Professional Documents
Culture Documents
Huawei FM1000A40 V200R003C00 CT Product Overview
Huawei FM1000A40 V200R003C00 CT Product Overview
Huawei FM1000A40 V200R003C00 CT Product Overview
V200R003C00
Product Overview
Issue Draft B
Date 2017-01-10
and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.
Website: http://e.huawei.com
Purpose
This document describes the FusionModule1000A prefabricated all-in-one data center
solution (FusionModule1000 for short) in terms of its overview, typical application scenarios,
product architecture, and key technical specifications, helping readers to systematically
understand the FusionModule1000.
Intended Audience
This document is intended for:
Sales engineers
Technical support engineers
System engineers
Symbol Conventions
The symbols that may be found in this document are defined as follows:
Symbol Description
Indicates an imminently hazardous situation which, if
not avoided, could result in death or serious injury.
Symbol Description
Calls attention to important information, best practices
and tips.
NOTE is used to address information not related to
personal injury, equipment damage, and environment
deterioration.
Change History
Changes between document issues are cumulative. The latest document issue contains all the
changes made in earlier issues.
Contents
1 Overview
1.1 Positioning
Huawei has developed the FusionModule1000, a green data center solution, based on a
thorough study on the reform and impact of the cloud computing to traditional data centers
and the practical experience of dozens of global cloud computing centers. The solution
features a flexible, hybrid, and modular design to help customers construct green
infrastructure adapting to cloud computing.
The FusionModule1000, foundation for cloud computing in enterprise data centers, integrates
power distribution, monitoring, cooling, racks, cable routing, and fire extinguishing. It is
characterized by good waterproof and quakeproof performances. The FusionModule1000
helps enterprise telecom operators and Internet operators to rapidly deploy data centers and
has unique advantages in the fields of disaster relief, military affairs, oil exploitation, survey,
and enterprise data for its availability in outdoor environments.
The FusionModule1000, located at the bottom layer of a data center, provides basic physical
construction for all services in the data center.
1.2 Benefits
The FusionModule1000 is a small-capacity prefabricated all-in-one data center that integrates
the container mechanical structure, power supply and distribution system, cooling system,
management system, fire extinguishing system, integrated cabling system, and server cabinets.
It features high security and reliability, rapid deployment, low cost, high efficiency, and
intelligent management.
Rapid Deployment
Streamlined manufacturing, professional division of labor, and good work conditions
ensure that modules and products of the FusionModule1000 are produced efficiently
with strict quality control. The standard manufacturing period is six to eight weeks.
Infrastructures such as cooling equipment, power supply equipment, and racks are
factory-installed. You only need to provide network cables, power cables, and water
pipes onsite for commissioning.
System commissioning is completed in factories, and therefore onsite deployment and
equipment room commissioning take less than one week.
The container can be easily relocated as it can be transported on level-3 roads and
applies to various scenarios such as dynamic data service deployment, military affairs,
disaster relief, and field operations.
Intelligent Management
Manages infrastructure of the FusionModule1000 in a central manner.
Supports O&M using a mobile app and remote unattended operation. Full WiFi coverage
is realized inside the container using a WiFi converter. WiFi coverage outside the
container is realized using a customer router gateway (optional).
Monitors equipment effectively in real time.
Monitors environments in real time to identify potential risks.
Provides various methods of collecting and analyzing power consumption data to realize
precision energy efficiency analysis. Such data is fundamental to improving the power
usage effectiveness (PUE). You can customize the data collection and analysis methods.
Provides a robust security mechanism to protect equipment and ensures a proper
environment.
Provides standard simple network management protocol (SNMP) ports to communicate
with third-party network management systems (NMSs).
The FusionModule1000 must not be transported with the CT equipment, power modules, and batteries
installed.
The FusionModule1000 can be deployed as a small integrated data center (IDC) for
enterprises in diverse environments such as the seaside, industrial parks, campuses, urban, and
suburban areas to meet specific application requirements such as business blowout and
capacity expansion.
The FusionModule1000 is most preferred when a data center must be quickly constructed and
deployed due to urgent service requirements.
3 System Architecture
(1) End door (for maintaining outdoor units) (2) Lock rod
(3) Ventilation window for the outdoor unit compartment (4) Container feeder window
(1) External fire alarm horn strobe (2) Emergency door (3) Air intake window
release button
(4) Device installation (5) Air exhaust window (6) End door (main
door/emergency door entrance)
(7) Card reader (8) Container ground point (9) Fire control box
Container Door
900 mm wide fire door:
The door resists fire for 90 min typically and up to 120 min if special treatment is
applied.
The door is protected to IP65.
The door uses a WK03 class theftproof structure.
The door is 900 mm wide (net) and 2250 mm high (net). It opens in and out rightwards
(the hinge is on the right side of the door), with a door handle outside and a pushrod
structure inside.
The door closer allows the door to open to an angle of at least 120°, and it stops the door
at the maximum position to keep the door open.
When the door is open, the door, door frame, and mechanical parts can withstand the
door weight and will not misshape permanently within 48 hours with a static load of 15
kilograms at any part.
The fire door uses rubber strips with a framework and composite adhesive to ensure the
waterproof performance.
1200 mm wide fire door:
The door is used for moving equipment in or out and can be opened only inwards.
The door resists fire for 90 min typically and up to 120 min if special treatment is
applied.
The door is protected to IP65.
The door uses a WK03 class theftproof structure.
The door is 1200 mm wide (net) and 2250 mm high (net). It opens in rightwards (the
hinge is on the right side of the door), with a pushrod structure inside.
The door closer allows the door to open to an angle of at least 120°, and it stops the door
at the maximum position to keep the door open.
When the door is open, the door, door frame, and mechanical parts can withstand the
door weight and will not misshape permanently within 48 hours with a static load of 15
kilograms at any part.
The fire door uses rubber strips with a framework and composite adhesive to ensure the
waterproof performance.
Container Specifications
Table 3-1 lists the container specifications.
Item Specifications
Container 40 ft standard ISO shipping container (40 ft x 8 ft x 9.5 ft)
Container The thermal transmission coefficient of the container is 0.4 W/(m2 x K) or
heat less.
insulation
performance
Integrated Power cables and signal cables are routed separately.
cabling
Protection IP55/IP65 (optional)
level
Installation Directly installed on the ground.
mode NOTE
The container can be installed on a concrete platform, with four 300 mm high steel
bases connected to the concrete platform using M16 bolts.
Item Specifications
Weight Empty container (excluding servers): 16,000 kg; fully-loaded container: <
25,000 kg
Typical Eight cabinets; dimensions (H x W x D) of each CT cabinet
cabinet (user-supplied): 2200 mm x 600 mm x 800 mm
capacity
Reliability The intelligent access control system and mechanical locks provide
multifold security protection and meets class 3 theftproof requirements
in EN 1627–EN 1630.
The access control system can be configured with permission at
different levels to monitor door status and generate alarms.
Standard container air vents feature good security and ventilation
designs.
Ground busbars are installed in the container for internal equipment
and the container itself. Surge protection measures are provided for
power ports and network ports to ensure the safety of the data center.
Real-time video surveillance is implemented for the protected area.
The container can withstand the 30 m/s wind speed when it is in
operation.
The container meets NEBS zone 3 antiseismic requirements.
Fireproof performance: The burning behavior of decorative materials
complies with the Code for Fire Prevention in Design of Interior
Decoration of Buildings (GB50222-95) of China. The materials can
withstand fire for 120 minutes.
Thermal insulation performance: The thermal transmission coefficient
of the container is 0.4 W/(m2 x K) or less.
Waterproof and dustproof performance: All external ports are protected
to IP55 (weather-tightness test) of the GB4208/IEC529 standard and
can be protected to IP65 if required.
Corrosion resistance: The container uses weathering steel and surface
treatment and passes the 720-hour cyclic salt spray test (1440-hour test
if special coating is applied).
Anti-mould performance: The container passes the 24 hours x 28 days
mould growth test.
Bullet-proof performance (optional): The container passes the 10 m
rifle test.
(1) Air conditioner (2) Low temperature component (3) Cabinets (4) Cold aisle
outdoor units for air conditioners
(5) Main input PDB (6) Entrance room (7) Fire (8) AC/DC
cylinder power system
(9) Battery racks (10) Air conditioner indoor (11) Hot
units aisle
The low-temperature component is deployed for air conditioners when the temperature is in the range of
–40°C to –20°C. When the temperature is below 0°C, the low-temperature component assembly at the
container level should be deployed.
Suspended Ceiling
Cold and hot aisles are isolated by a suspended ceiling to prevent mixture of cold and hot
air.
The aisle sealing plates are separate from cabinets and secured to the aluminum guide
rails at the top of the container.
The sealing plates for the suspending ceiling of the long aisle are hinged and can be
easily opened when overhead cables need to be maintained.
The suspended ceilings of the hot and cold aisles are assembled by three sealing plates.
The sealing plates on both sides can be removed when there is a need to maintain cables.
The hot aisle door is a glass sliding door that is installed before transportation.
(1) Sliding door guide rail (2) Glass door panel (3) Damper
(1) Signal cable feeder window (2) Power cable feeder window (3) Power PDB
Figure 3-7 shows the ports reserved for the humidifier water refill pipe and condensate
drainpipe.
Figure 3-7 Ports reserved for the humidifier water refill pipe and condensate drainpipe (unit: mm)
(1) Port reserved for the condensate (2) Port reserved for the humidifier water refill
drainpipe pipe
The port reserved for the humidifier water refill pipe is a 1 inch ball valve with internal threads. The port
reserved for the condensate drainpipe is a DN25 PP-R pipe port.
(1) Battery racks of the DC power system (2) Main input PDB
(3) AC/DC power system (4) Power PDB
Item Specifications
Rated input 380 V AC/400 V AC/415 V AC
voltage
Rated input 50 Hz/60 Hz
frequency
Input switch 250 A/3P MCCBx2
Output switch Route A main busbar output: 160 A/3P MCCBx1+63 A/3P
MCBx2+40 A/3P MCBx4+16 A/1P MCBx1
Route B main busbar output: 160 A/3P MCCBx1+63 A/3P
MCBx2+40 A/3P MCBx4+16 A/1P MCBx1
ATS combined output: 10 A/1P MCBx7+32 A/3P MCBx1+10 A/1P
RCDx1
Surge 60 kA (8/20 us)
protection
level
Enclosure IP20 (front)
protection
level
Cabling mode Top cabling for routes A and B, bottom cabling for the ATS
Installation Floor-mounted
mode
Dimensions 2000 mm x 600 mm x 300 mm
(H x W x D)
Monitoring Main input PDB total input electricity display and measurement:
three-phase voltage, current, reactive power, active power, and power
factor. The meter implements standard RS485 communication with the
monitoring host.
Item Specifications
System Dimensions (H 2000 mm x 600 mm x 600 mm
x W x D)
Rated capacity 1200 A (two to twenty-four 50 A rectifiers)
Cooling mode Natural cooling
Installation Floor-mounted (installed on the container floor or an ESD
mode floor)
Cabling mode Routed in and out from the top
Maintenance Maintained and operated from the front and located along a
mode wall with at least 100 mm clearance
Item Specifications
Protection IP20
level
AC Input mode 220/380 V AC, three-phase
power
distributi Input voltage 85–300 V AC (L-N); rated voltage: 220 V AC
on
Input capacity 1x200 A/3P (MCCB)
Surge 20 kA/40 kA, 8/20 µs
protection
DC Output voltage 45–58 V DC, 53.5 V DC by default
power
distributi Rated output 72 kW
on power
Battery route 2x1250 A (NT4)
Load route 4x500 A (NT3), 2x400 A (NT2), 2x100 A (NT00)
Surge 10 kA/20 kA, 8/20 µs
protection
Rectifier Efficiency > 98%
Output power 3000 W (176–300 V AC)
Operating –40°C to +75°C
temperature
Dimensions (H 40.8 mm x 105 mm x 281 mm
x W x D)
Weight < 2.5 kg
Power factor ≥ 0.99 (load ≥ 50%)
THD ≤ 5%
Monitori Alarm input Four Boolean value inputs
ng
module Alarm output Eight dry contact outputs
Communicatio Ethernet, RS485/RS232
ns port
Alarm storage 10,000 alarms and system logs
Display mode LCD
3.2.4 Batteries
Batteries store electricity.
(1) Air conditioner outdoor units (2) Air conditioner indoor units
3.3.2 Composition
3.3.2.1 Indoor Unit
Appearance
Figure 3-13 shows the indoor unit of a NetCol5000-A cooled in-row precision air conditioner.
Components
The indoor unit consists of a compressor, oil separator, fan, heat exchanger, one-way-valve,
filter dryer, sight glass, electric heater (optional), electrode humidifier (optional), electronic
expansion valve, water pump (optional), display panel, and other components.
Compressor
The DC variable-frequency compressor provides the cooling capacity ranging from 20%
to 100% to meet load requirements.
Oil separator
It is an oil-gas separator which separates the lubricant brought out due to exhaustion of
the compressor and brings back the separated lubricant to the compressor.
Fan
The EC fan implements stepless speed adjustment.
Heat exchanger
The efficient finned evaporator, an important part in the refrigerating system, absorbs
heat from indoor air to ensure that the indoor temperature and humidity meet
requirements.
Electronic expansion valve
The flow regulator uses a miniature controller to control the operation of the step motor,
thereby changing the pass-through area of the valve to regulate the flow of refrigerant.
One-way valve
The one-way valve efficiently controls backflow of gas or liquid.
Filter dryer
The filter dryer absorbs moisture from the refrigerant pipes and filters out foreign
matters, which reduces the component damage probability and improves operating
efficiency and reliability of components.
Sight glass
The sight glass allows users to observe the refrigerant flow and the content of gas and
liquid for easy maintenance and optimization.
Electric heater
The PTC heater features quick start, large heating capacity, and even heat dissipation. It
has multiple protection mechanisms to ensure the secure and stable running of the
equipment.
Electrode humidifier
The electrode humidifier provides stepless adjustment of humidification capacity and
precise control of indoor humidity.
Water pump
The water pump provides power for top drainage with 4 m.
Display panel
The 7-inch display panel with the true-color touchscreen provides user interfaces for
query, setting, monitoring, and maintenance.
3.3.2.2 Ports
Table 3-5 shows the physical ports on the NetCol5000-A in-row precision air conditioner.
Item Specifications
Refrigerant liquid pipe Copper pipe, external diameter 5/8 inch, pressure resistance ≥
4.5 MPa, soldering
Refrigerant gas pipe Copper pipe, external diameter 3/4 inch, pressure resistance ≥
4.5 MPa, soldering
Humidifier water inlet Reserved port: BSPP 1/2 in.; thread connection
pipe
Top drainpipe Reserved interface: 1/2 inch reserved copper tube
Bottom drainpipe Reserved port: threaded port for copper pipe with a diameter
of 5/8 in
Item Specifications
Operating 18–45°C
temperature
Operating 20%–80% RH
humidity
Storage –40°C to +70°C
temperature
Storage humidity 5%–95% RH (non-condensing)
Applicable Work with NetCol500-A026 (including a low-temperature
outdoor component): –40°C to +45°C
temperature Work with NetCol500-A026: –20°C to +55°C
Heating capacity 4 kW
Humidifier 1.5 kg/h
capacity
Protection level Indoor unit: IP20
Outdoor unit: IPX5
Installation mode Installed on an ESD floor or rack
Piping and Route pipes and cables from the top or bottom
cabling
Altitude 0–1000 m, derating at above 1000 m, max. 4000 m. For detailed
derating data, contact Huawei technical support.
Item Specifications
Cooling mode Air cooled
Refrigerant R410A
Air supply mode Horizontal flow
Dimensions (H x W x D) 2000 mm x 300 mm x 1100 mm (cabinet dimensions)
Certification REACH, RoHS, CE
Appearance
Figure 3-14 shows the model and appearance of the NetCol500 outdoor unit.
Product Composition
Figure 3-15 shows the composition of the NetCol500 outdoor unit.
Specifications
Figure 3-16 shows the dimensions of the NetCol500.
Table 3-10 lists the technical specifications of the NetCol500 outdoor unit.
Outdoor unit installation environments are classified as follows based on the harshness:
Class A (controlled environment): indoor environments where the ambient temperature and humidity
are controlled, including rooms where people live
Class B (uncontrollable environment): indoor environments where the ambient temperature and
humidity are not controlled or general outdoor environments with simple shielding measures where
the humidity sometimes reaches 100%
Class C (harsh environment): marine environments within 3.7 km from the coast or outdoor land
environments with simple shielding measures within 1.2 km from a pollution source
Class D (marine environment): environments within 500 m from the coast
(1) Safety valve (2) Liquid line port 1 (3) Liquid line port 2
(4) Condensing pressure control valve (5) Gas pipe port 1 (6) Gas pipe port 2
A low-temperature component is mandatory when the outdoor ambient temperature may drop
below –20ºC.
Item Specifications
Heater box power supply 220 V AC to 240 V AC, 1 P, 50 Hz/60 Hz
Heater box voltage tolerance Rated voltage±10%
Heater box frequency tolerance Rated frequency±3 Hz
Refrigerant R410A
Liquid pipe outer diameter 5/8 inch (15.9 mm)
Gas pipe outer diameter 7/8 inch (22.3 mm)
Dimensions (H x W x D) 944 mm x 632 mm x 507 mm (with
packing)
828 mm x 470 mm x 300 mm (without
packing)
Expansion bolt hole M12x60
Storage temperature –40°C to +70°C
Storage humidity 5%–95% RH (non-condensing)
Maximum operating pressure 4.35 MPa
NetEco V600R007C80 or a later version is applicable to the FusionModule1000. The iManager NetEco
configurator can be used for configuration.
The VESDA and hydrogen controller are optional and not configured by default.
Common card readers are configured for the access control system by default, and they should be
used at an ambient temperature ranging from –40°C to +85°C. Customized three-in-one fingerprint
and card readers with keypads are also supported, and they should be used at an ambient temperature
ranging from –10°C to +55°C. The three-in-one card readers cannot be used outdoors when the
ambient temperature is below –10°C or exceeds 55°C.
The camera uses an SD card with a capacity of 64 GB for storage by default, and supports 7x24
recording at 720P/512K. A video management device (VCN500) should be configured if there is a
need of longer-time storage, management, and configuration of external cameras.
3.4.1 Overview
The management system includes the management software NetEco (optional) and
management hardware ECC800 and provides the following linkage features:
Hydrogen Linkage
If the hydrogen sensor and hydrogen controller are configured, the hydrogen controller
controls the hydrogen exhaust fan.
Fire Linkage
The ECC800 monitors the fire control panel onsite. Upon detecting a gas release alarm, the
ECC800 issues a release command to the air conditioners in the FusionModule1000 so that
they will shut down.
Component Layout
Figure 3-19 shows the management system component layout diagram.
(1) Temperature and humidity sensor (2) Network frame (3) Access actuator
(4) Smart ETH gateway (5) Pad (6) Camera
(7) AC actuator (8) WiFi converter
(1) Combined module (2) Status indicator (3) 3G/4G antenna port
(4) FE ports (WAN_1-WAN_2 and (5) AI/DI_1–6 sensor (6) RF_Z antenna port
LAN_1-LAN_2) input ports
(7) SW button (8) DO_1–2 dry (9) RS485 port
contact output (COM1–4/12 V)
(10) Default button (11) USB port (12) ECC800 main
control module
Specifications
Table 3-13 lists the ECC800 technical specifications.
Item Specifications
Power input Dual AC input and dual –48 V DC power supply
Rated voltage: 200–240 V AC/100–120 V AC
Rated frequency: 50 Hz/60 Hz
Input current: 6.7 A
Power output Rated voltage: 53.5 V DC
Output power of two power supplies: 2000 W (176–300 V AC);
940 W (linear derating at 85–175 V AC)
Output power of a single power supply: 1000 W (176–300 V
AC); 470 W (linear derating at 85–175 V AC)
Output current: 14 A
System memory 512 MB
Solid state disk 2 GB and 128 MB of storage space
Item Specifications
FE port expansion Two WAN ports, two LAN ports, and 10/100M communications
rate
RS485 serial port Reserves four RS485 ports with a default communications rate
expansion of 9600 bit/s.
Each port provides 12 V DC power with a rated current of 450
mA.
AI/DI expansion Supports six AI/DI ports to connect to smoke sensors, water
(RJ45) sensors, and temperature sensors.
Each port provides 12 V DC power with a rated current of 85
mA.
DO expansion Supports two expansion dry contacts with contact point capacity
(RJ45) of 20 W, maximum withstand voltage of 60 V DC, and rated
current of 0.5 A.
Supports two active DO ports with the output voltage of 12 V
DC and output current of 450 mA.
Wireless Supports wireless communication that complies with
communication IEEE802.15.4.
3G Supports 3G (WCDMA) communication and is compatible with 2G
(GSM) communication. A standard SIM card slot is provided.
NOTE
A SIM card can be used only in sites with signal coverage.
Indicators
Table 3-14 describes the indicators on the ECC800 monitoring module.
On the WebUI, restoring factory settings by one-click is supported. Click Maintenance >
Configuration File > Restore Factory Settings.
The monitoring module IP address restores to the default value.
The video device IP address restores to the default value.
Configuration parameters of each device restore to default values (except the access control
configuration parameters).
The container plan view configuration is cleared.
Alarm parameter configuration restores to default values.
The NetEco communication parameters restore to default values.
The container name restores to the default value.
The WiFi function is disabled.
Table 3-16 Ports on the independent deployment AI/DI unit front panel
AI/DI_1–AI/ Provide 12 V DC outputs for sensors and are compatible with 4–20 mA
DI_8 current signals, signals from current-based smoke sensors and water
sensors, dry contact signals, and NTC signals.
Pin definition:
3: 12 V DC, 54 mA
6: D-
7: D+
8: GND
(1) PWR_IN cascading (2) FE_1 cascading signal (3) PoE_1–2 ports
power port port
(4) PoE_3–4 ports (5) 48V_OUT1 power output (6) 48V_OUT2 power
port output port
(7) FE_2 cascading signal (8) PWR_OUT cascading (9) BLINK button
port power port
(10) Status indicator
Specifications
Table 3-17 lists the environmental specifications for a smart ETH gateway.
Item Specifications
Power input PWR_IN D-type power input terminal, for power cascading, input voltage
range: 45–55 V DC
Power output PWR_OUT D-type power output terminal, for power cascading, output
voltage range: 45–55 V DC
48V_OUT1 and 48V_OUT2, phoenix terminal, output voltage range:
45–55 V DC
FE port Two FE ports, RJ45 terminal with an indicator, 10/100M communication
rate, for the cascading between smart ETH gateways and the
communication with the upstream computer
PoE port Four PoE ports, RJ45 terminal with an indicator, 10/100M
communications rate, 12 V DC of power output, complying with
IEEE802.3at
BLINK If you press the BLINK button, the RUN indicator blinks intermittently at
button super short intervals (blinking at super short intervals for 0.5s and then off
for 0.5s) for 10 seconds. This indicates that the smart ETH gateway
reports the Media Access Control (MAC) address and equipment serial
number (ESN) to the ECC800.
Indicators
Table 3-18 describes the indicators on a smart ETH gateway.
(1) 48 V power port (2) PoE port (3) RS485 port COM2
(4) RS485 port COM1 (5) Address DIP switch (6) Status indicator
(7) BLINK button (8) WG_2 Wiegand (9) WG_1 Wiegand interface
interface
(10) AI/DI_2 dry contact (11) AI/DI_1 dry contact (12)
LOCK/GND/GATE/GND/door
status and magnetic lock port
Specifications
Table 3-19 lists the access actuator technical specifications.
Item Specifications
Item Specifications
DI input One DI input port for connecting to the door status switch
RS485 serial Two RS485 ports (one route) with the default communications rate of
port 9600 bit/s, physical port cascading supported (reserved function)
expansion
Wiegand Two Wiegand interfaces, 12 V DC card reader operating power output;
interface two routes of card readers can operate at the same time.
BLINK Press the button for less than 1 second to start blinking.
button Hold down the button for 1–5 seconds to search for a network and start
networking.
Hold down the button for more than 6 seconds to clear network
parameters.
Address DIP 4-pin address DIP switch
switch
E-label Supported
Indicators
Table 3-20 describes the access actuator indicators.
Communications Ports
The access actuator provides one DO port (LOCK/GND) and one DI port (GATE/GND).
Table 3-21 lists the LOCK/GND/GATE/GND port pin definitions.
Item Description
LOCK/GND LOCK 12V_OUT
(control
magnetic GND GND
locks) pin
sequence
GATE/GND GATE DI1
(door status)
pin sequence GND GND
3.4.6 AC Actuator
The AC actuator is used in a container data center to receive infrared signals or upstream
instructions for controlling lights or fans. The AC actuator can connect to the ECC800
controller by wireless networking (802.15.4).
Specifications
Table 3-22 lists the AC actuator environmental specifications.
Item Specifications
Item Specifications
RS485 port One route of dual RS485 ports, not isolated (reserved)
AI/DI Two AI/DI dry contacts, reserved
detection
BLINK Press the button for less than 1 second to start blinking.
button Hold down the button for 1–5 seconds to search for a network and start
networking.
Hold down the button for more than 6 seconds to clear network
parameters.
Indicators
Table 3-23 describes the indicators on the AC actuator.
(1) RF_1 antenna port (2) RF_2 antenna port (3) Reset (4) WPS button
(5) Status indicator (6) 48 V power port (7) PoE port
Technical Specifications
Table 3-24 lists the WiFi converter technical specifications.
Item Specifications
Power input One power input port with the 3-pin Phoenix terminal; input voltage
range: 36–60 V DC
WiFi function 2.4 GHz frequency, two antennas, supporting eight STA connections,
50 m WiFi coverage (no blockage)
Support the WPS button
PoE port One PoE port, complying with IEEE802.3AT, 25.5 W
Reset button Press and hold down the button for more than 5s to restore the factory
settings of the WiFi converter
WPS button Support fast WiFi access by WPS
WPS function: If you choose Advanced settings > WPS connection on the WLAN of the intelligent
device and press the WPS button on the WiFi converter at the same time, the intelligent device will
quickly connect to the WiFi hotspot of the container.
Indicators
Table 3-25 describes the indicators on the WiFi converter.
3.4.8 IP Camera
An IP camera (IPC) IPC6325 is deployed inside a container. The camera has the following
features:
Support for the H.265 encoding format and dual-channel 1080p HD video encoding
Built-in 2.8 mm to 12 mm HD zoom lens, enabling more flexible surveillance
IP66 waterproof and dustproof rate, ensuring that the camera can run reliably outdoors
for a long time
IK10 vandal-proof rate, preventing video surveillance interruption due to violent
damages to the camera
Compliance with the railway industry certification, applicable to trackside scenarios
A super WDR of 120 dB, ensuring that both foreground and background objects are
clearly identified in environments with sharp light contrast
Intelligent defogging, enhancing image definition in foggy environments
Intelligent infrared lamp, automatically adjusting the infrared transmit power and angle
Five intelligent behavior analysis functions, color classification, human and vehicle
classification
Super Error Concealment (SEC) to ensure smooth images in case of 20% network packet
loss rate
Transmission quality diagnosis through Packet Conservation Algorithm for Internet
(iPCA)
Acousto-optic assisted focus, ensuring higher installation and commissioning efficiency
An ultra wide operating temperature that ranges from –30°C to +60°C
An ultra wide operating voltage range of ±25%
PoE, DC, and AC power supply modes; DC/AC power adapter and PoE in hot standby
mode
Parameter Value
Digital noise Self-adaptive to 2D or 3D DNR
reduction
(DNR)
Lens Focal length 2.8 mm to 12 mm manual focus, 4.3x optical zoom
Angle of view Horizontal: 36°(telephoto) to 106°(pantoscopic)
Vertical: 20°(telephoto) to 57°(pantoscopic)
Maximum iris F1.4
Automatic iris DC iris
Three-axis Horizontal: 0°to 356°; vertical: 0°to 75°; rotation: 0°to 356°
adjustment
angle
Functio Video H.265/H.264/MJPEG
n encoding
format
Maximum 1920 x 1080
resolution
Frame rate 60 Hz: 1 fps to 30/20 fps
50 Hz: 1 fps to 25/20 fps
Video bit rate 32 kbit/s to 16 Mbit/s
Multi-channel Support for three channels of streams and dual-channel 1080p
video encoding HD video encoding
Audio G.711a/G.711u/G.726/OPUS
encoding
format
Voice Voice intercom and broadcast
communication
PU access ONVIF Profile S/G, GB/T 28181-2014, Genetec Protocol
protocol v1.00, and Huawei SDK (proprietary)
Network TCP, UDP, IPv4, DHCP, DNS, ICMP, IGMP, HTTP, HTTPS,
protocol SFTP, RTP, RTSP, RTCP, SIP, ARP, TLS, NTP, SNMP
(V1/V2/V3), 802.1x, QoS, and DDNS
Security mode User name and password authentication, 802.1x (MD5
Challenge/EAP-TLS), and HTTPS digital certificate
Media security Stream encryption using the AES128/192/256 encryption
algorithm; support for digital watermark
Intelligent Support for tripwire detection, loitering detection, intrusion
video analysis detection, abandoned object detection, removed object
detection, object color identification, human and vehicle
classification, and metadata backhaul
Parameter Value
Motion Support for four motion detection and lens block detection
detection and areas
lens block
detection
Alarm linkage Alarm source: motion detection alarm/lens block
alarm/alarm input/intelligent analysis alarm
Alarm linkage: alarm output/preset position
invoking/scanning during parking actions/SD card video
recording/snapshot taking
Interfac Network One RJ45 10/100 Base-T adaptive Ethernet interface
e interface
Communicatio One RS-485 interface
n serial
interface
Alarm interface 1-channel alarm input, 1-channel alarm output
Video interface BNC interface; 1-channel hybrid analog video output through
the CVBS interface
Audio interface Support for 1-channel audio input and 1-channel audio output
through 3.5 mm audio interfaces
Storage One Micro SD card slot that supports SDHC or SDXC cards
interface (maximum capacity: 64 GB)
General Power supply PoE (802.3at/af), 18 V AC to 30 V AC, 18 V DC to 30 V DC,
specific 9 V DC to 15 V DC (non-polarity DC); DC/AC power adapter
ations and PoE in hot standby mode
Power Typical power consumption: 4 W; maximum power
consumption consumption: 10 W
Operating –30°C to +60°C
temperature
Operating 5% RH to 95% RH (noncondensing)
humidity
Surge 4 kV surge protection that meets the IEC 61000-4-5 standard
protection level
Anti-corrosion Compliance with the ISO9223 C4 corrosion resistance
standard and the IEC 60068-2-11 standard
Protection rate IP66 (meeting the IEC 60529 standard)
Vandal-proof IK10 (meeting the IEC 62262 standard)
rate
Railway Compliance with the EN 50121-4 EMC standard and
industry EN50125-3 anti-vibration standard
certification
Parameter Value
Weight Net weight: 1 kg; gross weight: 1.4 kg
Physical Φ135 mm x 112.5 mm
dimensions
Packing 260 mm x 195 mm x 148 mm
dimensions
Item Specifications
Operating voltage 12 V DC (9–16 V DC)
Signal output under the CLOSED
condition of no liquid detected
Signal output under the OPEN
condition of liquid detected
Insulation resistance > 500 megohms
Operating temperature –20°C to +70°C
Storage temperature –40°C to +85°C (non-condensing)
Protection level IP68
Length of the signal cable 1m
Reliability Failure rate: 8000 fits
Power consumption < 0.2 W
3.4.10 Pad
The pad allows the wireless access from the container data center management system. You
can monitor the equipment in the container data center and environmental parameters in real
time over the APP.
Item Specifications
Dimensions (L x 248.5 mm x 150 mm x 8.3 mm
W x H)
Weight 430 g
Touchscreen 9.6-inch, 800X1280, IPS screen 1600 million colors, and capacitive
5-point touch
Chip processor MSM8916, four cores, 4xA53@1.2 GHz
WLAN 802.11a/b/g/n@2.4 GHz&5 GHz
Storage ROM: 16 GB
RAM: 2 GB
Expansion card: micro SD (TF), a maximum of 64 GB supported
Button/Port Power switch and volume button
3.5 mm stereo headphones port
Micro SD card port
Micro-USB port that supports charging and synchronization with
PC data
Battery Materials: Li-polymer
Capacity: 4800 mAh
Standby time: about 570 hours
Power adapter charge time: about 5–6 hours
Operating Android 4.4 (KitKat)+Emotion UI 3.0
system
(1) Ground port (2) 48 V DC power input (3) PoE port (4) COM1/12 V
port port
(5) COM2/12 V (6) COM3 port (7) COM4 port (8) NTC1–3
port
(9) NTC4–6 (10) AI/DI_1 port (11) AI/DI_2 port (12) 12V_1 port
(13) 12V_2 port (14) SW button (15) Status
indicator
Technical Specifications
Table 3-29 lists the technical specifications for the rack environment unit.
Item Specifications
Indicators
Table 3-30 describes the rack environment unit indicators.
Item Specifications
CIM
The Communication Interface Module (CIM) is an intelligent battery management module
which collects wireless communication data from the downstream BIM groups, collects the
operating data of battery strings, calculates State Of Charge (SOC) and State Of Health (SOH)
of batteries and battery strings, estimates the battery health status, supports battery tripping
management, and uploads data to the MDU/ECC through RS485 or PoE ports.
Collects battery data detected by the BIM through wireless communication.
Each CIM can manage a maximum of four battery strings or 300 batteries.
An external Hall effect sensor is connected to monitor the current of each battery string.
Calculates the SOC and SOH of batteries and battery strings.
Accurately identifies weak batteries in a battery string.
Identifies loose battery terminals and battery terminal overtemperature, and controls
battery switch tripping.
If the upgrade package is transmitted to the CIM within 30 minutes, the upgrade is complete. The BIM
upgrade is finished through the CIM backend. The CIM ensures the successful upgrade of the BIM
through retransmitting and flow control.
Figure 3-31 shows the CIM front view, and Figure 3-32 shows the CIM rear view.
(1) –48 V 0.5 A port (power (2) PoE port (3) COM_IN port (RS485
input) communication input)
(4) COM_OUT port (RS485 (5) DI and DO ports (6) HALL_1–HALL_8 current
communication output) monitoring ports
(7) RF_Z antenna port (8) BCB_1–BCB_4 (9) BCB_OUT and BCB_IN
ports ports
(10) Networking switch (11) PWR indicator (12) RUN indicator
(13) ALM indicator (14) RF_Z indicator (15) Delivered antenna
BIM
The BIM (BIM01C3) is a battery monitoring module that supports 12 V power input and
monitors the voltages, internal resistances, and pole temperatures of batteries.
Monitors the voltages, internal resistances, and pole temperatures of batteries.
Provides the hibernation function (when it detects that the battery voltage is low, it turns
the battery to low-consumption mode).
Uploads battery data to CIM through wireless communication.
Figure 3-33 show the front and bottom views of a BIM.
Parameter Value
Camera Image sensor 1/2.8" 2.0-megapixel progressive scan CMOS
Effective pixels 1920 (H) x 1080 (V)
Minimum Multicolor: 0.01 lux (F1.4, AGC ON, 1/30s shutter speed,
illumination and 50 IRE) and 0.007 lux (F1.2, AGC ON, 1/30s shutter
speed, and 50 IRE)
B/W (infrared lamp enabled): 0 lux
Parameter Value
Day/Night Automatic ICR, multicolor, or B/W
mode
Shutter speed 1/16,000s to 1/25 (1/30)s
Gain control Automatic
Backlight Supported
compensation
(BLC)
Wide dynamic Digital WDR
range
White balance Manual/Auto/Indoor/Outdoor/Fixed sodium lamp/Fluorescent
lamp 1/Fluorescent lamp 2/Incandescent lamp/OnePush
Noise Self-adaptive to 2D or 3D DNR
reduction
Defogging Supported
Maximum 30 m
infrared
radiation
distance
Lens Lens type Built-in Φ14 motorized zoom lens with an IR-CUT filter
Focal length 2.8 mm to 12 mm (support for automatic focus)
Iris DC automatic iris; a maximum iris of F1.4
Angle of view Horizontal angle of view: 11.3°to 33.8°
Zoom 4.3x optical zoom
Functio Video H.264 Main Profile/Baseline Profile (support for Profile
n compression switchover) and MJPEG
standard
Video 1920 x 1080, 1280 x 720, 720 x 576, 720 x 480, 352 x 288,
resolution and 352 x 240 (H.264: 30 fps, 25 fps, 1 fps to 20 fps; MJPEG: 1
frame rate fps to 5 fps)
Video bit rate 100 kbit/s to 8 Mbit/s
ROI encoding Supported
Corridor Support for an aspect ratio of 9:16
format
Multi-channel Three types of streams (can encode one channel of primary
video encoding streams and two channels of secondary streams at the same
time); maximum resolution for primary streams: 1080p;
maximum resolution for secondary streams: D1
Parameter Value
Stream Four preset stream packages and four customized stream
package packages
ISP package Four preset ISP packages and eight customized ISP packages;
support for daily and monthly ISP package plans
Bit rate type Constants Bit Rate (CBR) or Variable Bit Rate (VBR)
Dynamic bit Supported
rate
Image quality H.264: CBR controlled by streams and VBR controlled by
adjustment stream upper limit (selectable image quality); MJPEG: JPEG
quality (QP) control
IP address IP address filtering by blacklist or whitelist
filtering
Communicatio One RJ-45 10M/100M adaptive Ethernet interface and one
n interface RS-485 interface (PELCO-P/D)
Alarm interface 2-channel alarm input and 2-channel alarm output (phoenix
connector)
Analog video BNC interface (1.0 Vp–p and 75 ohms); 1-channel hybrid
output analog video output through the CVBS interface
Audio G.711a/G.711u/G.726
encoding
format
Audio interface Support for 1-channel audio input and 1-channel audio output
through 3.5 mm audio interfaces
Voice Voice intercom (sound pickup required), voice broadcast, and
communication channel-associated voice
Motion Supported
detection
Privacy mask Supported
Image Vertical, horizontal, or both
mirroring
PU access ONVIF 2.4 and HUAWEI SDK
protocol
Network TCP, UDP, IPv4, DHCP, DNS, ICMP, IGMP, HTTP, HTTPS,
protocol SFTP, RTP, RTSP, RTCP, SIP, ARP, SSL, NTP, SNMP,
802.1x, and QoS
Stream mode Unicast and multicast
Maximum 10 (allows users to obtain a maximum of two channels of
number of 1080p video streams at the same time)
concurrent
login users
Parameter Value
Local storage Micro SD card (configured additionally) with a maximum
capacity of 32 GB and at least class 4 speed
Security mode User name and password authentication, 802.1x (MD5
Challenge), and PKI digital certificate
Media security Stream encryption using the AES128/192/256 encryption
algorithm
Data Stream smoothing parameter configuration, adaptive
transmission bandwidth, MTU configuration, and QoS configuration
optimization
Alarm linkage Alarm source: motion detection alarm/lens block
alarm/Boolean value input; linkage target: Boolean value
output
Browser 32-bit Windows XP Internet Explorer 8, 32- or 64-bit
Windows 7 Internet Explorer 8/9/10/11, 32- or 64-bit
Windows 8 Internet Explorer 10/11; 32-bit Internet Explorer
General Power supply 9 V DC to 15 V DC, 18 V DC to 30 V DC, 18 V AC to 30 V
parame AC, PoE 802.3at; power adapter and PoE in hot standby mode
ters
Power Typical power consumption: 9.5 W; maximum power
consumption consumption: 12.5 W
Operating Operating temperature: –40°C to +60°C; relative humidity:
environment 5% RH to 95% RH (noncondensing)
Protection rate IP66
Net weight 1.4 kg
Physical 120 mm x 353.6 mm x 128.1 mm (including the shield)
dimensions (H
x W x D)
Figure 3-35 shows the conceptual diagram of the CE fire extinguishing system, and Figure
3-36 shows the conceptual diagram of the standard fire extinguishing system.
(1) Fire control pipe (2) Smoke detector (3) Heat detector
(4) Indoor horn strobe (5) Fire alarm bell (6) Fire control box
(7) High-pressure hose (8) Fire cylinder
Table 3-33 lists the technical specifications of the extinguishant control panel.
Item Specifications
Input AC input frequency: ≤ 120 W
Item Specifications
AC input voltage and frequency: 230 V AC (tolerance ±10%), 50
Hz
DC backup power voltage: 24 V DC
24 V power output 3A
Capacit Number Three loops. Loops 1 and 2 respectively connect to smoke detectors
y of and heat detectors. Loop 3 is reserved by default.
detection
loops
Number ≤ 24 PCS
of
detectors
connecte
d to each
loop
Output loop current Output loop for the solenoid valve driver: 1 A
limiting Output loops for other drivers: 1 A
The extinguishant control panel is equipped with two 12 V batteries and the required cables.
Table 3-34 lists the technical specifications of the Heptafluoropropane fire extinguisher.
Item Specifications
Dimensions Outer diameter of the steel cylinder: 406 mm
Startup current 0.25 A
Startup voltage 24 V DC
Startup mode Electromagnetic startup
Maximum operating 50°C: 3.4 MPa
pressure
Storage pressure 20°C: 2.5 MPa
Cylinder volume 52 L
The CE-certified fire extinguishing system supports the customized copper fluoride
(NOVEC1230) extinguishant.
Copper fluoride (NOVEC1230) is a new-generation extinguishant that has been favored like
Heptafluoropropane (HFC-227ea) for recent years. Copper fluoride (NOVEC1230) has been
widely proved to be eco-friendly and safe. It can be used to extinguish fire caused by
flammable liquid, gas, and electrical equipment. Physical and chemical actions are combined
during extinguishing. Generally copper fluoride (NOVEC1230) is a colorless and odorless
liquid. It does not contain bromine or chlorine, does no harm to the ozonosphere (ODP = 0),
and resides for a short time in the atmosphere (ATL = 0.014Y).
Item Specifications
AC input power ≤ 120 W
Item Specifications
AC input voltage 220 V AC±20%
DC backup Voltage 24 V DC
power
Electric energy 7.0 Ah
Capacity Number of detection Two loops: one loop connected to the common
loops heat fire detector and the other connected to
the smoke detector
Number of detectors ≤ 20 (common detectors)
connected to each loop
Wire system of the detector loop Two-wire system
Length of the detector loop ≤ 1000 m
Relay contact capacity 7 A, 24 V DC for all relays
Output loop current limiting for the ≤3A
solenoid valve
Output loop current limit for other drivers ≤1A
Item Specifications
Dimensions Outer diameter of the steel cylinder: 364
mm
Maximum operating pressure 50°C: 3.4 MPa
Storage pressure 20°C: 2.5 MPa
Cylinder volume 70 L
Heptafluoropropane filling density ≤ 1120 kg/m3
Startup current 1.2 A
Startup voltage 24 V DC
(1) VESDA detection unit (2) Sampling pipes (3) Air sampling pipe plugs
Working Principle
The detection unit includes the suction pump, filter, high-sensitive smoke detector, and
precision electrical analyzer. The air detector of the VESDA can detect fire in the initial phase
and generates alarms at an early time.
The detection unit of the VESDA sucks air samples from the monitored environment through
the air sampling tube to the smoke detector and works out the dust density in the air. If the
dust density exceeds the preset alarm threshold, the VESDA blinks and sends an alarm signal
to the monitoring module.
Features
High sensitivity
The VESDA features extremely high sensitivity and wide sensitivity adjustment range
(0.005%–20% obs/m). It can detect both potential fire in the early phase and particles
released by the softened insulation layer of an overloaded power cable.
Precise detection result
The VESDA works in active air sampling mode. The efficient aspirator continuously
sends air samples from the protected area to the detection chamber for analysis. The
detection result and response time are less influenced by air flow compared with a
traditional fire detection method.
Flexible installation
The VESDA detection unit is compact and easy to install. The air sampling pipes can be
deployed depending on site requirements. The air sampling pipes are made of PVC and
can be installed on or under the ceiling, under the floor, at air return vents of air
conditioners, and in locations that need special protection. For example, the sampling
capillaries can be installed in a cabinet to monitor equipment in the cabinet.
Easy maintenance
The VESDA is equipped with a special filter that filters air for cleaning the laser
measuring chamber, ensuring that the laser detector has a long lifespan. The filter can be
easily maintained and replaced, and cleaned by blowing air into the air sampling pipes.
Therefore, you do not have to replace any other components.
Efficient auto-diagnosis system
The VESDA is designed with an efficient auto-diagnosis system for monitoring the
working status of itself, the network, and the air sampling pipes in real time. If a fault is
detected, the system generates an alarm and indicates the fault location for
troubleshooting.
Signal Ports
Indoor signal ports are protected to 1 kV for common mode.
Signal ports for routing cables out of the container pass the 3 kA impulse current test.
3.6.2 Grounding
Internal Grounding
The main earthing terminal (MET) is installed in the container and connects to the external
ground grid over ground downleads.
Devices in the container connect to the ground busbar over ground cables and are insulated
from other metal parts.
External Grounding
M12 bolt ground points are evenly located on the container exterior. Ensure that the two
diagonal ground points are connected to the ground grid. The FusionModule1000 provides
two external ground points, as shown in Figure 3-43. The ground resistance is within 10
ohms.
Item Specifications
Power supply Power input Two 250 A inputs, three-phase four-wire + PE,
and 380 V AC/400 V AC/415 V AC 50 Hz/60 Hz
distribution
Surge protection Class I, 100 kA (8/20 µs), 20 kA (10/350 µs)
level
Load power Total power ≤ 40 kW; single cabinet power ≤ 8
kW
Battery backup time 60 min
Cooling Cooling capacity 25 kW for each air conditioner, 3+1 mode
Refrigerant R410A
Fire Type Fire extinguishing system with the automatic fire
extinguishing detection and emergency gas release functions
Alarm Audible and visual alarming with automatic
monitoring and detection
Monitoring The analog addressable system releases the
gaseous extinguishant if fire alarms are generated
from dual detector loops.
Extinguishing agent Heptafluoropropane. Copper fluoride
(NOVEC1230) can be used in the CE version if
required.
Monitoring IP camera Dual-resolution IP cameras installed in the
container.
Management Monitors the temperature and humidity control
functions system, fire detection and control system, access
control system, and cooling system inside the
FusionModule1000 in real time
Item Specifications
O&M using the mobile APP, remote unattended
control
(Optional) The NetEco supports monitoring over
emails and Simple Network Management Protocol
(SNMP) short messages.
All backup power supplies are connected over
programmable dry contacts or fast Ethernet (FE)
ports. The AC/DC power system adopts the FE
port, and the DG supports the RS485 port and dry
contacts.
Structure Container 40 ft standard ISO shipping container (40 ft x 8 ft
x 9.5 ft)
Container heat The thermal transmission coefficient of the
insulation container is 0.4 W/(m2 x K) or less.
performance
Integrated cabling Power cables and signal cables are routed
separately.
Protection level IP55/IP65 (optional)
Installation mode Directly installed on the ground
NOTE
The container can be installed on a concrete platform,
with four 300 mm high steel bases connected to the
concrete platform using M16 bolts.
Item Specifications
Altitude 0–4000 m
The cooling capacity of the air conditioner is
derated when the altitude is from 1000 m to
4000 m. For the derating details, contact
Huawei technical support.
The PDB is derated when the altitude is from
2000 m to 4000 m. For the derating details,
contact Huawei technical support.
A
ATS automatic transfer switch
C
CE Conformite Europende
M
MCB miniature circuit breaker
MCCB molded case circuit breaker
N
NetEco network ecosystem
T
TCP/IP Transmission Control Protocol/Internet Protocol
P
PUE power usage effectiveness
S
SNMP Simple Network Management Protocol
U
UPS uninterruptible power system
V
VCN video cloud node