Professional Documents
Culture Documents
Al Rasheedi2015
Al Rasheedi2015
Abstract — Increase or decrease in the reactive power (VAR) the mentioned additional power, which will be reflected as an
load requirements on any bus leads to voltage fluctuations at that additional cost.
bus. Therefore, VAR flow control is very crucial for the integrity
of power systems as it may lead to voltage instability or severe What makes this situation worse is when you have a normally
circulating current. The circulating current in the power systems
closed substation configuration (double ended switchgear) or
will cause system stresses and will reduce the generator’s
capacity. Therefore, a quick automated control system is needed small generation plants connected in parallel, as shown in
to continually regulate the VAR flow. This can be done through Figures 1 and 2.
the VAR control system in either the generator or the
transformer; however, a very sophisticated control system is
needed for coordination between them. In this paper we will
share our experience in deploying an advanced technique to
coordinate between all VAR systems to stabilize the voltage and
minimize the circuiting current. We utilized the existing
Distributed Control System (DCS) infrastructure, in one of the
local industrial plants, to automate the VAR regulation without
adding any additional components. The new logic detects any
voltage instability or any circulating current and selects the most
appropriate VAR system, whether it is a generator VAR or a
transformer VAR, to correct the VAR flow. At the end, the
voltage will be fixed. In this paper we will describe how this
package works, the system logics, and the system operations.
Figure 1: Parallel transformers configuration. [1]
I. INTRODUCTION
Recently, power plants in the utilities and the industrial
facilities, pay considerable attention in managing the voltage
levels as well as the reactive power in both the transmission
and the distribution levels. Loads with high capacitance and Figure 2: Parallel generators configuration.
inductance, e.g., electric motors, put additional stress on the
grid. The reactive nature of these loads makes them draw more The current may circulate, due to voltage difference, between
current than comparable resistive loads, e.g., lighting systems, the closed tie buses in the double ended switchgear and also
would draw considering the same quantity of real power within the interconnected parallel substations. In the most
transferred. This extra current will result in heating of the elementary form, current will flow out of one bus, through the
electric network components such as the power transformer, paralleling bus and into the second bus. It does not flow into
and may result in reducing its service lifetime. Moreover, the load, but stresses the network. This current, called
uncorrected reactive power will create voltage stability issues. “Circulating Current,” is in addition to the normal line current
It will also drive the electric network components (such as supplied to the connected load.
cables, transformers, and generators) to be oversized to carry
This circulating current will reduce the capacity of the
generators and also will create fluctuation in the network
2
Figure 3: Current flow in transformers at parallel operation. [2] A. Parallel Operations of Generators
In a petrochemical complex, power system reliability is crucial
and power interruptions cannot be tolerated. Therefore, in
%R1 = %Z1 / √[(X/R1)2 + 1)] some cases a robust power generation stations is built. These
%X1 = %R1 x (X/R1) generation stations contain parallel generators feeding their
%R2 = %Z2 / √[(X/R2)2 + 1)]
3
own loads and are interconnected through closed tie additional generator master unit or load follower panel for the
substations or breaker and half configuration. transformers.
Each power station has to satisfy the VAR demand on its The control logic contains:
connected loads and minimize VAR flow from the other
generation stations. Subsequently, the problem when there is A. VAR Control for Generators
no coordination between the generators at the interconnected
B. VAR Control for Transformers OLTC
power stations, which leads to circulating current. Therefore,
the generator’s ability of producing active power will be
affected.
B. Generator Capability Curve
The capability curve of a typical generator is shown in Figure
4. Real power (MW) is plotted as the X-axis and the reactive
power (MVAR) is plotted as the Y-axis. The area under the
curve is the safe working area for the generator. It is obvious
that the more VAR the generator produces, the less W it safely
can produce. In other words, extra reactive will limit the real
power that the generator can produce.
its own bus. If not, then other generators will act to help, if not,
then the OLTC will take action to adjust the power flow to the
network.
Before moving to the logic, it is critical to identify the T1= time for first
requirements, namely: generator to act.
B. System Logics
C. System Operations
Where;
The logic also will set the tie line VAR exchange based on the
user setting.
Before moving to the logic, what does this control logic need?
It needs:
that the transformer’s tap position for the normally closed bus
are the same so there should be no circulating current.
T1= time for first
VII. DISCUSSION AND CONCLUSION
generator to act.
T2= Time for the other This package was completed and tested using all credible
generators to act.
scenarios, utilizing the vendor’s real time simulator. The
T3= time when generator package performance was satisfactory. The controller acted
package terminated and exactly as intended in Flowchart 1 and 2 and the circulating
OLTC package started. current was maintained below 10%.
VIII. REFERENCES