9 Relay Mapping Addresses
Sr. No. Analog Parameters Absolute Type of Parameter Values Applicable
Address Access Type
169. RELAY_CH_MAP_1 40169 Read/Write Int 0-6
170. RELAY_CH_MAP_2 40170 Read/Write Int 0-6
171. RELAY_CH_MAP_3 40171 Read/Write Int 0-6
172. RELAY_CH_MAP_4 40172 Read/Write Int 0-6
173. RELAY_CH_MAP_5 40173 Read /Write Int 0-6
174. RELAY_CH_MAP_6 40174 Read/Write Int 0-6
175. RELAY_CH_MAP_7 40175 Read/Write Int 0-6
176. RELAY_CH_MAP_8 40176 Read/Write Int 0-6
177. RELAY_CH_MAP_9 40177 Read/write Int 0-6
178. RELAY_CH_MAP_10 40178 Read/Write Int 0-6
179. RELAY_CH_MAP_11 40179 Read/Write Int 0-6
180. RELAY_CH_MAP_12 40180 Read/Write Int 0-6
181. RELAY_CH_MAP_13 40181 Read/Write Int 0-6
182. RELAY_CH_MAP_14 40182 Read/Write Int 0-6.
183. RELAY_CH_MAP_15 40183 Read/Write Int 0-6.
184. RELAY_CH_MAP_16 40184 Read/Write Int 0-6
185. RELAY_CH_MAP_17 40185 Read/Write Int 0-6.
186. RELAY_CH_MAP_18 40186 Read/Write Int 0-6
187. RELAY_CH_MAP_19 40187 Read/Write Int 0-6.
188. RELAY_CH_MAP_20 40188 Read/Write Int 0-6.
189. RELAY_CH_MAP_21 40189 Read/Write Int 0-6.
Page 39 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

190. RELAY_CH_MAP_22 40190 Read/Write Int 0-6


191. RELAY_CH_MAP_23 40191 Read/Write Int 0-6.
192. RELAY_CH_MAP_24 40192 Read/Write Int 0-6
Note: Applicable values are related to Slot configuration.
For 1 relay Settings
If only one slot is Relay card, a total of 3 groups are available (0-3) where as if both the slots are configured
as Relay card, a total of 6 groups are available (0-6).
For 2 relay Settings
If only one slot is Relay card, a total of 6 groups are available (0-5) where as if both the slots are configured
as Relay card, a total of 12 groups are available (0-12).

10.3.10 Retransmission mapping Addresses


Sr. No. Analog Parameters Absolute Type of Parameter Values
Address Access Type Applicable
193 RETRANS_CH_MAP_1 40193 Read/Write Int 0-4
194. RETRANS _CH_MAP_2 40194 Read/Write Int 0-4
195. RETRANS _CH_MAP_3 40195 Read/Write Int 0-4
196. RETRANS _CH_MAP_4 40196 Read/Write Int 0-4
197. RETRANS _CH_MAP_5 40197 Read /Write Int 0-4
198. RETRANS _CH_MAP_6 40198 Read/Write Int 0-4
199. RETRANS _CH_MAP_7 40199 Read/Write Int 0-4
200. RETRANS _CH_MAP_8 40200 Read/Write Int 0-4
201. RETRANS _CH_MAP_9 40201 Read/write Int 0-4
202. RETRANS _CH_MAP_10 40202 Read/Write Int 0-4
203. RETRANS _CH_MAP_11 40203 Read/Write Int 0-4
204. RETRANS _CH_MAP_12 40204 Read/Write Int 0-4
205. RETRANS _CH_MAP_13 40205 Read/Write Int 0-4
206. RETRANS _CH_MAP_14 40206 Read/Write Int 0-4
207. RETRANS _CH_MAP_15 40207 Read/Write Int 0-4
208. RETRANS _CH_MAP_16 40208 Read/Write Int 0-4
209. RETRANS _CH_MAP_17 40209 Read/Write Int 0-4
210. RETRANS _CH_MAP_18 40210 Read/Write Int 0-4
211. RETRANS _CH_MAP_19 40211 Read/Write Int 0-4
212. RETRANS _CH_MAP_20 40212 Read/Write Int 0-4
213. RETRANS _CH_MAP_21 40213 Read/Write Int 0-4.
214. RETRANS _CH_MAP_22 40214 Read/Write Int 0-4
215. RETRANS _CH_MAP_23 40215 Read/Write Int 0-4
216. RETRANS _CH_MAP_24 40216 Read/Write Int 0-4
Note: When both the slots are configured as Retransmission card, a total of 4 groups (0-4)output
is available, if only one slot is configured as Retransmission card only 2 groups (0-2)output is
available.
10.3.11 etransmission configuration Addresses

Sr. No. Analog Parameters Absolute Type of Parameter Values


Address Access Type Applicable
217 RETRANS_CONFG_1 40217 Read/Write Int 0-1.
218. RETRANS_CONFG_2 40218 Read/Write Int 0-1
219. RETRANS_CONFG_3 40219 Read/Write Int 0-1
220. RETRANS_CONFG_4 40220 Read/Write Int 0-1
Note: Retransmission configuration can be set as either Minimum or Maximum.

10.3.2 Skip – Unskip write and Alarm – Trip status Data read

Data read Query = [0 x Sr.No.], [0 x Fun Code], [0 x ADD. High], [0 x ADD. Low], [0 x Data.
High], [0 x Data. Low] [0 x CRC Low] [0 x CRC High]
Fun code = 0X01
Data word - Address word < 89
Response = [Sr.No.], [0 x Fun Code], [Byte count], [Data High], [Data Low]. [Data. High],
[Data. Low] [0 x CRC Low] [0 x CRC High]

Page 40 of 50 Operator Manual


Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

Data read Query = [0 x Sr.No.], [0 x 01], [0 x 00], [0 x 00] , [0 x 00], [0 x 48(h)] [0 x CRC
Low] [0 x CRC High]
Fun code = 0X01
Data word - Address word < 89.
Response = [Sr.No.], [0 x 01], [9], [255], [255], [255], [254] [255], [255] [254] [255], [255]
[0 x CRC Low] [0 x CRC High]

This is response of above query where


First 3 words represent status of skip-unskip of 24 channels. (Skip - 0, unskip - 1)
Second 3 words represent status of AL1 (Alarm) of 24 channels. (LED on –1, LED off –0)
Last 3 words represents status of AL2 (Trip) of 24 channels (LED on –1, LED off –0).

Data write Query = [0 x Sr.No.], [0 x Fun Code], [0 x ADD. High], [0 x ADD. Low], [0 x Data.
High], [0 x Data. Low] [0 x CRC Low] [0 x CRC High]
Fun code = 0X05
Data word - Address word < 25. Or = 73.
To Skip channel Data high = 0X00.
To Un- Skip channel Data high = 0XFF.
Response = [Sr.No.], [0 x Fun Code], [ADD High], [ADD Low], [Data. High], [Data. Low] [0 x
CRC Low] [0 x CRC High]

For Example
Query to skip channel 5
[0 x Sr.No.] , [0 x Fun Code], [0 x 00], [0 x 04] , [0 x 00], [0 x Data. Low] [0 x CRC Low] [0 x
CRC High]
Response after data write
[0 x Sr.No.] , [0 x Fun Code], [0 x 00], [0 x 04], [0 x 00], [0 x Data. Low] [0 x CRC Low] [0 x
CRC High]
Query to Un-skip channel 12
[0 x Sr.No.] , [0 x Fun Code], [0 x 00], [0 x 0B] , [0 x FF], [0 x Data. Low] [0 x CRC Low] [0 x
CRC High]
Response after data write
[0 x Sr.No.] , [0 x Fun Code], [0 x 00], [0 x 0B], [0 x FF], [0 x Data. Low] [0 x CRC Low] [0 x
CRC High]
Query to ACK
[0 x Sr.No.] , [0 x Fun Code], [0 x 00], [0 x 48], [0 x 00], [0 x Data. Low] [0 x CRC Low] [0 x
CRC High]
Response after data write
[0 x Sr.No.] , [0 x Fun Code], [0 x 00], [0 x 48], [0 x 00], [0 x Data. Low] [0 x CRC Low] [0 x
CRC High]
Query to ACK
[0 x Sr.No.] , [0 x Fun Code], [0 x 00], [0 x 48], [0 x 00], [0 x Data. Low] [0 x CRC Low] [0 x
CRC High]
Response after data write
[0 x Sr.No.] , [0 x Fun Code], [0 x 00], [0 x 48], [0 x 00], [0 x Data. Low] [0 x CRC Low] [0 x
CRC High]

NOTE: The total number of data to read in a single query should be of 16 or multiple of 16.

The starting address and total number of data to read the status of SKIP/UNSKIP and ALARM/TRIP
should start from either of following values.

Page 41 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

Starting Address in read Total data to read Details


query

0 88

0 15 Skip/Unskip status of channel 1 to 16

0 31 Skip/Unskip status of channel 1 to 24


and Alarm status of channel 1 to 16

0 47 Skip/Unskip status of channel 1 to 24


and Alarm status of channel 1 to 24

0 63 Skip/Unskip status of channel 1 to 24


and Alarm status of channel 1 to 16
and Trip status of channel 1 to 16

0 80 Skip/Unskip status of channel 1 to 24


and Alarm status of channel 1 to 24
and Trip status of channel 1 to 24 and
relay status of group 1 to 3(2 relay) or
1 to 6 (1 relay)

0 87 Skip/Unskip status of channel 1 to 24


and Alarm status of channel 1 to 24
and Trip status of channel 1 to 24 and
relay status of group 1 to 6(2 relay) or
1 to 12 (1 relay)

For address starting from 17,


Possible values of total number of data to read is 16, 32, 48, 64

For address starting from 33,


Possible values of total number of data to read is 16, 32, 48

For address starting from 49,


Possible values of total number of data to read is 16, 32

For address starting from 65,


Possible values of total number of data to read is 16

For address starting from 81,


Possible values of total number of data to read is 8

Page 42 of 50 Operator Manual


Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

10.3.2.1. Skip/Unskip channel address (0 = SKIP, 1 = UNSKIP)

Sr. No. Digital Parameters Absolute Type of Access Parameter Values


Address Type Applicable
1. SKIP1_1 00001 Read/Write Int 0-1
2. SKIP2_1 00002 Read/Write Int 0-1
3. SKIP3_1 00003 Read/Write Int 0-1
4. SKIP4_1 00004 Read/Write Int 0-1
5. SKIP5_1 00005 Read/Write Int 0-1
6. SKIP6_1 00006 Read/Write Int 0-1
7. SKIP7_1 00007 Read/Write Int 0-1
8. SKIP8_1 00008 Read/Write Int 0-1
9. SKIP9_1 00009 Read/Write Int 0-1
10. SKIP10_1 00010 Read/Write Int 0-1
11. SKIP11_1 00011 Read/Write Int 0-1
12. SKIP12_1 00012 Read/Write Int 0-1
13. SKIP13_1 00013 Read/Write Int 0-1
14. SKIP14_1 00014 Read/Write Int 0-1
15. SKIP15_1 00015 Read/Write Int 0-1
16. SKIP16_1 00016 Read/Write Int 0-1
17. SKIP17_1 00017 Read/Write Int 0-1
18. SKIP18_1 00018 Read/Write Int 0-1
19. SKIP19_1 00019 Read/Write Int 0-1
20. SKIP20_1 00020 Read/Write Int 0-1
21. SKIP21_1 00021 Read/Write Int 0-1
22. SKIP22_1 00022 Read/Write Int 0-1
23. SKIP23_1 00023 Read/Write Int 0-1
24. SKIP24_1 00024 Read/Write Int 0-1

10.3.2.2. Alarm (AL1) Status of individual channel (0 = LED OFF, 1 = LED ON)

Sr. No. Digital Parameters Absolute Type of Access Parameter Type Values
Address Applicable
25. DALM1_1 00025 Read only Int 0-1
26. DALM2_1 00026 Read only Int 0-1
27. DALM3_1 00027 Read only Int 0-1
28. DALM4_1 00028 Read only Int 0-1
29. DALM5_1 00029 Read only Int 0-1
30. DALM6_1 00030 Read only Int 0-1
31. DALM7_1 00031 Read only Int 0-1
32. DALM8_1 00032 Read only Int 0-1
33. DALM9_1 00033 Read only Int 0-1
34. DALM10_1 00034 Read only Int 0-1
35. DALM11_1 00035 Read only Int 0-1
36. DALM12_1 00036 Read only Int 0-1
37. DALM13_1 00037 Read only Int 0-1
38. DALM14_1 00038 Read only Int 0-1
39. DALM15_1 00039 Read only Int 0-1
40. DALM16_1 00040 Read only Int 0-1
41. DALM17_1 00041 Read only Int 0-1
42. DALM18_1 00042 Read only Int 0-1
43. DALM19_1 00043 Read only Int 0-1
44. DALM20_1 00044 Read only Int 0-1
45. DALM21_1 00045 Read only Int 0-1
46. DALM22_1 00046 Read only Int 0-1
47. DALM23_1 00047 Read only Int 0-1
48. DALM24_1 00048 Read only Int 0-1

10.3.2.3. Trip (AL2) Status of individual channel (0 = LED OFF, 1 = LED ON)
Sr. No. Digital Parameters Absolute Type of Access Parameter Type Values
Address Applicable
49. DTRIP1_1 00049 Read only Int 0-1
50. DTRIP2_1 00050 Read only Int 0-1
51. DTRIP3_1 00051 Read only Int 0-1

Page 43 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

52. DTRIP4_1 00052 Read only Int 0 - 1


53. DTRIP5_1 00053 Read only Int 0 - 1
54. DTRIP6_1 00054 Read only Int 0 - 1
55. DTRIP7_1 00055 Read only Int 0 - 1
56. DTRIP8_1 00056 Read only Int 0 - 1
57. DTRIP9_1 00057 Read only Int 0 - 1
58. DTRIP10_1 00058 Read only Int 0 - 1
59. DTRIP11_1 00059 Read only Int 0 - 1
60. DTRIP12_1 00060 Read only Int 0 - 1
61. DTRIP13_1 00061 Read only Int 0 - 1
62. DTRIP14_1 00062 Read only Int 0 - 1
63. DTRIP15_1 00063 Read only Int 0 - 1
64. DTRIP16_1 00064 Read only Int 0 - 1
65. DTRIP17_1 00065 Read only Int 0 - 1
66. DTRIP18_1 00066 Read only Int 0 - 1
67. DTRIP19_1 00067 Read only Int 0 - 1
68. DTRIP20_1 00068 Read only Int 0 - 1
69. DTRIP21_1 00069 Read only Int 0 - 1
70. DTRIP22_1 00070 Read only Int 0 - 1
71. DTRIP23_1 00071 Read only Int 0 - 1
72. DTRIP24_1 00072 Read only Int 0 - 1
73. ACK 00073 Write only Int 0 - 1

10.3.2.4. Relay Status of individual channel (1 Relay settings) (0 = OFF , 1 = ON)


Sr. No. Digital Parameters Absolute Type of Access Parameter Type Values
Address Applicable
75. ALARM RELAY 00075 Read only Int 0-1
GROUP1
76. TRIP RELAY 00076 Read only Int 0-1
GROUP1
77. ALARM RELAY GROUP2 00077 Read only Int 0 - 1
78. TRIP RELAY GROUP2 00078 Read only Int 0 - 1
79. ALARM RELAY GROUP3 00079 Read only Int 0 - 1
80. TRIP RELAY GROUP3 00080 Read only Int 0 - 1
81. ALAR MRELAY 00081 Read only Int 0 - 1
GROUP4
82. TRIP RELAY 00082 Read only Int 0-1
GROUP4
83. ALARM RELAY GROUP5 00083 Read only Int 0 - 1
84. TRIP RELAY GROUP5 00084 Read only Int 0 - 1
85. ALARM RELAY GROUP6 00085 Read only Int 0 - 1
86. TRIP RELAY GROUP6 00086 Read only Int 0 - 1
87. ------ 00087 Read only Int 0
88 ------ 00088 Read only Int 0

10.3.2.5. Relay Status of individual channel (2Relay settings) (0 = OFF , 1 = ON)


Sr. No. Digital Parameters Absolute Type of Access Parameter Type Values
Address Applicable
75. ALARM ELAY 00075 Read only Int 0-1
GROUP1
76. ALARM RELAY 00076 Read only Int 0-1
GROUP2
77. ALARM RELAY GROUP3 00077 Read only Int 0 - 1
78. ALARM RELAY GROUP4 00078 Read only Int 0 - 1
79. ALARM RELAY GROUP5 00079 Read only Int 0 - 1
80. ALARM RELAY GROUP6 00080 Read only Int 0 - 1
81. ALAR MRELAY 00081 Read only Int 0 - 1
GROUP7
82. ALARM RELAY 00082 Read only Int 0-1
GROUP8
83. ALARM RELAY GROUP9 00083 Read only Int 0-1
84. ALARM RELAY 00084 Read only Int 0-1
GROUP10
85. ALARM RELAY GROU11 00085 Read only Int 0-1
86. ALARM RELAY 00086 Read only Int 0-1
GROUP12
87. ------ 00087 Read only Int 0
Page 44 of 50 Operator Manual
Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

88 ------ 00088 Read only Int 0


10.3.2.6. Digital I/P Status of individual channel (24 channel) (0 = OFF, 1 = ON)

Data read Query = [0 x Sr.No.], [0 x Fun Code], [0 x ADD. High], [0 x ADD. Low], [0 x Data.
High], [0 x Data. Low] [0 x CRC Low] [0 x CRC High]

Fun code = 0X02


Data word - Address word < 25

Response = [Sr.No.], [0 x Fun Code], [Byte count], [Data High], [Data Low]. [Data. High],
[Data. Low] [0 x CRC Low] [0 x CRC High]

Sr. No. Digital Parameters Absolute Type of Access Parameter Type Values
Address Applicable
1. Digital I/P on channel 1 10001 Read only Int 0-1
2. Digital I/P on channel 2 10002 Read only Int 0-1
3. Digital I/P on channel 3 10003 Read only Int 0-1
4. Digital I/P on channel 4 10004 Read only Int 0-1
5. Digital I/P on channel 5 10005 Read only Int 0-1
6. Digital I/P on channel 6 10006 Read only Int 0-1
7. Digital I/P on channel 7 10007 Read only Int 0-1
8. Digital I/P on channel 8 10008 Read only Int 0-1
9. Digital I/P on channel 9 10009 Read only Int 0-1
10. Digital I/P on channel 10 10010 Read only Int 0-1
11. Digital I/P on channel 11 10011 Read only Int 0-1
12 Digital I/P on channel 12 10012 Read only Int 0-1
13 Digital I/P on channel 13 10013 Read only Int 0-1
14 Digital I/P on channel 14 10014 Read only Int 0-1
15 Digital I/P on channel 15 10015 Read only Int 0-1
16 Digital I/P on channel 16 10016 Read only Int 0-1
17 Digital I/P on channel 17 10017 Read only Int 0-1
18 Digital I/P on channel 18 10018 Read only Int 0-1
19 Digital I/P on channel 19 10019 Read only Int 0-1
20 Digital I/P on channel 20 10020 Read only Int 0-1
21 Digital I/P on channel 21 10021 Read only Int 0-1
22 Digital I/P on channel 22 10022 Read only Int 0-1
23 Digital I/P on channel 23 10023 Read only Int 0-1
24 Digital I/P on channel 24 10024 Read only Int 0-1

Note:

a) If any channel is skip, the status of that channel on modbus on that particular address in
function code 0x02 will be read as 0.

b) Similarly, if a channel is configured as any other input type other than Digital input, the status
in function code 0x02 at that channel address will read as 0.

10.3.3. Configuration parameter Read – write.

Data read Query = [0 x Sr.No.], [0 x 03], [0 x 01], [0 x ADD. Low], [0 x Data. High], [0 x Data.
Low] [0 x CRC Low] [0 x CRC High]
Fun code = 0X03
Data word - Address word < 24.
Response = [Sr.No.], [Fun code], [Byte count], [Data High], [Data Low]., [Data. High], [Data.
Low] [0 x CRC Low] [0 x CRC High]]
Data write Query = [0 x Sr.No.], [0 x 06], [0 x 01], [0 x ADD. Low] , [0 x Data. High], [0 x
Data. Low] [0 x CRC Low] [0 x CRC High]
Fun code = 0X06
Data word - Address word < 24.

Page 45 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

Response = [Sr.No.], [06], [ADD High], [ADD Low], [Data. High], [Data. Low] [0 x CRC Low] [0
x CRC High]

Sr. no Analog Parameters Absolute Type of Parameter Values Applicable


Address Access Type
1. I/P type 40257 Read/write Int 1 To 14
2. Configuration type 40258 Read/write Int 0-1
3. Scanner Type 40259 Read/write Int 8-16-24
4. Set Point Type 40260 Read/write Int 1-2-3
5. *Latch Led Byte & Common DP 40261 Read/write Int 0-1
6. Open Sensor 40262 Read/write Int 0-1
7. Hystersis Byte 40263 Read/write Int 0 to 100
8. Scan Time 40264 Read/write Int 1 to 99
9. Abnormal Logic AL1 40266 Read/write Int 0-1
10. Abnormal Logic AL2 40267 Read/write Int 0-1
11. **Normal Relay Status AL! and AL2 40268 Read/write Int See (a ) of Note Below
12. Password 40269 Read/write Int 0 to 99
13. Serial Configuration 40270 Read/write Int 0 -1
14. Serial Number 40271 Read/write Int 0 to 99
15. Baud Rate 40272 Read/write Int 5-6
16. Slot 1 Configuration 40273 Read/write Int 0 to 4
17. Slot 2 Configuration 40274 Read/write Int 0 to 4
18. Square root 40275 Read/write Int 0-1
19. Common Zero 40276 Read/write Int Act Zero to Act Span
20. Common Span 40277 Read/write Int Act Zero to Act Span
21. Open Collector Type 40278 Read/write Int 0 -1

Latch LED Byte value is in least Significant Byte from bits 0-1-2-3. Common DP value is in most
significant Byte 4-5-6-7.
** Normal relay status AL1 value is in least significant byte from bits 0-1-2-3. Normal relay
status al2 value is in most significant byte 4-5-6-7.

Note:

1) The values for above configuration parameter are as follows:

a) I/P Type:

 E - 1
 J - 2
 K - 3
 T - 4
 B - 5
 R - 6
 S - 7
 Cu-53 - 8
 PT46 - 9
 PT100 (RTD 1) - 10
 PT100 (RTD 0) - 11
 4-20 mA - 12
 0-5 V - 13
 Digital - 14

b) Configuration Type
 Fix - 0
 Mix - 1

c) Set Point Type


 hl - 1
 hh - 2
Page 46 of 50 Operator Manual
Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

 ll - 3

d) *Latch Led Byte


 No - 0
 Yes - 1

e) Open Sensor
 UP - 0
 Down - 1

f) Abnormal Logic AL1


 AL - 0
 tr - 1

g) Abnormal Logic AL2


 AL - 0
 Tr - 1

h) Serial Configuration
 Modb - 0
 Prnc - 1

i) Baud Rate
 9600 - 5
 19200 - 6

j) Slot 1 Configuration
 Relay - 0
 Open Collector - 1
 Retransmission - 2
 None - 4

k) Slot 2 Configurations
 Relay - 0
 Open Collector - 1
 Retransmission - 2
 None - 4

l) Square Root
 No - 0
 Yes - 1

(2) The values of normal_relay_status are as below.

For 1 relay settings:

0x00- CrL1 = OFF, CrL2 = OFF

0x01- CrL1 = ON, CrL2 = OFF

0x10- CrL1 = OFF, CrL2 = ON

0x11- CrL1 = ON, CrL2 = ON

Page 47 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

For 2 relay settings:

0x40- CrL1 = OFF, CrL2 = OFF

0x41- CrL1 = ON, CrL2 = OFF

0xC0- CrL1 = OFF, CrL2 = ON

0xC1- CrL1 = ON, CrL2 = ON

11. Open collector Pin details

11.1 “OR” Logic for 8508, 8516 and 8524


Switches s1, s2, s3 and s5 are required to be ON

Ch No Back plate legend detail (AL1 OR AL2) GND

1 OC1 DG
2 OC2
3 OC3
4 OC4
5 OC5
6 OC6
7 OC7
8 OC8
9 OC9
10 OC10
11 OC11
12 OC12
13 OC13
14 OC14
15 OC15
16 OC16
17 OC17
18 OC18
19 OC19
20 OC20
21 OC21
22 OC22
23 OC23
24 OC24

11.2. “IND” Logic test for 8508


For 8 channels and ”IND” ( Individual ) logic O/C Type (For 2 O/P AL1 & AL2 for 1 Channel)
Switches S1, S2,S3 and S5 are required to turn On.
Ch No. Back plate legend detail AL1 Back plate legend detail AL2 GND

1 OC1 OC9 DG
2 OC2 OC10
3 OC3 OC11
4 OC4 OC12
5 OC5 OC13
6 OC6 OC14
7 OC7 OC15
8 OC8 OC16

Page 48 of 50 Operator Manual


Date: 07/09/2011
Ref. No.: m83/om/403 masibus
Issue No.: 22

11.3 “IND” Logic test for 8516


For 16 channels and”IND” O/C Type (For 2 O/P AL1 AND AL2 for 1 Channel) Two types of O/P
configuration are available.
11.3.1 CASE - 1
O/P 1 to 16 as on card –1 (one) Switches S1, S3.S5 and S6 are required to turn on.
O/P 1 to 16 as on card –2 (two) Switches S2, S4.S7 and S8 are required to turn on.

Ch Back plate legend detail AL1 Back plate legend detail AL2 GND
No
1 OC1 OC9 DG
2 OC2 OC10
3 OC3 OC11
4 OC4 OC12
5 OC5 OC13
6 OC6 OC14
7 OC7 OC15
8 OC8 OC16
Back plate legend detail AL1 Back plate legend detail AL2 GND
9 OC25 OC33 DG
10 OC26 OC34
11 OC27 OC35
12 OC28 OC36
13 OC29 OC37
14 OC30 OC38
15 OC31 OC39
16 OC32 OC40
11.3.2 CASE - 2
O/P 1 to 16 as on card –1 (one) Switches S1,S2.S3 and S5 are required to turn On.
O/P 1 to 16 as on card –2 (two) Switches S4,S6.S7 and S8 are required to turn On.
Ch Back plate legend detail AL1 Back plate legend detail AL2 GND
No
1 OC1 OC25 DG
2 OC2 OC26
3 OC3 OC27
4 OC4 OC28
5 OC5 OC29
6 OC6 OC30
7 OC7 OC31
8 OC8 OC32
9 OC9 OC33
10 OC10 OC34
11 OC11 OC35
12 OC12 OC36
13 OC13 OC37
14 OC14 OC38
15 OC15 OC39
16 OC16 OC40
11.4 “IND” Logic test for 8524

For 24 channels and”IND” O/C Type (For 2 O/P for 1 Channel)


Switches S1, S2.S3 and S5 are required to turn On for Card -1.
Switches S4, S6.S7 and S8 are required to turn On for Card -2.

Ch No Back plate legend detail AL1 Back plate legend detail AL2 GND
1 OC1 OC25 DG
2 OC2 OC26
3 OC3 OC27
4 OC4 OC28
5 OC5 OC29
6 OC6 OC30
7 OC7 OC31
8 OC8 OC32
9 OC9 OC33
10 OC10 OC34

Page 49 of 50
Operator’s manual
Date: 13/7/2011
Ref. No.: m83/om/403

masibus
Issue No.: 22

11 OC11 OC35
12 OC12 OC36
13 OC13 OC37
14 OC14 OC38
15 OC15 OC39
16 OC16 OC40
17 OC17 OC41
18 OC18 OC42
19 OC19 OC43
20 OC20 OC44
21 OC21 OC45
22 OC22 OC46
23 OC23 OC47
24 OC24 OC48

Page 50 of 50 Operator Manual


Date: 07/09/2011

You might also like