Professional Documents
Culture Documents
Energy Conversion and Management: Sciencedirect
Energy Conversion and Management: Sciencedirect
A R T I C L E I N F O A B S T R A C T
Keywords: In this work, an operation strategy for a biomass-fired combined cooling, heating and power system, composed
Biomass of a cogeneration unit, an absorption chiller, and a thermal energy storage system, is formulated in order to
Combined Cooling, Heating and Power (CCHP) satisfy time-varying energy demands of an Italian cluster of residential multi-apartment buildings. This operation
system strategy is adopted for performing the economical optimization of the design of two of the devices composing the
Feasible investment cost
combined cooling, heating and power system, namely the absorption chiller and the storage system. A sensitivity
Thermal energy storage
analysis is carried out in order to evaluate the impact of the incentive for the electricity generation on the
Sensitivity analysis
Cold thermal energy storage optimized results, and also to evaluate, separately, the effects of the variation of the absorption chiller size, and
Design optimization the effects of the variation of the thermal energy storage system size on the system performance. In addition, the
inclusion into the system of a cold thermal energy storage system is analyzed, as well, assuming different
possible values for the cold storage system cost. The results of the sensitivity analysis indicate that the most
influencing factors from the economical point of view are represented by the incentive for the electricity gen-
eration and the absorption chiller power. Results also show that the combined use of a thermal energy storage
and of a cold thermal energy storage during the hot season could represent a viable solution from the economical
point of view.
⁎
Corresponding author.
E-mail address: martina.caliano@enea.it (M. Caliano).
http://dx.doi.org/10.1016/j.enconman.2017.07.048
Received 20 April 2017; Received in revised form 17 July 2017; Accepted 23 July 2017
0196-8904/ © 2017 Elsevier Ltd. All rights reserved.
M. Caliano et al. Energy Conversion and Management 149 (2017) 631–645
in three different operating conditions: summer, winter, and the tran- Mongibello et al. [24] compared two different operation strategies for
sitional seasons. In another work, Wang et al. [13] conducted cost al- residential CHP systems, i.e. heat dumping and load partialization, by
location and sensitivity analysis of the CCHP system integrated with conducting an economic optimization and an environmental analysis.
biomass gasification based on exergoeconomic methodology. Campor- Franco et al. [25] defined an optimal operational strategy for CHP
eale et al. [14] analyzed and compared, from the economic and en- plants connected to civil/residential district heating networks, based on
ergetic points of view, three operation strategies for a CHP plant fired a multi-objective approach. Several studies on operation and design
by a mix of biomass and natural gas, to serve a residential demand. Bai optimization of biomass-fuelled polygeneration systems have been
et al. [15] analyzed the thermodynamic and economic performances of published in the last years. Lund et al. [26] presented an optimal design
a polygeneration system based on the thermal gasification of cotton methodology for small CHP plants in Danish market in which the plant
stalk by concentrated solar power. Li et al. [16] analyzed a cogenera- size was optimized against various electricity prices. Taljan et al. [27]
tion system coupling biomass partial gasification and ground source optimized economically the operation of a biomass CHP plant and the
heat pump. Vakalis et al. [17] have recently introduced an integrated heat storage system. Noussan et al. [28] found out the optimal con-
efficiency index that can be used to compare the thermodynamic per- figuration of a biomass-fired CHP system with thermal energy storage
formances of different polygeneration systems based on small-scale from the economic and energetic points of view. Recently, many studies
biomass gasifiers. have been also focused on real-time management and dynamic opti-
As many researches pointed out, optimization of polygeneration mization of smart polygeneration systems, taking into account the
systems design and operational strategy is crucial to improve energy fluctuations occurring at the supply side and/or at the demand one, as
efficiency and to reduce overall energy costs and greenhouse gas the works of Powell et al. [29] and Rossi et al. [30]. Dominković et al.
emissions. Ahmadi et al. [18] analyzed and optimized a complex multi- [31] developed an optimization model for combining biomass trigen-
generation system considering as objectives the total cost rate mini- eration energy system and pit thermal energy storage for the Croatian
mization and the exergy efficiency maximization. Shaneb et al. [19] market.
proposed an online approach for the operation optimization of micro- This paper presents the operation strategy for biomass-fired CCHP
CHP systems. Fuentes-Cortés et al. [20] minimized the cost and the systems formulated to satisfy the time-varying energy demands of an
environmental impact of two residential users in Mexico. Li et al. [21] Italian cluster of residential multi-apartment buildings. The results of
optimized the design and the operation strategy of a CCHP system from the design optimization of two devices composing the system, namely
the energetic, economic, and environmental viewpoints, for hotels, of- the absorption chiller and the thermal energy storage system, per-
fices and residential buildings in Dalian (China). Mongibello et al. [22] formed by implementing the developed operation strategy are shown
and Caliano et al. [23] introduced a novel full-load heat-driven op- and discussed. Furthermore, the impact of the incentive for the elec-
eration strategy for natural gas-fired CHP systems, evaluating economic tricity generation on the optimized results is also analyzed. Finally, the
and environmental benefits of such approach. In another work, optimized results obtained including a cold storage system into the
632
M. Caliano et al. Energy Conversion and Management 149 (2017) 631–645
CCHP system, and assuming different possible values for the cold sto- gas boilers (AB) and electrical chillers (EC), are also included into the
rage system cost, are presented and discussed. system in order to integrate the CHP and absorption chiller generations.
The main novel contribution of the present work is represented by According to the scheme of Fig. 1, the CHP unit provides electricity
the results of the optimization analysis relative to the combined use of a to the external grid and heat for the domestic hot water (DHW) demand
thermal energy storage and a cold thermal energy storage during the over the entire year. During the cold season, it also provides heat for the
hot season. ambient heating (AH) demand, while during the hot season, the
Thermal energy storage can play a major role in many energetic thermal energy generated by the CHP unit is also used to provide
systems. In solar systems, thermal energy storage permits to mitigate a cooling by the absorption chiller.
mismatch between the energy demand and the availability of the en- The thermal energy storage system is included in order to store the
ergy source. In CHP and CCHP systems, apart from addressing mis- CHP unit heat generation surplus with respect to the heat demand for a
matches between the energy demand and supply, thermal energy sto- later use.
rage allows to concentrate the electricity generation during on-peak
hours, when generally the selling price is higher, storing the thermal 2.2. Operation strategy and modeling
energy for a later use. Furthermore, in air conditioning systems driven
by conventional electrical reversible heat pumps, the adoption of An hourly-based operation strategy of the system has been im-
thermal energy storage permits the shifting of the electric demand fully plemented in a numerical code written in Matlab, in order to evaluate
or partially from on-peak hours to off-peak ones. This generally implies the annual economic savings that can be obtained by using the CCHP
a reduction of the operating and equipment costs, since thermal energy system with respect to the separate generation of electricity, heat and
storage allows a reduction of the equipment size, and to have longer cooling, considered made by centralized power plants, natural gas
operating hours of equipment at full load. Nevertheless, in general, the boilers and electrical chillers, respectively. It is assumed that the CHP
use of thermal energy storage systems also presents some drawbacks, unit operates continuously for the entire year, and that there is not
namely high initial costs, complicated operation, maintenance, and electricity self-consumption, namely, that all the produced electricity is
control, and high encumbrance [32,33]. fed into the grid. This choice, that depends on the Italian RES subsidy
Typically, the combined use of hot water and cold water storages is rules [44], according to which, only the electricity from biomass fed
implemented in polygeneration systems driven by solar systems, such as into the grid is subject to a feed-in tariff, will be analytically justified
the ones investigated by Calise et al. [34,35], who in both the works later in the paper in Section 3.2.4. Therefore, the total electrical de-
performed a parametric analysis in order to evaluate the impact of the mand of the user is considered covered by the external grid.
storage systems attributes on the system performance, and the one The CHP unit thermal (Eth,CHP(h)) and electrical (Eel,CHP(h)) gen-
analyzed by Noro et al. [36], who also considered the use of phase erations, for each hour of the year (h), are:
change materials as storage media. Indeed, in previous studies, tri-
Eth,CHP (h) = Pth,CHP ·h (1)
generation systems with energy storage, in which, as in the present
work, the cooling energy is generated by an absorption chiller fed by Eel,CHP (h) = Pel,CHP ·h (2)
using the heat recovered from a prime mover burning fuels, such as
natural gas and biomass, include only one typology of thermal energy where Pth,CHP and Pel,CHP are the CHP unit thermal and electrical power,
storage, as in works of Farahnak et al. [37], Huang et al. [38], Martinez- respectively. The electricity sent to (Eel,sent(h)) and taken from the grid
Lera et al. [39], and Stanek et al. [40], where a thermal energy storage (Eel,taken(h)), for each hour of the year, are:
system is used, or as in the works of Jiang et al. [41], Lai and Hui [42], Eel,sent (h) = Eel,CHP (h) (3)
and Song et al. [43], where a cold thermal energy storage system is
employed. This is explained considering for example that, in case a Eel,taken (h) = electricaldemand (h) (4)
thermal energy storage is present, these systems can allow to store hot
water at a relatively high temperature (90–95 °C in order to avoid the
use of pressurized tanks), so that the absorption chiller can be also fed 2.2.1. Implementation model in the cold and intermediate seasons
by using the stored heat without a sensible decrease of its performance. During the cold season and the intermediate ones, the operation
Nevertheless, later in this paper, it is shown that the combined use strategy implementation model is practically the same, the only one
during the hot season of a thermal energy system and a cold thermal difference is the user heat demand, that during the intermediate seasons
energy storage system in residential biomass-fired CCHP plants can consists in the domestic hot water demand only, whereas during the
increase the percentage of useful heat relative to the total thermal en- cold one consists in the domestic hot water and space heating demands.
ergy production of the CCHP system, and could represent a viable so-
lution from the economical point of view.
This section reports the layout of the considered CCHP system, and
describes the approach adopted as concerns the operation of the system
components. The first subsections regard the basic configuration of the
CCHP system, namely the configuration without the cold thermal en-
ergy storage. The system operation, when a the cold thermal energy
storage is present, is analyzed at the end of the section.
The basic layout of the CCHP system considered in the present work
is shown in Fig. 1. It is composed of a biomass-fuelled CHP unit, an
absorption chiller (AC), and a thermal energy storage (TES) system,
providing electricity, heat, and cooling to an Italian cluster of re-
Fig. 1. Layout of the CCHP plant.
sidential multi-apartment buildings. Auxiliary systems, namely natural
633
M. Caliano et al. Energy Conversion and Management 149 (2017) 631–645
Therefore, in the following, the variable heat_demand(h) will refer to heat demand (h)
CTES (h) = CTES (h−1)−⎛⎜ −Eth,CHP (h)⎞⎟
space heating and domestic hot water thermal energy demand, if cold 1−Lf (5)
⎝ ⎠
season is considered; to domestic hot water thermal energy demand, for
the intermediate seasons. As concerns the thermal modeling of the where Lf is the loss factor taking into account thermal losses relative to
CCHP system, this is accomplished by evaluating three parameters at thermal energy distribution, considered equal to the 16% of the energy
each operation hour, represented by the capacity of the TES (CTES(h)), delivered to the user [45].
the auxiliary boilers generation (EAB(h)), and the thermal energy gen- In the second subcase, the storage system is emptied (CTES(h)
erated by the CHP unit in excess with respect to sum of the heat demand = 0), and EAB(h) is evaluated as follows:
and the energy required to fill the TES (Eth,dumped(h)). Fig. 2 shows the
EAB (h) = heat demand (h)−(Eth,CHP (h) + CTES (h))·(1−Lf ) (6)
block diagram relative to the CCHP system operation in the cold and
intermediate seasons, implemented on an hourly basis, while the ana-
lytical description of the operation strategy for the different cases that
2.2.1.2. Case 2. Cogeneration unit thermal energy generation higher than or
can occur at each operation hour is reported in the following subsec-
equal to the sum of heat demand and distribution thermal losses.
tions.
In this case EAB(h) is zero, and there are the following two subcases:
(1) the thermal energy generated by the CHP is also higher than the
2.2.1.1. Case 1. Cogeneration unit thermal energy generation lower than the
sum of heat demand, DTL and the energy necessary to fill the sto-
heat demand.
rage, evaluated as the difference of its maximum capacity (CTES,max)
In this case, the dumped thermal energy Eth,dumped(h) is zero, and there
and CTES(h − 1);
are two possibilities or subcases:
(2) the CHP unit thermal energy generation is lower than or equal to
the sum of heat demand, DTL and the energy necessary to fill the
(1) the sum of heat demand and the distribution thermal losses (DTL) is
storage.
lower than or equal to the sum of the CHP unit thermal energy
generation and the thermal energy in the storage;
In the first subcase, the thermal energy in excess is dumped and
(2) the sum of heat demand and DTL is higher than the sum of the CHP
evaluated as follows:
unit thermal energy generation and the thermal energy in the sto-
rage. heat demand (h)
Eth,dumped (h) = Eth,CHP (h)−⎜⎛ + (CTES,max−CTES (h−1))⎞⎟
⎝ 1−Lf ⎠
In the first subcase, the heat demand is covered by the CHP unit
(7)
and the TES system, EAB(h) is zero, and the TES capacity is updated and
evaluated as follows: and the TES system is filled (CTES(h) = CTES,max).
In the second subcase, Eth,dumped(h) is zero, while CTES(h) is
Fig. 2. Block diagram relative to the CCHP system operation in the cold and intermediate seasons.
634
M. Caliano et al. Energy Conversion and Management 149 (2017) 631–645
updated as follows: the heat demand. Then, the residual available thermal energy, if pre-
sent, can be used for cooling generation. Furthermore, it is also assumed
heat demand (h)
CTES (h) = CTES (h−1) + Eth,CHP (h)− that the absorption chiller cooling energy generation can be in excess
1−Lf (8) with respect to the cooling demand only when the absorption chiller is
fed without using the thermal energy stored, namely, when the ab-
sorption chiller is fed only by the surplus heat produced by the CHP
2.2.2. Implementation model in the hot season
system. Furthermore, it is also assumed that the absorption chiller
During the hot season, there are six variables parameters re-
cooling generation cannot be lower than the 60% of the absorption
presented by the three ones defined in the previous section, namely
chiller nominal power. In such a case, the absorption chiller is switched
CTES(h), EAB(h) and Eth,dumped(h), and the variables relative to the
off, and the cooling demand is entirely satisfied by the electrical chil-
cooling generation, which are the absorption chiller cooling generation
lers. This last assumption is justified in Section 3.2.2, where the devices
(EAC(h)), the electricity absorbed by the electrical chillers (EEC(h)), and
characteristics are described.
the dumped cooling energy (Ec,dumped(h)), that is the cooling energy
Fig. 3 reports the block diagram of the CCHP system operation
generated by the absorption chiller in excess with respect to the cooling
strategy during the hot season, implemented on an hourly basis. An
demand.
exhaustive analytical description of the operation strategy at the dif-
Relatively to the use of the thermal energy generated by the CHP
ferent cases that can occur at each operation hour is presented in the
unit and of the thermal energy stored both for heating and cooling, the
following subsections.
adopted operational strategy prescribes that the priority is on the heat
demand, this last consisting only in the DHW demand in this season.
This assumption involves that, at each hour, the thermal energy gen- 2.2.2.1. Case 1. Cogeneration unit thermal energy generation lower than the
erated by the CHP and the thermal energy stored are first used to satisfy heat demand.
Fig. 3. Block diagram relative to the CCHP system operation in the hot season.
635
M. Caliano et al. Energy Conversion and Management 149 (2017) 631–645
In this case, Eth,dumped(h) and Ec,dumped(h) are zero, and, similarly to what as follows:
reported in Section 2.2.1.1, there are two main subcases:
heat demand (h)
Eth,surplus = Eth,CHP (h)−⎜⎛ + (CTES,max−CTES (h)) ⎞⎟
(1) the sum of heat demand and DTL is lower than or equal to the sum ⎝ 1−Lf ⎠ (15)
of the CHP unit thermal energy generation and the thermal energy In this case, the TES system is updated as follows
in the storage;
(2) the sum of heat demand and DTL is higher than the sum of the CHP ′ = CTES,max
CTES (16)
unit thermal energy generation and the thermal energy in the sto- If Eth,surplus multiplied by the absorption chiller coefficient of per-
rage. formance is higher than or equal to the cooling energy that is necessary
to satisfy the cooling demand, plus DTL, then the TES system remains
In the first main subcase, the heat demand is covered by the CHP full (CTES(h) = C′TES), the cooling energy generated by the absorption
unit and the TES system, EAB(h) is zero, and the TES capacity is updated chiller is given by:
as follows:
EAC (h) = min(PAC ·h,Eth,surplus ·COPAC (h)) (17)
heat demand (h)
′ = CTES (h−1) + Eth,CHP (h)−
CTES and the thermal energy dumped by:
1−Lf (9)
EAC (h)
If C′TES multiplied by the absorption chiller coefficient of perfor- Eth,dumped (h) = Eth,surplus−
mance is higher than or equal to the cooling energy that is necessary to COPAC (h) (18)
satisfy the cooling demand (cooling_demand(h)), plus DTL, then the If EAC(h) is higher than or equal to the cooling demand plus DTL,
cooling energy generated by the absorption chiller is given by: then EEC(h) is zero and the cooling energy dumped is given by:
coolingdemand (h) ⎞ coolingdemand (h)
EAC (h) = min ⎛⎜PAC ·h, ⎟ Ec,dumped (h) = EAC (h)−
⎝ 1−Lf ⎠ (10) 1−Lf (19)
where PAC is the nominal power of the absorption chiller. The TES Otherwise, if EAC(h) is lower than the cooling demand plus DTL,
capacity is updated as follows: then Ec,dumped(h) is zero, and the electricity absorbed by the electrical
chiller is evaluated by using Eq. (12).
EAC (h) In case Eth,surplus multiplied by the absorption chiller coefficient of
′ −
CTES (h) = CTES
COPAC (h) (11) performance is lower than the cooling energy that is necessary to satisfy
where COPAC is the coefficient of performance of the absorption chiller. the cooling demand, plus DTL, then Ec,dumped(h) is 0, and there are two
In this case, the electricity absorbed by the electrical chillers is given different subcases, with respect to the present one, that can verify:
by:
(1) the sum of Eth,surplus and C′TES multiplied by the absorption chiller
coolingdemand (h)−EAC (h)·(1−Lf ) coefficient is lower than the cooling energy that is necessary to
EEC (h) =
COPEC (h) (12) satisfy the cooling demand, plus DTL;
(2) the sum of Eth,surplus and C′TES multiplied by the absorption chiller
where COPEC is the electrical chillers coefficient of performance.
coefficient is higher than or equal to the cooling energy that is
Otherwise, if C′TES multiplied by the absorption chiller coefficient of
necessary to satisfy the cooling demand, plus DTL.
performance is lower than the cooling energy that is necessary to satisfy
cooling demand, plus DTL, then the cooling energy generated by the
In the first subcase, the cooling energy generated by the absorption
absorption chiller is given by:
chiller is given by
′ ·COPAC (h),PAC ·h)
EAC (h) = min(CTES (13)
′ )·COPAC (h))
EAC (h) = min(PAC ·h,(Eth,surplus + CTES (20)
The TES capacity is calculated using Eq. (11), and the electricity
In this case, EEC(h) is evaluated by Eq. (12), and Eth,dumped(h) is given
absorbed by the electrical chillers is calculated with Eq. (12).
by:
In the second main subcase, the storage system is emptied
(CTES(h) = 0), and EAB(h) is evaluated as in Eq. (6). In this case, EAC(h) P (h)
Eth,dumped (h) = max ⎛Eth,surplus− AC
⎜ ,0⎞ ⎟
is zero since the thermal energy generated by the CHP unit and the COPAC (h) ⎠ (21)
⎝
stored one are entirely used for covering the heat demand, and the
cooling demand is completely satisfied by the electrical chillers, with and the stored energy is updated as follows:
the electricity absorbed by the electrical chillers equal to: E (h)
′ −max ⎛ AC
CTES (h) = CTES ⎜ −Eth,surplus,0⎞ ⎟
EEC (h) =
coolingdemand (h) ⎝ COPAC (h) ⎠ (22)
COPEC (h) (14)
In the second subcase, the cooling energy generated by the absorption
chiller is given by:
2.2.2.2. Case 2. Cogeneration unit thermal energy generation higher than or coolingdemand (h) ⎞
equal to the sum of heat demand and distribution thermal losses. EAC (h) = min ⎛⎜PAC ·h, ⎟
⎝ 1−Lf ⎠ (23)
In this case EAB(h) is zero, and the two main subcases are:
and EEC(h), Eth,dumped(h), and CTES(h) are calculated using Eqs. (12),
(1) the thermal energy generated by the CHP is also higher than the (21), and (22), respectively.
sum of heat demand, DTL and the energy necessary to fill the sto- In the second main subcase, Eth,dumped(h) is zero, and consequently
rage; also Ec,dumped(h) is zero, while the stored energy is updated as follows:
(2) the CHP unit thermal energy generation is lower than or equal to
heat demand (h)
the sum of heat demand, DTL and the energy necessary to fill the ′ = CTES (h−1) + Eth,CHP (h)−
CTES
1−Lf (24)
storage.
In case C′TES multiplied by the absorption chiller coefficient of
In the first main subcase, the thermal energy surplus is evaluated performance is lower than the cooling energy that is necessary to satisfy
636
M. Caliano et al. Energy Conversion and Management 149 (2017) 631–645
the cooling demand, plus DTL, then the cooling energy generated by the 3.1. Objective function
absorption chiller is given by:
The objective function that is minimized in the optimization pro-
′ ·COPAC (h))
EAC (h) = min(PAC ·h,CTES (25) blem is given by:
else, it is given by Obj F = −FICCHP (30)
coolingdemand (h) ⎞ in which FICCHP is evaluated by fixing the payback period to 5 years:
EAC (h) = min ⎛⎜PAC ·h, ⎟
⎝ 1−Lf ⎠ (26) 5
FICCHP = ∑ ⎛ Fj ⎞−(ITES + IAC )
⎜ ⎟
CTES and EEC(h) are evaluated by Eqs. (11) and (12), respectively. j
j=1 ⎝ (1 + r ) ⎠ (31)
In Eq. (31) r is the discount rate, ITES and IAC are the investment
2.3. Inclusion of the cold thermal energy storage
costs for the purchase of the storage system and absorption chiller,
respectively, while Fj is the annual cash flow over the year j, that de-
Fig. 4 shows the layout of the CCHP system with integrated a cold
pends on the annual economic savings (ESj) with respect to the separate
thermal energy storage system (CTES), that is included into the system
generation, and on the operation and maintenance costs (OMTES)
to store the absorption chiller generation during the hot season when it
(OMAC) (OMCHP) of TES, absorption chiller and CHP unit, respectively,
is higher than the cooling demand, for a later use. Although, in general,
according to the following relation:
a cold thermal energy storage system provide more flexibility and a
higher efficiency to a tri-generation system, in cases like the present one Fj = ESj−(OMTES + OMAC + OMCHP )j (32)
it could seem to be unnecessary, and not convenient from the eco-
nomical point of view, since the absorption chiller can be also feed by
using the heat stored in the thermal energy storage system, this last 3.2. Inputs of the optimization problem
being already present in the basic CCHP system configuration con-
sidered. Later in this paper it is shown that the combined use of a The inputs of the optimization problem are the user main char-
thermal energy storage and of a cold thermal energy storage could be acteristics and its energy demands, the devices characteristics, energy
convenient also from the economical point of view, essentially because price and devices costs, and the Italian incentives for cogeneration
the cost per stored kWh of the cold thermal energy storage system can using biomass.
be much lower than the thermal energy storage system one. Indeed,
differently from the thermal energy storage systems, cold thermal en-
ergy storage systems does not supply sanitary water, and thus they can 3.2.1. Energy demand
be manufactured using much cheaper materials and processes. The user is represented by a residential cluster of 15 buildings, each
As to the operation strategy with the cold storage, it is assumed that consisting of 8 apartments of 100 m2, located in the Italian climatic
the absorption chiller can feed the cold storage system only when the zone E. This zone is representative of all the Italian locations char-
thermal energy in input to the absorption chiller consists in a surplus of acterized by heating degree-days ranging from 2100 to 3000 and a
the CHP unit thermal production with respect to the sum of the heat heating period ranging from October 15th to April 15th [46]. For the
demand and the energy necessary to fill the thermal energy storage. In specific considered location, situated in the north-west of Italy, the
more simple words, it is assumed that energy cannot be transferred heating degree-days are 2611.
from the TES to the CTES. The electrical appliances, domestic hot water and ambient heating
The implementation model of the cold thermal energy storage in the demands, equal to 18, 15 and 68 kWh/m2/yr, respectively, and their
hot season is similar to the thermal storage system one in the cold and hourly load profiles have been evaluated as in [22], while the cooling
intermediate seasons (see Section 2.2.1), and thus its details are not demand is fixed to 21 kWh/m2/yr [47]. The load profiles of electrical
reported here. appliances and domestic hot water demand are the same for each day of
the year, while the cooling demand one is the same for each day of the
hot season. For the ambient heating demand, each month is represented
3. Optimization by a different load profile. Fig. 5 shows the domestic hot water, elec-
trical appliances and cooling demand profiles of the selected user,
The variables of the optimization problem are CTES,max and PAC, whereas Fig. 6 shows ambient heating demand profiles relative to the
whose variation is limited in the ranges reported in Eqs. (28) and (29) representative days of the months of the cold season. The monthly
in order to limit the computational cost, respectively. thermal demand over the entire year is shown in Fig. 7.
0 ⩽ CTES,max ⩽ 4·Eth,CHP (28)
In Eq. (28), the upper limit of the variation range of the maximum
thermal energy storage capacity is fixed at four times the thermal en-
ergy generated by the CHP unit in an hour, because, as it will be clear
from the results in Section 4, this range includes all solutions of the
optimization and sensitivity analyses. As to the maximum possible
cooling power of the absorption chiller in Eq. (29), this has been fixed
on the basis of the maximum cooling demand of the user, and will be
detailed in Section 3.2.2.
The thermal energy storage system and absorption chiller design
optimization is performed by means of the Matlab patternsearch opti-
mization algorithm, with the objective of maximizing the feasible in-
Fig. 4. Layout of the CCHP system with cold storage.
vestment cost (FICCHP) relative to the purchase of the CHP unit.
637
M. Caliano et al. Energy Conversion and Management 149 (2017) 631–645
• constant mass flow rate of the hot water through the absorption
chiller generator heat exchanger;
• the maximum and minimum hot water inlet temperature are 95 °C
and 75 °C, respectively;
Fig. 5. DHW, electrical appliances, and cooling demand profiles.
• during the absorption chiller operation, the temperature of the
chilled water exiting the evaporator heat exchanger is kept fixed by
varying the chilled water mass flow rate.
Under the above assumptions, COPAC variation with the hot water
inlet temperature can be considered negligible, and its variation with
the ambient temperature is assumed to be linear within the range going
from 17 °C and 28 °C, namely the range of variation of the hourly
averaged ambient temperature at the selected location evaluated con-
sidering the entire hot season period, with a rate of −0.0114/°C.
Further, the cooling power can be considered to be a linear function of
the hot water inlet temperature, ranging from the nominal cooling
power, when hot water inlet temperature is 95 °C, to the minimum
cooling power, equal to the 60% of the nominal one, that is obtained
when the hot water inlet temperature is equal to 75 °C.
Fig. 8 shows the variation of COPAC as a function of the hourly
Fig. 6. AH demand profiles. averaged ambient temperature. The temperature profile and COPAC one
are normalized using the maximum average temperature equal to 28 °C,
and the maximum value of COPAC, assumed equal to 0.8, respectively.
Relatively to the electrical chillers, the adoption of a modular so-
lution composed of two electrical vapor compression chillers with hy-
dronic loop and inverters, both having a cooling power of 175 kW, has
been hypothesized in this study. This solution guarantees a low varia-
tion of the coefficient of performance COPEC at partial loads with re-
spect to the nominal one. Indeed, COPEC is assumed to be a function of
the ambient temperature only. The variation of COPEC as a function of
the hourly averaged ambient temperature is shown in Fig. 8, where
COPEC profile is normalized assuming its maximum value equal to 3
[51].
Finally, a modular solution is hypothesized also for the auxiliary
boilers, consisting of two natural gas-fired boilers of 325 kW each,
capable of satisfying the entire thermal energy demand. The boilers
Fig. 7. Monthly thermal demands. efficiency is considered constant and equal to 0.9, that can be assumed
as an average value between conventional and high-efficiency com-
3.2.2. Devices and fuel characteristics mercial solutions.
The CHP unit considered in the present work is a commercial co-
generation system consisting of a fixed bed gasifier and of an internal 3.2.3. Energy price and devices costs
combustion engine, fuelled by wood-chip-biomass with lower heat In order to evaluate the economic saving (ESj) with respect to the
value equal to 4.76 kWh/kg [48]. Its characteristics are shown in separate generation, the biomass, natural gas and electricity costs are
Table 1. taken into account. The biomass cost is fixed to 0.16 €/kg [52], while
A single effect LiBr-H2O absorption chiller is considered in the the natural gas cost, used to feed the auxiliary boilers, and the imported
present work. LiBr-H2O absorption chillers are the most commercia- electricity cost are evaluated according to [53], as a function of the
lized absorption chillers in the market, and the choice of considering a climatic zone, the consumption ranges and, as regards the cost of
single effect one is essentially due to the maximum hot water tem- electricity, also as a function of the installed electrical power. In the
perature in the thermal energy storage system, assumed lower than present analysis, the average costs of natural gas and imported
100 °C in order to avoid the use of a pressurized storage tank in a re-
sidential area. For such chillers, the condenser and the absorber can be Table 1
either water-cooled or air-cooled. Great part of the commercialized CHP unit main characteristics.
absorption chillers are water-cooled, nevertheless air-cooled ones can
Pth (kW) Pel (kW) ηth ηel
be more suitable for residential applications since they do not require
the cooling tower, and thus they can save both space and water [49,50]. CHP unit 120 50 0.40 0.21
638
M. Caliano et al. Energy Conversion and Management 149 (2017) 631–645
namely only if the real incentive for the electricity generation is high
enough to yield a positive operational economic balance at each op-
eration hour, as it actually happens in the present case. In fact, Eq. (34),
used to calculate the value of the incentive for the electricity generation
above which the continuous operation of the CHP unit is economically
convenient, that corresponds to the value obtained by imposing OEB
equal to zero, gives an incentive of 209 €/MWh, that is well below the
actual value of the feed-in tariff, i.e. 229 €/MWh.
j=1 ⎝ (1 + r ) ⎠ (36)
Eq. (33).
in which Fj is evaluated as follows:
OEB (h) = Eel,CHP ·incentive (h) + Eth,CHP ·UHF (h)·UHEV (h)
Eel,CHP 1 Fj = ESj−(OMTES + OMAC + OMCHP + OMCTES) j (37)
+ ∑ OMi (h)−costbiom· ·
ηel LHVbiom (33)
i = CHP ,TES ,AC ICTES in Eq. (36) and OMCTES in Eq. (37) are the investment and the
In the above equation, incentive represents the economic value of the operation and maintenance cost of CTES, respectively.
electricity generated by the CHP unit, expressed in €/kWh, UHF is the
fraction of useful heat relative to the total thermal generation of the 4. Results
CHP unit, UHEV is the economic value of the useful heat expressed in
€/kWh, costbiom is the biomass cost in €/kg, and LHVbiom is the biomass All the results presented in this section represent solutions of
lower heat value in kWh/kg. Clearly, the case in which the fraction of
Table 2
useful heat is zero represents the worst case from the economical point
Investment, and operating and maintenance costs.
of view. In this case, Eq. (33) becomes:
Eel,CHP 1 Investment cost (I) Operation and maintenance cost (OM)
OEB (h) = Eel,CHP ·incentive (h)−OMCHP−costbiom· ·
ηel LHVbiom (34) TES system 50 (€/kWh) 0.0012 (€/kWh)
AC 500 (€/kW) 0.002 (€/kWh)
Therefore, the assumption of continuous operation of the CHP unit CHP unit – 2.448 (€/h)
makes sense only if OEB evaluated using Eq. (34) is always positive,
639
M. Caliano et al. Energy Conversion and Management 149 (2017) 631–645
PAC (kW), FT, FP PAC = 0, 10, 20, 40, 65, CTES,max Eq. (28)
4.1.2. Sensitivity to the thermal energy storage size
87.5, 110, 130, 150, 175;
FT = 229; FP = 40
Fig. 11 shows the influence of the thermal energy storage system
size on the CHP unit feasible investment cost, as it shows the variation
CTES,max (kWh), CTES,max = 0, 30, 60, 120, PAC Eq. (29) of the non-dimensional feasible investment cost obtained at different,
FT, FP 240, 480; FT = 229; fixed values of the thermal energy storage system size, and optimizing
FP = 40
the absorption chiller power, whereas Fig. 12 shows, for each value of
CTES,max, the value of PAC resulting from the optimization problem re-
optimization problems formulated considering one, two or three opti- solution. The non-dimensional feasible investment cost (FIC″CHP) is
mization variables. calculated as follows:
FICCHP−min(FICCHP )
″ =
FICCHP ∗
4.1. Basic combined cooling, heating and power system configuration FICCHP −min(FICCHP ) (38)
where the minimum value of FICCHP, evaluated among all the analyzed
In this subsection, the optimized results relative to the case in which cases presented in Fig. 11, is equal to 5703 €/kWel and corresponds to
the CCHP system includes only the TES system are reported and dis- the case without the thermal energy storage. It can be noted that the
cussed. First, the results obtained by optimizing both TES system and above minimum value is not much lower than the value of the feasible
the absorption chiller sizes are shown, and the sensitivity of the opti- investment cost relative to the two variable optimization (FIC∗CHP),
mized results to the variation of the incentive is discussed. Successively, namely 5810 €/kWel. This result indicates that the variation of the
the results of the sensitivity analyses conducted by varying the TES thermal energy storage system size, within the considered set of values,
system size and the absorption chiller one are shown and discussed as has a low influence from the economical point of view.
well. In Fig. 11, it can be noticed that the feasible investment cost in-
creases by increasing CTES,max until reaching its maximum value for
4.1.1. Results of the 2-variables optimization and sensitivity to the incentive CTES,max equal to C∗TES;max, then it decreases. The increase of CTES,max
for the electricity generation from 0 to 400 kWh makes the CCHP system more flexible and allows to
The 2-variables optimization problem consists in the identification have a better management of the CHP unit heat generation. This can be
of the optimal sizes of the thermal energy storage system and of the explained by considering the total and seasonal heat dumping shown in
absorption chiller in case the cold thermal energy is not included. The Figs. 13 and 14, respectively. From these figures it can be seen that the
solution of the 2-variables optimization problem formulated con- total heat dumping always decreases by increasing CTES,max, and this is
sidering the real incentive for the electricity fed into the grid, indicated mainly due to the reduction of the wintry heat dumping. When CTES,max
in the following with (∗), presents a feasible investment cost (FIC∗CHP) is higher than C∗TES;max, although the heat dumping continues to re-
equal to 5810 €/kWel, and the optimized variables C∗TES;max and P∗AC duce, the feasible investment cost decreases due to the higher cost of
equal to 400 kWh and 33 kW, respectively. the thermal energy storage system. Figs. 12, 15, and 16 show that,
As concerns the optimal results obtained by varying the feed-in when CTES,max is higher than 60 kWh, PAC, the absorption chiller cooling
tariff and fixing the feed-in premium, the variation of the feed-in tariff energy generation, and the cooling energy dumped do not significantly
leads to a variation of the feasible investment cost, while the sizes of the vary with the storage system size. This is due to the fact that, with
thermal energy storage system and of the absorption chiller remain CTES,max higher than 60 kWh, although the increase of the absorption
equal to 400 kWh and 33 kW, respectively. This is because in the three chiller power would have a positive effect by reducing the electricity
different cases, since the CHP unit operates continuously, and being the cost for air conditioning, the increase of the absorption chiller size
feed-in premium the same, which means that the heat recovery is would cause the increase of the component cost, with a consequent
equally incentivized, the hourly useful heat is the same, and so the
devices sizes. Fig. 9 shows the influence of the variation of the feed-in
tariff on the feasible investment cost. Clearly, the feasible investment
cost increases by increasing the feed-in tariff value.
From the above, it is clear that, for a fixed feed-in tariff, the increase
in the feed-in premium leads to a higher feasible investment cost, TES
size and absorption chiller one, as shown in Fig. 10. In this figure, the
values of the feasible investment cost, the thermal energy storage
system and the absorption chiller sizes are normalized with respect to
the maximum ones, obtained, of course, with the maximum considered
value of the feed-in preminum, i.e. 80 €/MWh, equal to 6589 €/kWel,
433 kWh, and 42 kW, respectively.
Table 4 shows the main energetic output data resulting from the 2-
variables optimization problems resolution. As stated above, the var-
iation of the feed-in tariff does not influence the energetic results,
which are reported in the central row of Table 4 under FT variable, Fig. 9. Feasible investment costs obtained by varying the feed-in tariff and fixing the
feed-in premium.
FP = 40. It can be seen that by increasing the feed-in premium, the
640
M. Caliano et al. Energy Conversion and Management 149 (2017) 631–645
Fig. 10. Normalized feasible investment costs, TES and AC sizes, obtained by fixing the
feed-in tariff and varying the feed-in premium. Fig. 11. Non-dimensional feasible investment cost at different values of CTES,max.
Table 4
Main energetic output data of 2-variables optimization problems resolution.
Auxiliary boilers total Electrical chillers total AC total cooling Total heat Total cooling Seasonal heat dumping (kWh)
heat generation (kWh) cooling generation generation (kWh) dumping (kWh) energy dumped
(kWh) (kWh) Winter Intermediate Summer
seasons
FT = 229, 4.92 * 105 2.16 * 105 4.59 * 104 4.43 * 105 2.68 * 103 8.63 * 104 2.08 * 105 1.48 * 105
FP = 0
FT variable, 4.45 * 105 1.99 * 105 7.16 * 104 3.52 * 105 8.44 * 103 3.14 * 104 2.08 * 105 1.12 * 105
FP = 40
FT = 229, 4.41 * 105 1.92 * 105 8.84 * 104 3.24 * 105 1.53 * 104 2.61 * 104 2.08 * 105 8.92 * 104
FP = 80
641
M. Caliano et al. Energy Conversion and Management 149 (2017) 631–645
Fig. 14. Seasonal heat dumping obtained at different values of CTES,max. Fig. 18. TES system maximum capacity at different values of PAC.
Fig. 15. Absorption chiller generation. Fig. 19. Absorption chiller generation.
Fig. 16. Total cooling energy dumped obtained at different values of CTES,max.
Fig. 20. Total cooling energy dumped obtained at different values of PAC.
642
M. Caliano et al. Energy Conversion and Management 149 (2017) 631–645
Fig. 26. Absorption chiller nominal power and CTES sizes obtained by varying the CTES
Fig. 22. Seasonal heat dumping obtained at different values of PAC.
cost and the incentive.
Fig. 23. Cold storage maximum capacity and absorption chiller nominal power at dif-
ferent cold storage investment cost.
Fig. 27. Non-dimensional feasible investment cost obtained by varying the CTES cost and
the incentive.
Table 5
Minimum and maximum feasible investment costs obtained by varying the CTES cost and
the incentive.
to feed the absorption chiller. For PAC higher than 87.5 kW, the total
Fig. 24. Hourly profiles of the cooling demand, the cooling energy stored, and the cooling heat dumping is practically constant and the seasonal one is null.
energy generated by the electrical chillers.
643
M. Caliano et al. Energy Conversion and Management 149 (2017) 631–645
function of the ratio between CostCTES and CostTES. From this figure, it economic optimization of the absorption chiller and the storage system
can be seen that for CostCTES equal to or higher than 0.5∗CostTES, the sizes have been presented and discussed. A sensitivity analysis has been
maximum capacity of the cold storage system is zero, while the ab- also presented to show the impact of the incentive for the electricity
sorption chiller power and the CHP unit feasible investment cost are generation on the optimized results, consisting in a basic feed-in tariff,
33 kW and 5810 €/kWel, respectively, or rather those obtained from the plus a feed-in premium in case of positive PES index, and also to show,
2-variables optimization problem resolution. It can be also seen that, for separately, the effects of the variation of the absorption chiller size and
CostCTES going from 0.5∗CostTES to 0, CCTES,max and PAC increase up to the effects relative to the variation of the thermal energy storage system
their maximum values (CCTES,max equal to 555 kWh and PAC equal to size on the CCHP system performance. Furthermore, the inclusion into
70 kW), obtained in the limit case when CostCTES is zero. Moreover, for the system of a cold thermal energy storage system has been in-
CostCTES going from 0.5∗CostTES to 0, also the CHP unit feasible in- vestigated.
vestment cost increases with respect to the one obtained from the 2- The main results of the present work are:
variables optimization problem resolution. At CostCTES equal to zero,
the CHP unit feasible investment cost is equal to 5937 €/kWel. • the optimal sizes of the thermal energy storage system, the ab-
Fig. 24 shows, for three different values of CostCTES in the range sorption chiller, and the cold thermal energy storage system are
0–0.5∗CostTES, corresponding to three different values of CCTES,max in highly influenced by the value of feed-in premium, whereas the
Fig. 23, the hourly profiles of the cooling demand, the cooling energy optimal sizes of the above devices have shown no sensibility to the
stored, and the cooling energy generated by the electrical chillers over a variation of the feed-in tariff;
representative summer day. From this figure, it can be argued that the • the variation of the thermal energy storage size has a negligible
increase of the cold storage size involves the decrease of the electricity effect on the CCHP system performance from the economical point
absorbed by the electrical chillers. This justifies the increase in the CHP of view;
unit feasible investment cost. • the variation of the absorption chiller size highly influences the
The above results indicate that the inclusion of a cold thermal en- CCHP system economic and energetic performances;
ergy storage in the considered CCHP system could represent a viable • the inclusion of a cold thermal energy storage in the considered
solution from the economical point of view in case the cost per stored CCHP system could represent a viable solution from the economical
kWh of the cold thermal energy storage is much lower than the thermal point of view in case the cost per stored kWh of the cold thermal
energy storage one. energy storage is much lower than the thermal energy storage one.
644
M. Caliano et al. Energy Conversion and Management 149 (2017) 631–645
645