4100 Fire Alarm: Programming Unit Version 9 Supplement
4100 Fire Alarm: Programming Unit Version 9 Supplement
Programming Unit
Version 9 Supplement
579-127
Rev. A
1-1
THIS PAGE IS BLANK.
1-2
Copyrights and Trademarks
Copyrights Copyright Simplex Time Recorder Co., 2000. All rights reserved. Printed in
the United States of America.
Copyright 2000 Simplex International Time Equipment Co., Ltd.,
Mississauga, Ontario L4V 1H3 Canada.
All specifications and other information shown were current as of publication,
and are subject to change without notice. No part of this document may be
reproduced or transmitted in any form or by any means, electronic or
mechanical, for any purpose, without the express written consent of Simplex
Time Recorder Company.
The suffix “C” following an eight-digit Product ID number denotes a ULC-
listed product.
1-3
BLANK
This page is blank
1-4
Cautions and Warnings
1-5
Cautions and Warnings, Continued
Explanation of Symbols The following symbols are used in this publication to alert you to unusual and
possibly hazardous conditions.
WARNING - When you see this symbol, it indicates a potential danger that
requires correct procedures or practices in order to prevent personal injury.
1-6
Contents
List of Figures................................................................................................. ix
List of Tables ................................................................................................... x
How to Use this Publication ........................................................................... xi
Conventions Used ....................................................................................... xi
Keyboard Conventions................................................................................ xi
Convention Summary ................................................................................ xii
About this Document .................................................................................... xiii
Introduction............................................................................................... xiii
About the Appendices............................................................................... xiii
Related Documents ................................................................................... xiii
vii
4100/4020 Programming .............................................................................. 3-4
Step 1: Specifying One or More TrueAlert Addressable Controllers ....... 3-4
Step 2: Defining TrueAlert Appliances..................................................... 3-8
Step 3: Setting Class A and LED Options ............................................. 3-11
Step 4: Saving the Job............................................................................. 3-11
Step 5: Checking Default Virtual NACs................................................ 3-12
Step 6: Creating Custom Virtual NACs .................................................. 3-14
Editing the Configuration........................................................................ 3-16
What’s Next? .......................................................................................... 3-17
viii
Figures
ix
Tables
x
How to Use this Publication
Conventions Used Before you start using the 4100 Fire Alarm Programming Unit Version 9
Supplement, it's important to understand the conventions used in this
publication.
The following conventions are used in this publication to identify special names
or text.
• Italic type indicates important terms or publication titles, such as the 4100
Fire Alarm Programming Unit Version 9 Supplement, it's important to
understand the conventions used in this publication.
• Text enclosed in quotation marks indicates the title of a chapter or section
of the manual, such as “How to Use this Publication.”
• Bulleted lists, such as this one, provide you with information. They are also
used to indicate alternatives in numbered procedural steps.
• Numbered lists indicate procedures with steps that you must carry out
sequentially.
Keyboard Conventions The following conventions are used to describe keys and key combinations.
• Key names appear in bold type and in capital letters and are referred to by
their names only, without the word “key.” For example, “press SHIFT”
means press the keyboard key labeled "Shift."
• A plus sign (+) between two key names means that you hold down the first
key while pressing the second key. For example, “press SHIFT+F1”
means hold down the SHIFT key while pressing the F1 key. If the key
sequence includes three or more key names, hold down all of the keys
except for the last one, and then press and release the last key. For
example, “press CTRL+ALT+DEL” means hold down the CTRL and ALT
keys, and then press the DEL key.
• A comma between key names means that you press and release the first
key, and than press and release the second key, and so on. For example,
“press ALT, F, P” means press ALT and release it, press F and release it,
and press P and release it.
• Arrow keys is the collective name for the UP ARROW, DOWN ARROW,
LEFT ARROW, and RIGHT ARROW keys.
xi
How to Use this Publication, Continued
Convention Summary The document conventions are summarized in the following table.
Document Conventions
xii
About this Document
Introduction This publication has been created as an addendum to the following publications
to document the operation of the special features specific to Version 9 of the
4100 Programming Unit (hereafter referred to as the 4100 Programmer).
xiii
BLANK PAGE
xiv
Chapter 1
Version 9 Overview
In this Chapter This chapter discusses the topics listed in the following table. Refer to the page
number listed after the topic for information on that topic.
1-1
Version 9 System Description
Compatability with 4100/4020 To use TrueAlert functionality, Version 9 (or higher) of the 4100/4020 firmware
Version 8 Firmware is required. In addition, the 4100/4020 requires the use of a TrueAlert
Addressable Controller connected to the 4100 (via an RUI card).
The Version 9 firmware maintains compatability with all systems that are
curently compatable with Version 8.01 (or higher) of the 4100/4020 FACP.
Version 9 of the 4100/4020 requires no changes to other systems, and will
operate alongside other 4100s or 4020s on a 4120 Network (i.e., panels on a
network not using TrueAlert do not have to be upgraded if they are already at
Version 8.0X). Although TrueAlert appliances do not report over the 4120
Network, Virtual NACs can report to the network as signal circuits.
TrueAlert Controller The TrueAlert appliances are interfaced to the 4100/4020 FACP through the use
of the TrueAlert Addressable Controller. The TrueAlert Addressable Controller
is an intelligent external slave device that uses an RUI interface and consumes
one card address.
1-2
Version 9 System Description, Continued
Virtual NACs A Virtual NAC (or VNAC) is a collection of TrueAlert appliances grouped
together to allow control functions. Each 4100/4020 system can support up to 64
Virtual NACs (8 default VNACs plus 56 user-defined VNACs). A VNAC can
be made up of TrueAlert appliances from any or all of the TrueAlert Controller
channels. (A VNAC may cross channel or controller boundaries.)
The 4100/4020 supports custom labels for VNACs, and treats VNACs as
notification appliance circuits that can be controlled as system points. An
example of this might be a high rise, where every floor wires a single A/V unit
in the stairwell. All of the stairwell A/Vs could belong to a single VNAC,
although they are distributed across many TrueAlert channels.
Figure 1-1 shows a graphical representation of VNACs. Any appliance may be
assigned to up to three VNACs (in addition to the default VNACs). A TrueAlert
channel can then control the VNACs via VNAC addressing. This means that it
can tell all the appliances in a VNAC to turn on or off with a single command
that is VNAC-addressed. An appliance maintains internal status for each of its
VNACs. With the exception of the default groups, the appliance will be on
whenever any of its member points are on.
FACP Channel 1
TrueAlert
To/From TrueAlert
Slave
4100/4020 Addressable
Card Channel 2
FACP Controller
Channel 3
VNAC 116
Group VNAC 125
Group VNAC
Group13
7
1-3
Version 9 System Description, Continued
LED/Switch Modes TrueAlert appliances cannot be used as a reference for LED or Switch modes.
Only VNACs may be programmed as a reference address to a LED/Switch
mode. The following table shows the supported modes:
1-4
Chapter 2
Installing the 4100 Programmer
In this Chapter This chapter discusses the topics listed in the following table. Refer to the page
number listed after the topic for information on that topic.
2-1
About the Programming Unit Disk Set
Disk Set Contents The 4100 Version 9 Service Tools (553-856) consists of the following
floppy disks:
• The 4100 Programming Unit disk set (553-855) contains three 3.5 inch
floppy disks at Version 9.01 (or later). Disks 1 through 3 contain the files
necessary to do the following:
− Run the program
− Generate various screens used by the Programming Unit
− Provide Audio and Custom Control Editor functionality
− Create a job file that can be downloaded to the FACP
• The UT Master Exec Disk (553-852)
• The 4020 Master Exec Disk (553-853)
• The Database Comparison Disk (553-859)
2-2
Programmer Operating Environment
Hardware Requirements The 4100 Programming Unit (hereafter referred to as ‘the Programmer’) has the
following hardware requirements:
• IBM compatible PC with 486DX-66 processor or better
(Pentium recommended).
• 8 MB RAM MINIMUM for Windows 95 (16 MB RAM is recommended).
• 16 MB RAM MINIMUM for Windows NT (32 MB RAM
is recommended).
• One 3 ½” floppy drive for program installation and job archives,
or backups.
• One serial port & cable for communication with the 4100.
• One parallel port for the Security Key.
• One Security Key.
Security Key The Security Key controls user access to the Programmer and is checked during
Programmer startup. When you start the Programmer, the software looks for a
Security Key on the PC parallel port before the main window for the
Programmer is displayed. If the correct key is not detected, a message box is
presented to you noting that there is either a missing or incorrect key. Then the
Programmer terminates execution with no further action.
Operating System The Programmer installs and runs under either the Microsoft Windows 95 or the
Requirements Microsoft Windows NT operating system.
Simplex Programmer When the Programmer is installed, the software creates the Simplex group in the
Location Start (Programs) area. There is an entry added within the Simplex group labeled
4100 Programmer 9.0X (where ‘0X’ refers to the software revision). If the
Simplex group already exists (from installation of other Simplex windows
programs such as the 4120 Programmer or 4120 Network Programmer), the
Programmer entry is added to this existing group.
2-3
Installing the Programmer
Introduction The 4100 Programmer has a built-in installation procedure which permits you to
easily load the Programmer software onto your computer's hard drive (default is
Drive C). This procedure is described in the following paragraphs.
Installing the Programmer The 4100 Programmer is a Microsoft DOS-based application that uses the
Software from Floppies InstallShield installation wizard. Use the following procedure to install the
Programmer software:
1. Place Disk 1 (the System Disk) into Drive A.
2. Click the Start button and select Run from the Start menu.
Enter a:\install.exe in the Open window of the Run dialog.
(See Figure 2-1.)
2-4
Launching the Programmer
Entry Points The Programmer can be launched (started) directly from the Simplex program
group like any other Windows application.
Normal Startup Procedure Use the following procedure to start the Programmer:
1. Using the Windows 95 or Windows NT Start button, select Programs.
2. Select Simplex; then select 4100 Programmer.
How to Exit the Programmer The File - Exit menu selection exits the Programmer. If the currently-loaded
job has not been saved, you will first be prompted to either save the job or exit
and lose any changes.
2-5
BLANK PAGE
2-6
Chapter 3
4100/4020 Programming
3-1
Custom Control Programming
Programming Guidelines for a Although Custom Control may be used to further configure your system, you
Standalone System should observe the following guidelines:
• TrueAlert Appliances cannot be directly controlled via Custom Control.
− VNACs must be created to control TrueAlert Appliances.
• Coding output qualifiers such as TEMPORAL or MARCH TIME are not
allowed with VNACs.
− There is no error checking for illegal qualifiers.
• Multiple VNACs are allowed in user lists for global control of
associated appliances.
• Only use HOLD, SET, or TRACK when referencing signal coding. If
you try to use Custom Control to configure signal codes, such as
Temporal or March Time, you will not receive an error message, but
your custom codes will be ignored in favor of the signal codes that are
programmed in the 4100 Programer TrueAlert Data Card Entry screen.
• Default VNACs 2 and 4 should be changed to the SIGNAL point type
for any custom control selective programming. Point types SSIGNAL
and RSIGNAL will default to general alarm.
• If conventional signal cards are added to or deleted from the 4100 host
panel, the VNAC point numbers will change. Be sure to update custom
control equations to reflect changed point numbers.
3-2
Virtual NACs
4100/4020 Support Capacity The 4100/4020 can support up to 64 VNACs (8 default VNACs and 56 user-
defined VNACs). In addition, the 4100/4020 supports custom labels for
VNACs, and treats VNACs as notification points that can be controlled as system
entities. An example of this might be a high rise, where every floor has a single
A/V unit in the stairwell. All of the stairwell A/Vs could belong to a single
VNAC, although they would be distributed across many TrueAlert channels. It
is therefore incumbent on the panel to keep track of which channels are part of
the VNAC.
A graphical representation of a 4100/4020 VNAC grouping is shown in Figure 1-1
on Page 1-3.
Notes:
1. The VNAC “card” is automatically allocated when a new
job database is created. The VNAC “card” has the
constant card address of 175.
2. You can create up to 56 user-defined VNACs, in addition
to the 8 default VNACs shown in Table 3-1.
3. VNAC Point Name depends on job. (The Point Name
may be SIG9, SIG10, etc.)
4. Default operation for all TrueAlert appliances is General
Alarm, with all audibles OFF ON SIGNAL SILENCE and
all visuals OFF ON RESET through VNACs 2 and 4.
3-3
4100/4020 Programming
CARD ADDRESS
3-4
4100/4020 Programming, Continued
Step 1:
Specifying One or More 5. Press A to add a card to the list. The second Card Configuration screen
TrueAlert Addressable comes up, with categories of device types that you can add. The line of text
Controllers (Continued) below the selection box describes the selection, as shown in Figure 3-3.
6. Use the arrow keys to select the Interface option, and press ENTER. A list
of interface cards comes up.
Note: The 4020 FACP includes the RUI. Select the ‘(4009T) TrueAlert
Controller’ option, enter the quantity of TrueAlert Controllers, and
proceed to Step 10.
7. 4100 only: Use the arrow keys to select the ‘(0304) Remote Unit Interface
(RUI)’ card, press ENTER, and then type in the number of RUI cards you
want to add. Press ENTER again. You are now prompted for the unit
number. The default is L (for Local). If this is the first RUI card you are
adding, press ENTER and continue to Step 8.
3-5
4100/4020 Programming, Continued
Step 1: Note: If you are adding a remote RUI card, type a number to identify
Specifying One or More the unit at the “Enter Unit number:” prompt, and press ENTER.
TrueAlert Addressable Finally, at the “Enter Remote Unit Interface number:” prompt,
Controllers (Continued) type an appropriate number. If this is the first remote RUI card,
type 1. If it is the second remote RUI card, type 2, and so on.
Press ENTER.
8. Use the arrow keys to select the (4009T) TrueAlert Controller option, press
ENTER, and then type in the number of Addressable Controllers you want
to add.
9. Press ENTER once more. If you are programming a 4020, skip ahead to
Step 10. If you are programming a 4100, refer to Figure 3-5a. Type a
number for the ‘(4009T) TrueAlert Controller’ at the “Enter Unit number:”
prompt and press ENTER. Finally, at the “Enter Remote Unit Interface
number:” prompt, type the number that corresponds to the RUIx number in
the Range column of the Card Configuration Editor table (as shown in
Figure 3-5b). Press ENTER.
10. Press ESC+ESC to return to the first screen of the Card Configuration
Editor. (The 4100 version of this screen is shown in Figure 3-5b.)
Figure 3-5a
Figure 3-5b
3-6
4100/4020 Programming, Continued
Step 1: At this point, one ‘(4009T) TrueAlert Controller’ card should be listed for every
Specifying One or More TrueAlert Addressable Controller you intend to connect to the FACP. There can
TrueAlert Addressable be a maximum of three ‘(4009T) TrueAlert Controller’ cards per RUI. A 4100
Controllers (Continued) (with Rev. 9.01 or later firmware) and six TrueAlert Controller cards would be
configured as shown in Figure 3-6.
3-7
4100/4020 Programming, Continued
Step 2: Now it’s time to define each TrueAlert appliance that will connect to a given
Defining TrueAlert Appliances Addressable Controller. To do this, make sure the Card Configuration Editor
screen as shown in Figures 3-6 and 3-7 is already open (if it’s not, select
CONFIGURATION and then SYSTEM CARDS from the main screen). Then
follow the steps below.
1. Select the first applicable ‘(4009T) TrueAlert Controller’ entry, and press
ENTER. If you are configuring a 4020, skip ahead to Step 3.
2. 4100 only: The Remote Unit Configuration Menu comes up, as shown in
Figure 3-7. Select the “Configure” option, highlight the appropriate card
if multiple TrueAlert Controllers are listed, and then press ENTER.
3-8
4100/4020 Programming, Continued
Step 2: 3. The TrueAlert Card Data Entry screen comes up. Press F2 on the currently
Defining TrueAlert Appliances highlighted field (Dev Type) so that the screen looks like Figure 3-8.
(Continued)
3-9
4100/4020 Programming, Continued
Step 2: 6. Press ENTER again so that the first row of the Coding Type column is
Defining TrueAlert Appliances highlighted. The Coding Type refers to how the audible signal is coded. The
(Continued) visual signal defaults to standard, 60 pulses per minute.
• If the device type is a HORN or A/V, the default audible code is
TEMPORAL. Press F2 to see the entire list of available codes. Use the
arrow keys to select the desired audible code, and press ENTER. (See
Figure 3-10.)
• If the device type is STRB or ISO, the Coding Type is listed as
STANDARD and N/A, respectively, and cannot be changed.
7. Press ENTER so that the Dev Type for the second row is highlighted.
Repeat Steps 1-6 for every TrueAlert appliance.
8. Press ESC to exit this screen, unless:
• A Class A Adapter Card is being used
• You want TrueAlert appliance LEDs to blink when they are polled
In either of these two cases, continue to “Step 3: Setting Class A and LED
Options.” Otherwise, skip ahead to “Step 4: Saving the Job.”
3-10
4100/4020 Programming, Continued
Step 3: You can specify whether a Class A card will be used, or whether LEDs should
Setting Class A and blink when they are polled, at any time in the TrueAlert Card Data Entry screen.
LED Options
Use the following procedure to set the Class A and LED blink toggle options.
1. Press ALT+F6 to bring up the Toggle Options box as shown in Figure 3-11.
This box shows options that are global for all three SLCs.
Step 4: Whenever you exit a screen by pressing ESC, you are prompted as to
Saving the Job whether you want to save, quit, continue, or make a revision history entry,
as shown in Figure 3-12.
3-11
4100/4020 Programming, Continued
Step 5: The last step of the process is to check the default Virtual NACs and create new
Checking Default ones if necessary. Use the following procedure to open the Virtual NAC Data
Virtual NACs Entry screen.
1. Press ESC as many times as necessary to return to the System
Configuration Menu, and then highlight the VIRTUAL NACs item.
Press ENTER.
2. The VIRTUAL NAC DATA ENTRY screen appears (Figure 3-13).
Step 5: In Figure 3-13, Virtual NAC 1 uses circuit type A/V, and a SIGNAL point type.
Checking Default This means all TrueAlert appliances are members of that VNAC. (See Table 3-1
Virtual NACs (Continued) on Page 3-3.
If you press F9 to open the Tag List for that VNAC, a list is displayed, as shown
in Figure 3-14.
ARROWS DENOTE
TAGGED APPLIANCES
Figure 3-14 shows all of the appliances that are potential members of that
VNAC. Each appliance that has an arrow to the left of its address is tagged; that
is, it has been selected as a member of that Virtual NAC. In this default list, all
notification appliances are tagged (isolators are not tagged).
Note that since this is one of the eight default Virtual NACs, it is ‘read-only.’
The list can be sorted, however, by pressing D (to sort by address, in ascending
order) or T (to sort by device type).
A default Virtual NAC exists for every type of appliance, and more than one
device type usually occupies each Virtual NAC. The first VNAC shown in
Figure 3-13, for example, contains all appliance outputs. VNAC 2, meanwhile,
contains all audible appliances.
3-13
4100/4020 Programming, Continued
Step 6: You can create up to 56 of your own VNACs, and you can edit appliance
Creating Custom memberships for each one. The following instructions show you how to create them.
Virtual NACs
1. From the Virtual NAC Data Entry screen, press the down arrow key until you
reach VNAC 9 (or any empty row). Make sure the Ckt Type field is highlighted,
and press F2. The VNAC Circuit Types box appears, as shown in Figure 3-15.
3-14
4100/4020 Programming, Continued
ARROWS INDICATE
TAGGED APPLIANCES
VNAC NUMBERS
TO WHICH EACH
UNTAGGED APPLIANCE IS
APPLIANCES TAGGED
3-16
4100/4020 Programming, Continued
Editing the Configuration Type Y to keep your change. Type N to revert to the last setting. This message
(Continued) will repeat for every VNAC circuit type you change.
When you are done, you will want to check the VNACs to see how they were
affected, and re-associate the appropriate appliances with the changed VNACs.
What’s Next? When you are done programming the 4100 or 4020, refer to the programming
documentation to upload the job to the FACP.
3-17
BLANK
3-18
Appendix A
WalkTest Programming
Overview This appendix provides guidelines for programming the WalkTest procedures
for TrueAlert Appliances.
A-1
TrueAlert Appliance Walktest
Procedure Notes:
1. In order for the TrueAlert Appliance Walktest to work properly, only
one VNAC is allowed per Walktest group.
2. The TrueAlert strobes will not flash during this test.
The TrueAlert Addressable Controller will fully support the Non-Voice Simplex
Walktest. Use the following procedure to initiate the TrueAlert Walktest.
1. From the programmer edit the Walktest groups monitor list to create eight
groups (any combination) and enter in the table below.
A-2
Appendix B
Network Programming Guidelines
B-1
Version 8/Version 9 FACP Compatability
Compatability Guidelines Follow the recommendations below to ensure Version 8/Version 9 FACP
compatibility.
• Previously, when a node programmed at a higher version of software was
added to the network, all existing nodes on the network had to be upgraded
to the new version of software. With the release of Version 9.01 software,
it is now permissible to have an existing network at Version 8.01 (or higher)
co-exist with new panels programmed at Version 9.01.
• Building a 4120 Network when Version 8.0X and 9.01 co-exist requires
extreme caution. The 4120 Network Programmer can only be assigned to
load one version of the 4120 Programmer. The lowest version of the
Programmer should be the one that the 4120 Network Programmer initiates.
Thus, on a 4120 Network with co-existing panels, this would be whatever
version that the Version 8.0X FACP resides at. (For information on how to
load software, refer to Chapter 2.)
• “All Build” and “Build Changed” selections in the 4120 Network
Programmer with Version 9.01 of the 4100 Programmer must not be used.
• Panels at Version 9.01 must be individually built through Version 9.01 of
the 4100 Programmer.
B-2
TrueAlert Notes
TrueAlert Programming Notes Use the following notes when programming your TrueAlert Network jobs.
• TrueAlert appliances cannot be programmed as “PUBLIC” points in the
4120 Network Interface Data Entry screen.
• Status Troubles associated with TrueAlert appliances and the TrueAlert
Addressable Controller are reported over the panel’s “COMMON
TROUBLE” Pseudo.
• A VNAC group’s associated SIG X point can be programmed as a
“PUBLIC” point on the 4120 Network.
• A “PUBLIC” VNAC SIG X point can be declared as “EXTERNAL” on any
remote Network node capable of accepting External Points. An External
VNAC point should be programmed for control only. Associated VNAC
status is limited to ON/OFF, DISABLED TROUBLE, and MANUAL
OVERRIDE TROUBLE reporting.
• External VNAC signal points are autogenerated in remote panel lists
depending on the point type assigned to the VNAC and the option selected.
(See WARNING at the beginning of this appendix.)
• Local VNAC signal points are autogeneration point type specific. If they
are capable of being autogenerated, they will be placed in Local Lists L48
and L49.
B-3
General Programming Notes
Guidelines for Programming Use the following guidelines when programming Network operations.
• All nodes must have the same version or a compatible version of software
and firmware.
• All nodes must use the same baud rate.
• To reduce Net activity and increase efficiency, it is recommended that you
do the following:
− Avoid making control points Public.
− Program all control functions in the node that contains the
control points.
− Use Lists to minimize the network traffic. (Nest only one list within a
main list.) Do not make a list Public that already contains External
Points.
− Do not use the SET command when writing Custom Control for a
Network node unless absolutely necessary. It acts on every poll cycle
and slows down the network response time. Use TRACK rather than
SET whenever possible.
• Do not make an NDU point Public above offset 1535.
• Never set the value of an External Analog Pseudo Point through
the Network.
• Do not use P212, P210 or P211 at the same time for Network System Reset.
Refer to Pages B7 and B8 for correct programming.
• Use P217 for Network Signal Silence. Refer to Pages B7 and B8 for
correct programming.
• Avoid Version Mismatch. If you change a label or device type or point type
on a point that is EXTERNAL to other nodes, you must build and
download all affected nodes. If you change the Job Title in the General Info
screen, or the Network Prefix in the Network Points in the Info Screen, you
must build all nodes and download all nodes.
B-4
Network Alarm Silence
Central Network Silence Central Network silence may be initiated from any 4120 Network Node.
• Inhibit and Cutout Timers handled locally
• System Points involved:
− P217 Network Signal Silence
− L106 External Alarm Silence Points
Node 1
L106
2:P217
3:P217
4:P217
Node 4 Node 2
Public Public
P217 P217
Node 3
Public
P217
B-5
Network Alarm Silence, Continued
Distributed Network Silence Distributed Network Silence is used in a peer-to-peer 4120 Network.
• System Points involved:
− P217 Network Signal Silence
− L106 External Alarm Silence Points
Node 1
L106
2:P217
3:P217
4:P217
Node 4 Node 2
L106 L106
1:P217 1:P217
2:P217 3:P217
3:P217 4:P217
Node 3
L106
1:P217
2:P217
4:P217
B-6
Network System Reset
Central Network Reset Central Network Reset may be initiated from any Node.
• Separate internal Detector Reset and System Reset.
• All General Alarm Points are being monitored and SMPL-controlled by the
Central Node.
• System Points involved:
− P210 Network Detector Reset/L103 External Detector Reset Points
− P211 Network System Reset/L104 External Control Reset Points
Node 1
L103
2:P210
3:P210
4:P210
L104
2:P211
3:P211 Node 2
Node 4
4:P211 Public
Public
P210 P210
P211 P211
Node 3
Public
P210
P211
B-7
Network System Reset, Continued
Distributed Network Reset Distributed Network Reset is used in a peer-to-peer 4120 Network.
• Each node controls its own General Alarm Points.
• System Reset can be initiated from any node and all other nodes may also
experience the reset operation.
• System Points involved:
− P212 Detector/System Reset.
− L105 External Entire System Reset Points.
Node 1
L105
2:P212
3:P212
4:P212
Node 4 Node 2
L105 L105
1:P212 1:P212
2:P212 3:P212
3:P212 4:P212
Node 3
L105
1:P212
2:P212
4:P212
B-8
BLANK
PAGE
SEC-31-503