Professional Documents
Culture Documents
Hydrocom Specification Petronor NP HISA V1 - 0
Hydrocom Specification Petronor NP HISA V1 - 0
0
for
PETRONOR
Bilbao
Version 1.0
1 PREFACE .............................................................................................................1
2 ABBREVIATIONS .................................................................................................2
3 INTRODUCTION ...................................................................................................3
4 OPERATING CONDITIONS..................................................................................4
6.4 Block-diagrams and function of the control logic in the DCS ............................................. 10
6.4.1 Basics .................................................................................................................................. 10
6.4.2 Make-up 2nd stage ............................................................................................................... 10
6.4.3 Make-up 1st stage................................................................................................................ 13
6.4.4 Recycle stage ...................................................................................................................... 15
6.4.5 Enable Hydraulic Unit.......................................................................................................... 17
6.4.6 Enable HydroCOM CIU ....................................................................................................... 17
Part of the gas in the cylinder flows back into the suction chamber.
After closing the suction valves with electronic commands,
compression of the remaining gas in the cylinder is started.
-1-
2 Abbreviations
Throughout this document the following abbreviations and terms are
used:
-2-
3 Introduction
The HydroCOM compressor control system is an integrated
compact solution which is capable to adjust gas flow (capacity) of a
compressor steplessly between 30% (depending on operating
condition and gas) to 100%.
The control task itself, however, is not done inside the CIU.
Therefore, controllers have to be implemented in the DCS. This
document describes the layout of the control system and how the
controller output signals must be scaled and limited to allow highest
performance of HydroCOM system.
-3-
4 Operating conditions
Among others the following operating conditions as design condition
are defined:
Name Gas MOL-weight Suction pressure End pressure Suction temp. Minimum load
000 (Design) H2+CH4+ 2.7 / 5.7 13.6 / 65.5bara 66.2 / 91.3bara 38.0 / 65.0°C 30% / 30%
200 (Nitrogen) N2 28.0 / 28.0 7.8 / 17.2bara 17.8 / 25.1bara 33.0 / 40.0°C 100% / 100%
Remarks: first values are make-up unit / second values are recycle
-4-
5 Scheme of the Plant
Two compressors are made of three stages (four cylinders, one for
each stage make-up and two for stage recycle) to compress gas in
two separate units: The first two stages compress gas as make-up
unit. The third stage as recycle unit delivers gas of the discharge
make-up and recycle of the process.
PT
MAKE UP A RECYCLE A
PT PT PT
PROCESS
1st stage 2nd stage 3rd stage
FT
MAKE UP B RECYCLE B
PT
Spill back valve
-5-
6 Controller Layout
6.1 Control strategy
The tow stages of the make-up unit maintain the pressure
downstream the process acc. to the demand of gas. The recycle
stage controls the total flow to the process.
-6-
6.1.4 Basic control layout
Basically the main control variable is the pressure downstream the
process. Thus a pressure transmitter senses this pressure and
transmits the value to the DCS.
The recycle stage controls the total flow to the process (combined
flow make-up and recycle gas of the process) according a manual
load signal.
Setting of
Split-point
A A or (M) M
W W
PIC PIC HIC 090
Split- Split-
Range Range
(Manual (Manual
Input) Input)
PT
PROCESS
1st stage 2nd stage 3rd stage
FT
MAKE UP B RECYCLE B
PT
-7-
6.2 Tasks of control
The concept is based on a complete integration of the control logic
in the DCS.
-8-
Main motor
Main Motor running status
Compressor A / B
CIU Error
6.3 Signals between field and DCS
CIU Warning
GIM of CIU of
-9-
DCS
SIM 1 of CIU of
Load signal 1st stage
Compressor A/ B
SIM 3 of CIU of
Compressor A/ B Load signal 3rd stage
Binary Signal
Analogue Signal
between the Hoerbiger Compressor Interface Unit (CIU) and the
The following diagram shows the binary and analogue signals
23.03.05 / LE
6.4 Block-diagrams and function of the control logic in the DCS
6.4.1 Basics
One control loop in the DCS is used per compressor stage, in total
four. Common logic functions have to be integrated in the DCS too.
In In
TDON TDOFF
Out Out
Time < delay time Time > delay time time
Pressure
Automatic or (Manual)
0..100% Load Signal
PI-Controller
Make-up unit
Set point
Pressure
The figure below shows how this load signal has to be processed:
- 10 -
x / 100%
Split point
Load Signal
Make-up unit A
Load Signal
Make-up unit B
Spillback valve:
Automatic / Manual
Minimum load x = 30%
- 11 -
The figures below show how these two independent loadsignals
have to be processed:
Activate = 1
Activate Stop ramp
Start ramp
MIN
Minimum load x = 30%
Stop ramp
Activate = 1
Activate Stop ramp
Start ramp
MIN
Minimum load x = 30%
Stop ramp
- 12 -
6.4.3 Make-up 1st stage
The figures below show the control loop of the make-up 1st stage of
each compressor:
Suction
Pressure 2nd stage
Automatic
0..100% Load Signal
PI-Controller
Make-up 1st stage
Set point
Suction Pressure
2nd stage
The figure below shows how this load signal has to be processed:
x / 100%
Split point
Load Signal
Make-up A
1st stage
Load Signal 0..100% 0..100% x..100%
Split range Limitation
Make-up 1st stage
Load Signal
Make-up B
1st stage
Spillback valve:
Automatic / Manual
Minimum load x = 30%
- 13 -
As soon as the load signal is processed in the limitation block it has
to be divided for both compressors.
The figures below show how these two independent load signals
have to be processed:
Activate = 1
Activate Stop ramp
Start ramp
MIN
Minimum load x = 30%
Stop ramp
Activate = 1
Activate Stop ramp
Start ramp
MIN
Minimum load x = 30%
Stop ramp
- 14 -
binary signal is used. As soon as the compressor is on idle, the
compressor has to be stopped within a certain time (typical 3
minutes). For further details please refer to the section “Stop-Ramp”.
Load Signal
Manual Recycle unit A
0..100% x..100%
PI-Controller Limitation
Load Signal
Recycle unit B
- 15 -
The figures below show how these two independent loadsignals
have to be processed:
Activate = 1
Activate Stop ramp
Start ramp
MIN
Minimum load x = 30%
Stop ramp
Activate = 1
Activate Stop ramp
Start ramp
MIN
Minimum load x = 30%
Stop ramp
- 16 -
6.4.5 Enable Hydraulic Unit
The figure below shows the block diagram to enable/disable the
Hydraulic Unit.
1= HU running
HU Start HU Motor
local / automatic 0= HU off running status
1=error
Emergency stop
From DCS
1=error 1= HU enabled
HydroCOM Motor HU
OR NOT OR
system error Enable
0= HU off
0= operation
Maintenance switch
1= maintenance
Figure 15.: Block diagram to enable and disable the HU in the DCS
- 17 -
6.5 Description of functions blocks
6.5.1 PI-Controller (proportional gain Kc and integral time Ti)
The PI controllers can be adjusted to the controlled system with their
controller parameters, the integral time (Ti) and the proportional gain
(kc).
kC 0.8-3.5
Ti 10-90s
⎛ t ⎞
y (t ) = k c ⎜ e (t ) + ∫ e(τ ) dτ ⎟⎟
1
⎜ Ti
⎝ 0 ⎠
kC proportional gain
Ti integral time
e control error
y control signal
- 18 -
6.5.2 Split Range
The HydroCOM-system as well as the bypass valves are using the
same controller output signal. Therefore, the control signal is split up
into two signals: One for the HydroCOM actuators and one for the
spillback valve (bypass valve).
HydroCOM 1 = error
NOT AND
system error
100 %
Selector
input = 0
x / 100% Split point to
Selector Split range
x% function block
Selector
input = 1 Minimum load x = 30%
Split Range
Split Range Bypass valve/HydroCOM
100% Bypass valve/HydroCOM 100% 100% (in failure condition) 100%
(open) (open) HydroCOM
Control Signal bypass valve
Control Signal bypass valve
B
O
yp
oC
ass
as
dr
s
Output:
Output:
Output:
Output:
Hy
va
valv
l ve
e
0% 0% 0% 0%
(closed) 0% SP=30% 100% (closed) 0% SP=100%
Input: controller output signal Input: controller output signal
- 19 -
6.5.3 Limitation
This function prevents the system on overheating at part load. If the
HydroCOM is driven on low load for a longer time, then the suction
gas temperature increases due to valve losses which occur during
suction and reverse flow. Following diagrams show the suction gas
heating effect based on actual load conditions. To prevent damage
to suction valves and to the compressor, the load has to be limited.
120°C
110°C Discharge temperature
100°C
90°C
80°C
70°C
60°C Suction temperature
50°C
Minimum Load
40°C
30°C
20°C
10°C
0°C
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Capacity [%]
Limitation
HydroCOM Make-up 1st and 2nd / Recycle
100%
signal HydroCOM
M
Limited control
O
C
ro
Output:
yd
H
x = 30%
Minimum load
0% 100%
Input: split range output
- 20 -
Typically the limitation function is programmed as follows:
This block allows higher controller dynamic by cutting off the lower
and upper dead band.
These dead bands are caused by the fact that the HydroCOM is an
universal system for all sizes of reciprocating compressors. To
compensate the different geometries the control signal to the CIU
has to be scaled. In between those two points the change rate of the
capacity is almost linear and needs not to be linearized.
94% 19,0mA
69% 15,0mA
63% 14,0mA
control signal to CIU
56% 13,0mA
50% 12,0mA
44% 11,0mA
38% 10,0mA
31% 9,0mA
25% 8,0mA
Minimum Load
19% 7,0mA
13% 6,0mA
6% 5,0mA
0% 4,0mA
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
compressor capacity (equals to controller signal)
- 21 -
From above diagram following control current limits can be
determined:
- 22 -
6.5.5 Start-ramp
In general a linear ramp function leads the make-up 1st , 2nd and
recycle stage of the compressors smoothly from 0% load to the
actual load signal, at least to minimum load from Limitation block. At
this point the ramp is quit and operation is passed over to the PI-
controller of the DCS.
CIU Enable
on
off
time
Typically 1 to 5 minutes
Start ramp
30%
0% Start-Ramp
stopped time
For details to start the compressor please refer to the section “Start
sequence”.
- 23 -
6.5.6 Stop-ramp
In general a linear ramp function leads the make-up 1st , 2nd and
recycle stage of the compressors smoothly from the actual load
signal to 0% load. At this point the ramp is quit and the operator has
to stop the compressor within a certain time (e.g. three minutes).
Activate
Stopramp
on
off
time
Typically 1 to 5 minutes
Start-Ramp
Stop ramp
30% stopped
0%
time
For details to stop the compressor please refer to the section “Stop
sequence”.
- 24 -
6.5.7 Set point interstage pressure
The PI-controller compares the actual interstage pressure with a
defined set point. This set points can be calculated out of the actual
suction pressure make-up 1st stage and discharge pressure make-
up 2nd stage to reach equalized compression ranges over all two
stages.
Example:
ps1 ps2 pd
Cond. 000 (ITKK) 13.59 29.58 66.20
Ideal 13.59 29,96 66.20
Correction factor 0.99
ks2 = 0,99
- 25 -
7 Special operating conditions
7.1 Start Sequence
Before starting the compressor main drive, the hydraulic unit must
be started manually or automatically (e.g. together with the oil-pump
of the compressor).
Compressor
drive
on
Compressor drive is started and the
signal “Main motor running status” is
off set in the DCS.
time
Main motor
running status
on
off
time
Motor speed
max
After short time, normal speed of the
0 compressor drive is reached.
CIU Enable time
on
After 20s the enable signal for the CIU
off is set by the DCS. The compressor is
time ready to feed gas.
Typically 1 to 5 minutes
- 26 -
7.2 Stop of compressor
To stop the compressor and do not harm the process by immediate
load steps (capacity reduction) the compressor has to brought to idle
operation. This will be done by a stop ramp. This sequence ends in
an unloaded compressor. As soon as the compressor is unloaded
the compressor has to be stopped within a certain time (e.g. the next
three minutes).
Activate
Stopramp
on
By setting the signal “Activate Stop-
off ramp” the stop-ramp function is
Typically 1 to 3 minutes
time initialized.
Control signal Load signal to Load signal from This functions will ramp the load down
to scaling block Scaling block Limitation block to idle operation.
100%
off
CIU Enable time
Time delay 30seconds
on
off
time
- 27 -
7.3 Shutdown sequence of the HydroCOM system
The processing of this signal has to be done in the DCS.
At the same time the binary signal “HU motor running” will be reset.
Once the “HydroCOM system error occurred, the enable to the CIU
is reset as well (delayed for 30sec). For details refer to section
“Block diagrams to Enable HydroCOM”.
0=error
CIU Error NOT
Hydraulic Oil
0=low
Level Low NOT
Shut down
- 28 -
7.3.1 CIU Error
The integrated diagnostic function of the HydroCOM-system has
detected one or more electric or electronic errors. Concerned
suction valves have been unloaded automatically.
Hydraulic 1=Shutdown HU
1=>80°C Hydraulic Oil Temp.
Oil Temperature
Shut down HU
High-High
- 29 -
7.4 HydroCOM system warning
The processing of this signal has to be done in the DCS.
Hydraulic 1=Warning
Oil Temperature
high
Hydraulic 1=Warning
Oil Pressure
low
- 30 -