Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Line Trap/CVT Mounting

The extremely high cantilever


strength of Trench’s Capacitor
Voltage Transformers and Trench’s air core
Line Trap
unique Line Trap Pedestal mounting
arrangement allow most Line Traps
to be mounted directly on top of
the Capacitor Voltage Transformer
or Coupling Capacitor. Pedestal C/W stainless
steel Hardware supplied
This type of mounting scheme re- by Haefely Trench
duces space requirements in most
substations, while facilitating the
electrical connection between the
Line Trap and CVT. The mechanical
connection between the two units
also serves as the electrical connect-
ion.

In assessing the suitability of this


mounting scheme, Trench assumes
a 300lb. (136kg) horizontal terminal
load at the top of the CVT. Also,
specific wind load and electrody-
namic forces are calculated. A
minimum safety factor of 2 on por-
celain breaking strength is main-
tained in all calculations.
Typical Trench
Due to the plurality of Line Trap Line Trap mounted on
and CVT designs, it is not practical a Trench CVT or CC
to list all possible mounting com-
binations. Please consult Trench
for specific mounting requirements.
Trench will perform all calculations
and advise suitability in each case.

E 214.64