SPECIFIED PROPOSED
[NB: For alternative materials a Compliance Report must be provided]
MFR MFR
AGENT AGENT
MAKE/ MAKE/
MODEL MODEL
Omniyat regarding residential hot water tank sizing and recovery rates for both the C-Una
ccept
abl
e,Re-
Submi
t
hotel and residential. We confirm that CSA are in disagreement regarding the sig-
TheAr chit
ec t
/E ngineer’
srevi
ewof t
hi sma t
erial/dr
a wing/
documenti sf ort hepur poseofa s
c ert
a i
ningc onformity
wit
ht heba sicc onc ept,pr
ofilesandgener alarrangement s
nificant reduction in storage capacity for the residential elements of the building
only.Therev i
ews hallnotbec onstruedt omea ntha tthe
Archit
ec t/ Engi neera ccepts fina li nstall
ation det ai
l
,
res
pons ibi
li
tyf orwhi chwi l
lrema inwi tht heCont ractor
.
TheCont ractori sresponsibl
efora nyer ror
sorommi s
sions
and especially for the penthouses. Once RPJV has obtained Omniyat’s approval,
i
nt he ma teria ls ample/dr a
wi ng/doc umenta nd for
meet i
ngt her equi rementsoftheCont ractdoc ument s.
Venkat
Name………………………. Signature……………………… 19.Apr.2020
Date………………………..
Consultant Review Comments: Digital Stamping
The approval for the proposed design changes shall be obtained from the
design consultant and the client.
Mohammad Issa
Name………………………. Signature……………………… 07/05/2020
Date………………………..
12th Mar. 2020
Table of Contents
They have indicated the hot water temperature as 65 deg C. This is · COMPLIED
2 unacceptable and is a safety risk. The water temperature needs to be
lowered to 60 deg C or below.
The type of tanks and heaters they are using shows a shell and tube
type heat exchanger inserted in the tank. This is not what was
specified. We specifically showed external plate and frame heat
exchangers for the simple reason of contamination. When the heat
3 exchanger is inserted in the tank and if there is a leak from the LTHW · Complied with External Heat exchanger as per
side, the domestic water will become contaminated. The plate and CSA design intent
frame heat exchanger we have specified are external to the tanks and
are double wall vented. This means that if there is a leak in the heat
exchanger wall, this will mean that the water will drip onto the floor
and be investigated.
They are using insertion type heat exchangers with a 3-way valve. In
this case we can overheat the water. Our design shows the plate and
4 · Complied with External Heat exchanger as per
frame heat exchanger with a circulating pump on the tank side. This
CSA design intent
will give us much better control of the maximum water temperature in
the tank.
5 -
Water storage capacities, boiler sizes, and recovery rates:
3
They have referenced ASHRAE for the hot water recovery duration
· As per our contract agreed V.E , we are using 2 hour recovery
and have indicated it as 2 hours. I have looked at the highlighted items
on the ASHRAE sheets in their report and it does not say that the rate to meet related authority requirements.
5.a recovery rate is 2 hours. In fact, it clearly says that the flows given in In addition , we have utilized ASHRAE as design reference ,
the table are L/hr NOT L/2 hrs. Furthermore, the sample calculation PLUMBING DESIGN GUIDE & as well as the manufacturer's
provided by ASHRAE uses the “probable maximum recommendation.
demand/3600”. 3600 is the number of seconds in one hour. NOT 2
hours.
5.b Hotel: -
More than likely, these apartments will become part of the hotel and
i will be used by visitors/tourists. Therefore, we highly recommend that ·We are considering residential apartment in our calculation as per
our contract with Omniyat.
the apartments are designed similar to the hotel. Omniyat to confirm.
ii Based on the above, the storage capacity for levels 28-7 should be · We are considering residential apartment in our calculation as
reviewed and revised. per our contract with Omniyat.
The ASHRAE standards cannot be used for sizing the tanks for 23-27
x As per our agreed Contract , we are following this design to
and 28-31 as the number of apartments are relatively small. The
ASHRAE standards are more geared to larger installations where you meet the authority requirement.
iii get the benefit from diversity. In addition these are all penthouse
apartments and failure to provide hot water will become an issue. We
recommend that the size of these tanks are revisited on a more practical
basis where the number of shower heads are actually counted, the
duration of flow is approximated, and then a possible diversity applied.
5.d Heaters:
o Solar system is deleted from original IFC drawings as per latest layouts.
o Plumbing Fixtures units for residential and hotel side have changed quantities
LTHW)
· All calculation produced in this report are refereeing to ASHRAE handbooks and
standards.
3
Basis of Design calculation
1) Residential apartments
o Demand factor : 0.3
o Storage factor : 1.25
o Recovery time : 2 hours
1) AHRAE handbook – HVAC application (Hot water demand for various building – Table 7)
2) AHRAE handbook – HVAC application (Hot water demand per fixture – Table 10)
3
$SSHQGLFHV
o $SSHQGL[$ +RWHOIL[WXUHXQLWVFRXQWDQGORDGFDOFXODWLRQV
o $SSHQGL[' 5HVLGHQWLDOIL[WXUHXQLWVFRXQWDQGORDGFDOFXODWLRQV
o $SSHQGL[( %RLOHU6L]LQJFDOFXODWLRQ
o $SSHQGL[) )$+8$+8VFKHGXOH
o $SSHQGL[* 5HYLVHGVFKHPDWLFV
o $SSHQGL[+ 5HFRYHU\WLPHVXSSRUWGRFXPHQWV
o $SSHQGL[, %RLOHUVGDWDVKHHWV
o $SSHQGL[- $6+5$(UHIHUHQFH
o $SSHQGL[. /3*5),UHVSRQVH
3
Appendix A
Hotel fixture unit’s count and load calculations
HOT WATER CALCULATIONS HOTEL - BOILER SIZING
Type of Guest Room Room Tag W/B Shower Bath tub Kitchen sink
7th floor
1Bed Suite
Living Toilet 701 1
Bedroom Toilet 2 1 1
Deluxe Room 702 2 1 1
Deluxe Room 703 2 1 1
Deluxe Room 704 2 1 1
Deluxe Room 705 2 1 1
Deluxe Room 706 2 1 1
1Bed Suite Living Duplex 707 1
Deluxe Room 708 2 1 1
Deluxe Room 709 2 1
Deluxe (Junior Suite) 710 2 1 1
8th floor
1Bed Suite
Lvg toilet 801 1
Bedroom toilet 2 1 1
Deluxe Room 802 2 1 1
Deluxe Room 803 2 1 1
Deluxe Room 804 2 1 1
Deluxe Room 805 2 1 1
Deluxe Room 806 2 1 1
1Bed suit BR duplex 707.7 2 1 1
Deluxe Room 807 2 1
Deluxe (Junior Suite) 808 2 1 1
9th floor
1Bed Suite
Lvg toilet 901 1
Bedroom toilet 2 1 1
Deluxe Room 902 2 1 1
Deluxe Room 903 2 1 1
Deluxe Room 904 2 1 1
Deluxe Room 905 2 1 1
Deluxe Room 906 2 1 1
1Bed Suite
Lvg toilet 907 1
Bedroom toilet 2 1 1
1Bed Suite
Lvg toilet 908 1
Bedroom toilet 2 1 1
Deluxe Room 909 2 1
1Bed Suite 910 2 1 1
ϭ
HOT WATER CALCULATIONS HOTEL - BOILER SIZING
Type of Guest Room Room Tag W/B Shower Bath tub Kitchen sink
10th floor
1Bed Suite
Lvg toilet 1001 1
Bedroom toilet 2 1 1
Deluxe Room 1002 2 1 1
Deluxe Room 1003 2 1 1
Deluxe Room 1004 2 1 1
Deluxe Room 1005 2 1 1
Deluxe Room 1006 2 1 1
1Bed Suite
Lvg toilet 1007 1
Bedroom toilet 2 1 1
Deluxe Room 1008 2 1
Deluxe Room 1009 2 1 1
11th floor
1Bed Suite
Lvg toilet 1101 1
Bedroom toilet 2 1 1
Deluxe Room 1102 2 1 1
Deluxe Room 1103 2 1 1
Deluxe Room 1104 2 1 1
Deluxe Room 1105 2 1 1
Deluxe Room 1106 2 1 1
Deluxe Room 1107 2 1 1
Deluxe Room 1108 2 1
Deluxe (Junior Suite) 1109 2 1 1
12th floor
1Bed Suite
Lvg toilet 1201 1
Bedroom toilet 2 1 1
Deluxe Room 1202 2 1 1
Deluxe Room 1203 2 1 1
1Bed Suite
Lvg toilet 1204 1 1
Bedroom toilet 2 1 1
Deluxe Room 1205 2 1 1
Deluxe Room 1206 2 1 1
1Bed Suite
Lvg toilet 1207 1 1
Bedroom toilet 2 1 1
Deluxe Room 1208 2 1 1
Deluxe Room 1209 2 1 1
1Bed Suite
Lvg toilet 1210 1
Bedroom toilet 2 1 1
Ϯ
HOT WATER CALCULATIONS HOTEL - BOILER SIZING
Type of Guest Room Room Tag W/B Shower Bath tub Kitchen sink
1Bed Suite
Lvg toilet 1211 1
Bedroom toilet 2 1 1
Deluxe Room 1212 2 1
Deluxe Room 1213 1 1 1
Deluxe Room 1214 2 1 1
Deluxe Room 1215 2 1 1
Deluxe Room 1216 2 1 1
Deluxe Room 1217 2 1 1
1Bed Suite 1218 2 1 1
13th floor
1Bed Suite
Lvg toilet 1301 1
Bedroom toilet 2 1 1
Deluxe Room 1302 2 1 1
Deluxe Room 1303 2 1 1
1Bed Suite
Lvg toilet 1304 1 1
Bedroom toilet 2 1 1
Deluxe Room 1305 2 1 1
Deluxe Room 1306 2 1 1
1Bed Suite
Lvg toilet 1307 1 1
Bedroom toilet 2 1 1
Deluxe Room 1309 2 1 1
Deluxe Room 1310 2 1 1
1Bed Suite Living duplex 1311 1
Deluxe Room 1312 2 1 1
Deluxe Room 1313 2 1
Deluxe Room 1314 1 1 1
Deluxe Room 1315 2 1 1
Deluxe Room 1316 2 1 1
Deluxe Room 1317 2 1 1
Deluxe Room 1318 2 1 1
1Bed Suite 1319 2 1 1
14th floor
1Bed Suite
Lvg toilet 1401 1
Bedroom toilet 2 1 1
Deluxe Room 1402 2 1 1
Deluxe Room 1403 2 1 1
1Bed Suite
Lvg toilet 1404 1 1
Bedroom toilet 2 1 1
Deluxe Room 1405 2 1 1
Deluxe Room 1406 2 1 1
ϯ
HOT WATER CALCULATIONS HOTEL - BOILER SIZING
Type of Guest Room Room Tag W/B Shower Bath tub Kitchen sink
1Bed Suite
Lvg toilet 1407 1 1
Bedroom toilet 2 1 1
Deluxe Room 1408 2 1 1
Deluxe Room 1409 2 1 1
1Bed Suite BR Duplex 1311.1 2 1 1
Deluxe Room 1410 2 1
Deluxe Room 1411 1 1 1
Deluxe Room 1412 2 1 1
Deluxe Room 1413 2 1 1
Deluxe Room 1414 2 1 1
Deluxe Room 1415 2 1 1
1Bed Suite 1416 2 1 1
15th floor
1Bed Suite
Lvg toilet 1501 1
Bedroom toilet 2 1 1
Deluxe Room 1502 2 1 1
Deluxe Room 1503 2 1 1
1Bed Suite
Lvg toilet 1504 1 1
Bedroom toilet 2 1 1
Deluxe Room 1505 2 1 1
Deluxe Room 1506 2 1 1
1Bed Suite
Lvg toilet 1507 1 1
Bedroom toilet 2 1 1
Deluxe Room 1508 2 1 1
Deluxe Room 1509 2 1 1
1Bed Suite Living Duplex 1510 1
Deluxe Room 1511 2 1 1
Deluxe Room 1512 2 1
Deluxe Room 1513 1 1 1
Deluxe Room 1514 2 1 1
Deluxe Room 1515 2 1 1
Deluxe Room 1516 2 1 1
Deluxe Room 1517 2 1 1
1Bed Suite 1518 2 1 1
16th floor
1Bed Suite
Lvg toilet 1601 1
Bedroom toilet 2 1 1
1Bed Suite
Lvg toilet 1602 1 1
Bedroom toilet 2 1 1
Deluxe Room 1603 2 1 1
ϰ
HOT WATER CALCULATIONS HOTEL - BOILER SIZING
Type of Guest Room Room Tag W/B Shower Bath tub Kitchen sink
Deluxe Room 1604 2 1 1
Deluxe Room 1605 2 1 1
Deluxe Room 1606 2 1 1
1Bed Suite
Lvg toilet 1607 1 1
Bedroom toilet 2 1 1
Deluxe Room 1608 2 1 1
Deluxe Room 1609 2 1 1
1Bed Suite Br Duplex 1510.1 2 1 1
Deluxe Room 1610 2 1
Deluxe Room 1611 1 1 1
Deluxe Room 1612 2 1 1
Deluxe Room 1613 2 1 1
Deluxe Room 1614 2 1 1
Deluxe Room 1615 2 1 1
Deluxe Room 1616 2 1 1
19th floor
1Bed Suite
Lvg toilet 1901 1
Bedroom toilet 2 1 1
Presidental Suite
Bedroom-01 2 1 1
1902
Bedroom-02 2 1 1
Living area 1 1
Deluxe Room 1903 2 1 1
1Bed Suite 1904 2 1 1
20th floor
1Bed Suite
Lvg toilet 2001 1
Bedroom toilet 2 1 1
Deluxe Room 2002 2 1 1
Deluxe Room 2003 2 1 1
1Bed Suite
Lvg toilet 2004 1 1
Bedroom toilet 2 1 1
1Bed Suite Living duplex 2005 1
Deluxe Room 2006 2 1 1
1Bed Suite 2007 2 1 1
21st floor
1Bed Suite
Lvg toilet 2101 1
Bedroom toilet 2 1 1
Deluxe Room 2102 2 1 1
Deluxe Room 2103 2 1 1
ϱ
HOT WATER CALCULATIONS HOTEL - BOILER SIZING
Type of Guest Room Room Tag W/B Shower Bath tub Kitchen sink
1Bed Suite
Lvg toilet 2104 1 1
Bedroom toilet 2 1 1
1Bed Suite BR Duplex 2005.1 2 1 1
1Bed Suite 2105 2 1 1
22nd floor
1Bed Suite
Lvg toilet 2201 1
Bedroom toilet 2 1 1
1Bed Suite
Lvg toilet 2202 1 1
Bedroom toilet 2 1 1
Deluxe Room 2203 2 1 1
Deluxe Room 2204 2 1 1
1Bed Suite
Lvg toilet 2205 1
Bedroom toilet 2 1 1
1Bed Suite 2206 2 1 1
23rd floor
1Bed Suite
Lvg toilet 2301 1
Bedroom toilet 2 1 1
Deluxe Room 2302 2 1 1
Deluxe Room 2303 2 1 1
1Bed Suite
Lvg toilet 2304 1 1
Bedroom toilet 2 1 1
Deluxe Room 2305 2 1 1
1Bed Suite 2306 2 1 1
24th floor
1Bed Suite
Lvg toilet 2401 1
Bedroom toilet 2 1 1
1Bed Suite
Lvg toilet 2402 1
Bedroom toilet 2 1 1
Deluxe Room 2403 2 1 1
Deluxe Room 2404 2 1 1
Deluxe Room 2405 2 1 1
Deluxe Room 2406 2 1 1
1Bed Suite
Lvg toilet 2407 1 1
Bedroom toilet 2 1 1
Deluxe Room 2408 2 1 1
Deluxe Room 2409 2 1 1
ϲ
HOT WATER CALCULATIONS HOTEL - BOILER SIZING
Type of Guest Room Room Tag W/B Shower Bath tub Kitchen sink
1Bed suit BR duplex 2410 1
Deluxe Room 2411 2 1 1
Deluxe Room 2412 2 1
Deluxe Room 2413 1 1 1
Deluxe Room 2414 2 1 1
Deluxe Room 2415 2 1 1
Deluxe Room 2416 2 1 1
Deluxe Room 2417 2 1 1
1Bed Suite 2418 2 1 1
25th floor
1Bed Suite
Lvg toilet 2501 1
Bedroom toilet 2 1 1
1Bed Suite
Lvg toilet 2502 1
Bedroom toilet 2 1 1
Deluxe Room 2503 2 1 1
Deluxe Room 2504 2 1 1
Deluxe Room 2505 2 1 1
Deluxe Room 2506 2 1 1
1Bed Suite
Lvg toilet 2507 1 1
Bedroom toilet 2 1 1
Deluxe Room 2508 2 1 1
Deluxe Room 2509 2 1 1
1Bed Suite Living Duplex 2410.1 2 1 1
Deluxe Room 2510 2 1
Deluxe Room 2511 1 1 1
Deluxe Room 2512 2 1 1
Deluxe Room 2513 2 1 1
Deluxe Room 2514 2 1 1
Deluxe Room 2515 2 1 1
1Bed Suite 2516 2 1 1
26th floor
1Bed Suite
Lvg toilet 2601 1
Bedroom toilet 2 1 1
1Bed Suite
Lvg toilet 2602 1
Bedroom toilet 2 1 1
Deluxe Room 2603 2 1 1
Deluxe Room 2604 2 1 1
1Bed Suite
Lvg toilet 2605 1 1
Bedroom toilet 2 1 1
Deluxe Room 2606 2 1 1
ϳ
HOT WATER CALCULATIONS HOTEL - BOILER SIZING
Type of Guest Room Room Tag W/B Shower Bath tub Kitchen sink
Deluxe Room 2607 2 1 1
2 1 1
Royal Suite 2608 2 1 1
1 1
Deluxe Room 2609 2 1
Deluxe Room 2610 1 1 1
Deluxe Room 2611 2 1 1
Deluxe Room 2612 2 1 1
Deluxe Room 2613 2 1 1
Deluxe Room 2614 2 1 1
1Bed Suite 2615 2 1 1
27th floor
1Bed Suite
Lvg toilet 2701 1
Bedroom toilet 2 1 1
1Bed Suite
Lvg toilet 2702 1
Bedroom toilet 2 1 1
Deluxe Room 2703 2 1 1
Deluxe Room 2704 2 1 1
1Bed Suite
Lvg toilet 2705 1 1
Bedroom toilet 2 1 1
Deluxe Room 2706 2 1 1
Deluxe Room 2707 2 1 1
1Bed Suite
Lvg toilet 2708 1 1
Bedroom toilet 2 1 1
Deluxe Room 2709 2 1 1
Deluxe Room 2710 2 1
Deluxe Room 2711 1 1 1
Deluxe Room 2712 2 1 1
Deluxe Room 2713 2 1 1
Deluxe Room 2714 2 1 1
Deluxe Room 2715 2 1 1
1Bed Suite 2615 2 1 1
ϴ
TotalLoadforhotelguestroomsasperASHRAE
demandperfixture
Item No.offixtures Total
(L/Hr)
W/B 500 7.6 3,800.00
Shower 227 284 64,468.00
TotalCount
BathTub 213 76 16,188.00
KitchenSink 21 114 2,394.00
Possiblemaximumdemand(L/Hr) 86,850.00
TotalStorageTanks(L)[storagefactor0.8] 17,370.00
TotalTankscapcity(L)selectedaspersupplier 18,000.00
CapacityofeachTank(L) 3,000.00
Recoverytime(Hours) 2.00
TotalLoad M=18000/2=9000L,Cp=4.187kJ/kgͲK,DeltaT=40C,Efficiency=87.5%
Hotwaterload(Q=M.Cp.DeltaT)[kW] 478.51
Note1 Tankstobelocatedinlevel28plantroom
Note2 TheseTanksshallserveHotelbuildinglevel7uptolevel27Only
Note3 ReferappendixGforschematics
Appendix B
Commercial kitchen load calculations
TotalLoadforCommercialKitcheninB1
demandperfixture
Item No.offixtures Total
(L/Hr)
NumberofcalorifiersasperIFCdesign 2.00
Total
CapacityofeachTank(L)asperIFCdesign 3,500.00
Capcity
TotalTankscapcity(L)asperIFCdesign 7,000.00
TotalTankscapcity(L)selectedaspersupplier 8,000.00
Selected
TotalquantityofTanks 2.00
Tanks
CapacityofeachTank(L) 4,000.00
Recoverytime(Hours) 2.00
TotalLoad M=8000/2=4000L,Cp=4.187kJ/kgͲK,DeltaT=40C,Efficiency=87.5%
Hotwaterload(Q=M.Cp.DeltaT)[kW] 212.67
Note1 TankstobelocatedinBasement2
Note2 TheseTanksshallservecommercialkitchenonlyinB1
Note3 ReferappendixGforschematics
Appendix C
LTHW load calculations
TotalLoadforLTHWsystemaspersupplierflowrates
# FAHU/AHU HotwaterCoilflowLPS
1 FAHUͲHOTͲL06Ͳ01 0.47
2 FAHUͲHOTͲL17Ͳ01 0.24
3 FAHUͲHOTͲL28Ͳ01 0.52
4 FAHUͲHOTͲL05Ͳ01 0.48
5 FAHUͲHOTͲL05Ͳ02 0.48
6 FAHUͲHOTͲL23Ͳ01 1.41
7 FAHUͲHOTͲL23Ͳ02 0.42
8 FAHUͲHOTͲB02Ͳ01 0.33
9 FAHUͲHOTͲB02Ͳ02 0.99
10 FAHUͲHOTͲB02Ͳ03 0.27
11 FAHUͲHOTͲB01Ͳ01 0.19
12 FAHUͲHOTͲL01Ͳ01 0.72
13 FAHUͲHOTͲL05Ͳ01 0.27
14 FAHUͲHOTͲL05Ͳ02 0.59
15 FAHUͲHOTͲL18Ͳ01 0.59
16 FAHUͲHOTͲL28Ͳ02 0.14
17 FAHUͲHOTͲL28Ͳ03 0.37
18 AHUͲHOTͲB01Ͳ01 0.21
19 AHUͲHOTͲB01Ͳ02 0.21
20 AHUͲHOTͲL01Ͳ01 0.49
21 AHUͲHOTͲL01Ͳ02 0.73
22 AHUͲHOTͲL01Ͳ03 0.47
23 AHUͲHOTͲL01Ͳ04 0.47
24 AHUͲHOTͲL05Ͳ01 0.77
25 AHUͲHOTͲL06Ͳ01 0.39
26 AHUͲHOTͲL06Ͳ02 1.07
27 AHUͲHOTͲL06Ͳ03 0.05
28 AHUͲHOTͲL17Ͳ01 0.18
29 AHUͲHOTͲL28Ͳ01 0.49
30 AHUͲHOTͲL28Ͳ02 0.44
31 AHUͲRESͲL05Ͳ01 0.27
32 AHUͲRESͲL05Ͳ02 1.16
33 AHUͲRESͲL05Ͳ03 0.09
34 AHUͲRESͲL23Ͳ01 0.26
35 AHUͲRESͲL23Ͳ02 0.09
36 AHUͲRESͲL23Ͳ03 0.17
TotalFlowLPS 16.49
Diversity70% 0.70
TotalDiversifiedFlowLPS 11.54
M=10.92LPS,Cp=4.187kJ/kgͲK,DeltaT=20C
Hotwaterload(Q=M.Cp.DeltaT)[kW] 966.61
Note1 ReferappendixFforDaikinselectionsheets
Note2 ReferappendixGforschematics
Appendix D
Residential fixture unit’s count and load calculations
HOT WATER CALCULATIONS RESIDENTIAL - BOILER SIZING
1
HOT WATER CALCULATIONS RESIDENTIAL - BOILER SIZING
2
HOT WATER CALCULATIONS RESIDENTIAL - BOILER SIZING
3
Appendix E
Boiler Sizing
BoilerSizingcalculation
TotalHotwaterLoad
# Item
(kW)
1 ResidentialBuilding 324.33
2 HotelBuilding 478.51
3 CommercialKitchen 212.67
TotalLoadkW 1,015.51
SafetyFacoty(10%) 1,117.07
4 LTHWsystem 966.61
TotalHotwaterLoad(kW) 2,083.68
HOTEL
SPECIFIED AHU-HOT-B01-01 BASEMENT 01 RESIDENTIAL LV ROOM COOLING 0 1250 1250 PLUG FAN 150 1.5 400/3/50 23.1/16.0 13.0/11.0 0.48 5.5 14.5 35 18.2 16.06 13 24 1250 0.2 80 60 35 16.91 1
OFFERED AHU-HOT-B01-01 BASEMENT 01 RESIDENTIAL LV ROOM COOLING 0 1250 1250 PLUG FAN 150 1.5 400/3/50 23.1/16.0 12.5/11.7 0.46 5.5 14.5 27 17.2 16.2 12.5 24 1250 0.21 80 60 16 17.7 910X1180 2560 1180 1010 527 1
SPECIFIED AHU-HOT-B01-02 BASEMENT 01 HOTEL LV ROOM COOLING 0 1250 1250 PLUG FAN 150 1.5 400/3/50 23.1/16.0 13.0/11.0 0.48 5.5 14.5 35 18.2 16.06 13 24 1250 0.2 80 60 35 16.91 1
OFFERED AHU-HOT-B01-02 BASEMENT 01 HOTEL LV ROOM COOLING 0 1250 1250 PLUG FAN 150 1.5 400/3/50 23.1/16.0 12.5/11.7 0.46 5.5 14.5 27 17.2 16.2 12.5 24 1250 0.21 80 60 16 17.7 910X1180 2560 1180 1010 527 1
SPECIFIED AHU-HOT-L01-01 LEVEL 01 LG PRE-FUNCTION AREA 800 2200 3000 PLUG FAN 300 5.5 400/3/50 23.2/17.5 13.0/12.8 1.26 5.5 14.5 35 47.32 34.58 13 24 3000 0.48 80 60 35 40.59 1
OFFERED AHU-HOT-L01-01 LEVEL 01 LG PRE-FUNCTION AREA 800 2200 3000 PLUG FAN 300 7.5 400/3/50 23.2/17.5 13.0/12.8 1.25 5.5 14.5 33 47.4 37.4 13 24 3000 0.49 80 60 18 40.7 1280X1600 3150 1600 1510 927 1
SPECIFIED AHU-HOT-L01-02 LEVEL 01 LG BREAKOUT AREA 550 3800 4350 PLUG FAN 300 7.5 400/3/50 23.2/16.4 13.0/12.0 1.64 5.5 14.5 35 61.93 51.63 13 24 4350 0.7 80 60 35 58.86 1
OFFERED AHU-HOT-L01-02 LEVEL 01 LG BREAKOUT AREA 550 3800 4350 PLUG FAN 300 7.5 400/3/50 23.2/16.4 12.6/12.0 1.64 5.5 14.5 27 62 56.4 12.6 24 4350 0.73 80 60 13 61.2 1580X1730 3350 1730 1810 1196 1
SPECIFIED AHU-HOT-L01-03 LEVEL 01 LG BALLROOM-01 800 1900 2700 PLUG FAN 300 5.5 400/3/50 23.1/17.8 13.0/12.2 1.35 5.5 14.5 35 51.04 34.48 13 24 2700 0.44 80 60 35 36.53 1
OFFERED AHU-HOT-L01-03 LEVEL 01 LG BALLROOM-01 800 1900 2700 PLUG FAN 300 5.5 400/3/50 23.1/17.8 12.2/12.1 1.36 5.5 14.5 30 51.5 36 12.2 24 2700 0.47 80 60 15 39.3 1330X1410 3180 1410 1560 886 1
SPECIFIED AHU-HOT-L01-04 LEVEL 01 LG BALLROOM-02 800 1900 2700 PLUG FAN 300 5.5 400/3/50 23.1/17.8 13.0/12.2 1.35 5.5 14.5 35 51.04 34.48 13 24 2700 0.44 80 60 35 36.53 1
OFFERED AHU-HOT-L01-04 LEVEL 01 LG BALLROOM-02 800 1900 2700 PLUG FAN 300 5.5 400/3/50 23.1/17.8 12.2/12.1 1.36 5.5 14.5 30 51.5 36 12.2 24 2700 0.47 80 60 15 39.3 1330X1410 3180 1410 1560 886 1
SPECIFIED AHU-HOT-L05-01 LEVEL 05 ALL DAY DINING COOLING 0 4700 4700 PLUG FAN 500 7.5 400/3/50 24.0/18.6 13.0/12.8 2.48 5.5 14.5 35 93.29 63.45 13 24 4700 0.76 80 60 35 63.59 1
OFFERED AHU-HOT-L05-01 LEVEL 05 ALL DAY DINING COOLING 0 4700 4700 PLUG FAN 500 11 400/3/50 24.0/18.6 12.9/12.9 2.47 5.5 14.5 30 93.3 63.4 12.9 24 4700 0.77 80 60 15 64.4 1580X1840 3050 1840 1680 1281 1
SPECIFIED AHU-HOT-L06-01 LEVEL 06 LOW LEVELS HOTEL CORRIDOR COOLING 355 2000 2355 PLUG FAN 500 5.5 400/3/50 27.3/20.0 13.0/12.5 1.63 5.5 14.5 35 61.56 41.35 13 24 2355 0.38 80 60 35 31.86 1
OFFERED AHU-HOT-L06-01 LEVEL 06 LOW LEVELS HOTEL CORRIDOR COOLING 355 2000 2355 PLUG FAN 500 5.5 400/3/50 27.3/20.0 12.7/12.7 1.63 5.5 14.5 28 61.6 42.5 12.7 24 2355 0.39 80 60 11 32.8 1210X1400 3190 1400 1440 846 1
SPECIFIED AHU-HOT-L06-02 LEVEL 06 L02 HOTEL GRAND ENTRANCE 596 5604 6200 PLUG FAN 500 11 400/3/50 25.5/18.6 13.0/12.3 3.56 5.5 14.5 35 134.3 95.04 13 24 6200 1 80 60 35 83.89 1
OFFERED AHU-HOT-L06-02 LEVEL 06 L02 HOTEL GRAND ENTRANCE 596 5604 6200 PLUG FAN 500 15 400/3/50 25.5/18.6 12.3/12.3 3.55 5.5 14.5 32 134.3 100.7 12.3 24 6200 1.07 80 60 12 89.5 1710X2150 3860 2150 1940 1737 1
SPECIFIED AHU-HOT-L06-03 LEVEL 06 HOTEL FIRE FIGHTING LOBBY COOLING 0 320 320 PLUG FAN 350 1 400/3/50 23.7/14.2 13.0/9.7 0.11 5.5 14.5 35 4.25 4.18 13 24 320 0.05 80 60 35 4.33 1
OFFERED AHU-HOT-L06-03 LEVEL 06 HOTEL FIRE FIGHTING LOBBY COOLING 0 320 320 PLUG FAN 350 0.55 400/3/50 23.7/14.2 13.0/9.9 0.11 5.5 14.5 11 4.2 4.2 13 24 320 0.05 80 60 1 4.3 780X790 2250 790 880 325 1
SPECIFIED AHU-HOT-L17-01 LEVEL 17 LOW LEVELS HOTEL CORRIDOR COOLING 155 925 1080 PLUG FAN 500 2.2 400/3/50 27.2/19.8 13.0/12.5 0.73 5.5 14.5 35 27.66 18.76 13 24 1080 0.17 80 60 35 14.61 1
OFFERED AHU-HOT-L17-01 LEVEL 17 LOW LEVELS HOTEL CORRIDOR COOLING 155 925 1080 PLUG FAN 500 2.2 400/3/50 27.2/19.8 12.6/12.5 0.73 5.5 14.5 29 27.7 19.4 12.6 24 1080 0.18 80 60 11 15.2 900X1070 2870 1070 1130 530 1
SPECIFIED AHU-HOT-L28-01 LEVEL 28 HIGH LEVELS HOTEL CORRIDOR COOLING 448 2387 2835 PLUG FAN 500 5.5 400/3/50 25.1/19.3 13.0/12.6 1.81 5.5 14.5 35 68.07 41.08 13 24 2835 0.46 80 60 35 38.36 1
OFFERED AHU-HOT-L28-01 LEVEL 28 HIGH LEVELS HOTEL CORRIDOR COOLING 448 2387 2835 PLUG FAN 500 7.5 400/3/50 25.1/19.3 12.4/12.4 1.8 5.5 14.5 29 68.1 44.3 12.4 24 2835 0.49 80 60 17 40.6 1220x1600 3210 1600 1450 954 1
SPECIFIED AHU-HOT-L28-02 LEVEL 28 GYM COOLING 0 2600 2600 PLUG FAN 350 4 400/3/50 24.2/17.0 13.0/12.8 1.16 5.5 14.5 35 43.54 35.79 13 24 2600 0.42 80 60 35 35.18 1
OFFERED AHU-HOT-L28-02 LEVEL 28 GYM COOLING 0 2600 2600 PLUG FAN 350 5.5 400/3/50 24.2/17.0 12.5/12.2 1.1 5.5 14.5 34 41.6 37 12.5 24 2600 0.44 80 60 13 36.9 1330X1370 2710 1370 1430 809 1
RESIDENTIAL
SPECIFIED AHU-RES-L05-01 LEVEL 05 LOW LEVEL APARTMENT CORRIDOR COOLING 370 1299 1669 PLUG FAN 500 5.5 400/3/50 28.5/21.4 13.0/13.0 1.29 5.5 14.5 35 48.55 29.07 13 24 1669 0.27 80 60 35 22.58 1
OFFERED AHU-RES-L05-01 LEVEL 05 LOW LEVEL APARTMENT CORRIDOR COOLING 370 1299 1669 PLUG FAN 500 4 400/3/50 28.5/21.4 13.0/13.0 1.37 5.5 14.5 25 51.8 31.6 13 24 1669 0.27 80 60 10 22.7 970x1360 3010 1360 1200 697 1
SPECIFIED AHU-RES-L05-02 LEVEL 05 LEVEL 02 RESIDENTIAL LOBBY COOLING 565 6135 6700 PLUG FAN 500 11 400/3/50 24.1/18.2 13.0/12.4 3.55 5.5 14.5 35 133.87 91.78 13 24 6700 1.08 80 60 35 90.65 1
OFFERED AHU-RES-L05-02 LEVEL 05 LEVEL 02 RESIDENTIAL LOBBY COOLING 565 6135 6700 PLUG FAN 500 15 400/3/50 24.1/18.2 12.3/12.3 3.54 5.5 14.5 26 133.9 96.4 12.3 24 6700 1.16 80 60 14 96.7 1890x2070 4030 2070 2120 1838 1
SPECIFIED AHU-RES-L05-03 LEVEL 05 RESIDENTIAL FIRE FIGHTING LOBBY COOLING 0 480 480 PLUG FAN 200 1 400/3/50 23.0/16.9 13.0/12.2 0.21 5.5 14.5 35 7.78 5.91 13 24 480 0.08 80 60 35 6.49 1
OFFERED AHU-RES-L05-03 LEVEL 05 RESIDENTIAL FIRE FIGHTING LOBBY COOLING 0 480 480 PLUG FAN 200 0.75 400/3/50 23.0/16.9 12.0/12.0 0.21 5.5 14.5 12 7.8 6.5 12 24 480 0.09 80 60 2 7.1 780X850 2390 850 880 368 1
SPECIFIED AHU-RES-L23-01 LEVEL 23 HIGH LEVEL APARTMENT CORRIDOR COOLING 365 1250 1615 PLUG FAN 500 5.5 400/3/50 28.5/21.4 13.0/13.0 1.96 5.5 14.5 35 47.46 28.35 13 24 1615 0.26 0.28 60 35 21.85 1
OFFERED AHU-RES-L23-01 LEVEL 23 HIGH LEVEL APARTMENT CORRIDOR COOLING 365 1250 1615 PLUG FAN 500 4 400/3/50 28.5/21.4 13.0/13.0 1.33 5.5 14.5 28 50.1 30.6 13 24 1615 0.26 80 60 9 21.9 970x1330 3020 1330 1200 676 1
SPECIFIED AHU-RES-L23-02 LEVEL 23 RESIDENTIAL FIRE FIGHTING LOBBY COOLING 0 480 480 PLUG FAN 200 1 400/3/50 23.0/16.9 13.0/12.2 0.21 5.5 14.5 35 7.78 5.91 13 24 480 0.08 80 60 35 6.49 1
OFFERED AHU-RES-L23-02 LEVEL 23 RESIDENTIAL FIRE FIGHTING LOBBY COOLING 0 480 480 PLUG FAN 200 0.75 400/3/50 23.0/16.9 12.0/12.0 0.21 5.5 14.5 12 7.8 6.5 12 24 480 0.09 80 60 2 7.1 780X850 2390 850 880 368 1
SPECIFIED AHU-RES-L23-03 LEVEL 23 PENTHOUSE CORRIDOR COOLING 210 805 1015 PLUG FAN 500 2.2 400/3/50 28.6/22.0 13.0/13.0 0.89 5.5 14.5 35 33.58 19.38 13 24 1015 0.16 80 60 35 13.73 1
OFFERED AHU-RES-L23-03 LEVEL 23 PENTHOUSE CORRIDOR COOLING 210 805 1015 PLUG FAN 500 2.2 400/3/50 28.6/22.0 13.0/13.0 0.91 5.5 14.5 25 34.2 19.5 13 24 1015 0.17 80 60 8 13.8 900X1030 2890 1030 1130 521 1
Page 1 of 1
PROJECT:DORCHESTER HOTEL, ON PLOT NO 18, BUSINESS BAY DUBAI
DATE:06-02-20
HOTEL
SPECIFIED FAHU-HOT-B02-01 BASEMENT 02 HOTEL KITCHEN MAKE-UP AIR 2000 PLUG FAN 500 3 400/3/50 35.0/32.0 14.0/14.0 3.27 5.5 18.5 35 178.12 54.33 14 24 2000 0.29 80 60 35 24.6 1
OFFERED FAHU-HOT-B02-01 BASEMENT 02 HOTEL KITCHEN MAKE-UP AIR 2000 PLUG FAN 500 5.5 400/3/50 35.0/32.0 13.0/13.0 3.31 5.5 18.5 36 180.4 54.1 13 24 2000 0.33 80 60 16 27.2 1150X1300 2905 1300 1250 844 1
SPECIFIED FAHU-HOT-B02-02 BASEMENT 02 HOTEL KITCHEN MAKE-UP AIR 7100 PLUG FAN 500 11 400/3/50 35.0/32.0 14.0/14.0 10.88 5.5 18.5 35 592.24 180.66 14 24 7100 1.04 80 60 35 87.33 1
OFFERED FAHU-HOT-B02-02 BASEMENT 02 HOTEL KITCHEN MAKE-UP AIR 7100 PLUG FAN 500 18.5 400/3/50 35.0/32.0 14.6/14.0 11.33 5.5 18.5 34 617.7 179.1 14.6 24 7100 0.99 80 60 13 82.4 1890X2170 3535 2170 1990 2098 1
SPECIFIED FAHU-HOT-B02-03 BASEMENT 02 EMPLOYEE FACILITIES FRESH AIR 1515 PLUG FAN 300 2.2 400/3/50 35.0/32.0 13.0/13.0 2.57 5.5 18.5 35 139.79 43.06 13 24 1515 0.24 80 60 35 20.05 1
OFFERED FAHU-HOT-B02-03 BASEMENT 02 EMPLOYEE FACILITIES FRESH AIR 1515 PLUG FAN 300 3 400/3/50 35.0/32.0 12.0/12.0 2.59 5.5 18.5 35 141.4 43.8 12 24 1515 0.27 80 60 9 22.4 970X1270 2870 1270 1070 729 1
SPECIFIED FAHU-HOT-B01-01 BASEMENT 01 BOILER ROOM FRESH AIR 1450 PLUG FAN 300 2.2 400/3/50 35.0/32.0 16.0/15.6 2.25 5.5 18.5 35 122.68 35.66 16 24 1450 0.17 80 60 35 14.27 1
OFFERED FAHU-HOT-B01-01 BASEMENT 01 BOILER ROOM FRESH AIR 1450 PLUG FAN 300 3 400/3/50 35.0/32.0 15.2/14.7 2.25 5.5 18.5 31 122.7 35.6 15.2 24 1450 0.19 80 60 14 15.8 910X1320 2700 1320 1010 652 1
SPECIFIED FAHU-HOT-L01-01 LEVEL 01 BOILER ROOM FRESH AIR 4400 PLUG FAN 500 7.5 400/3/50 35.0/32.0 14.0/14.0 7.2 5.5 18.5 35 391.86 119.53 14 24 4400 0.65 80 60 35 54.12 1
OFFERED FAHU-HOT-L01-01 LEVEL 01 BOILER ROOM FRESH AIR 4400 PLUG FAN 500 11 400/3/50 35.0/32.0 13.0/13.0 7.28 5.5 18.5 29 396.9 119.1 13 24 4400 0.72 80 60 21 59.7 1580X1750 3270 1750 1680 1547 1
SPECIFIED FAHU-HOT-L05-01 LEVEL 05 HOTEL BANQUET KITCHEN MAKE-UP AIR 1500 PLUG FAN 500 3 400/3/50 35.0/32.0 13.0/13.0 2.54 5.5 18.5 35 138.48 42.64 13 24 1500 0.24 80 60 35 20.3 1
OFFERED FAHU-HOT-L05-01 LEVEL 05 HOTEL BANQUET KITCHEN MAKE-UP AIR 1500 PLUG FAN 500 4 400/3/50 35.0/32.0 12.0/12.0 2.57 5.5 18.5 35 140 43.4 12 24 1500 0.27 80 60 9 22.2 970X1260 2890 1260 1070 742 1
SPECIFIED FAHU-HOT-L05-02 LEVEL 05 ALL DAY DINING KITCHEN MAKE-UP AIR 3300 PLUG FAN 500 5.5 400/3/50 35.0/32.0 13.0/13.0 5.59 5.5 18.5 35 304.48 93.8 13 24 3300 0.53 80 60 35 44.65 1
OFFERED FAHU-HOT-L05-02 LEVEL 05 ALL DAY DINING KITCHEN MAKE-UP AIR 3300 PLUG FAN 500 7.5 400/3/50 35.0/32.0 12.0/12.0 5.65 5.5 18.5 34 307.9 95.4 12 24 3300 0.59 80 60 12 48.8 1450X1510 3195 1510 1550 1226 1
SPECIFIED FAHU-HOT-L18-01 LEVEL 18 BAR & SPECIALITY RESTURANT FRESH AIR 3300 PLUG FAN 500 5.5 400/3/50 35.0/32.0 13.0/13.0 5.59 5.5 18.5 35 304.48 93.8 13 24 3300 0.53 80 60 35 44.65 1
OFFERED FAHU-HOT-L18-01 LEVEL 18 BAR & SPECIALITY RESTURANT FRESH AIR 3300 PLUG FAN 500 7.5 400/3/50 35.0/32.0 12.0/12.0 5.65 5.5 18.5 34 307.9 95.4 12 24 3300 0.59 80 60 12 48.8 1450X1510 3195 1510 1550 1226 1
SPECIFIED FAHU-HOT-L28-02 LEVEL 28 SPA/GYM FRESH AIR 865 PLUG FAN 300 2.2 400/3/50 35.0/32.0 14.0/14.0 1.42 5.5 18.5 35 77.04 23.5 14 24 865 0.13 80 60 35 10.64 1
OFFERED FAHU-HOT-L28-02 LEVEL 28 SPA/GYM FRESH AIR 865 PLUG FAN 300 1.5 400/3/50 35.0/32.0 13.0/13.0 1.43 5.5 18.5 30 78 23.4 13 24 865 0.14 80 60 6 11.7 900X930 2665 930 1000 503 1
SPECIFIED FAHU-HOT-L28-03 LEVEL 28 POOL RESTURANT FRESH AIR 2100 PLUG FAN 500 4 400/3/50 35.0/32.0 13.0/13.0 3.56 5.5 18.5 35 193.76 59.69 13 24 2100 0.34 80 60 35 28.41 1
OFFERED FAHU-HOT-L28-03 LEVEL 28 POOL RESTURANT FRESH AIR 2100 PLUG FAN 500 5.5 400/3/50 35.0/32.0 12.0/12.0 3.59 5.5 18.5 35 195.8 60.7 12 24 2100 0.37 80 60 21 31.1 1150X1350 2940 1350 1250 888 1
Page 1 of 1
PROJECT:DORCHESTER HOTEL, ON PLOT NO 18, BUSINESS BAY DUBAI
DATE: 06-02-20
OFFERED FAHU-HOT-L06-01 LEVEL 06 HOTEL LOW LEVELS VENTILATION (R1-R7) 3022 PLUG FAN 500 7.5 400/3/50 2704 500 5.5 400/3/50 35.0/32.0 27.8/24.0 24.0/17.0 32.1/28.3 0.18 27.8/24.0 13.5/13.5 2.29 5.5 18.5 29 125.1 52.6 13.5 24 2704 0.47 80 60 15 39.2 1100x1900 4480 1900 2240 2121 1
SPECIFIED FAHU-HOT-L17-01 LEVEL 17 HOTEL LOW LEVELS VENTILATION (R8-R12) 1369 PLUG FAN 500 4 400/3/50 1131 500 2.2 400/3/50 35.0/32.0 28.1/24.3 24.0/17.0 32.9/29.4 28.1/24.3 14.9/14.9 0.96 5.5 18.5 15.63 52.23 22.65 12 24.04 1131 0.25 80 60 2.17 20.24 1
OFFERED FAHU-HOT-L17-01 LEVEL 17 HOTEL LOW LEVELS VENTILATION (R8-R12) 1369 PLUG FAN 500 4 400/3/50 1131 500 2.2 400/3/50 35.0/32.0 28.2/22.6 24.0/17.0 32.2/27.4 0.04 28.2/22.6 12.2/12.2 0.97 5.5 18.5 30 53 27 12.2 24 1131 0.24 80 60 20 19.9 850x1360 3995 1360 1740 1268 1
SPECIFIED FAHU-HOT-L28-01 LEVEL 28 HOTEL HIGH LEVEL VENTILATION 3367 PLUG FAN 500 11 400/3/50 2801 500 5.5 400/3/50 35.0/32.0 28.2/24.3 24.0/17.0 32.7/29.2 28.2/24.3 14.0/13.9 2.55 5.5 18.5 34.47 139.04 60.19 12 24 2801 0.6 80 60 32.86 49.61 1
OFFERED FAHU-HOT-L28-01 LEVEL 28 HOTEL HIGH LEVEL VENTILATION 3367 PLUG FAN 500 7.5 400/3/50 2801 500 5.5 400/3/50 35.0/32.0 28.3/24.7 24.0/17.0 32.1/28.3 0.18 28.3/24.7 13.5/13.5 2.79 5.5 18.5 30 152.3 60.9 13.5 24 2801 0.52 80 60 9 43.7 1170x1950 4555 1950 2140 2199 1
RESIDENTIAL
SPECIFIED FAHU-RES-L05-01 LEVEL 05 RESIDENTIAL LOW LEVELS VENTILATION 3134 PLUG FAN 500 7.5 400/3/50 1935 500 3 400/3/50 35.0/32.0 29.2/25.4 24.0/17.0 34.3/31.0 29.2/25.4 14.0/13.9 2.69 5.5 18.5 38.11 146.57 60.1 12 23.85 1935 0.55 80 60 6.58 45.59 1
OFFERED FAHU-RES-L05-01 LEVEL 05 RESIDENTIAL LOW LEVELS VENTILATION 3134 PLUG FAN 500 7.5 400/3/50 1935 500 4 400/3/50 35.0/32.0 29.1/25.9 24.0/17.0 33.6/29.9 0.18 29.1/25.9 13.5/13.5 2.91 5.5 18.5 28 158.8 60.4 13.5 24 1935 0.48 80 60 16 40.1 1110x1960 4390 1960 2080 2087 1
SPECIFIED FAHU-RES-L05-02 LEVEL 05 RESIDENTIAL LOW LEVELS VENTILATION 3134 PLUG FAN 500 7.5 400/3/50 1935 500 3 400/3/50 35.0/32.0 29.2/25.4 24.0/17.0 34.3/31.0 29.2/25.4 14.0/13.9 2.69 5.5 18.5 38.11 146.57 60.1 12 23.85 1935 0.55 80 60 6.58 45.59 1
OFFERED FAHU-RES-L05-02 LEVEL 05 RESIDENTIAL LOW LEVELS VENTILATION 3134 PLUG FAN 500 7.5 400/3/50 1935 500 4 400/3/50 35.0/32.0 29.3/26.2 24.0/17.0 33.3/29.5 0.18 29.3/26.2 13.5/13.5 3.02 5.5 18.5 30 164.5 60.9 13.5 24 1935 0.48 80 60 16 40.1 1110x1960 4390 1960 2080 2076 1
SPECIFIED FAHU-RES-L23-01 LEVEL 23 RESIDENTIAL HIGH LEVELS VENTILATION 8653 500 22 400/3/50 3891 500 5.5 400/3/50 35.0/32.0 30.8/27.4 24.0/17.0 34.4/31.4 30.8/27.4 14.0/14.0 9.09 5.5 18.5 38.9 495.55 183.79 12 24.07 3891 1.55 80 60 25.79 128.23 1
OFFERED FAHU-RES-L23-01 LEVEL 23 RESIDENTIAL HIGH LEVELS VENTILATION 8653 PLUG FAN 500 22 400/3/50 3891 500 7.5 400/3/50 35.0/32.0 30.5/27.6 24.0/17.0 34.0/30.2 0.37 30.5/27.6 13.0/13.0 9.99 5.5 18.5 36 544.9 185.3 13 24 3891 1.41 80 60 11 117.5 1790x2750 5275 2750 2900 4044 1
SPECIFIED FAHU-RES-L23-02 LEVEL 23 RESIDENTIAL PENTHOUSES VENTILATION 2686 PLUG FAN 500 7.5 400/3/50 1070 500 1.5 400/3/50 35.0/32.0 30.8/27.4 24.0/17.0 34.4/31.4 30.8/27.4 14.0/14.0 2.83 5.5 18.5 37.31 154.09 57.13 12 23.96 1070 2.83 80 60 5 39.46 1
OFFERED FAHU-RES-L23-02 LEVEL 23 RESIDENTIAL PENTHOUSES VENTILATION 2686 PLUG FAN 500 7.5 400/3/50 1070 500 1.5 400/3/50 35.0/32.0 30.9/28.2 24.0/17.0 34.3/30.5 0.18 30.9/28.2 13.5/13.5 3.18 5.5 18.5 33 173.2 57.2 13.5 24 1070 0.42 80 60 12 34.8 1040x1840 4060 1840 1940 1751 1
Page 1 of 1
Appendix G
Updated Schematics
FOR LOCAL AUTHORITY USE ONLY
55°C
55°C
GV GV
79°C 79°C
59°C 59°C
60°C
60°C
60°C
60°C
60°C
60°C
GV GV GV GV GV GV
79°C DRV
79°C DRV
79°C DRV
79°C DRV
79°C DRV
79°C
DRV
2 WAY 2 WAY 2 WAY 2 WAY 2 WAY 2 WAY
3000 Ltrs 3000 Ltrs 3000 Ltrs 3000 Ltrs 3000 Ltrs 3000 Ltrs
HW CALORIFER (HOTEL) HW CALORIFER (HOTEL) HW CALORIFER (HOTEL) HW CALORIFER (HOTEL) HW CALORIFER (HOTEL) HW CALORIFER (HOTEL)
KEY PLAN
QIB N
L A
FLOW DIRECTION
NOTES
60°C
60°C
60°C
55°C
55°C GV GV GV GV GV GV
600 Ltrs 600 Ltrs 2500 Ltrs 2500 Ltrs 2500 Ltrs 2500 Ltrs
HW CALORIFER (RESIDENTIAL) HW CALORIFER (RESIDENTIAL) HW CALORIFER (RESIDENTIAL) HW CALORIFER (RESIDENTIAL) HW CALORIFER (RESIDENTIAL) HW CALORIFER (RESIDENTIAL)
FAHU-HOT-L18-01
BAR & SPECIALITY RESTAURANT
FRESH AIR
0.534 L/s
FAHU-HOT-L17-01 AHU-HOT-L17-01
HOTEL LOW LEVELS VENTILATION LOW LEVELS HOTEL CORRIDOR
(R8 - R12) COOLING
0.218 L/s 0.175 L/s
MAIN CONSULTANT
AHU-HOT-L01-03 AHU-HOT-L01-01
BREWER SMITH BREWER GULF
FAHU-HOT-L01-01 AHU-HOT-L01-01 AHU-HOT-L01-02
LG MEETING ROOM / BALL ROOM LG PRE-FUNCTION AREA LG BREAKOUT AREA LG BALL ROOM - 01
0.437 L/s
LG BALL ROOM - 02
0.437 L/s
P.O.BOX 50667
FRESH AIR 0.485 L/s 0.704 L/s
0.647 L/s DUBAI, U.A.E.
T +971 4 2942042 F +971 4 2942101
EMAIL: INFO@BSBGULF.COM
RESIDENTIAL HOT WATER CIRCULATION
PUMP
(2 DUTY + 1 STAND BY)
MEP ENGINEER
HOTEL HOT WATER CIRCULATION PUMP
(2 DUTY + 1 STAND BY) CLARKE SAMADHIN ASSOCIATES
P.O.BOX 120223
DUBAI, U.A.E.
FAHU-HOT-B01-01 AHU-HOT-B01-01 AHU-HOT-B01-02 T +971 4 4342135 F +971 4 4342136
CHEMICAL DOSING BOILER ROOM FRESH AIR RESIDENTIAL LV ROOM COOLING HOTEL LV ROOM COOLING
SYSTEM
80°C 90°C 80°C 90°C 80°C 90°C
0.233 L/s 0.202 L/s 0.202 L/s EMAIL: INFO@CLARKESAMADHIN.COM
BFV BFV BFV BFV BFV BFV
DRV NRV NRV DRV DRV NRV NRV DRV DRV NRV NRV DRV
HOT WATER SYSTEM SUPPLIER
60°C 70°C 60°C 70°C 60°C 70°C
EMAIL: INFO@SOLOENERGYME.COM
BOILER 540kW BOILER 540kW BOILER 540kW BOILER 540kW
PROJECT
PROPOSED DEVELOPMENT ON
HWS HWR HWS HWR
PLOT 3466829
60°C 60°C
FAHU-HOT-B02-01 FAHU-HOT-B02-02 FAHU-HOT-B02-03
PLOT 18 DUBAI, UAE
HOTEL KITCHEN MAKE-UP AIR HOTEL KITCHEN MAKE-UP AIR EMPLOYEE FACILITIES FRESH AIR
0.294 L/s 1.044 L/s 0.2452 L/s
DRAWING TITLE
55°C
55°C
GV GV
DRV
79°C DRV
79°C
2 WAY 2 WAY
NRV NRV
59°C 59°C
4000 Ltrs
HW CALORIFER (HOTEL KITCHEN)
4000 Ltrs
HW CALORIFER (HOTEL KITCHEN) HOT WATER SYSTEM SCHEMATIC LAYOUT
Including:
)URP EDKDVDHHG#VRORHQHUJ\PHFRP
6HQW 0RQGD\)HEUXDU\30
7R %DKDD6KHKDGHK)XWXUH0HWUR//&
6XEMHFW 5(UHFRYHU\WLPH
'HDUEDKDD
5HJXODUSUDFWLFHIRUVL]LQJKRWZDWHUV\VWHPLVWZRKRXUVUHFRYHU\E\XVLQJ/3*V\VWHP
%DKD¶6DHHG
SoloEnergyEquipmentTradingLLC
2IILFH6,77RZHU'XEDL6LOLFRQ2DVLV
32%R['XEDL8QLWHG$UDE(PLUDWHV
7HO)D[
(PDLOEDKDVDHHG#VRORHQHUJ\PHFRP
Web:www.soloenergyme.com
ȱ
Pleaseȱdoȱnotȱprintȱthisȱemailȱunlessȱitȱisȱabsolutelyȱnecessary.
From:BahaaShehadehͲFutureMetroLLC<bahaa.shehadeh@futuremetro.ae>
Sent:Monday,February24,202002:20PM
To:Baha<baha.saeed@soloenergyme.com>
Subject:recoverytime
DearBahaa,
Couldyoupleaseadvisewhatistherequiredrecoverytimeforsizingthehotwatertanks(calorifiers)?
Thanks & Regards,
Bahaa Shehadeh| MEP – Engineering Coordinator
Tel: +971 4 3711 611 | Fax: +971 4 3711 666.
Prime Tower | Business Bay | P.O: 86189 | Dubai – UAE
bahaa.shehadeh@futuremetro.ae | www.futuremetro.ae
3ThinkGreenͲPleaseconsidertheenvironmentbeforeprintingthisemail!!!
1
%DKDD6KHKDGHK)XWXUH0HWUR//&
)URP 1L]DU<DVHUQL]DU\#IMWFRFRP!
6HQW 0RQGD\)HEUXDU\30
7R %DKDD6KHKDGHK)XWXUH0HWUR//&
&F NKDOHGPLVPDU#IMWFRFRP$KPDG6DODK)XWXUH0HWUR
6XEMHFW ):5HFRYHU\WLPH
DearEngr.Baha’a
Kindlynotethatthereisnospecificstandardfortherecoverytimeselection.
However;themostcommonpracticeistoselecttwohoursrecoverytime.
Generallyshortrecoverytimes(1hourorless)increasestheheatingsourcesizeandthusincreasesthefuelconsumption
andthepossibilityforshortcycling,whilelongrecoverytimes(4hoursormore)mayresultinlessheatingefficiencyand
fortheheatingsourcetobenotabletoheatupthesysteminthepeaktimes,Thusmeanrecoverytime(twohours)isan
intermediatesolutionbetweentheshortrecoverytimeandthelongrecoverytimewhichtendstobethebestsolution.
ThanksandRegards,
NIZARYASERHAMED Tel: +97148105105 FJEnergySolutionsLLC
Fax: +97148105106
SalesManager AMemberofFJGroup
Direct: +97148105192
PackagedBoilerSystems
+971551233778
DubaiInvestmentParkͲ1
Mob:
nizar.y@fjtco.com P.O.Box:1871,DubaiͲUAE
www.fjtco.com
OurCoreValues
Character:Wearerespectful,honest,positiveandfairtoallstakeholders.
ContinuousImprovement:Weembraceacultureofcontinuouslyimprovingourproducts,ourprocessesandourselves.
Partnership:Westrivetoachieveourcommongoalsthroughinterdependencyandcollaboration.
Commitment:Wetakeownershipofachievingourmissiontothecompletesatisfactionofallourstakeholders.
Disclaimer:Thismessage(includinganyattachments)isconfidentialandmaybeprivileged.IfyouhavereceiveditbymistakepleasenotifythesenderbyreturneͲmailanddeletethismessage
fromyoursystem.Anyunauthorizeduseordisseminationofthismessageinwholeorinpartisstrictlyprohibited.PleasenotethateͲmailsaresusceptibletochange.FaisalJassimTradingCo.
LLCincludingitsgroupcompaniesshallnotbeliablefortheimproperorincompletetransmissionoftheinformationcontainedinthiscommunicationnorforanydelayinitsreceiptordamage
toyoursystem.FaisalJassimTradingCo.LLC(oritsgroupcompanies)doesnotguaranteethattheintegrityofthiscommunicationhasbeenmaintainednorthatthiscommunicationisfreeof
viruses,interceptionsorinterference.
From:BahaaShehadehͲFutureMetroLLC<bahaa.shehadeh@futuremetro.ae>
Sent:Monday,24February,20202:20PM
To:nizar.y@fjtco.com
Subject:Recoverytime
DearNizar,
Couldyoupleaseadvisewhatistherequiredrecoverytimeforsizingthehotwatertanks(calorifiers)?
Thanks & Regards,
Bahaa Shehadeh| MEP – Engineering Coordinator
Tel: +971 4 3711 611 | Fax: +971 4 3711 666.
Prime Tower | Business Bay | P.O: 86189 | Dubai – UAE
bahaa.shehadeh@futuremetro.ae | www.futuremetro.ae
1
Appendix I
Boilers data sheets
Technical description
Technical data
TRIGON XL
300 400 500 570
Nominal heat output at 80/60ºC max/min kW 285,7/56,5 381,3/75,2 476,7/94,6 540,2/120,0
Nominal heat output at 40/30ºC max/min kW 303,3/64,2 404,3/85,6 505,2/106,9 572,8/135,1
Nominal heat input Hi max/min kW 291,0/58,2 388,0/77,6 485,0/97,0 550,0/122,2
Efficiency at 80/60ºC % 98,2 98,3 98,3 98,2
Efficiency at 40/30ºC % 104,2 104,2 104,2 104,2
RAL 40/30 average % 110,4 110,4 110,4 110,3
Max. condensate flow l/h 18,5 24,7 30,7 34,8
Gas consumption G20 max/min (10,9 kWh/m 3) m3/h 26,7/5,3 35,6/7,1 44,5/8,9 50,5/11,2
Gas consumption G25 max/min (8,34 kWh/m 3) m3/h 34,9/7,0 46,5/9,3 58,2/11,6 65,9/14,7
Gas consumption G31 max/min (12,8 kWh/kg) kg/h 22,7/4,5 30,3/6,1 37,9/7,6 43,0/9,5
Gas pressure G20 mbar 20
Gas pressure G25 mbar 25
Gas pressure G31 mbar 30/50
Maximum gas pressure mbar 50
Max. temperature flue gas (high limit) °C 90
Flue gas temperature at 80/60ºC max/min ºC 75/58 75/59 75/59 76/58
Flue gas temperature at 40/30ºC max/min ºC 55/30 56/30 56/30 56/30
Flue gas quantity max/min m3/h 377/77 502/102 628/128 712/161
CO2 level G20-G25 max/min % 10,2/9,4 ± 0,2 (Limitation type 570 delta max/min !0,8)
CO2 level G31 max/min % 11,9/10,0 ± 0,2
NOx level at 80/60 °C max/min mg/kWh 36/18 34/17 37/18 40/19
CO level at 80/60 °C max/min mg/kWh 14/5 14/8 16/5 18/1
Max. permissible flue resistance max/min Pa 160/10 400/10 300/10 400/10
Water volume l 60 63 71 77
Water pressure max/min bar 8/1
Max. water temperature (High limit thermostat) ºC 100
Maximum temperature setpoint ºC 90
Nominal water flow at dT=20K m3/h 12,2 16,3 20,3 23,1
Hydraulic resistance at nominal flow rate kPa 11,9 32,3 34,3 57,1
Electrical connection V 230/400
Frequency Hz 50
Mains connection fuse A 16
IP class - IP20
Electrical consumption boiler max/min (without pump) W 230/50 504/54 620/64 676/61
Electrical consumption speed controlled pump W 310/12 470/25 590/25 800/38
Weight (empty) kg 434 496 540 595
Sound Power Level (LWA) dB 70,3 77,3 77,3 77,3
Ionisation current max/min µA 10,0/4,5
PH value condensate - 3,2
CE certification code - CE - 0063CQ3970
Water connections - DN65 PN16 DN65 PN16 DN65 PN16 DN65 PN16
Gas connection - R1.1/2" R1.1/2" R2" R2"
Flue gas connection (DN) mm 200 250 250 250
Air intake connect. (room sealed use) (DN) mm 130 130 150 150
Condensate connection mm 32 32 32 32
6
Appendix J
ASHRAE reference
Service Water Heating 49.19
Table 10 Hot Water Demand per Fixture for Various Types of Buildings
(Litres of water per hour per fixture, calculated at a final temperature of 60°C)
Apartment Industrial Office Private
House Club Gymnasium Hospital Hotel Plant Building Residence School YMCA
1. Basin, private lavatory 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6 7.6
2. Basin, public lavatory 15 23 30 23 30 45.5 23 — 57 30
3. Bathtubc 76 76 114 76 76 — — 76 — 114
4. Dishwashera 57 190-570 — 190-570 190-760 76-380 — 57 76-380 76-380
5. Foot basin 11 11 46 11 11 46 — 11 11 46
6. Kitchen sink 38 76 — 76 114 76 76 38 76 76
7. Laundry, stationary tub 76 106 — 106 106 — — 76 — 106
8. Pantry sink 19 38 — 38 38 — 38 19 38 38
9. Shower 114 568 850 284 284 850 114 114 850 850
10. Service sink 76 76 — 76 114 76 76 57 76 76
11. Hydrotherapeutic shower 1520
12. Hubbard bath 2270
13. Leg bath 380
14. Arm bath 130
15. Sitz bath 114
16. Continuous-flow bath 625
17. Circular wash sink 76 76 114 76 114
18. Semicircular wash sink 38 38 57 38 57
19. DEMAND FACTOR 0.30 0.30 0.40 0.25 0.25 0.40 0.30 0.30 0.40 0.40
20. STORAGE CAPACITY FACTORb 1.25 0.90 1.00 0.60 0.80 1.00 2.00 0.70 1.00 1.00
Note: Data sources predate low-flow fixtures and appliances. bRatio of storage tank capacity to probable maximum demand/h. Storage capacity may be reduced
aDishwasher requirements should be taken from this table or from where unlimited supply of steam is available from central street steam system or large boiler plant.
manufacturers’ data for model to be used, if known. cWhirlpool baths require specific consideration based on capacity. They are not included in the bath-
tub category.
Probable maximum demand = 9576 u 0.30 = 2870 L/h addition, an ample supply of general-purpose hot water, usually 60
Heater or coil capacity = 2870/3600 = 0.80 L/s to 65°C, is required for the wash cycle of dishwashers. Although a
Storage tank capacity = 2870 u 1.25 = 3590 L/s water temperature of 60°C is reasonable for dish washing in private
Showers. In many housing installations such as motels, hotels, dwellings, in public places, the NSF (e.g., Standard 3) or local
and dormitories, peak hot-water load is usually from shower use. health departments require 82 to 90°C water in the rinsing cycle.
Table 10 indicates the probable hourly hot-water demand and rec- However, the NSF allows a lower temperature when certain types of
ommended demand and storage capacity factors for various types of machines and chemicals are used. The two-temperature hot-water
buildings. Hotels could have a 3 to 4 h peak shower load. Motels requirements of food service establishments present special
require similar volumes of hot water, but peak demand may last for problems. The lower-temperature water is distributed for general
only a 2 h period. In some types of housing, such as barracks, fra- use, but the 82°C water should be confined to the equipment requir-
ternity houses, and dormitories, all occupants may take showers ing it and should be obtained by boosting the temperature. It would
within a very short period. In this case, it is best to find the peak load be dangerous to distribute 82°C water for general use. ANSI/NSF
by determining the number of shower heads and rate of flow per Standard 3-2001 covers the design of dishwashers and water heaters
head; then estimate the length of time the shower will be on. It is used by restaurants. The American Gas Association’s (Dunn et al.
estimated that the average shower time per individual is 7.5 min 1959) recommended procedure for sizing water heaters for restau-
(Meier 1985). rants consists of determining the following:
Flow rate from a shower head varies depending on type, size, • Types and sizes of dishwashers used (manufacturers’ data should be
and water pressure. At 280 kPa water pressure, available shower consulted to determine the initial fill requirements of the wash tanks)
heads have nominal flow rates of blended hot and cold water from • Required quantity of general-purpose hot water
about 160 to 380 mL/s. In multiple-shower installations, flow con- • Duration of peak hot-water demand period
trol valves on shower heads are recommended because they reduce • Inlet water temperature
flow rate and maintain it regardless of fluctuations in water pres-
• Type and capacity of existing water-heating system
sure. Flow can usually be reduced to 50% of the manufacturer’s
• Type of water heating system desired
maximum flow rating without adversely affecting the spray pattern
of the shower head. Flow control valves are commonly available After the quantity of hot water withdrawn from the storage tank
with capacities from 95 to 250 mL/s. each hour has been taken into account, the following equation may
If the manufacturer’s flow rate for a shower head is not available be used to size the required heater(s). The general-purpose and 82 to
and no flow control valve is used, the following average flow rates 90°C water requirements are determined from Tables 11 and 12.
may serve as a guide for sizing the water heater:
Small shower head 160 mL/s qi = Qh cp U ' t e K (14)
Medium shower head 280 mL/s
Large shower head 380 mL/s where
qi = heater input, W
Note that the maximum flow rate allowed by U.S. federal energy Qh = flow rate, mL/s
efficiency standards is 160 mL/s, as of 1992. However, higher-flow- cp = specific heat of water = 4.1868 kJ/(kg·K)
rate models are still sold. U = density of water = 1.0 kg/L
Food Service. In restaurants, bacteria are usually killed by rins- 't = temperature rise, K
ing washed dishes with 82 to 90°C water for several seconds. In K = heater efficiency
49.14 2007 ASHRAE Handbook—HVAC Applications (SI)
Requirements for high schools are based on daytime use. Recom- Table 8 Hot-Water Demand and Use Guidelines for
mendations do not take into account hot-water use for additional Apartment Buildings
activities such as night school. In such cases, the maximum hourly (Litres per Person at 49°C Delivered to Fixtures)
demand remains the same, but the maximum and average daily use
increase, usually by the number of additional people using showers Peak Minutes
Maximum Average
and, to a lesser extent, eating and washing facilities. Guideline 5 15 30 60 120 180 Daily Daily
Additional Data. Low 1.5 3.8 6.4 10.6 17.0 23.1 76 53
Fast Food Restaurants. Hot water is used for food preparation, Medium 2.6 6.4 11.0 18.2 30.3 41.6 185 114
cleanup, and rest rooms. Dish washing is usually not a significant High 4.5 11.4 19.3 32.2 54.9 71.9 340 204
load. In most facilities, peak usage occurs during the cleanup
period, typically soon after opening and immediately before clos- Fig. 15 Apartment Building Cumulative Hot-Water Use Ver-
ing. Hot-water consumption varies significantly among individual sus Time (from Table 8)
facilities. Fast food restaurants typically consume 1000 to 2000 L
per day (EPRI 1994).
Supermarkets. The trend in supermarket design is to incorporate
food preparation and food service functions, substantially increas-
ing the usage of hot water. Peak usage is usually associated with
cleanup periods, often at night, with a total consumption of 1100 to
3800 L per day (EPRI 1994).
Apartments. Table 8 shows cumulative hot-water use over time for
apartment buildings, taken from a series of field tests by Becker et al.
(1991), Goldner (1994a, 1994b), Goldner and Price (1999), and
Thrasher and DeWerth (1994). These data include use diversity infor-
mation, and enable use of modern water-heating equipment sizing
methods for this building type, making it easy to understand the vari-
ety of heating rate and storage volume combinations that can serve a
given load profile (see Example 1). Unlike Table 7, Table 8 presents Fig. 15 Apartment Building Cumulative Hot-Water Use
low/medium/high (LMH) guidelines rather than specific singular vol- Versus Time (from Table 8)
umes, and gives better time resolution of peak hot-water use informa-
tion. The same information is shown graphically in Figure 15. The medium-use peak hot-water consumption profile represents
The low-use peak hot-water consumption profile represents the the overall average highest peak profile seen in the tests, and is gen-
lowest peak profile seen in the tests, and is generally associated with erally associated with apartment buildings having mostly a mix of
apartment buildings having mostly a mix of the following occupant the following occupant demographics:
demographics:
• Families
• All occupants working
• Singles
• One person working, while one stays at home
• On public assistance
• Seniors
• Single-parent households
• Couples
• Middle income The high-use peak hot-water consumption profile represents the
• Higher population density highest peak profile seen in the tests, and is generally associated
$SSHQGL[.
/3*5),UHVSRQVH