Step 1: Given Data
Step 1: Given Data
Sl No Type of Self Weight (kN) Floor Finish (kN) Terrace Water profing
Floor
Head Type 1 3 2.55 - 0.15 - 0.15 = 2.25 Type 2 2 5.55 - 0.225 - 0.225 =
1
room
-- -- Type 3 2 4.05 - 0.225 - 0.225 =
--
Other
2 Type 2 4 4.165 - 0.15 - 0.15 = 3.865 Type 5 4 4.05 - 0.225 - 0.225 =
floors
Other
2
floors
Other Type 2 4 4.165 - 0.15 - 0.15 = 3.865 Type 5 4 4.05 - 0.225 - 0.225 =
2
floors
w4 =256.289 + 861.357 + 52.84 + 193.988 + 121.874 + ( 480.872 / 2) + 58.634 + ( 58.634 / 2 ) +53.663 +( 143.1 /
2 ) kN = 1939.948 kN
841.592
2 3 9 2031.003 164511.243 259.712
841.592
3 2 6 2031.003 73116.108 115.428
4 1 3 1790.567 16115.103 25.441
Total 7792.521 533094.966 841.592
B. Level 3 :
Q3 + 2Q3 + 2Q3 + Q3 = 259.712
So Q3 = 43.285 kN
჻ Shear at End column = 43.285 kN
Shear at intermediate Column = 2 x 43.285 kN = 86.57 kN
C. Level 2 :
Q2 + 2Q2 + 2Q2 + Q2 = 115.428
So Q2 = 19.238 kN
჻ Shear at End column = 19.238 kN
Shear at intermediate Column = 2 x 19.238 kN = 38.476 kN
D. Level 1 :
Q1 + 2Q1 + 2Q1 + Q1 = 25.441
So Q1 = 4.24 kN
჻ Shear at End column = 4.240 kN
Shear at intermediate Column = 2 x 4.24 kN = 8.48 kN
Terrace Water profing (kN) Total Weight (kN)
Absent 777.459