Professional Documents
Culture Documents
DAMPERS DFD-350, GREEHECK 3 Horas
DAMPERS DFD-350, GREEHECK 3 Horas
DAMPERS DFD-350, GREEHECK 3 Horas
Job: DMPERS
Mark: DFD-33
Model: DFD-350
RATINGS W H Damper
PRODUCT DETAILS
H
Frame: Galvanized
O
Frame Depth: 3.688
Blade: Galvanized HORIZONTAL MOUNT
Closure Device: Fusible Link
Closure Temp: 286 F
• This drawing shows a general damper configuration and is not
Velocity: 2,000 ft/min
intended to depict the exact configuration of all dampers
Mounting: Horizontal
in this submittal.
Sizing: Nominal
• Damper is furnished approximately 0.250 in. undersize.
(Add sleeve thickness for overall sleeved damper dimension)
OPTIONS & ACCESSORIES • Installation instructions available at www.greenheck.com.
Transition: B2
Transition Location: Both Sides
Union Label: No Preference
CODES APPROVED
This model meets the requirements for fire dampers established by:
• UL Classfied (U.S. and Canada)
Standard UL 555 (Listing #R13317)
• National Fire Protection Association
NFPA Standard 80,90A & 101
• IBC: International Building Codes
• California State Fire Marshal: CSFM listing # 3225-981:102
SUMMARY
ID # TAG QTY Width Height CONFIGURATION
Sections Wide: Sections High: "O" Dim: Sleeve Length:
1 1 24.000 in. 12.000 in.
3-1 1 24.000 in. 21.000 in.
Sleeve Thickness: Damper Location:
20 ga 6.000 in.
H*
Horizont
Stainless Steel Fusible Link (replaceable)
Closure Spring
3 11/16 in. Vertical Mount
(94mm)
Horizontal Mount
Sleeve
Damper
H*
K
Damper CL Damper Frame
Location W*
L
Overall Sleeve Length
Sealed Option
When sealed option is selected, B transition will need
to be field sealed in the area where duct to sleeve
connection is made.
Size Limitations P
3 in.
(914 x 914) in.
(102 x 102) (102 x 76) (914 x 787)
Vertical
O*
Multi H* 48 x 48 48 x 45 W*
W *
16 in.
10 in.
36 in. (914mm) max.
Vertical 1219) 1143) Type A
Single
4x4 30 x 30 4x3 30 x 26
Section
3 in.
(102 x 102) (762 x 762) (102 x 76) (762 x 660)
Horizontal
W* K dim.
Multi
40 x 36 40 x 33 Sleeve
Section** NA NA Length
(1016 x 914) (1016 x 838) Varies
Horizontal Maximum Single Type B2
Section
Maximum Single Section Dimensions Dimensions
2 Multi-Section Limitations
Maximum damper height is 48 in. (1219mm) when combination width is 48 in. (1219mm) or less.
48 in.
(1219mm)
max.
36 in. (914mm) max.
36 in.(914mm)
Max.
Type A Single Section
48 in.
(1219mm)
max.
Multi-Section Limitations
Maximum damper height is 48 in. (1219mm) when combination width is 48 in. (1219mm) or less.
31 in.(787mm)
Max.
45 in. (1143mm)
Max.
36 in.(914mm)
Max.
48 in.
(1219mm)
Type B Single Section max.
48 in.
Multi Section Limitations
Maximum damper height is 45 in. (1143mm) when combination
(1219mm)
width is 48 in. (1219mm) or less.
Max.
48 in.
(1219mm)
max.
Type A, B, & B2.... DFD-350
3 in.
O*
H*
Vertical Mount
10 in.
H* O* H* O*
3 in.
4 (102) 6 (152) 26 (660) 30 (762) W*
* Dimension is inches (mm). These dimensions are furnished approximately 1⁄4 in. (6mm) undersize. All ‘H’ dimensions larger than single section height
are two sections high. Refer to size limitations chart. The top section is a Type B/B2 and the bottom section are Type A.
Multi 44 46 x 44 46
Section** NA NA NA
Vertical (1118) (1168 x 1118) (1168)
Single 3 25 3x3 28 x 25 3 28
Section
Horizontal (76) (635) (76 x 76) (711 x 635) (76) (711)
Multi 32 38 x 32 34
Section** NA NA NA
Horizontal (813) (965 x 813) (864)
*1 With 2 in. (51mm) offset. Sizes adjust with 0 offset and 1 in. (25mm) offset.
** Consult factory for number of sections.
Type C, CO, CR & R.... DFD-350
Maximum Single Section Dimensions Overall Damper Dimensions
D*+2
Type C Type CO
Type CR
O*
30in.
(762mm) 30 in.
max. (762mm)
max.
D*
34 in. 34 in. W*+2
(864mm) (864mm)
max. max.
Type CO
Type CR Type R
O*
H*
W*
W*+2
Type C
34 in.
(889mm)
O*
30 in. max.
(762mm) H*
max. Type R transition is centered on
damper frame. (Dimension are with
2 in. (51mm) offset.)
W*
* Dimension is inches (mm). These dimensions are furnished approximately 1⁄4 in. (6mm) undersize. All ‘H’ dimensions larger than single section height
are two sections high. Refer to size limitations chart.
These instructions apply to 11⁄2 and 3 hour rated fire dampers mounted (blades must be horizontal) in: 1) masonry,
block, or stud walls and 2) concrete floors. Specific requirements in these instructions are mandatory. Dampers must
be installed in accordance with these instructions to meet the requirements of UL 555.
Note: Fire dampers are manufactured and labeled for either vertical or horizontal installation. The dampers must be
installed in accordance with labeling.
Table of Contents
General Information ....................................... 2
Pre-Installation Guidelines ............................ 2
Installation.................................................3-11
• Preparation of Openings ......................... 3
• Clearances Required Between Damper
Sleeves & Wall/Floor Openings .............. 4
• Installing Multiple Section Assemblies.... 4
• Maximum Assembly Tables..................... 5
Receiving and Handling • Sleeve Length Requirements................5-6
Upon receiving dampers, check for both obvious
and hidden damage. If damage is found, record all • Securing the Damper/Sleeve
necessary information on the bill of lading and file Assembly to Wall/Floor Openings .......6-8
a claim with the final carrier. Check to be sure that • Duct to Sleeve Connection.................9-10
all parts of the shipment, including accessories, are
accounted for. • No Connecting Duct or
Transfer Opening................................... 11
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is Commissioning and Periodic Testing........... 11
highly recommended. Do not store at temperatures in
Maintenance ................................................ 11
excess of 100°F (38°C).
Troubleshooting ........................................... 11
Safety Warning
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury
or death. Read the installation, operating, and
maintenance instructions thoroughly before installing
or servicing this equipment.
This manual is the property of the owner and is required for future maintenance. Please leave it with the owner when
the job is complete.
Curtain Fire Dampers 1
General Information
“UL CLASSIFIED (see complete marking on Pre-Installation Guidelines
product)” The following items will aid in completing the damper
“UL CLASSIFIED to Canadian safety standards installation in a timely and effective manner.
(see complete marking on product)”
1) Check the schedules for proper damper locations
Standard 555 (Listing #R13317)
within the building. Visually inspect the damper for
damage and verify that the fusible link is in place and
has not activated. Never install a fire damper without
Installation Supplements the proper UL approved fusible link in place. Visually
Refer to the appropriate Greenheck installation inspect the link to verify its not damaged. Replace
supplements for special requirements: link as necessary.
• Closed Indicator Switch 2) Lift or handle damper using sleeve or frame. Do not
• Concrete Floor with Steel Deck lift damper using blades.
• Drive Slip Breakaway Connection 3) Dampers have a label indicating the required
• Field Installed Sleeve mounting orientation. When the mounting orientation
• Fire Resistant Ventilated Duct Assembly is horizontal, the 'K side' must be up. Care must
• Firestop Material be taken to ensure that the indicated orientation is
• Fusible Link Replacement adhered to.
• Grille Installation W*
Installation supplements available at www.greenheck. 5) Damper must be kept clean and protected from
com. dirt, dust and other foreign materials prior to and
after installation. Examples of such foreign materials
include but are not limited to:
a) Mortar dust
b) Drywall dust
c) Firesafing materials
d) Wall texture
e) Paint overspray
6) Damper should be sufficiently covered as to prevent
overspray if wall texturing or spray painting will be
performed within 5 feet of the damper.
7) Caulking is not necessary, nor is it allowed, between
the damper sleeve and the wall or floor opening
(annular space). However, caulking may be applied to
the retaining angles.
8) ACCESS: Suitable access (such that the fusible
link may be removed and the damper's blade stack
may be reset, etc.) must be provided for damper
inspection and servicing. Where it is not possible to
achieve sufficient size access, it will be necessary to
install a removable section of duct. (Refer to NFPA
90A).
9) The Code Authority Having Jurisdiction (AHJ) must
evaluate and provide approval of final installation
where variations to these instructions are necessary.
2 Curtain Fire Dampers
Preparation of Openings
• Frame wall openings as shown below (see Figure 1 & 2).
• Gypsum wall board must be fastened 12 in. (305mm) on center to all stud and runner flanges surrounding opening.
• Prepare opening between studs and sleeve assembly as shown below (see Figure 3 & 4).
• All construction and fasteners must meet the requirements of the appropriate wall design (See UL Fire Resistance
Directory) and/or local codes.
Second set of studs are not required on openings
Second set of studs are not required on openings 36 in. x 36 in. (914mm x 914mm) or smaller. 36 in. x 36 in. (914mm x 914mm) or smaller.
12 in.
24 in. o.c.
Maximum
2 in. (51mm)
2 Panhead
Screws
2 in. (51mm)
Figure 1 Figure 2
Gypsum Wallboard
Stud or Runner
Retaining
Angle
Gypsum Wallboard
Gypsum Wallboard
Stud or Runner
Stud or Runner
Retaining
Angle Retaining
Angle
Gypsum Wallboard
Curtain Fire Dampers 3
Stud or Runner
Clearances Required Between Damper Sleeves & Wall/Floor Openings
Two-sided Angle Installation
Two sided angle installations require clearances for thermal expansion between the damper sleeve and the wall/floor
opening. The minimum required clearances are:
• For galvanized steel fire dampers and sleeves: 1⁄8 in. per foot (3mm per .3 m) of damper width and 1⁄8 in.
per foot (3mm per .3 m) height with a minimum clearance of 1⁄4 in. (6mm). The total gap may be up to 6 in.
(152mm), 3 in. (76mm) per side, as long as the retaining angles overlap the wall/floor by a minimum of 1 in.
(25mm).
• For stainless steel fire/smoke dampers and stainless steel or galvanized sleeves: 3⁄16 in. per foot (5mm per
.3 m) of damper width and height with a minimum clearance of 1/4 in. (6mm), maximum of 2 in. (51mm).
Example:
A 12 in. x 12 in. (305mm x 305mm) will
require a minimum clearance of 1/4 in.
(6mm) width and 1/4 in. (6mm) on height
A 48 in. x 12 in. (1219mm x 305mm)
damper will required a minimum
clearance of 1/2 in. (13mm) on width and
1/4 in. (13mm) on height.
These are total clearances (ignoring fastener heads) and do not need to be equally spaced around the damper.
Although the minimum requirements are listed above, for ease of installation the following are the recommended
clearances for galvanized dampers:
• Width/Height of 48 in. (1219 mm) or less - ½ in. (13mm) clearance
• Width/Height between 48.01 in. (1220 mm) and 96 in. (2438 mm): 1 in. (25mm) clearance
• Width/Height greater than 96 in. (2438 mm): 1½ in. (38 mm) clearance
Single Side Angle Installation
On vertical mount single side angle installations there are no minimum clearance requirements between the wall
opening and the damper sleeve. However, to facilitate installation, clearances between the wall opening and the
damper sleeve are recommended.
On horizontal mount single side angle installations a minimum clearance is required between the outside of the
damper sleeve and the floor opening of 1⁄8 in. per foot (3mm per .3m) of damper width and 1⁄8 in. per foot
(3mm per .3m) height with a minimum clearance of 1/4 in. (6mm).
Installing Multiple Section Assemblies
Attachments--Do not
A damper assembly is not restricted to a maximum place attachments
between blade channels
number of sections, but must not exceed the section
sizes and overall sizes shown (see chart below).
The damper sections must be attached together with Blade
Channel
#10 (3/4 in. max. [19mm]) sheet metal screws, 1/4 in.
(6mm) diameter nuts and bolts, tack or spot welds, or
3
⁄16 in. (48mm) diameter steel pop rivets. Attachments
must be spaced a maximum of 6 in. (152mm) on
centers and a maximum of 2 in. (51mm) from corners.
Attachments must be made on front face and back face
(air entering and air exiting side) of damper sections.
Figure 5
4 Curtain Fire Dampers
Maximum Assembly Tables
When multiple sections are shipped unassembled, installer shall fasten dampers together. The table shows
maximum sizes for multiple section dampers. Dampers that are two or more sections tall must be factory
assembled. Note: All dimensions are shown in inches (W x H). * Sizes listed is the damper size, not transition size.
Sleeve Requirements
All fire dampers must be installed in a steel sleeve of the required gauge and length. Note that DFD-150X and
FD-150X series dampers are provided with an integral sleeve. See Table on page 10 for required minimum sleeve
gauges. Maximum sleeve thickness is 10 gauge (3.5mm). Sleeve inside dimensions must equal damper outside
dimensions.
Sleeves shall extend a maximum of 6 in. (152mm) beyond the wall or floor opening on each side. When a factory
mounted access door is incorporated as a part of the sleeve the sleeve may extend a maximum of 16 in. (406mm)
beyond the wall or floor opening on the access door side.
attached to the sleeve with one row of attachments on NOTE: Attachments must not enter blade
channel or they may cause interference with
each side of the blade channel. Attachments must be blade closure. Narrow Line and Ultra Thin
spaced a maximum of 6 in. (152mm) on centers and a Blade
Channel
dampers do not have flange for attachments
and must be welded to sleeve.
maximum of 2 in. (51mm) from corners. A minimum of
4 attachments (2 on each side of the blade channel) per
side (16 per damper) are required. One of the methods
of attachment shown below must be used: 2 in. Max.
2 in
. M
ax.
Damper
Sleeve Damper
Sleeve
Figure 8: Single Side Angle With Steel Stud Wall - Angle Figure 9: Single Side Angle With Wood Stud Wall
Over Wallboard
Top Side
Damper Angle Fastener
Sleeve
Damper
Sleeve
Two layers of 1/2 in. UL
Classified Gypsum Masonry or
Concrete
Wallboard for 2 hour Masonry or
Wall
rated walls. One layer Concrete
Floor
for 1 hour rated walls
(see UL Rated Wall
Metal Stud Design for Additional
or Runner Details).
Angle Fastener
Damper
Sleeve
Figure 10: Single Side Angle With Steel Stud Wall - Figure 11: S
ingle Side Angle With Masonry or
Angle Under Wallboard Concrete Wall and Floor
Curtain Fire Dampers 7
Maximum Maximum
6 in. 6 in.
Damper
Sleeve
Damper Sleeve Damper
#10 sheet metal screws
#10 sheet metal screws, 2 Stud or Runner spaced 6 in. on center
1/2 inches long, spaced 6 and a maximum of 2 in. Stud or Runner
in. on center and a from the corners Two layers of 1/2 in.
Wall or floor
maximum of 2 in. from the (minimum of 2 screws per UL Classified Gypsum
corners (minimum of 2 Two layers of 1/2 in. UL side). Screw into studs so Wallboard for 2 hour
screws per side). Screw Classified Gypsum as to avoid space Maximum rated walls. One layer
Maximum
into studs so as to avoid Wallboard for 2 hour conflicts with the grille 6 in. for 1 hour rated6 walls
in.
space conflicts with the rated walls. One layer for
Angle Fastener (see UL Rated Wall
grille. 1 hour rated walls (see Design for Additional
Angle Fastener UL Rated Wall Design for
Details).
Additional Details).
Damper
Retaining Angle/Flange
Duct
Retaining Angle Grille (supplied
Grille (supplied by others) by others)
Type B
Figure 12: Wood Stud - Grille 1/4 in. minimum
total clearance
Figure 13: Metal Stud - Grille
(See Section 1)
On types R, CO & CR factory
1/4 in. minimum Duct
furnished duct collar
total clearance Sleeve
qualifies as breakaway
Retaining Angles (See Sleeve Requirements)
connection.
(See Section 4) Wall or Floor
Type A
Retaining Angles
Wall or floor
Wall or floor
Wall or Floor
Max. 6Maximum
in.
Maximum Maximum
Maximum 6 in.
6 in. “K” side 6 in. Wall or
6 in. Retaining angle leg
Floor
shall not exceed 7 in. 1 in. min.
(178mm) overlap
Four sides Sleeve
Mounting Angles
Damper (See Para. 4)
Sleeve
Damper
Max. 6 in. Damper 1/4 in. minimum
total clearance
Duct (See Para. 1) Damper
Duct
Duct
Damper Type C, CO, CR, & R
Retaining Angles Type B
Duct Duct
Type A Sleeve
Retaining Angles (See Sleeve Requirements)
Factory or Field installed
Wall Sleeve
or Floor (See Section 4) Factory Sleeve Factory Sleeve
Type B
Type A
Damper
Damper
Wall or floor
Wall or floor
Damper
On types R & CR factory
Retaining angle leg furnished duct collar
shall not exceed 7 in. qualifies as breakaway
(178mm) connection (See Connecting
Sleeve Ducts to Fire Damper Sleeve)
Damper
Duct Damper
Type B
Transverse Joints
The transverse joints shown below are approved as breakaway connections.
• A maximum of two #10 (19mm) sheet metal screws on each side and on the bottom may be used. The
screws should be located in the center of the slip pocket and penetrate both sides of the slip pocket.
• Dampers up to 20 inches (508mm) high may use transverse joints on the top and bottom and Drive Slip
joints (see Figure 16) on the sides.
(Attach per
manufacturer’s
instructions) 3/8 in. bolts in corners
between all angles
Figure 18
Proprietary Flange System Breakaway Connections
(TDC by Lockformer, TDF by Engle)
TDC and TDF systems are approved as breakaway connections when installed as described in the TDC or TDF
addendum to the SMACNA Duct Construction. Standard 6 in. (152mm) metal clip may be used with spacing as
shown in diagram (see Figure 19 & 20). 33⁄8 in. (9.5mm) metal bolts and nuts may be used to fasten together corner
pieces (see Figure 21). Clip Spacing Std. Clip
Length
9 in.
6 in. 6 in. 6 in.
60 in. Duct
4 Req’d. Duct End
Clip Spacing
7 in. Std. Clip 7 in. Flange
Length
48 in. Duct
3 Req’d. 9 in.
5 in. 5 in. Corner Piece
6 in. 6 in. 6 in.
Sleeve Duct 60Duct
36 in. in. Duct
3 Req’d.
4 Req’d.
5 in. 5 in.
7 in. 7 in.
24 in. Duct
48 in. Duct
2 Req’d. 3/8 in. bolt
Typical TDC/TDF joint 3 Req’d. (optional)
18 in. Duct & 5 in. 5 in.
Figure 19
Sleeve Duct
Smaller
1 36 in. Duct
Req’d. CL
3 Req’d. Duct
5 in. 5 in.
24 in. Duct
2 Req’d.
Typical TDC/TDF joint
18 in. Duct &
Smaller
1 Req’d. CL Figure 21
Duct
Figure 20
10 Curtain Fire Dampers
No Connecting Duct or Transfer Opening
Openings where duct does not attach on either side will not
require a breakaway connection. Transfer openings are typical of
a non-ducted installation (see Figure 22).
• Sleeve may end flush with the rated wall/floor on both
sides
• Refer to Securing the Damper/Sleeve Assembly to
Wall/Floor Openings for securing retaining angles to
the sleeve.
Damper Maintenance
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use
mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and
jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust.
Damper Troubleshooting
The following is a possible cause and correction list for common concerns with the dampers.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Product warranties can be found online at Greenheck.com, either on the specific product page or in the literature
section of the website at Greenheck.com/Resources/Library/Literature.
Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
GFC 481324 • DFD DFDX FD FDX, Rev. 7, November 2018 Copyright 2018 © Greenheck Fan Corporation