Comment Sheet

#REF! #REF! DCS Ref. : #REF!

#REF! #REF! Date : 09-03-2020

Receipt Date : #REF! KSEBL Previous DCS : #REF!

Drawing / Document No. Rev. Approval Code Document / Drawing Title

5427PC048-ETU-000-SYD-SRI-S5020-SL-0002 RO AC LT SINGLE LINE DIAGRAM (AC-DC)


5427PC048-VIZ-000-SYD-SRI-S5020-SL-0002
#REF! #REF!

Sl NO KSEB COMMENTS GE REPLY ON 09.07.20

1 Feeder no 1- sheet no 01-load is 100kW, by calculation 100kW load will draw 148A max, but
the feeder MCCB rating is 125A only - Change the MCCB rating accoriding the load Noted & Updated in our revised submission.

2 Sheet no 1- All MCCB and MCB Tripping Curve to be mentioned in the SLD
Sheet no 2- Please Ensure All DC MCB and MCCB's are to be DC rated Noted & Same will be reflected in vendor drawings.
Noted & Complied.

3 Sheet no 1- EOT crane Feeder no 14- 5KW is seems insufficient


We confirm that rating of EOT crane is less than 5 KW.
4 Sheet no 1- Air Condition -Feeder 27-10KW is seems insufficient and please furnish the sizing
Noted & Updated in our revised submission.
calculation
5 Sheet no 1- Welding Plug point shall be 3 no - 2 no inside the GIS room and One number in
the yard. Please note that each welding receptacles plug point are able to connect 3-4
welding sockets by Loop-in & Loop-out arrangement and it`s a general
industrial practice followed in all projects.

6 Sheet no 1- A Distribution Kiosk shall be erected in the Yard for extending supply( from
feeder no 1) for oil filtering purpose and the kiosk have 3/1 phase industrial sockets and one Noted but Same is not reflecting in our BPS schedule and will be supplied with
welding point suitable implications.

7 Sheet no 2- Cable from Battery Charger to Battery shall be armoured cable only, and provide
2x35mm2 cable for each battery bank Kindly note that there is no line item in LOA for 2C x 35 Sq.mm cable. We have
considered 2 runs of 1C x 35 Sq.mm PVC FRLS PVC Copper Cable as per line
item : 70 as per supply BOQ. Same is of armoured cable only.

8 Sheet 2- An automatic change over for DC light shall be included


Noted & Same shall be shown in DC Lighting panel vendor drawings.

9 Sheet 1- Star Rating of Distribution Transformer may be shown in the SLD


Noted and Incorporated.
10 51G protection is statutory for LT power sources above 63KVA rating. Hence 51G has to be
provided with NCT rating not less than 1/5th of line CT rating at 250KVA,11/0.433kV We clarify that there is no such statutory requirement for 51G and even KSEB
Transformer. specification doesn`t ask for the same. Further, we havn`t provided for KSEB
package - 1 also. Hence kindly accept the same.

11 400A, MCCBs are to be of 4pole as per clause 5.3 of Tender specifications. Also MCCBs
should have inbuilt protection(3OC+1EF). These protection rating has to be shown in the Noted and incorporated in notes. Regarding protection`s same will be reflected
drawing. in respective vendor drwaings.

12 As per tender specification there is provision for sub DB panel other than MLDB.
16A, SP, MCB is found to shown in main ACDB. Rating of
We clarify that there is no specific line item for new lighting panels/DB`s in
16A,MCB has to be checked with bus bar fault level. It is advisable to provide seperate
either KSEB supply BOQ / work order BOQ. But as a general practice we had
subDB with 100mA, ELCB for 16A, MCB feeders.
considered Lighting & power distribution panels in our illumination layout
which be billed seperately alongwith 3 phase junction box used for outdoor
lightings. Note that RCCB is already considered in the outogings of lighting
panels (Refer lighting layouts). Further, we suggest to have a lighting
transformer for better isolation purpose in MLDB`s & ELDB`s.

13 63A, TPN, MCB for MLDB& ELDBs have to be replaced with 30mA, ELCB. Also TPN, MCB
for welding power plug, EOT crane , FFPH, HVAC, Airconditioner feeders have to be Note that RCCB is already considered in the outogings of lighting panels (Refer
replaced with ELCBs lighting layouts). Further, we suggest to have a lighting transformer for better
isolation purpose in MLDB`s & ELDB`s. Also note that all other equipment`s
like welding plug, EOT crane, FFPH, HVAC, Airconditioner feeders will be
provided with MCCB/MCB only as ELCB not operate for
overcurrent/overload protection.

14 KW rating of Battery charger circuit will have to be sufficient to meet 10H initial charging Noted & we clarify that battery charger KW rating is considered based on its
current rating. rectifier transformer rating.
15 Provide a facility for paralleling two DC DB BUS bar for reliable DC supply
Noted and considered. Further, addition of feeders in DCDB with respect to
supply billing price schedule will be supplied with suitable implications.

16 As per Technical Specification clause 1-chapter 18- “The AC distribution Boards shall be
SCADA compatible and shall transmit status of incoming breaker , Incoming current and
voltages through IEC 61850 compatible communication devices”-status of incomer breaker Noted and same will be routed to SCADA through Aux Panel.
shall be extended to SCADA

1
17 This approval of KW ratings is subject to confirmation after receiving the sizing calculation of
downstream loads/Equipments Noted.

2
Comment Sheet

#REF! #REF! DCS Ref. : #REF!

#REF! #REF! Date : 09-03-2020

Receipt Date : #REF! KSEBL Previous DCS : #REF!

Drawing / Document No. Rev. Approval Code Document / Drawing Title

5427PC048-ETU-000-SYD-SRI-S5020-SL-0002 RO AC LT SINGLE LINE DIAGRAM (AC-DC)


5427PC048-VIZ-000-SYD-SRI-S5020-SL-0002
#REF! #REF!

Sl NO KSEB COMMENTS GE REPLY ON 09.07.20

1 Feeder no 1- sheet no 01-load is 100kW, by calculation 100kW load will draw 148A max, but
the feeder MCCB rating is 125A only - Change the MCCB rating accoriding the load Noted & Updated in our revised submission.

2 Sheet no 1- All MCCB and MCB Tripping Curve to be mentioned in the SLD
Sheet no 2- Please Ensure All DC MCB and MCCB's are to be DC rated Noted & Same will be reflected in vendor drawings.
Noted & Complied.

3 Sheet no 1- EOT crane Feeder no 14- 5KW is seems insufficient


We confirm that rating of EOT crane is less than 5 KW.
4 Sheet no 1- Air Condition -Feeder 27-10KW is seems insufficient and please furnish the sizing
Noted & Updated in our revised submission.
calculation
5 Sheet no 1- Welding Plug point shall be 3 no - 2 no inside the GIS room and One number in
the yard. Please note that each welding receptacles plug point are able to connect 3-4
welding sockets by Loop-in & Loop-out arrangement and it`s a general
industrial practice followed in all projects.

6 Sheet no 1- A Distribution Kiosk shall be erected in the Yard for extending supply( from
feeder no 1) for oil filtering purpose and the kiosk have 3/1 phase industrial sockets and one Noted but Same is not reflecting in our BPS schedule and will be supplied with
welding point suitable implications.

7 Sheet no 2- Cable from Battery Charger to Battery shall be armoured cable only, and provide
2x35mm2 cable for each battery bank Kindly note that there is no line item in LOA for 2C x 35 Sq.mm cable. We have
considered 2 runs of 1C x 35 Sq.mm PVC FRLS PVC Copper Cable as per line
item : 70 as per supply BOQ. Same is of armoured cable only.

8 Sheet 2- An automatic change over for DC light shall be included


Noted & Same shall be shown in DC Lighting panel vendor drawings.

9 Sheet 1- Star Rating of Distribution Transformer may be shown in the SLD


Noted and Incorporated.
10 51G protection is statutory for LT power sources above 63KVA rating. Hence 51G has to be
provided with NCT rating not less than 1/5th of line CT rating at 250KVA,11/0.433kV We clarify that there is no such statutory requirement for 51G and even KSEB
Transformer. specification doesn`t ask for the same. Further, we havn`t provided for KSEB
package - 1 also. Hence kindly accept the same.

11 400A, MCCBs are to be of 4pole as per clause 5.3 of Tender specifications. Also MCCBs
should have inbuilt protection(3OC+1EF). These protection rating has to be shown in the Noted and incorporated in notes. Regarding protection`s same will be reflected
drawing. in respective vendor drwaings.

12 As per tender specification there is provision for sub DB panel other than MLDB.
16A, SP, MCB is found to shown in main ACDB. Rating of
We clarify that there is no specific line item for new lighting panels/DB`s in
16A,MCB has to be checked with bus bar fault level. It is advisable to provide seperate
either KSEB supply BOQ / work order BOQ. But as a general practice we had
subDB with 100mA, ELCB for 16A, MCB feeders.
considered Lighting & power distribution panels in our illumination layout
which be billed seperately alongwith 3 phase junction box used for outdoor
lightings. Note that RCCB is already considered in the outogings of lighting
panels (Refer lighting layouts). Further, we suggest to have a lighting
transformer for better isolation purpose in MLDB`s & ELDB`s.

13 63A, TPN, MCB for MLDB& ELDBs have to be replaced with 30mA, ELCB. Also TPN, MCB
for welding power plug, EOT crane , FFPH, HVAC, Airconditioner feeders have to be Note that RCCB is already considered in the outogings of lighting panels (Refer
replaced with ELCBs lighting layouts). Further, we suggest to have a lighting transformer for better
isolation purpose in MLDB`s & ELDB`s. Also note that all other equipment`s
like welding plug, EOT crane, FFPH, HVAC, Airconditioner feeders will be
provided with MCCB/MCB only as ELCB not operate for
overcurrent/overload protection.

14 KW rating of Battery charger circuit will have to be sufficient to meet 10H initial charging Noted & we clarify that battery charger KW rating is considered based on its
current rating. rectifier transformer rating.
15 Provide a facility for paralleling two DC DB BUS bar for reliable DC supply
Noted and considered. Further, addition of feeders in DCDB with respect to
supply billing price schedule will be supplied with suitable implications.

16 As per Technical Specification clause 1-chapter 18- “The AC distribution Boards shall be
SCADA compatible and shall transmit status of incoming breaker , Incoming current and
voltages through IEC 61850 compatible communication devices”-status of incomer breaker Noted and same will be routed to SCADA through Aux Panel.
shall be extended to SCADA

3
17 This approval of KW ratings is subject to confirmation after receiving the sizing calculation of
downstream loads/Equipments Noted.