Professional Documents
Culture Documents
Easergy MiCOM P63x Protection Relays - P63283
Easergy MiCOM P63x Protection Relays - P63283
Easergy MiCOM P63x Protection Relays - P63283
Main
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Range of product MiCOM P63x
Device short name P632
Relay application Transformer
Protection type Breaker failure
Earth fault ANSI code: 50G/51G
Negative sequence/unbalance ANSI code: 46
Restricted earth fault
Thermal overload protection ANSI code: 49RMS
Two-winding transformer differential ANSI code: 87T
Undervoltage ANSI code: 27
Overvoltage ANSI code: 59
Underfrequency ANSI code: 81L
Overfrequency
Number of inputs 34 discrete
1 analog
8 current input CT...X/5 A and X/1 A
1 voltage
1 temperature sensor
Number of outputs 22 discrete
2 analog
Communication port protocol Modbus RTU
Ethernet
IEC 60870-5-103
IEC 61850
DNP3
Complementary
Auxiliary supply 24...60 V DC 19…72 V
60...250 V DC 48…300 V
100...230 V AC 100…230 V
Network and machine diagnosis type Fault recording
Event recording
Disturbance recording16.4 s
Switchgear diagnosis type CT/VT supervision
Discrete input voltage 24...250 V DC 18 V standard variant
24...250 V DC 73 V further option
24...250 V DC 90 V further option
24...250 V DC 146 V further option
24...250 V DC 155 V further option
Environment
Height 184.5 mm total:
177.5 mm embedded:
Width 481.6 mm
Depth 257.1 mm total:
Mounting mode Surface mounted
Contractual warranty
Warranty 18 months