AFP-3030 Fire Alarm Control Panel

Disclaimer: These battery calculations are designed exclusively for architects, engineers, consultants and NOTIFIER
authorized distributors to assist in the development of fire alarm equipment quotations. There are no implied warrantie
guarantees in the documents generated by this program other than the standard limited warranty offered by NOTIFIER.
NOTIFIER cannot ensure that any documents generated using this program meet all applicable codes and laws. The user
this program must be familiar with required codes and laws as well as the requirements of the Authority Having Jurisdicti
and must amend the generated documents as necessary. At some point in time, some of these devices may no longer be
available from NOTIFIER.

This workbook contains battery calculation worksheets that allow you to:

Calculate system current draw


Determine battery size and select batteries
0
ntrol Panel
sultants and NOTIFIER
ere are no implied warranties or
ranty offered by NOTIFIER.
le codes and laws. The user of
e Authority Having Jurisdiction
ese devices may no longer be

Version 1.0b
System Current Draw

Current Draw Select devices using the "Qty" column.


C1 0.615 A Use yellow cells to enter quantities and current values.
C2 14.419 A Power Used
Primary (Amps)- C1
Quiescent
C3 0.615 A
0.6
C4 14.419 A
0.0 0.9 1.8 2.7 3.6 4.5 5.4

C1 - Primary Quiescent
Total Primary Quiescent Current
0.615
(amps):
Device Qty Draw Non-Alarm
1. Main System
AFP-3030 / NCA-2 with Display 1 x 0.20500 0.20500
AFP-3030 / NCA-2 without Display 0 x 0.14000
2. Panel Modules
LCM Loop Control Module (11584) 1 x 0.13000 0.13000
LEM Loop Expansion Module (10138) 0 x 0.10000
ARE/C ARE Interface to suit Centaur (ASY-02-037) 0 x 0.02000
ARE/R ARE Interface to suit Romtech (ASY-02-039) 0 x 0.02000
ARE/CR ARE Interface to suit Code Red (ASY-02-041) 0 x 0.02000
3. Networking
NCM/W Network Control Module- Wire (10556) 0 x 0.11000
NCM/F Network Control Module- Fibre (10730) 0 x 0.11000
NCM/SMOF Network Module- SMOF (10691) 0 x 0.11000
RPT-W Repeater Module- Wire (4813) 0 x 0.01700
RPT-WF Repeater Mod Wire-MMOF (3778) 0 x 0.01700
RPT-F Repeater Module- Fibre 0 x 0.01700
HS-NCM-W High Speed NCM- Wire (FG-29-004) 0 x 0.40000
HS-NCM-MF High Speed NCM- MMOF (FG-29-005) 0 x 0.40000
HS-NCM-SF High Speed NCM- SMOF (FG-29-006) 0 x 0.40000
HS-NCM-WMF Hi Speed- Wire/MMOF (FG-29-008) 0 x 0.40000
HS-NCM-WSF Hi Speed- Wire/SMOF (FG-29-009) 0 x 0.40000
HS-NCM-MFSF Hi Speed- MMOF/SMOF (FG-29-011) 0 x 0.40000
NFN-GW-EM-3 Embedded NFN Gateway (FG-29-001) 0 x 0.36000
BACNET-GW-3 Bacnet Gateway (FG-29-002) 0 x 0.36000
ModBus-GW-3 ModBus Gateway (FG-29-007) 0 x 0.36000
VESDA-HLI-GW VESDAnet Gateway (FG-29-017) 0 x 0.36000
NWS-3 Notifier Web Server (FG-29-003) 0 x 0.36000
4. Warning System
DA-30 30Watt Occupant Warning Amp (ASY-02-002) 0 x 0.08000
DA-60 60Watt Occupant Warning Amp (ASY-02-003) 0 x 0.14000
DA-120 120Watt Occupant Warning Amp (ASY-02-004) 2 x 0.14000 0.28000
SDM-4 Speaker Distribution Module (ASY-01-005) 0 x 0.09000
IFS-993F Strobe/Sounder Output Board (ASY-01-002) 0 x 0.02020
5. Compatible Devices- EIA-485
LCD2-80 Remote Mimic Display 0 x 0.08400
ACM-8RA Relay Expansion Module (ASY-02-022) 0 x 0.02000
ACM-ZM Zone Mimic Module 0 x 0.02000
AEM-ZM8 Zone Mimic Expansion Module 0 x 0.00500
ACM-24AT Annunciator Module 0 x 0.01600
AEM-24AT Annunciator Expansion Module 0 x 0.00200
ACM-48A Annunciator Module 0 x 0.01600
AEM-48A Annunciator Expansion Module 0 x 0.00200
SCS-8 Smoke Control Station (10145) 0 x 0.04000
LDM-32 Lamp/Relay Driver Module (10460) 0 x 0.04000
LDM-R32 32x Relay Module (2686) 0 x 0.00000
6. SLC Devices (Appendix A.5.3 SLC maximum current draw per Loop cannot exceed 200mA)
SDX-851AUS CLIP Photo-optical Smoke (FG-03-005) 0 x 0.00030
FDX-851AUS CLIP Fixed Temp Thermal (FG-003-006) 0 x 0.00030
FDX-851RAUS CLIP RoR Thermal (FG-03-007) 0 x 0.00030
SDX-751CTEM CLIP Intelliquad Sensor 0 x 0.00020
IDX-751AE CLIP Intrinsically Safe Photo Smoke 0 x 0.00033
IMX-1E Intrinsically Safe Translator Mod (FG-01-056) 0 x 0.01400
FSP-851 FlashScan Photo-optical Smoke (FG-03-011) 0 x 0.00030
FSI-851 FlashScan Ionization Sensor (FG-03-012) 0 x 0.00030
FAPT-851AUS FlashScan Acclimate (FG-03-013) 0 x 0.00030
FST-851AUS FlashScan Fixed Thermal (FG-03-014) 0 x 0.00030
FST-851RAUS FlashScan RoR Thermal (FG-03-015) 0 x 0.00030
FST-851-WP FlashScan Sealed Fixed (FG-03-009) 0 x 0.00030
FST-851R-WP FlashScan Sealed RoR (FG-03-010) 0 x 0.00030
FST-851H 88°C FlashScan High-Temp Thermal 0 x 0.00030
FSC-851 FlashScan Intelliquad Sensor (FG-03-002) 0 x 0.00030
FSL-751 FlashScan Laser Sensor (FG-03-016) 0 x 0.00026
FSA-8000 FAAST Detector 0 x 0.46500
FSB-200 FlashScan Beam Detector (FG-03-017) 0 x 0.00200
FSB-200S FlashScan Beam w/Test (FG-03-018) 0 x 0.00200
FMM-101 Single Input Mini-module (FG-05-026) 0 x 0.00038
FMM-1 Single Input Monitor Module (FG-05-027) 0 x 0.00038
FDM-1 Dual Input Monitor Module (FG-05-028) 0 x 0.00075
FMM-4-20 4-20mA Module 0 x 0.00100
FZM-1 Single Conventional Zone Module (FG-05-029) 0 x 0.00940
FDMR-1 Dual Input/Output Module (FG-05-030) 0 x 0.00110
FRM-1 Single Intelligent Relay Module (FG-05-025) 0 x 0.00026
FCM-1 Single Intelligent Control Module (FG-05-024) 0 x 0.00038
ISO-X Loop Isolator Module (FG-05-035) 0 x 0.00040
MMX-2 Conventional Zone Module 0 x 0.00940
XP-10M 10-input Monitor Module (FG-05-031) 0 x 0.00350
XP-6MA 6way Conventional Zone Module (FG-05-032) 0 x 0.00220
XP-6R 6 way Relay Output Module (FG-05-033) 0 x 0.00145
XP-6C 6 way Control Output Module (FG-05-034) 0 x 0.00225
FSM500k FlashScan Manual Call Point (FG-05-019) 0 x 0.00020
NFX-MCP FlashScan Manual Call Point (FG-05-049) 0 x 0.00039
WCP-5A Adressable Outdoor MCP (FG-05-020) 0 x 0.00040
AWS32/R Intelligent Wall Sounder Red (FG-05-004) 0 x 0.00011
AWSB32/R/R Intelligent Sounder/Beacon (FG-05-005) 0 x 0.00011
AWB/R Intelligent Wall Beacon (FG-05-006) 0 x 0.00011
ABS32/W Intelligent Base Sounder (FG-05-001) 0 x 0.00011
AIBS32/W Base Sounder w/ Isolator (FG-05-002) 0 x 0.00020
ABSB32/W/R Base Sounder/Beacon (FG-05-003) 0 x 0.00011
NFX-WS-R Loop Sounder Red (FG-05-037) 0 x 0.00045
NFX-WS-IV Loop Sounder White (FG-05-038) 0 x 0.00045
NFX-WSF-RR Loop Sounder/Strobe Red (FG-05-039) 0 x 0.00045
NFX-WF-RR Loop Strobe Red (FG-05-041) 0 x 0.00045
NFX-BS-IV Sounder Base Off-White (FG-05-043) 0 x 0.00045
NFXI-BS-IV Sounder Base w/ Isolator (FG-05-044) 0 x 0.00045
NFX-BF-IVR Strobe Base Red (FG-05-045) 0 x 0.00045
NFX-BSF-IVR Sounder/Strobe Base Red (FG-05-046) 0 x 0.00045
7. Notification Appliances
SOU-SSR-4 Surface Mount Sounder Red IP66 (11187) 0 x 0.00000
SOU-LPR-4 Low Profile Sounder Red (11198) 0 x 0.00000
SOU-SSW-4 Surface Mount Sounder White IP66 (11201 0 x 0.00000
MHWZA Mini-Horn Sounder White (FG-70-015) 0 x 0.00000
MHRZA Mini-Horn Sounder Red (FG-70-016) 0 x 0.00000
DBS-4-W Sounder Base White (11108) 0 x 0.00000
STR-SRR-2 Indoor Strobe Red (11205) 0 x 0.00000
STR-SSRR-2 Outdoor Strobe Red IP66 (11206) 0 x 0.00000
STR-SRA-2 Indoor Strobe Amber (11208) 0 x 0.00000
STR-SRRA-2 Outdoor Strobe Amber (11209) 0 x 0.00000
SOLEX10/R Red Xenon Strobe (11246) 0 x 0.00000
SOLEX10/A Amber Xenon Strobe (11247) 0 x 0.00000
SOLEX10/B Blue Xenon Strobe (11264) 0 x 0.00000
ROSHNI Sounder (2119) 0 x 0.00000
FLASHNI Strobe/Sounder (1456) 1 x 0.00000 0.00000
Red & Amber DUAL Strobe (11145) 0 x 0.00000
S2475RLFIRE Indoor Brigade Strobe (11170) 0 x 0.00000
SRHKRLFIRE Outdoor Brigade Strobe IP66 (FG-70-021) 0 x 0.00000
BELL/6/U 150mm Fire Bell 24VDC (2434) 0 x 0.00000
BELL/8/U 200mm Fire Bell 24VDC (2392) 0 x 0.00000
8. Agent Release System
GRM/DUAL Gas Release Module (ASY-01-008) 0 x 0.15000
STOP/GAS Remote Station 0 x 0.00000
WSR-I Red Indoor Warning Sign (FG-42-003) 0 x 0.00000
WSR-O Red Outdoor Warning Sign (FG-42-004) 0 x 0.00000
WSA-I/SI Indoor System Inoperative Sign (FG-42-005) 0 x 0.00000
WSA-O/SI Indoor System Inoperative Sign (FG-42-006) 0 x 0.00000
9. Miscellaneous
ASE Romtek 0 x 0.06000
ASE Centaur 0 x 0.10000
ASE Code Red 0 x 0.15000
ASE Almos 0 x 0.03000
C4 - Secondary Fire Alarm Current Draw
Only include those additional power supplies that are backed up by the control panels batteries.

Device Qty Draw Total


Total Alarm Load AFP-3030 1 14.419 14.419

Total Secondary Fire Alarm Current (amps): 14.419


tem Current Draw - AFP-3030

t values.

Power UsedAlarm
Primary (Amps)- C2
14.4

5.4 0.0 1.6 3.2 4.8 6.4 8.0 9.6 11.2

C2 - Primary Alarm C3 - Secondary Quiescent


Total Primary Fire Alarm Total Secondary Quiescent
14.419 0.615
Current (amps): Current (amps):
Qty Draw Alarm Qty Draw Non-Alarm

1 x 0.22500 0.22500 1 x 0.20500 0.20500


0 x 0.15000 0 x 0.14000

1 x 0.13000 0.13000 1 x 0.13000 0.13000


0 x 0.10000 0 x 0.10000
0 x 0.03500 0 x 0.02000
0 x 0.03500 0 x 0.02000
0 x 0.03500 0 x 0.02000

0 x 0.11000 0 x 0.11000
0 x 0.11000 0 x 0.11000
0 x 0.11000 0 x 0.11000
0 x 0.01700 0 x 0.01700
0 x 0.01700 0 x 0.01700
0 x 0.01700 0 x 0.01700
0 x 0.40000 0 x 0.40000
0 x 0.40000 0 x 0.40000
0 x 0.40000 0 x 0.40000
0 x 0.40000 0 x 0.40000
0 x 0.40000 0 x 0.40000
0 x 0.40000 0 x 0.40000
0 x 0.36000 0 x 0.36000
0 x 0.36000 0 x 0.36000
0 x 0.36000 0 x 0.36000
0 x 0.36000 0 x 0.36000
0 x 0.36000 0 x 0.36000

0 x 1.70000 0 x 0.08000
0 x 3.50000 0 x 0.14000
2 x 7.00000 14.00000 2 x 0.14000 0.28000
0 x 0.09000 0 x 0.09000
0 x 0.07900 0 x 0.02020
0 x 0.09800 0 x 0.08400
0 x 0.03500 0 x 0.02500
0 x 0.02500 0 x 0.02000
0 x 0.02500 0 x 0.00500
0 x 0.07000 0 x 0.01600
0 x 0.05600 0 x 0.00200
0 x 0.07000 0 x 0.01600
0 x 0.05600 0 x 0.00200
0 x 0.18000 0 x 0.04000
0 x 0.20000 0 x 0.04000
0 x 0.08800 0 x 0.00000
mA)
0 x 0.00650 0 x 0.00030
0 x 0.00650 0 x 0.00030
0 x 0.00650 0 x 0.00030
0 x 0.00700 0 x 0.00020
0 x 0.00420 0 x 0.00033
0 x 0.01400 0 x 0.01400
0 x 0.00650 0 x 0.00030
0 x 0.00650 0 x 0.00030
0 x 0.00650 0 x 0.00030
0 x 0.00650 0 x 0.00030
0 x 0.00650 0 x 0.00030
0 x 0.00650 0 x 0.00030
0 x 0.00650 0 x 0.00030
0 x 0.00650 0 x 0.00030
0 x 0.00700 0 x 0.00030
0 x 0.00650 0 x 0.00026
0 x 0.49300 0 x 0.46500
0 x 0.00850 0 x 0.00200
0 x 0.00850 0 x 0.00200
0 x 0.00060 0 x 0.00038
0 x 0.00510 0 x 0.00038
0 x 0.00570 0 x 0.00075
0 x 0.00800 0 x 0.00100
0 x 0.09000 0 x 0.00940
0 x 0.00600 0 x 0.00110
0 x 0.00650 0 x 0.00026
0 x 0.00650 0 x 0.00038
0 x 0.00500 0 x 0.00040
0 x 0.09000 0 x 0.00940
0 x 0.05500 0 x 0.00350
0 x 0.58000 0 x 0.00220
0 x 0.03200 0 x 0.00145
0 x 0.03500 0 x 0.00225
0 x 0.00500 0 x 0.00020
0 x 0.00780 0 x 0.00039
0 x 0.00760 0 x 0.00040
0 x 0.00900 0 x 0.00011
0 x 0.00900 0 x 0.00011
0 x 0.00900 0 x 0.00011
0 x 0.00900 0 x 0.00011
0 x 0.00900 0 x 0.00020
0 x 0.00900 0 x 0.00011
0 x 0.00558 0 x 0.00045
0 x 0.00558 0 x 0.00045
0 x 0.00886 0 x 0.00045
0 x 0.00328 0 x 0.00045
0 x 0.00455 0 x 0.00045
0 x 0.00474 0 x 0.00045
0 x 0.00328 0 x 0.00045
0 x 0.00783 0 x 0.00045

0 x 0.01200 0 x 0.00000
0 x 0.01200 0 x 0.00000
0 x 0.01200 0 x 0.00000
0 x 0.01600 0 x 0.00000
0 x 0.01600 0 x 0.00000
0 x 0.01200 0 x 0.00000
0 x 0.10000 0 x 0.00000
0 x 0.10000 0 x 0.00000
0 x 0.10000 0 x 0.00000
0 x 0.10000 0 x 0.00000
0 x 0.08000 0 x 0.00000
0 x 0.08000 0 x 0.00000
0 x 0.08000 0 x 0.00000
0 x 0.01200 0 x 0.00000
1 x 0.06400 0.06400 1 x 0.00000 0.00000
0 x 0.10000 0 x 0.00000
0 x 0.18000 0 x 0.00000
0 x 0.18000 0 x 0.00000
0 x 0.06000 0 x 0.00000
0 x 0.06000 0 x 0.00000

0 x 1.00000 0 x 0.15000
0 x 0.00000 0 x 0.00000
0 x 0.14000 0 x 0.00000
0 x 0.14000 0 x 0.00000
0 x 0.14000 0 x 0.00000
0 x 0.14000 0 x 0.00000

0 x 0.15000 0 x 0.06000
0 x 0.45000 0 x 0.10000
0 x 0.15000 0 x 0.15000
0 x 0.03000 0 x 0.03000
System Power Requirements
AFP-3030 Fire Alarm Control Panel

Protected Premises:
Address:
City: State:

Prepared By:
Address: Email:
City: State:

Primary Quiescent Load 0.62 Amps


Current load on the primary power supply during
non-alarm conditions.

Primary Alarm Load 14.42 Amps


Current load on the primary power supply during
alarm conditions.

Secondary Load Requirements 36.47 Amp Hours


Total Secondary Load from the calculation table below.

Battery Power Equation: C₂₀ = 1.25 [(Iǫ x Tǫ) + Fᴄ(Iₐ x Tₐ)]

Current Draw Time (hours)


Secondary Quiescent Current Iǫ Required Quiescent Time Tǫ
x
0.615 A 24 hours
Secondary Fire Alarm Current Iₐ Required Alarm Time Tₐ x Dera
x
14.419 A 1.000 hours
Total Secondary Loa
Battery Compensation facto
Secondary Load Requirements

Battery Selection: 12 Amp Hours x 2 Batteries


Select available batteries from the list on the right.
(Battery size must be greater than Secondary Load requirements)
Check the chart below for battery power distribution
1
Battery Distribution Chart
Shows amp-hour distribution of your selections.

3
30%
1
40%

2
30%

Comments
1. If battery size exceeds FACP cabinet capacity. External battery box may be required.
2. Selected battery size should meet secondary load requirements.

Spare Battery Capacity -24.47 Battery Selection (AH) - Secondary Load Requiremen
Secondary Standby Load 18.45 Secondary Standby Load (AH) * Derating Factor
Secondary Alarm Load 18.02 Secondary Alarm Load (AH) * Derating Factor
Requirements
el

Date:

Postcode:

Phone:

Postcode:

Use NPS Power Supply


NPS-5 5.6 A
NPS-11 11.7 A

Time (hours) Total (AH)


ed Quiescent Time Tǫ
24 hours 14.76
Alarm Time Tₐ x Derating Factor Fᴄ
1.000 hours 14.42 Panel Batteries Approved to AS1603.4
Total Secondary Load 29.18 1.3 AH [BATT/1.3 FG-65-001] (97 L x 43 W x 58 H)
y Compensation factor x 1.25 7 AH [BATT/7 FG-65-002] (151 L x 65 W x 101 H)
Load Requirements 36.47 AH 12 AH [BATT/12 FG-65-003] (151 L x 95 W x 101 H)
18 AH [BATT/18 FG-65-004] (181 L x 77 W x 167 H)
26 AH [BATT/26 FG-65-005] (175 L x 166 W x 125 H)
ours x 2 Batteries 33 AH [BATT/33 FG-65-006] (195 L x 130 W x 180 H)
40 AH [BATT/40 FG-65-007] (197 L x 165 W x 175 H)
85 AH [BATT/85 FG-65-008] (305 L x 168 W x 210 H)
100 AH [BATT/100 FG-65-009] (330 L x 172 W x 221 H)
150 AH [BATT/150 FG-65-010] (485 L x 172 W x 240 H)
1 2 3

required.

condary Load Requirements (AH)


H) * Derating Factor
) * Derating Factor