SPARE PART

NOTICE

Services, Wärtsilä Finland Oy


Engine section Engine type Ref. Date Issue Document No. Page
23 WECS See below WFI–S 29.11.2007 01 WS23P003 1(2)

Relay module RM10 replaced by RM11a


Engine type This bulletin concerns WÄRTSILÄ® 20, 32, 46, WÄRTSILÄ® Vasa 32 and
32LN engines equipped with WECS 2000 (Wärtsilä Engine Control System).

General The relay module RM-10 has been replaced by a new type, RM-11a. When
replacing the RM-10 with RM-11a the actions described below must be
observed.

LUBE OIL SHUTDOWN STOP RELAY


LUBE OIL SHUTDOWN LOCAL START BLOCKING
BLOCKING
BACKUP U1 U2 U3 U4 U5
OPTIONAL SHUTDOWN LOCAL START

WECS START
MCU STOP/SHUTDOWN
LOCAL STOP FUEL LIMITER + 12 VDC

OVERSPEED SHUTDOWN SLOW TURNING

EMERGENCY STOP FAILURE ALARM


OVERSPEED
WECS WATCHDOG SPEED SWITCH 1
BY-PASS
STOP/SHUTDOWN OVERRIDE SPEED SWITCH 2

SHUTDOWN RESET SPEED PULSE

LUBE OIL SHUTDOWN SWITCH FAILURE

OPTIONAL SHUTDOWN SWITCH FAILURE


RELAY
ENERGIZED STOP SOLENOID FAILURE MODULE
EMERGENCY STOP FAILURE
RM-11
SHORT CIRCUIT

Instructions On RM-11a the cable supervision circuits are using a 10 kohm end
resistor instead of 100 kohm resistor used by the RM10. These
resistors needs to be changed if cable supervision failure alarms
trigger when installed. See Fig 1 of typical connections on the RM for
the cable supervision resistors

R4 n.c.
Lube oil press, 1 1
10k
PSZ201
switch R5 1 PSZ201
3 P Lube oil pressure
R6 2 2x0,75 Cu
10k 2 2 switch
Optional R7
shutdown
switch R8

Fig 1. Typical cable supervision resistor connections on the Relay Module

Wärtsilä Finland Oy P.O. Box 252 (Tarhaajantie 2) Telecop. +358 10 709 1847 Tel. +358 10 709 0000 Business ID 0773744-3
Services, Vaasa FIN-65101 Vaasa, Finland Telecop. +358 10 709 1380 Registered Office: Vaasa
Wärtsilä Finland Oy P.O. Box 50 (Stålarminkatu 45) Telecop. +358 10 709 3279 Tel. +358 10 709 0000
Services, Turku FIN-20811 Turku, Finland Telecop. +358 10 709 3410
Services, Wärtsilä Finland Oy Spare Parts Notice
Issue Document No. Page
01 WS23P003 2(2)

The emergency stop input has also a cable supervision function on


the RM-11a and here a 10kohm resistor needs to be added over the
contact switches of the external emergency stop button. See fig 2 for
a typical connection.
10k

24 VDC reference for


X4.8 31 W1 31 X1.D1 Emergency
emergency stop input
RM.R12 32 41x0.75 stop
32 X1.D2 Emergency stop input

Fig 2. Typical cable supervision resistor connection for the emergency stop
button.

For further information about the connections please check


installation specific drawings.

Ordering instructions Contact your closest Wärtsilä Service Network. When ordering please
specify the engine serial number and part number:

Ref type Part number Version Description


32 501 135 0002 Relay module
W20 501 027 002 Relay card
W32 516 037 007 Relay card
W46 502 035 002 Relay card

Letter distribution Wärtsilä Service Network and owners/operators of engines concerned.

Letter validity Until further notice.

© 2007 Wärtsilä Finland Oy – All rights reserved

No part of this publication may be reproduced or copied in any form or by any means (electronic, mechanical, graphic, photocopying,
recording, taping or other information retrieval systems) without the prior written permission of the copyright holder. Wärtsilä Finland Oy
makes no representation, warranty (express or implied) in this publication and assumes no responsibility for the correctness, errors or
omissions for information contained herein. Information in this publication is subject to change without notice.

Unless otherwise expressly set forth, no recommendation contained in this document is to be construed as provided due to a
defect in the engine, but merely as an improvement of the engine and/or the maintenance procedures relating thereto. Any actions
by the owner/operator as a result of the recommendations are not covered under any warranty provided by Wärtsilä and such
actions will thus be at the owners/operators own cost and expense.

NO LIABILITY WHETHER DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL, IS ASSUMED WITH RESPECT TO THE
INFORMATION CONTAINED HEREIN. THIS PUBLICATION IS CONFIDENTIAL AND INTENDED FOR INFORMATION PURPOSES
ONLY.