Huawei FM1000A40 V200R003C00 CT Product Overview

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 85

FusionModule1000A40 CT Solution

V200R003C00
Product Overview

Issue Draft B

Date 2017-01-10

HUAWEI TECHNOLOGIES CO., LTD.


Copyright © Huawei Technologies Co., Ltd. 2017. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China

Website: http://e.huawei.com

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential i


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview About This Document

About This Document

Purpose
This document describes the FusionModule1000A prefabricated all-in-one data center
solution (FusionModule1000 for short) in terms of its overview, typical application scenarios,
product architecture, and key technical specifications, helping readers to systematically
understand the FusionModule1000.

Intended Audience
This document is intended for:
 Sales engineers
 Technical support engineers
 System engineers

Symbol Conventions
The symbols that may be found in this document are defined as follows:

Symbol Description
Indicates an imminently hazardous situation which, if
not avoided, could result in death or serious injury.

Indicates a potentially hazardous situation which, if not


avoided, could result in death or serious injury.

Indicates a potentially hazardous situation which, if not


avoided, may result in minor or moderate injury.

Indicates a potentially hazardous situation which, if not


avoided, could result in equipment damage, data loss,
performance deterioration, or other unanticipated results.
NOTICE is used to address practices not related to
personal injury.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential ii


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview About This Document

Symbol Description
Calls attention to important information, best practices
and tips.
NOTE is used to address information not related to
personal injury, equipment damage, and environment
deterioration.

Change History
Changes between document issues are cumulative. The latest document issue contains all the
changes made in earlier issues.

Issue Draft B (2017-01-10)


Updated the container ground point position diagram.

Issue Draft A (2016-10-15)


This issue is used for first office application (FOA).

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential iii


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview Contents

Contents

About This Document .................................................................................................................... ii


1 Overview......................................................................................................................................... 1
1.1 Positioning .................................................................................................................................................................... 1
1.2 Benefits ......................................................................................................................................................................... 2

2 Typical Application Scenarios and Typical Configuration .................................................. 4


2.1 Typical Application Scenarios ...................................................................................................................................... 4
2.2 Typical configuration .................................................................................................................................................... 6

3 System Architecture ...................................................................................................................... 8


3.1 Container Structural System ......................................................................................................................................... 8
3.1.1 Container ................................................................................................................................................................... 8
3.1.2 Container Interior Layout ........................................................................................................................................ 11
3.1.3 Components Inside the Container ............................................................................................................................ 12
3.1.4 External Container Ports .......................................................................................................................................... 14
3.2 Power Supply and Distribution System ...................................................................................................................... 15
3.2.1 Overview ................................................................................................................................................................. 15
3.2.2 Main Input PDB ....................................................................................................................................................... 17
3.2.3 AC/DC Power System ............................................................................................................................................. 17
3.2.4 Batteries ................................................................................................................................................................... 19
3.3 Cooling System ........................................................................................................................................................... 20
3.3.1 Overview ................................................................................................................................................................. 20
3.3.2 Composition ............................................................................................................................................................. 21
3.3.2.1 Indoor Unit............................................................................................................................................................ 21
3.3.2.2 Ports ...................................................................................................................................................................... 23
3.3.2.3 Operating Environment Specifications ................................................................................................................. 23
3.3.2.4 Technical Specifications ....................................................................................................................................... 24
3.3.2.5 Outdoor Unit ......................................................................................................................................................... 26
3.3.3 Low-Temperature Component ................................................................................................................................. 28
3.4 Management System ................................................................................................................................................... 30
3.4.1 Overview ................................................................................................................................................................. 32
3.4.2 ECC800 Collector .................................................................................................................................................... 33
3.4.3 Independent Deployment AI/DI Unit ....................................................................................................................... 38
3.4.4 Smart ETH Gateway ................................................................................................................................................ 38

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential iv


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview Contents

3.4.5 Access Actuator ....................................................................................................................................................... 40


3.4.6 AC Actuator ............................................................................................................................................................. 44
3.4.7 WiFi Converter ........................................................................................................................................................ 46
3.4.8 IP Camera ................................................................................................................................................................ 48
3.4.9 Water Sensor ............................................................................................................................................................ 52
3.4.10 Pad ......................................................................................................................................................................... 53
3.4.11 Rack Environment Unit (Optional) ........................................................................................................................ 54
3.4.12 Cabinet Access Control System (Optional) ........................................................................................................... 55
3.4.13 Intelligent Battery Monitoring System (Optional) ................................................................................................. 56
3.4.14 External Camera (optional) .................................................................................................................................... 59
3.5 Fire Extinguishing System .......................................................................................................................................... 62
3.5.1 Overview ................................................................................................................................................................. 62
3.5.2 CE Fire Extinguishing System ................................................................................................................................. 65
3.5.2.1 Extinguishant Control Panel ................................................................................................................................. 65
3.5.2.2 Heptafluoropropane Fire Extinguisher .................................................................................................................. 66
3.5.3 Standard Fire Extinguishing System ........................................................................................................................ 68
3.5.3.1 Fire Alarm Control Panel ...................................................................................................................................... 68
3.5.3.2 Heptafluoropropane Fire Extinguisher .................................................................................................................. 69
3.5.4 VESDA (Optional) ................................................................................................................................................... 70
3.6 Surge Protection and Grounding ................................................................................................................................. 72
3.6.1 Surge Protection....................................................................................................................................................... 72
3.6.2 Grounding ................................................................................................................................................................ 72
3.7 Integrated Cabling ...................................................................................................................................................... 73

4 Key Technical Specifications .................................................................................................... 75


A Acronyms and Abbreviations .................................................................................................. 78

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential v


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 1 Overview

1 Overview

1.1 Positioning
Huawei has developed the FusionModule1000, a green data center solution, based on a
thorough study on the reform and impact of the cloud computing to traditional data centers
and the practical experience of dozens of global cloud computing centers. The solution
features a flexible, hybrid, and modular design to help customers construct green
infrastructure adapting to cloud computing.
The FusionModule1000, foundation for cloud computing in enterprise data centers, integrates
power distribution, monitoring, cooling, racks, cable routing, and fire extinguishing. It is
characterized by good waterproof and quakeproof performances. The FusionModule1000
helps enterprise telecom operators and Internet operators to rapidly deploy data centers and
has unique advantages in the fields of disaster relief, military affairs, oil exploitation, survey,
and enterprise data for its availability in outdoor environments.
The FusionModule1000, located at the bottom layer of a data center, provides basic physical
construction for all services in the data center.

Figure 1-1 Data center architecture

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 1


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 1 Overview

1.2 Benefits
The FusionModule1000 is a small-capacity prefabricated all-in-one data center that integrates
the container mechanical structure, power supply and distribution system, cooling system,
management system, fire extinguishing system, integrated cabling system, and server cabinets.
It features high security and reliability, rapid deployment, low cost, high efficiency, and
intelligent management.

High Security and Reliability


 The design of two porches prevents sand from entering the equipment compartment
when doors are open during maintenance, ensuring that the FusionModule1000 applies
to various harsh environments.
 The container is properly grounded and resists electromagnetic interference. Its
electromagnetic compatibility (EMC) meets Class A requirements specified in the
CISPR22/EN55022 standard.
 The data center uses International Organization for Standardization (ISO) standard 668
containers which provides IP65 protection (IP55 by default; IP65 available by changing
the dustproof module at the air vent) as the containers feature mature welding
technologies and are well sealed to be waterproof and dustproof.
 The bullet-proof function can be provided for the container if required. The container
passes the 10 m rifle test as it is armed with 4.2 mm bullet-proof steel plates on its sides
and 2.4 mm bullet-proof steel plates on the top.
 The container works well at low ambient temperatures (–40°C to +45°C) and normal
temperatures (–20°C to +55°C).
 The container meets NEBS zone 3 antiseismic requirements, and equipment supports
shock absorption.
 Product design complies with the TIA-942 standard.
 The intelligent access control system and mechanical locks provide multifold security
protection and meets class 3 theftproof requirements in EN 1627–EN 1630.
 The container interior is decorated with B1 fire-resistant materials, the enclosure
structure uses the high-density A1 fire-resistant rock wool material, and the exterior is
coated with the customized flame-retardant paint, providing fire resistance duration of
120 minutes as stipulated by UL.
 The fire extinguishing system is reliable, clean, insulating, and environment-friendly, and
can put out a fire efficiently and safely without damaging CT devices, thereby ensuring
high device availability. The extinguishant is Heptafluoropropane. The fire extinguishing
system complies with China's CCC certification in the standard version and the EU's CE
certification in the CE version. Copper fluoride (NOVEC1230) can also be used if
required in the CE version.

Rapid Deployment
 Streamlined manufacturing, professional division of labor, and good work conditions
ensure that modules and products of the FusionModule1000 are produced efficiently
with strict quality control. The standard manufacturing period is six to eight weeks.
 Infrastructures such as cooling equipment, power supply equipment, and racks are
factory-installed. You only need to provide network cables, power cables, and water
pipes onsite for commissioning.
 System commissioning is completed in factories, and therefore onsite deployment and
equipment room commissioning take less than one week.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 2


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 1 Overview

 The container can be easily relocated as it can be transported on level-3 roads and
applies to various scenarios such as dynamic data service deployment, military affairs,
disaster relief, and field operations.

Cost-Effectiveness and High Energy Efficiency


 The container integrates the cabinets, cooling, power distribution, monitoring, security,
and other facilities that are pre-installed in the factory. The FusionModule1000 is
pre-commissioned and put into trial run before delivery. Customers can inspect and try
the product in the factory.
 Civil engineering is simple when the FusionModule1000 is deployed outdoors. It starts
to work after being installed on a concrete podium or platform and connected to a
humidifier, water supply, mains power supply, and network.
 Mature delivery mode, modular structure, and low-cost transportation of the container
ensure fast deployment of the FusionModule1000, and simple and convenient expansion
and upgrade.
 The FusionModule1000 is energy-efficient. The hot and cold aisles are separated in the
equipment compartment to ensure high cooling efficiency.

Intelligent Management
 Manages infrastructure of the FusionModule1000 in a central manner.
 Supports O&M using a mobile app and remote unattended operation. Full WiFi coverage
is realized inside the container using a WiFi converter. WiFi coverage outside the
container is realized using a customer router gateway (optional).
 Monitors equipment effectively in real time.
 Monitors environments in real time to identify potential risks.
 Provides various methods of collecting and analyzing power consumption data to realize
precision energy efficiency analysis. Such data is fundamental to improving the power
usage effectiveness (PUE). You can customize the data collection and analysis methods.
 Provides a robust security mechanism to protect equipment and ensures a proper
environment.
 Provides standard simple network management protocol (SNMP) ports to communicate
with third-party network management systems (NMSs).

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 3


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution 2 Typical Application Scenarios and Typical
Product Overview Configuration

2 Typical Application Scenarios and Typical


Configuration

2.1 Typical Application Scenarios


The FusionModule1000 is a prefabricated container data center, and integrates the power
distribution box (PDB), air conditioner, and cabinets. It can be put into operation immediately
after connecting to the tap water, power supply and network.
The All-in-One is focused on fast deployment of outdoor small-size CT equipment rooms for
carriers and enterprises. It can integrate standard and nonstandard mainstream CT equipment,
supports the 1.2 m cabinet layout, and can be easily relocated.

Table 2-1 Typical application scenarios of the FusionModule1000


CT Energy Government Large Others
Equipment Industry Enterprise
Room
 Equipment  Distributed  Distributed  Primarily  Distributed
room single-contai single-contai for private single-contai
construction ner ner use ner
and deployment deployment  Mobile fast deployment
modernizati  Areas such  Diverse deployment  Suburban
on as environment areas
 High
 Distributed wilderness, s such as the without
reliability
and mobile mineries, seaside, class equipment
single-contai and deserts industrial rooms
ner parks,
deployment campuses,
and urban
areas

Distributed and mobile single-container deployment applies to equipment room construction


or modernization.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 4


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution 2 Typical Application Scenarios and Typical
Product Overview Configuration

Figure 2-1 Mobile All-in-One

The FusionModule1000 must not be transported with the CT equipment, power modules, and batteries
installed.

The FusionModule1000 can be deployed as a small integrated data center (IDC) for
enterprises in diverse environments such as the seaside, industrial parks, campuses, urban, and
suburban areas to meet specific application requirements such as business blowout and
capacity expansion.
The FusionModule1000 is most preferred when a data center must be quickly constructed and
deployed due to urgent service requirements.

Figure 2-2 All-in-One in an enterprise park

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 5


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution 2 Typical Application Scenarios and Typical
Product Overview Configuration

The FusionModule1000 supports distributed single-container deployment in outdoor areas


such as wilderness, mineries, and deserts to meet application requirements of the energy
industry.

Figure 2-3 All-in-One in harsh environments

2.2 Typical configuration


In a typical CT scenario, the FusionModule1000 provides a maximum capacity of 40 kW, and
can house a maximum of 10 cabinets.

Table 2-2 Typical configuration

Type System Composition


Structural system  There is no raised floor or CT cabinets (user-supplied). The
supported CT cabinet dimensions (H x W x D) are 2200 mm x 600
mm x 800 mm.
 Cables and terminals for connecting the AC/DC power system to
CT cabinets are not configured.
Low-temperature component assembly (configured when the
temperature is below 0°C)
Power supply Main input PDB, AC/DC power system (TP481200B-N20B1), 1000
and distribution Ah battery
system
Cooling Low 25 kW half-sized variable frequency air-cooled air conditioner with the
system tempe outdoor unit, remote T/H sensor, low-temperature component
rature (configured when the temperature is in the range of –40°C to –20°C)

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 6


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution 2 Typical Application Scenarios and Typical
Product Overview Configuration

Type System Composition


Norm 25 kW half-sized variable frequency air cooled air conditioner with the
al outdoor unit, remote temperature and humidity sensor
tempe
rature
Monitoring ECC800, independent deployment AI/DI unit, smart ETH gateway,
system access actuator, AC actuator, WiFi converter, water sensor, pad,
camera, emergency door release, reader, door status sensor, magnetic
lock, rack environment unit (optional), cabinet access control device
(optional), iBAT (optional), and external camera (optional).
Fire CE Extinguishant control panel, smoke detector, heat detector, fire alarm
extingui versio bell, horn strobe, emergency light, external horn strobe, extinguishant
shing n abort button, warning signs, electrical actuator, pneumatic switch, fire
system nozzle, fire cylinder, and VESDA (optional)
Standa Fire alarm control panel, smoke detector, heat fire detector, fire alarm
rd sounder, fire alarm horn/strobe, emergency light, external fire alarm
Versio horn/strobe, emergency start/abort switch, gas release indicator, fire
n nozzle, fire cylinder, and VESDA (optional)

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 7


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

3 System Architecture

3.1 Container Structural System


3.1.1 Container
Container Appearance
The dimensions and corner pieces of the container comply with the ISO668 standard. The
container exterior can be made of aluminum grilles or Eterpan panels.

Figure 3-1 Appearance 1

(1) End door (for maintaining outdoor units) (2) Lock rod
(3) Ventilation window for the outdoor unit compartment (4) Container feeder window

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 8


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-2 Appearance 2

(1) External fire alarm horn strobe (2) Emergency door (3) Air intake window
release button
(4) Device installation (5) Air exhaust window (6) End door (main
door/emergency door entrance)
(7) Card reader (8) Container ground point (9) Fire control box

Thermal Insulation Structure


The container is furnished with a thermal insulation layer composed of steel plates, rock wool
(density: 120 kg/m3), and color steel plate. The heat transfer coefficient of the container is
equal to or less than 0.4 W/(m2 x K).

Container Door
900 mm wide fire door:
 The door resists fire for 90 min typically and up to 120 min if special treatment is
applied.
 The door is protected to IP65.
 The door uses a WK03 class theftproof structure.
 The door is 900 mm wide (net) and 2250 mm high (net). It opens in and out rightwards
(the hinge is on the right side of the door), with a door handle outside and a pushrod
structure inside.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 9


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

 The door closer allows the door to open to an angle of at least 120°, and it stops the door
at the maximum position to keep the door open.
 When the door is open, the door, door frame, and mechanical parts can withstand the
door weight and will not misshape permanently within 48 hours with a static load of 15
kilograms at any part.
 The fire door uses rubber strips with a framework and composite adhesive to ensure the
waterproof performance.
1200 mm wide fire door:
 The door is used for moving equipment in or out and can be opened only inwards.
 The door resists fire for 90 min typically and up to 120 min if special treatment is
applied.
 The door is protected to IP65.
 The door uses a WK03 class theftproof structure.
 The door is 1200 mm wide (net) and 2250 mm high (net). It opens in rightwards (the
hinge is on the right side of the door), with a pushrod structure inside.
 The door closer allows the door to open to an angle of at least 120°, and it stops the door
at the maximum position to keep the door open.
 When the door is open, the door, door frame, and mechanical parts can withstand the
door weight and will not misshape permanently within 48 hours with a static load of 15
kilograms at any part.
 The fire door uses rubber strips with a framework and composite adhesive to ensure the
waterproof performance.

Container Specifications
Table 3-1 lists the container specifications.

Table 3-1 Container specifications

Item Specifications
Container 40 ft standard ISO shipping container (40 ft x 8 ft x 9.5 ft)
Container The thermal transmission coefficient of the container is 0.4 W/(m2 x K) or
heat less.
insulation
performance
Integrated Power cables and signal cables are routed separately.
cabling
Protection IP55/IP65 (optional)
level
Installation Directly installed on the ground.
mode NOTE
The container can be installed on a concrete platform, with four 300 mm high steel
bases connected to the concrete platform using M16 bolts.

Dimensions 2896 mm x 2438 mm x 12,192 mm


(H x W x D)

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 10


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Item Specifications
Weight Empty container (excluding servers): 16,000 kg; fully-loaded container: <
25,000 kg
Typical Eight cabinets; dimensions (H x W x D) of each CT cabinet
cabinet (user-supplied): 2200 mm x 600 mm x 800 mm
capacity
Reliability  The intelligent access control system and mechanical locks provide
multifold security protection and meets class 3 theftproof requirements
in EN 1627–EN 1630.
 The access control system can be configured with permission at
different levels to monitor door status and generate alarms.
 Standard container air vents feature good security and ventilation
designs.
 Ground busbars are installed in the container for internal equipment
and the container itself. Surge protection measures are provided for
power ports and network ports to ensure the safety of the data center.
 Real-time video surveillance is implemented for the protected area.
 The container can withstand the 30 m/s wind speed when it is in
operation.
 The container meets NEBS zone 3 antiseismic requirements.
 Fireproof performance: The burning behavior of decorative materials
complies with the Code for Fire Prevention in Design of Interior
Decoration of Buildings (GB50222-95) of China. The materials can
withstand fire for 120 minutes.
 Thermal insulation performance: The thermal transmission coefficient
of the container is 0.4 W/(m2 x K) or less.
 Waterproof and dustproof performance: All external ports are protected
to IP55 (weather-tightness test) of the GB4208/IEC529 standard and
can be protected to IP65 if required.
 Corrosion resistance: The container uses weathering steel and surface
treatment and passes the 720-hour cyclic salt spray test (1440-hour test
if special coating is applied).
 Anti-mould performance: The container passes the 24 hours x 28 days
mould growth test.
 Bullet-proof performance (optional): The container passes the 10 m
rifle test.

3.1.2 Container Interior Layout


In the container, the hot aisle is 500 mm wide, the cold aisle is 1350 mm wide, and the long
aisle is 650 mm wide. Cabinets are directly secured to the floor and cannot slide.
Figure 3-3 shows the interior layout of the container.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 11


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-3 Interior layout

(1) Air conditioner (2) Low temperature component (3) Cabinets (4) Cold aisle
outdoor units for air conditioners
(5) Main input PDB (6) Entrance room (7) Fire (8) AC/DC
cylinder power system
(9) Battery racks (10) Air conditioner indoor (11) Hot
units aisle

The low-temperature component is deployed for air conditioners when the temperature is in the range of
–40°C to –20°C. When the temperature is below 0°C, the low-temperature component assembly at the
container level should be deployed.

3.1.3 Components Inside the Container


Overhead Cable Tray
 Cable trays are classified into strong-current cable trays and weak-current cable trays.
Cable trays are reserved for optical fibers.
 Cable trays are assembled by section steel. Cable trays are separate from cabinets and
compatible with different cabinet arrangements.
 Aluminum guide rails are deployed along the length side of the container and secured to
the C-shaped beams at the top of the container. Cable trays are secured to the aluminum
guide rails using sliding nuts.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 12


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-4 Overhead cable tray

Suspended Ceiling
 Cold and hot aisles are isolated by a suspended ceiling to prevent mixture of cold and hot
air.
 The aisle sealing plates are separate from cabinets and secured to the aluminum guide
rails at the top of the container.
 The sealing plates for the suspending ceiling of the long aisle are hinged and can be
easily opened when overhead cables need to be maintained.
 The suspended ceilings of the hot and cold aisles are assembled by three sealing plates.
The sealing plates on both sides can be removed when there is a need to maintain cables.
 The hot aisle door is a glass sliding door that is installed before transportation.

Aisle Sliding Door


There are cold and hot aisles between cabinets in the equipment zone of the container. The
sliding door seals an aisle to form aisle containment (hot aisle containment by default).
The top of the aisle sliding door is secured to the sealing plates of the suspended ceiling, and a
damper is installed at the bottom of the sliding door to prevent the door from swaying during
transportation or movement.
The sliding door is 2046 mm high and 755 mm wide.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 13


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-5 Aisle sliding door

(1) Sliding door guide rail (2) Glass door panel (3) Damper

3.1.4 External Container Ports


End connectors are used at container exterior ports designed for routing power cables, optical
fibers, and network cables on the container exterior. Sealing modules are used at the ports
designed for routing refrigerant pipes and water pipes. All ports provide good water tightness
and thermal insulation performance and meet equipment compartment weathering
requirements. Pipe ports feature an anti-backflow design to meet diverse configuration
requirements. Fire extinguishing devices on the container exterior meet sealing conditions.
A power PDB is deployed on the left side of the container to connect input power cables on
the container exterior. The design avoids the need to route power cables into the container and
simplifies cable connection.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 14


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-6 Power PDB (left view)

(1) Signal cable feeder window (2) Power cable feeder window (3) Power PDB

Figure 3-7 shows the ports reserved for the humidifier water refill pipe and condensate
drainpipe.

Figure 3-7 Ports reserved for the humidifier water refill pipe and condensate drainpipe (unit: mm)

(1) Port reserved for the condensate (2) Port reserved for the humidifier water refill
drainpipe pipe

The port reserved for the humidifier water refill pipe is a 1 inch ball valve with internal threads. The port
reserved for the condensate drainpipe is a DN25 PP-R pipe port.

3.2 Power Supply and Distribution System


3.2.1 Overview
CT equipment and power equipment have separate power supplies. The total power of
equipment is 40 kW, 2N configuration is adopted, and the power backup time for equipment
is 1 hour. A wall-mounted power distribution box (PDB) with dual inputs and dual outputs is
deployed for the main input. An AC/DC power system with batteries inside supplies power to
equipment without using a rack power distribution unit (rPDU).
The dual 250 A three-phase power inputs comply with the three-phase five-wire TN-S system.
By default, cabinets as well as cables and terminals for connecting the AC-DC power system
to the cabinets are not provided.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 15


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

 Dual power supplies are adopted for CT equipment.


 The air conditioners, lights, AC/DC power system, and fire extinguishing system are
powered by the main input PDB.
 The monitoring system is powered by the AC/DC power system.
Figure 3-8 shows the conceptual diagram of the power supply and distribution system.

Figure 3-8 Conceptual diagram

Figure 3-9 Layout of power supply and distribution devices

(1) Battery racks of the DC power system (2) Main input PDB
(3) AC/DC power system (4) Power PDB

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 16


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

3.2.2 Main Input PDB


The main input PDB provides two 3-pole 250 A input MCCBs, two 3-pole 160 A output
circuit breakers for supplying power to the AC/DC power system (TP481200B), and two
3-pole 63 A output circuit breakers for supplying power to the 4-pole 63 A automatic transfer
switch (ATS). The ATS supplies power to loads such as fire extinguishing devices and lights.
Two 3-pole 63 A circuit breakers are reserved for connecting two UPS2000-Gs to provide
backup power for two 25 kW half-sized variable frequency air cooled air conditioners to
ensure continuous cooling.

Table 3-2 Technical specifications of the main input PDB

Item Specifications
Rated input 380 V AC/400 V AC/415 V AC
voltage
Rated input 50 Hz/60 Hz
frequency
Input switch 250 A/3P MCCBx2
Output switch  Route A main busbar output: 160 A/3P MCCBx1+63 A/3P
MCBx2+40 A/3P MCBx4+16 A/1P MCBx1
 Route B main busbar output: 160 A/3P MCCBx1+63 A/3P
MCBx2+40 A/3P MCBx4+16 A/1P MCBx1
 ATS combined output: 10 A/1P MCBx7+32 A/3P MCBx1+10 A/1P
RCDx1
Surge 60 kA (8/20 us)
protection
level
Enclosure IP20 (front)
protection
level
Cabling mode Top cabling for routes A and B, bottom cabling for the ATS
Installation Floor-mounted
mode
Dimensions 2000 mm x 600 mm x 300 mm
(H x W x D)
Monitoring Main input PDB total input electricity display and measurement:
three-phase voltage, current, reactive power, active power, and power
factor. The meter implements standard RS485 communication with the
monitoring host.

3.2.3 AC/DC Power System


The AC/DC power system model is TP481200B-N20B1, as shown in Figure 3-10. Table 3-3
lists its technical specifications.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 17


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-10 Exterior

Table 3-3 Technical specifications

Item Specifications
System Dimensions (H 2000 mm x 600 mm x 600 mm
x W x D)
Rated capacity 1200 A (two to twenty-four 50 A rectifiers)
Cooling mode Natural cooling
Installation Floor-mounted (installed on the container floor or an ESD
mode floor)
Cabling mode Routed in and out from the top
Maintenance Maintained and operated from the front and located along a
mode wall with at least 100 mm clearance

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 18


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Item Specifications
Protection IP20
level
AC Input mode 220/380 V AC, three-phase
power
distributi Input voltage 85–300 V AC (L-N); rated voltage: 220 V AC
on
Input capacity 1x200 A/3P (MCCB)
Surge 20 kA/40 kA, 8/20 µs
protection
DC Output voltage 45–58 V DC, 53.5 V DC by default
power
distributi Rated output 72 kW
on power
Battery route 2x1250 A (NT4)
Load route 4x500 A (NT3), 2x400 A (NT2), 2x100 A (NT00)
Surge 10 kA/20 kA, 8/20 µs
protection
Rectifier Efficiency > 98%
Output power 3000 W (176–300 V AC)
Operating –40°C to +75°C
temperature
Dimensions (H 40.8 mm x 105 mm x 281 mm
x W x D)
Weight < 2.5 kg
Power factor ≥ 0.99 (load ≥ 50%)
THD ≤ 5%
Monitori Alarm input Four Boolean value inputs
ng
module Alarm output Eight dry contact outputs
Communicatio Ethernet, RS485/RS232
ns port
Alarm storage 10,000 alarms and system logs
Display mode LCD

3.2.4 Batteries
Batteries store electricity.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 19


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Table 3-4 Storage battery specifications

Specifications Vendor Cell Weight Dimensions (H x W x D)


Model Voltage

1000 Ah Shuangdeng 2V 59 kg 181 mm x 370 mm x 365


GFM-1000 mm

3.3 Cooling System


3.3.1 Overview
Air-cooled in-row precision air conditioners are used in the cooling system. The air
conditioners and cabinets form contained cold (hot) aisles to isolate hot air from cold air. Air
flows in from the front and out from the rear. Air conditioners cool hot air from servers and
generate cold air for servers.
 Air conditioners are deployed close to heat sources and provides horizontal airflow. This
mechanism shortens the air supply distance, reduces airflow pressure loss, and
minimizes cold air leakage during air supply, thereby improving the cooling efficiency.
 Teamwork control ensures that air conditioners work in reasonable mode to improve
efficiency.
 Precision air conditioners with constant temperature and humidity and those with cooling
only can collaborate to dynamically control the temperature and humidity inside the
container.

Figure 3-11 Cooling system conceptual diagram

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 20


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-12 Layout of cooling components

(1) Air conditioner outdoor units (2) Air conditioner indoor units

3.3.2 Composition
3.3.2.1 Indoor Unit

Appearance
Figure 3-13 shows the indoor unit of a NetCol5000-A cooled in-row precision air conditioner.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 21


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-13 Indoor unit

Components
The indoor unit consists of a compressor, oil separator, fan, heat exchanger, one-way-valve,
filter dryer, sight glass, electric heater (optional), electrode humidifier (optional), electronic
expansion valve, water pump (optional), display panel, and other components.
 Compressor
The DC variable-frequency compressor provides the cooling capacity ranging from 20%
to 100% to meet load requirements.
 Oil separator
It is an oil-gas separator which separates the lubricant brought out due to exhaustion of
the compressor and brings back the separated lubricant to the compressor.
 Fan
The EC fan implements stepless speed adjustment.
 Heat exchanger
The efficient finned evaporator, an important part in the refrigerating system, absorbs
heat from indoor air to ensure that the indoor temperature and humidity meet
requirements.
 Electronic expansion valve
The flow regulator uses a miniature controller to control the operation of the step motor,
thereby changing the pass-through area of the valve to regulate the flow of refrigerant.
 One-way valve
The one-way valve efficiently controls backflow of gas or liquid.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 22


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

 Filter dryer
The filter dryer absorbs moisture from the refrigerant pipes and filters out foreign
matters, which reduces the component damage probability and improves operating
efficiency and reliability of components.
 Sight glass
The sight glass allows users to observe the refrigerant flow and the content of gas and
liquid for easy maintenance and optimization.
 Electric heater
The PTC heater features quick start, large heating capacity, and even heat dissipation. It
has multiple protection mechanisms to ensure the secure and stable running of the
equipment.
 Electrode humidifier
The electrode humidifier provides stepless adjustment of humidification capacity and
precise control of indoor humidity.
 Water pump
The water pump provides power for top drainage with 4 m.
 Display panel
The 7-inch display panel with the true-color touchscreen provides user interfaces for
query, setting, monitoring, and maintenance.

3.3.2.2 Ports
Table 3-5 shows the physical ports on the NetCol5000-A in-row precision air conditioner.

Table 3-5 Port description

Item Specifications
Refrigerant liquid pipe Copper pipe, external diameter 5/8 inch, pressure resistance ≥
4.5 MPa, soldering
Refrigerant gas pipe Copper pipe, external diameter 3/4 inch, pressure resistance ≥
4.5 MPa, soldering
Humidifier water inlet Reserved port: BSPP 1/2 in.; thread connection
pipe
Top drainpipe Reserved interface: 1/2 inch reserved copper tube
Bottom drainpipe Reserved port: threaded port for copper pipe with a diameter
of 5/8 in

3.3.2.3 Operating Environment Specifications


Table 3-6 describes the operating environment specifications of the NetCol5000-A in-row
precision air conditioner.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 23


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Table 3-6 Operating environment specifications

Item Specifications
Operating 18–45°C
temperature
Operating 20%–80% RH
humidity
Storage –40°C to +70°C
temperature
Storage humidity 5%–95% RH (non-condensing)
Applicable  Work with NetCol500-A026 (including a low-temperature
outdoor component): –40°C to +45°C
temperature  Work with NetCol500-A026: –20°C to +55°C
Heating capacity 4 kW
Humidifier 1.5 kg/h
capacity
Protection level  Indoor unit: IP20
 Outdoor unit: IPX5
Installation mode Installed on an ESD floor or rack
Piping and Route pipes and cables from the top or bottom
cabling
Altitude 0–1000 m, derating at above 1000 m, max. 4000 m. For detailed
derating data, contact Huawei technical support.

Table 3-7 Humidifier inlet water quality requirements

Item Requirement Unit

Hydrogen ion 7–8.5 pH


Conductivity at 20°C (σ20)a 125–1250 µS/cm
a: If σ20 is less than 125 µS/cm, it takes a longer time for the humidifier to generate vapor
for the first time. If σ20 is greater than 1250 µS/cm, the humidifier service life is affected.

3.3.2.4 Technical Specifications


Table 3-8 and Table 3-9 describe the technical specifications of the NetCol5000-A in-row
precision air conditioner.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 24


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Table 3-8 Generic specifications

Item Specifications
Cooling mode Air cooled
Refrigerant R410A
Air supply mode Horizontal flow
Dimensions (H x W x D) 2000 mm x 300 mm x 1100 mm (cabinet dimensions)
Certification REACH, RoHS, CE

Table 3-9 Optional specifications

Item NetCol5000-A025H412D2 NetCol5000-A025H412D2


0020E1 E120E1

Power supply Dual power supplies Dual power supplies


Cooling capacity 25 kW
Air volume 5000 m3/h
Current 20 A 30 A
Power system Supports the 380–415 V, 3PH+N+PE, 50/60 Hz power
system, and applies to scenarios where the voltage range is
342–457 V and frequency range is 47–63 Hz.
Voltage tolerance Rated voltage±10%
If the upstream voltage fluctuation exceeds this range, add a
voltage stabilizer; otherwise, the air conditioner will
frequently generate alarms and fail to work
Frequency tolerance Rated frequency±3 Hz
Heating function No 4 kW
Humidification function No 1.5 kg/h
Piping Route pipes from the top or Route pipes from the top or
bottom bottom
Condensate pump Yes Yes
Pump lift 4m 4m
In the preceding table, No indicates that the corresponding model does not provide the
function.
Cooling capacity test conditions: dry bulb temperature at air return vent: 37.8°C; wet bulb
temperature at air return vent: 20.8°C; condensing temperature: 45°C

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 25


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

3.3.2.5 Outdoor Unit

Appearance
Figure 3-14 shows the model and appearance of the NetCol500 outdoor unit.

Figure 3-14 NetCol500 appearance

Product Composition
Figure 3-15 shows the composition of the NetCol500 outdoor unit.

Figure 3-15 Composition of the NetCol500 outdoor unit

(1) Fan (2) Rack (3) Fan drive

Specifications
Figure 3-16 shows the dimensions of the NetCol500.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 26


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-16 Dimensions of the NetCol500

Table 3-10 lists the technical specifications of the NetCol500 outdoor unit.

Table 3-10 Technical specifications of the NetCol500 outdoor unit

Product Model NetCol500-A0265S11E0


Power system 380–480 V AC, 3 Ph/N/PE, 50 Hz/60 Hz (for a
unit with a low-temperature component, the
power system is 380–415 V AC, 3 Ph/N/PE, 50
Hz/60 Hz)
Voltage tolerancea Rated voltage±10%
Frequency tolerance Rated frequency±3 Hz
Maximum current 2.5 A
Air volume 12,000 m3/h
Number of fans 1
Dimensions H x W1 (W2) x D 620 mm x 1120 (985) mm x 1094 mm
Liquid pipe outer diameter 5/8 in (15.9 mm)
Gas pipe outer diameter 3/4 inch (19.1 mm)
Net weight 132 kg
Certification RoHS, REACH, CE
Operating temperature Depends on the indoor unit. For details, see the
product overview in the indoor unit user
manual.
Storage temperature –40°C to +70°C
Storage humidity 5%–95% RH (non-condensing)

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 27


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Product Model NetCol500-A0265S11E0


Altitude 0–1000 m: normal use; above 1000 m: derating.
For derating details, see the product overview in
the indoor unit user manual delivered with the
equipment.
a: If the upstream voltage may fluctuate outside the voltage tolerance, add a voltage
stabilizer; otherwise, the air conditioner may fail to run properly due to frequent alarms.

Outdoor unit installation environments are classified as follows based on the harshness:
 Class A (controlled environment): indoor environments where the ambient temperature and humidity
are controlled, including rooms where people live
 Class B (uncontrollable environment): indoor environments where the ambient temperature and
humidity are not controlled or general outdoor environments with simple shielding measures where
the humidity sometimes reaches 100%
 Class C (harsh environment): marine environments within 3.7 km from the coast or outdoor land
environments with simple shielding measures within 1.2 km from a pollution source
 Class D (marine environment): environments within 500 m from the coast

The NetCol500-A026 cannot be used in class D environments.

3.3.3 Low-Temperature Component


Working Principle
When the outdoor temperature is below the operating temperature lower limit specified for the
product, the condensing pressure of the system for the outdoor unit condenser with natural
cooling may still below the safe operating pressure of the compressor. A low-temperature
component is required to address this issue.
The low-temperature component intelligently controls the condensing pressure to ensure that
the equipment can work safely and reliably at an outdoor ambient temperature as low as
–40ºC. When detecting that the outdoor condensing pressure is low, the pressure stabilizing
valve automatically opens to bypass hot gas to the liquid storage tank, thereby ensuring that
the condensing pressure stays in the range for safe and reliable operation. When detecting that
the condensing pressure exceeds the threshold, the pressure stabilizing valve automatically
closes the bypass.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 28


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-17 Low-temperature component

(1) Safety valve (2) Liquid line port 1 (3) Liquid line port 2
(4) Condensing pressure control valve (5) Gas pipe port 1 (6) Gas pipe port 2

A low-temperature component is mandatory when the outdoor ambient temperature may drop
below –20ºC.

Table 3-11 Low-temperature component specifications

Item Specifications
Heater box power supply 220 V AC to 240 V AC, 1 P, 50 Hz/60 Hz
Heater box voltage tolerance Rated voltage±10%
Heater box frequency tolerance Rated frequency±3 Hz
Refrigerant R410A
Liquid pipe outer diameter 5/8 inch (15.9 mm)
Gas pipe outer diameter 7/8 inch (22.3 mm)
Dimensions (H x W x D) 944 mm x 632 mm x 507 mm (with
packing)
828 mm x 470 mm x 300 mm (without
packing)
Expansion bolt hole M12x60
Storage temperature –40°C to +70°C
Storage humidity 5%–95% RH (non-condensing)
Maximum operating pressure 4.35 MPa

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 29


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

3.4 Management System


The FusionModule1000 uses the ECC800 for local monitoring by default, and the NetEco can
be configured.

Table 3-12 NetEco configuration scenario

Function ECC800 NetEco Remarks


Client authorization 6 PCS Basic license. One  A single
license manages up container can
to 25 smart nodes, contain 14 smart
and a maximum of nodes.
20 licenses can be  The number of
configured. smart nodes
applies to the
standard
configuration.
Optional license, N/A
subject to
on-demand
configuration.
Work order No Yes N/A
management
Energy efficiency Yes Yes N/A
management
Capacity No Yes N/A
management
SNMP northbound Yes Yes N/A
device alarm
SNMP northbound Yes Yes N/A
device data
monitoring
Mobile app O&M Yes Yes N/A
NE data and alarm Yes Yes N/A
monitoring
Access management Yes Yes N/A
Intelligent lighting Yes Yes N/A
View presetting Yes No (manually drag) N/A
Adaptive software ECC800 NetEco N/A
version V100R001C20 V600R007C80 and
later

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 30


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Function ECC800 NetEco Remarks


Configuration Standard Optional: N/A
principle configuration  Single-container
deployment:
advise the
customer not to
configure.
 Multiple-contain
er deployment:
advise the
customer to
configure for
managing
multiple sites
through one port.
Hardware N/A  As servers use It is recommended
configuration AC power, that the NetEco
additional hardware be
inverters can be deployed in the
configured to customer's
convert DC monitoring room to
power into AC facilitate central
power for monitoring of
reliable power distributed sites.
supply. Two If the NetEco is
inverters should deployed inside the
be configured, container, it
and they occupy occupies space for
2 U space. server cabinets.
 LAN switch: The
number of
connected ports
depends on the
number of
connected
ECC800s. It
usually occupies
1 U space.
 Server: It is
configured for
the NetEco and
usually occupies
2 U space.
 1 U cabling
space

NetEco V600R007C80 or a later version is applicable to the FusionModule1000. The iManager NetEco
configurator can be used for configuration.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 31


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-18 Monitoring network diagram

 The VESDA and hydrogen controller are optional and not configured by default.
 Common card readers are configured for the access control system by default, and they should be
used at an ambient temperature ranging from –40°C to +85°C. Customized three-in-one fingerprint
and card readers with keypads are also supported, and they should be used at an ambient temperature
ranging from –10°C to +55°C. The three-in-one card readers cannot be used outdoors when the
ambient temperature is below –10°C or exceeds 55°C.
 The camera uses an SD card with a capacity of 64 GB for storage by default, and supports 7x24
recording at 720P/512K. A video management device (VCN500) should be configured if there is a
need of longer-time storage, management, and configuration of external cameras.

3.4.1 Overview
The management system includes the management software NetEco (optional) and
management hardware ECC800 and provides the following linkage features:

Hydrogen Linkage
If the hydrogen sensor and hydrogen controller are configured, the hydrogen controller
controls the hydrogen exhaust fan.

Fire Linkage
The ECC800 monitors the fire control panel onsite. Upon detecting a gas release alarm, the
ECC800 issues a release command to the air conditioners in the FusionModule1000 so that
they will shut down.

For the sake of safety, this function is disabled by default.

Component Layout
Figure 3-19 shows the management system component layout diagram.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 32


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-19 Layout of management components

(1) Temperature and humidity sensor (2) Network frame (3) Access actuator
(4) Smart ETH gateway (5) Pad (6) Camera
(7) AC actuator (8) WiFi converter

3.4.2 ECC800 Collector


The ECC800 manages the real-time status, alarm information, and configuration information
of devices (including the PDC, air conditioner, AC/DC power system, environment sensors,
lights, access controllers, PDC monitoring units, and fire extinguishing system) inside a
container, and provides a GUI for O&M. It consists of two power supply units (PSUs) and
one ECC800 monitoring module.
Figure 3-20 and Figure 3-21 show an ECC800 controller.

Figure 3-20 ECC800 controller (front view)

(1) Combined module (2) Status indicator (3) 3G/4G antenna port

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 33


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

(4) FE ports (WAN_1-WAN_2 and (5) AI/DI_1–6 sensor (6) RF_Z antenna port
LAN_1-LAN_2) input ports
(7) SW button (8) DO_1–2 dry (9) RS485 port
contact output (COM1–4/12 V)
(10) Default button (11) USB port (12) ECC800 main
control module

Figure 3-21 ECC800 controller (rear view)

(1) 53.5 V DC_OUT1 (2) 53.5 V DC_OUT2


(3) AC_INPUT1 (4) AC_INPUT2

Specifications
Table 3-13 lists the ECC800 technical specifications.

Table 3-13 ECC800 technical specifications

Item Specifications
Power input  Dual AC input and dual –48 V DC power supply
 Rated voltage: 200–240 V AC/100–120 V AC
 Rated frequency: 50 Hz/60 Hz
 Input current: 6.7 A
Power output  Rated voltage: 53.5 V DC
 Output power of two power supplies: 2000 W (176–300 V AC);
940 W (linear derating at 85–175 V AC)
 Output power of a single power supply: 1000 W (176–300 V
AC); 470 W (linear derating at 85–175 V AC)
 Output current: 14 A
System memory 512 MB
Solid state disk 2 GB and 128 MB of storage space

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 34


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Item Specifications
FE port expansion Two WAN ports, two LAN ports, and 10/100M communications
rate
RS485 serial port  Reserves four RS485 ports with a default communications rate
expansion of 9600 bit/s.
 Each port provides 12 V DC power with a rated current of 450
mA.
AI/DI expansion  Supports six AI/DI ports to connect to smoke sensors, water
(RJ45) sensors, and temperature sensors.
 Each port provides 12 V DC power with a rated current of 85
mA.
DO expansion  Supports two expansion dry contacts with contact point capacity
(RJ45) of 20 W, maximum withstand voltage of 60 V DC, and rated
current of 0.5 A.
 Supports two active DO ports with the output voltage of 12 V
DC and output current of 450 mA.
Wireless Supports wireless communication that complies with
communication IEEE802.15.4.
3G Supports 3G (WCDMA) communication and is compatible with 2G
(GSM) communication. A standard SIM card slot is provided.
NOTE
A SIM card can be used only in sites with signal coverage.

USB Provides a general USB port.


Button  SW: wireless network pairing button
 Default: restores the default IP address

Indicators
Table 3-14 describes the indicators on the ECC800 monitoring module.

Table 3-14 Indicators on the ECC800 monitoring module

Indicator Color Name Status Description


RUN Green Running status Steady on The power supply is normal, the
indicator program is being loaded, or
WiFi WPS is pairing.
Off The power supply is abnormal.
Blinking at The software runs properly (the
long indicator blinks at 0.5 Hz, on for
intervals 1s and then off for 1s) or the
ECC800 registers with the
NetEco successfully.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 35


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Indicator Color Name Status Description


Blinking at The ECC800 does not register
short with the NetEco (the indicator
intervals blinks at 4 Hz, on for 0.125s and
then off for 0.125s).
ALM Red Alarm indicator Steady on A system failure alarm is
generated.
Off The system is normal.
3G Green 3G status Steady on The 3G module is powered on.
indicator
Off The 3G module stops running,
or no 3G module is configured.
Blinking at The 3G module succeeds in
long dial-up (the indicator blinks at
intervals 0.5 Hz, on for 1s and then off
for 1s).
Blinking at The 3G module registers with
short the operator network
intervals successfully (the indicator
blinks at 4 Hz, on for 0.125s and
then off for 0.125s).
RF_Z Green Communication Steady on No network parameters exist, or
status indicator a network is to be created.
Blinking at A network is set up, and no
long node access is allowed (the
intervals indicator blinks at 0.5 Hz, on for
1s and then off for 1s).
Blinking at A network is set up, and node
super short access is allowed (the indicator
intervals blinks at 10 Hz, on for 0.05s and
then off for 0.05s).

Wireless Network Pairing (SW) and IP Address Reset (Default) Buttons


Table 3-15 describes the wireless network pairing and IP address reset buttons.

Table 3-15 Wireless network pairing and IP address reset buttons

Button Function Operation Description Indicator Status


Name Description

SW Wireless In non-wireless network (802.15.4) The RF_Z indicator


network pairing mode, press and hold down is blinking at super
(802.15.4) the button for 1.2s to 5s to enter the short intervals.
pairing wireless network pairing mode.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 36


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Button Function Operation Description Indicator Status


Name Description
In wireless network (802.15.4) The RF_Z indicator
pairing mode, press and hold down is blinking at long
the button for 1.2s to 5s to exit the intervals.
pairing mode; or the system
automatically exits the pairing mode
after 30 minutes without pressing
the button.
Press and hold down the button for The RF_Z indicator
more than 6s to clear network is on.
parameters.
WiFi pairing In non-WiFi pairing mode, press the  When the system
button button for less than 1.2s to enter the enters the pairing
WiFi pairing mode. mode, the RUN
indicator is
steady on.
 After pairing
succeeds, the
RUN indicator
blinks just as
before WiFi
pairing.
 If pairing does
not succeed in
three minutes, the
RUN indicator
blinks just as
before WiFi
pairing.
Default IP address reset Press and hold down the button for None
3s. Then the IP address for the
ECC800 WAN_1 port will be
restored to the default address
192.168.1.10.

On the WebUI, restoring factory settings by one-click is supported. Click Maintenance >
Configuration File > Restore Factory Settings.
 The monitoring module IP address restores to the default value.
 The video device IP address restores to the default value.
 Configuration parameters of each device restore to default values (except the access control
configuration parameters).
 The container plan view configuration is cleared.
 Alarm parameter configuration restores to default values.
 The NetEco communication parameters restore to default values.
 The container name restores to the default value.
 The WiFi function is disabled.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 37


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

 The time and time zone restore to default values.

3.4.3 Independent Deployment AI/DI Unit


An independent deployment AI/DI unit provides a maximum of eight AI/DI inputs to collect
AI/DI signals. It can be mounted on a 19-inch rack.

Figure 3-22 Ports on an independent deployment AI/DI unit

Table 3-16 Ports on the independent deployment AI/DI unit front panel

Silk Screen Port Description


COM_IN Cascading ports. COM_IN connects to the RS485 port on the ECC800, and
COM_OUT COM_OUT connects to another independent deployment AI/DI unit.

AI/DI_1–AI/ Provide 12 V DC outputs for sensors and are compatible with 4–20 mA
DI_8 current signals, signals from current-based smoke sensors and water
sensors, dry contact signals, and NTC signals.
Pin definition:
3: 12 V DC, 54 mA
6: D-
7: D+
8: GND

3.4.4 Smart ETH Gateway


A smart ETH gateway allows the extension of the 53.5 V DC power supply and FE
communication for the ECC800 and can be flexibly deployed in a FusionModule1000 data
center.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 38


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-23 Smart ETH gateway

(1) PWR_IN cascading (2) FE_1 cascading signal (3) PoE_1–2 ports
power port port
(4) PoE_3–4 ports (5) 48V_OUT1 power output (6) 48V_OUT2 power
port output port
(7) FE_2 cascading signal (8) PWR_OUT cascading (9) BLINK button
port power port
(10) Status indicator

Specifications
Table 3-17 lists the environmental specifications for a smart ETH gateway.

Table 3-17 Technical specifications for a smart ETH gateway

Item Specifications
Power input PWR_IN D-type power input terminal, for power cascading, input voltage
range: 45–55 V DC
Power output  PWR_OUT D-type power output terminal, for power cascading, output
voltage range: 45–55 V DC
 48V_OUT1 and 48V_OUT2, phoenix terminal, output voltage range:
45–55 V DC
FE port Two FE ports, RJ45 terminal with an indicator, 10/100M communication
rate, for the cascading between smart ETH gateways and the
communication with the upstream computer
PoE port Four PoE ports, RJ45 terminal with an indicator, 10/100M
communications rate, 12 V DC of power output, complying with
IEEE802.3at
BLINK If you press the BLINK button, the RUN indicator blinks intermittently at
button super short intervals (blinking at super short intervals for 0.5s and then off
for 0.5s) for 10 seconds. This indicates that the smart ETH gateway
reports the Media Access Control (MAC) address and equipment serial
number (ESN) to the ECC800.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 39


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Indicators
Table 3-18 describes the indicators on a smart ETH gateway.

Table 3-18 Indicators on a smart ETH gateway

Indicator Color Name Status Description

PWR Green Power Steady on The power input is normal.


input
status Off There is no power input.
indicator
RUN Green Module Off The power supply is abnormal.
running
status Blinking at The smart ETH gateway
indicator long intervals successfully registers with the
ECC800 and the software runs
properly (the indicator blinks at 0.5
Hz, on for 1s and then off for 1s).
Blinking at The smart ETH gateway does not
short intervals register with the ECC800 (the
indicator blinks at 4 Hz, on for
0.125s and then off for 0.125s).
Blinking The indicator blinks at super short
intervals for 0.5s (blinking at 10 Hz,
on for 0.05s and then off for 0.05s)
and then turns off for 0.5s. The
cycle lasts for 10s.
ALM Red Alarm Steady on A system failure alarm is generated.
indicator
Off No system alarm is generated.

3.4.5 Access Actuator


The access actuator is the control component for the front door in a modular data center of a
prefabricated all-in-one data center. It connects to the ECC800 controller system over the FE
port, wireless networking (802.15.4), or RS485 port. It opens the magnetic lock by detecting
the card swiping information of the card reader, door open button information, and fire
linkage information. It has access right management, access event recording, and alarm
recording functions.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 40


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-24 Access actuator

(1) 48 V power port (2) PoE port (3) RS485 port COM2
(4) RS485 port COM1 (5) Address DIP switch (6) Status indicator
(7) BLINK button (8) WG_2 Wiegand (9) WG_1 Wiegand interface
interface
(10) AI/DI_2 dry contact (11) AI/DI_1 dry contact (12)
LOCK/GND/GATE/GND/door
status and magnetic lock port

Specifications
Table 3-19 lists the access actuator technical specifications.

Table 3-19 Access actuator technical specifications

Item Specifications

Power input 36–60 V DC input voltage, phoenix terminal


PoE port FE communication, 10/100M communications rate, 12 V DC power
output
Wireless One wireless communication port that complies with IEEE802.15.4,
communicatio mutual backup with FE communication
n
AI/DI port Two AI/DI ports, can connect to the fire alarm and exit button
DO output One 12 V DC power output that controls magnetic locks, phoenix terminal

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 41


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Item Specifications
DI input One DI input port for connecting to the door status switch
RS485 serial Two RS485 ports (one route) with the default communications rate of
port 9600 bit/s, physical port cascading supported (reserved function)
expansion
Wiegand Two Wiegand interfaces, 12 V DC card reader operating power output;
interface two routes of card readers can operate at the same time.
BLINK  Press the button for less than 1 second to start blinking.
button  Hold down the button for 1–5 seconds to search for a network and start
networking.
 Hold down the button for more than 6 seconds to clear network
parameters.
Address DIP 4-pin address DIP switch
switch
E-label Supported

Indicators
Table 3-20 describes the access actuator indicators.

Table 3-20 Access actuator indicator description

Indicator Color Name Status Description


PWR Green Power Steady on The power input is normal.
input
status Off There is no power input.
indicator
RUN Green Communi Off The power is abnormal or the board
cation program is loading.
status
indicator Blinking at The access actuator successfully
long intervals registers with the ECC800 and the
software runs properly (the
indicator blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at The communication is disconnected
short intervals or the access actuator fails to
register with the ECC800 (the
indicator blinks at 4 Hz, on for
0.125s and then off for 0.125s).

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 42


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Indicator Color Name Status Description


Blinking The indicator blinks at super short
intervals for 0.5s (blinking at 10 Hz,
on for 0.05s and then off for 0.05s)
and then turns off for 0.5s. The
cycle lasts for 10s.
ALM Red Alarm Steady on A system failure alarm is generated.
indicator
Off No system alarm is generated.
RF_Z Green Wireless Steady on No network parameters exist, or a
communic network is to be created.
ation
status Blinking at A network is set up, and no node
indicator long intervals access is allowed (the indicator
blinks at 0.5 Hz, on for 1s and then
off for 1s).
Blinking at A network is set up, and node
super short access is allowed (the indicator
intervals blinks at 10 Hz, on for 0.05s and
then off for 0.05s).
Blinking The access actuator is searching for
intermittently a network (the indicator blinks at
at super short super short intervals for 0.5s and
intervals then turns off for 0.5s).

Communications Ports
The access actuator provides one DO port (LOCK/GND) and one DI port (GATE/GND).
Table 3-21 lists the LOCK/GND/GATE/GND port pin definitions.

Table 3-21 LOCK/GND/GATE/GND port pin definitions

Item Description
LOCK/GND LOCK 12V_OUT
(control
magnetic GND GND
locks) pin
sequence
GATE/GND GATE DI1
(door status)
pin sequence GND GND

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 43


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

3.4.6 AC Actuator
The AC actuator is used in a container data center to receive infrared signals or upstream
instructions for controlling lights or fans. The AC actuator can connect to the ECC800
controller by wireless networking (802.15.4).

Figure 3-25 AC actuator

(1) AC OUT2 port (2) AC OUT1 port (3) AC IN port


(4) Status indicator (5) BLINK button (6) AI/DI dry contact
(7) COM1–2 RS485 port

Specifications
Table 3-22 lists the AC actuator environmental specifications.

Table 3-22 AC actuator technical specifications

Item Specifications

Power input One AC input, 90–240 V AC


Power output Two AC outputs, 90–240 V AC, maximum current 5 A
Wireless One wireless communication port, complying with IEEE802.15.4
communicatio
n

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 44


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Item Specifications
RS485 port One route of dual RS485 ports, not isolated (reserved)
AI/DI Two AI/DI dry contacts, reserved
detection
BLINK  Press the button for less than 1 second to start blinking.
button  Hold down the button for 1–5 seconds to search for a network and start
networking.
 Hold down the button for more than 6 seconds to clear network
parameters.

Indicators
Table 3-23 describes the indicators on the AC actuator.

Table 3-23 AC actuator indicators

Indicator Color Name Status Description


Power Green Power Steady on The power input is normal.
status
indicator Off There is no power input.

RUN Green Running Off The power is abnormal or the board


status program is loading.
indicator
Blinking at The AC actuator successfully
long intervals registers with the ECC800 and the
software runs properly (the
indicator blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at The communication is disconnected
short intervals or the AC actuator fails to register
with the ECC800 (the indicator
blinks at 4 Hz, on for 0.125s and
then off for 0.125s).
Blinking The indicator blinks at super short
intervals for 0.5s (blinking at 10 Hz,
on for 0.05s and then off for 0.05s)
and then turns off for 0.5s. The
cycle lasts for 10s.
ALM Red Alarm Steady on A system failure alarm is generated.
indicator
Off No system alarm is generated.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 45


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Indicator Color Name Status Description


RF_Z Green Communi Steady on No network parameters exist, or a
cation network is to be created.
status
indicator Blinking at A network is set up, and no node
long intervals access is allowed (the indicator
blinks at 0.5 Hz, on for 1s and then
off for 1s).
Blinking at A network is set up, and node
super short access is allowed (the indicator
intervals blinks at 10 Hz, on for 0.05s and
then off for 0.05s).
Blinking The AC actuator is searching for a
intermittently network (the indicator blinks at
at super short super short intervals for 0.5s and
intervals then turns off for 0.5s).

3.4.7 WiFi Converter


The WiFi converter is used in the FusionModule1000 to convert PoE signals into WiFi signals
for communicating with devices such as the pad and mobile phone.

Figure 3-26 WiFi converter

(1) RF_1 antenna port (2) RF_2 antenna port (3) Reset (4) WPS button
(5) Status indicator (6) 48 V power port (7) PoE port

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 46


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Technical Specifications
Table 3-24 lists the WiFi converter technical specifications.

Table 3-24 WiFi converter technical specifications

Item Specifications

Power input One power input port with the 3-pin Phoenix terminal; input voltage
range: 36–60 V DC
WiFi function  2.4 GHz frequency, two antennas, supporting eight STA connections,
50 m WiFi coverage (no blockage)
 Support the WPS button
PoE port One PoE port, complying with IEEE802.3AT, 25.5 W
Reset button Press and hold down the button for more than 5s to restore the factory
settings of the WiFi converter
WPS button Support fast WiFi access by WPS

WPS function: If you choose Advanced settings > WPS connection on the WLAN of the intelligent
device and press the WPS button on the WiFi converter at the same time, the intelligent device will
quickly connect to the WiFi hotspot of the container.

Indicators
Table 3-25 describes the indicators on the WiFi converter.

Table 3-25 WiFi converter indicators

Indicator Color Name Status Description


RUN Green Running Steady on The power supply is normal.
status
indicator Off The power supply is abnormal.
Blinking at The WiFi converter successfully
long intervals registers with the ECC800 and the
software runs properly (the
indicator blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at The WiFi converter fails to register
short intervals with the ECC800 or the
communication is disconnected (the
indicator blinks at 4 Hz, on for
0.125s and then off for 0.125s).
ALM Red Alarm Steady on A system failure alarm is generated.
indicator
Off No system alarm is generated.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 47


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Indicator Color Name Status Description


WiFi Green WiFi Steady on The WiFi converter is powered on
status but there is no data communication.
indicator
Blinking Data communication is in progress.
WPS Green WPS Off The WPS is normal.
mode
indicator Blinking WPS matching mode. If the
matching fails, the WPS indicator
turns off after blinking for 2
minutes. If the matching is
successful, the WPS indicator turns
off.

3.4.8 IP Camera
An IP camera (IPC) IPC6325 is deployed inside a container. The camera has the following
features:
 Support for the H.265 encoding format and dual-channel 1080p HD video encoding
 Built-in 2.8 mm to 12 mm HD zoom lens, enabling more flexible surveillance
 IP66 waterproof and dustproof rate, ensuring that the camera can run reliably outdoors
for a long time
 IK10 vandal-proof rate, preventing video surveillance interruption due to violent
damages to the camera
 Compliance with the railway industry certification, applicable to trackside scenarios
 A super WDR of 120 dB, ensuring that both foreground and background objects are
clearly identified in environments with sharp light contrast
 Intelligent defogging, enhancing image definition in foggy environments
 Intelligent infrared lamp, automatically adjusting the infrared transmit power and angle
 Five intelligent behavior analysis functions, color classification, human and vehicle
classification
 Super Error Concealment (SEC) to ensure smooth images in case of 20% network packet
loss rate
 Transmission quality diagnosis through Packet Conservation Algorithm for Internet
(iPCA)
 Acousto-optic assisted focus, ensuring higher installation and commissioning efficiency
 An ultra wide operating temperature that ranges from –30°C to +60°C
 An ultra wide operating voltage range of ±25%
 PoE, DC, and AC power supply modes; DC/AC power adapter and PoE in hot standby
mode

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 48


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-27 IPC6325 camera

Table 3-26 lists the IPC6325 camera technical specifications.

Table 3-26 Technical specifications of IPC6325


Parameter Value

Camera Image sensor 1/2.7" 2.0-megapixel progressive scan CMOS


Maximum 1920 (H) x 1080 (V)
image
resolution
Minimum  Multicolor: 0.01 lux (F1.4, AGC ON)
illumination  B/W: 0.004 lux (F1.4 and AGC on)
 B/W (infrared lamp enabled): 0 lux
Maximum 30 m
infrared
radiation
distance
Day/Night Automatic, Multicolor, or B/W (ICR)
mode
Electronic 1/100000s to 1s
shutter speed
Gain control Automatic or manual
WDR 120 dB
Backlight Supported
compensation
(BLC)
Image Automatic or manual
defogging
White balance Automatic/Automatic tracking/Manual/OnePush; support for
scene selection (indoor/outdoor/incandescent lamp/fluorescent
lamp)

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 49


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Parameter Value
Digital noise Self-adaptive to 2D or 3D DNR
reduction
(DNR)
Lens Focal length 2.8 mm to 12 mm manual focus, 4.3x optical zoom
Angle of view  Horizontal: 36°(telephoto) to 106°(pantoscopic)
 Vertical: 20°(telephoto) to 57°(pantoscopic)
Maximum iris F1.4
Automatic iris DC iris
Three-axis Horizontal: 0°to 356°; vertical: 0°to 75°; rotation: 0°to 356°
adjustment
angle
Functio Video H.265/H.264/MJPEG
n encoding
format
Maximum 1920 x 1080
resolution
Frame rate  60 Hz: 1 fps to 30/20 fps
 50 Hz: 1 fps to 25/20 fps
Video bit rate 32 kbit/s to 16 Mbit/s
Multi-channel Support for three channels of streams and dual-channel 1080p
video encoding HD video encoding
Audio G.711a/G.711u/G.726/OPUS
encoding
format
Voice Voice intercom and broadcast
communication
PU access ONVIF Profile S/G, GB/T 28181-2014, Genetec Protocol
protocol v1.00, and Huawei SDK (proprietary)
Network TCP, UDP, IPv4, DHCP, DNS, ICMP, IGMP, HTTP, HTTPS,
protocol SFTP, RTP, RTSP, RTCP, SIP, ARP, TLS, NTP, SNMP
(V1/V2/V3), 802.1x, QoS, and DDNS
Security mode User name and password authentication, 802.1x (MD5
Challenge/EAP-TLS), and HTTPS digital certificate
Media security Stream encryption using the AES128/192/256 encryption
algorithm; support for digital watermark
Intelligent Support for tripwire detection, loitering detection, intrusion
video analysis detection, abandoned object detection, removed object
detection, object color identification, human and vehicle
classification, and metadata backhaul

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 50


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Parameter Value
Motion Support for four motion detection and lens block detection
detection and areas
lens block
detection
Alarm linkage  Alarm source: motion detection alarm/lens block
alarm/alarm input/intelligent analysis alarm
 Alarm linkage: alarm output/preset position
invoking/scanning during parking actions/SD card video
recording/snapshot taking
Interfac Network One RJ45 10/100 Base-T adaptive Ethernet interface
e interface
Communicatio One RS-485 interface
n serial
interface
Alarm interface 1-channel alarm input, 1-channel alarm output
Video interface BNC interface; 1-channel hybrid analog video output through
the CVBS interface
Audio interface Support for 1-channel audio input and 1-channel audio output
through 3.5 mm audio interfaces
Storage One Micro SD card slot that supports SDHC or SDXC cards
interface (maximum capacity: 64 GB)
General Power supply PoE (802.3at/af), 18 V AC to 30 V AC, 18 V DC to 30 V DC,
specific 9 V DC to 15 V DC (non-polarity DC); DC/AC power adapter
ations and PoE in hot standby mode
Power Typical power consumption: 4 W; maximum power
consumption consumption: 10 W
Operating –30°C to +60°C
temperature
Operating 5% RH to 95% RH (noncondensing)
humidity
Surge 4 kV surge protection that meets the IEC 61000-4-5 standard
protection level
Anti-corrosion Compliance with the ISO9223 C4 corrosion resistance
standard and the IEC 60068-2-11 standard
Protection rate IP66 (meeting the IEC 60529 standard)
Vandal-proof IK10 (meeting the IEC 62262 standard)
rate
Railway Compliance with the EN 50121-4 EMC standard and
industry EN50125-3 anti-vibration standard
certification

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 51


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Parameter Value
Weight Net weight: 1 kg; gross weight: 1.4 kg
Physical Φ135 mm x 112.5 mm
dimensions
Packing 260 mm x 195 mm x 148 mm
dimensions

3.4.9 Water Sensor


The water sensor monitors water leaks on the floor in real time. When water intrusion is found,
the water sensor generates an audible alarm and delivers dry contact signals to report the
alarm.

Figure 3-28 Water sensor

Table 3-27 Water sensor technical specifications

Item Specifications
Operating voltage 12 V DC (9–16 V DC)
Signal output under the CLOSED
condition of no liquid detected
Signal output under the OPEN
condition of liquid detected
Insulation resistance > 500 megohms
Operating temperature –20°C to +70°C
Storage temperature –40°C to +85°C (non-condensing)
Protection level IP68
Length of the signal cable 1m
Reliability Failure rate: 8000 fits
Power consumption < 0.2 W

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 52


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

3.4.10 Pad
The pad allows the wireless access from the container data center management system. You
can monitor the equipment in the container data center and environmental parameters in real
time over the APP.

Table 3-28 Structural specifications

Item Specifications
Dimensions (L x 248.5 mm x 150 mm x 8.3 mm
W x H)
Weight 430 g
Touchscreen 9.6-inch, 800X1280, IPS screen 1600 million colors, and capacitive
5-point touch
Chip processor MSM8916, four cores, 4xA53@1.2 GHz
WLAN 802.11a/b/g/n@2.4 GHz&5 GHz
Storage  ROM: 16 GB
 RAM: 2 GB
 Expansion card: micro SD (TF), a maximum of 64 GB supported
Button/Port  Power switch and volume button
 3.5 mm stereo headphones port
 Micro SD card port
 Micro-USB port that supports charging and synchronization with
PC data
Battery  Materials: Li-polymer
 Capacity: 4800 mAh
 Standby time: about 570 hours
 Power adapter charge time: about 5–6 hours
Operating Android 4.4 (KitKat)+Emotion UI 3.0
system

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 53


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

3.4.11 Rack Environment Unit (Optional)


Figure 3-29 Rack environment unit

(1) Ground port (2) 48 V DC power input (3) PoE port (4) COM1/12 V
port port
(5) COM2/12 V (6) COM3 port (7) COM4 port (8) NTC1–3
port
(9) NTC4–6 (10) AI/DI_1 port (11) AI/DI_2 port (12) 12V_1 port
(13) 12V_2 port (14) SW button (15) Status
indicator

Technical Specifications
Table 3-29 lists the technical specifications for the rack environment unit.

Table 3-29 Technical specifications for the rack environment unit

Item Specifications

Power input Phoenix terminal, with input voltage of 36–60 V DC


12 V power Two 12 V DC power outputs with the rated output current of 250 mA
output
PoE port  FE communication with the rate of 10/100M
 12 V DC power output
RS485 serial  Four RS485 ports with a default communications rate of 9600 bit/s
port  Among the four RS485 ports, two support 12 V DC, 400 mA power
expansion output.
 The other two are isolated, with the default communications rate of
9600 bit/s, and do not support power output.
AI/DI input Two active 12 V DC, 200 mA AI/DI input ports
Temperature Provides two RJ45 ports to connect to six temperature sensors, each RJ45
sensor port port connecting to three temperature sensors.
BLINK Provides a BLINK button.
button

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 54


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Indicators
Table 3-30 describes the rack environment unit indicators.

Table 3-30 Indicator description

Indicator Color Name Status Description

PWR Green Power Steady on The power input is normal.


input
status Off There is no power input.
indicator
RUN Green Module Off The power is abnormal or the board
running program is loading.
status
indicator Blinking at The software runs properly (the
long indicator blinks at 0.5 Hz, on for 1s
intervals and then off for 1s).
Blinking at PoE communication fails (the
short indicator blinks at 4 Hz, on for
intervals 0.125s and then off for 0.125s).
Blinking The indicator blinks at super short
intervals for 0.5s (blinking at 10 Hz,
on for 0.05s and then off for 0.05s)
and then turns off for 0.5s. The
cycle lasts for 10s.
ALM Red Alarm Steady on A system failure alarm is generated.
indicator
Off No system alarm is generated.

3.4.12 Cabinet Access Control System (Optional)


Cabinet-level access control is available for containers to further improve the data and device
security.
The cabinet access control system has the following features:
 The IC card for the cabinet access control system can be used after being authorized by
using software.
 An IC card can be authorized for one electric lock or for all electric locks.
 Door opening events can be logged in the management system.
 The system displays the status of cabinet doors and locks in real time, and generates
alarms for unauthorized door opening.
 The system supports remote door opening by using the NMS (network management
system).
Figure 3-30 shows a cabinet electronic lock. Table 3-31 lists its technical specifications.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 55


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-30 Cabinet electronic lock

Table 3-31 Technical specifications

Item Specifications

Rated input voltage 12–24 V DC


Rated current 200–300 mA
Lock opening mode By powering on the lock
Available card IC card
Supporting mechanically unlocking Yes

3.4.13 Intelligent Battery Monitoring System (Optional)


The intelligent battery monitoring system consists of a CIM (CIM01C2) and BIMs
(BIM01C3/BIM02C1), and is configured when the iBAT is required.

CIM
The Communication Interface Module (CIM) is an intelligent battery management module
which collects wireless communication data from the downstream BIM groups, collects the
operating data of battery strings, calculates State Of Charge (SOC) and State Of Health (SOH)
of batteries and battery strings, estimates the battery health status, supports battery tripping
management, and uploads data to the MDU/ECC through RS485 or PoE ports.
 Collects battery data detected by the BIM through wireless communication.
 Each CIM can manage a maximum of four battery strings or 300 batteries.
 An external Hall effect sensor is connected to monitor the current of each battery string.
 Calculates the SOC and SOH of batteries and battery strings.
 Accurately identifies weak batteries in a battery string.
 Identifies loose battery terminals and battery terminal overtemperature, and controls
battery switch tripping.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 56


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

 Supports WebUI display, northbound communication over FE and RS485, and a


third-party NMS.
 Supports CIM and BIM online upgrade on an upstream management unit.

If the upgrade package is transmitted to the CIM within 30 minutes, the upgrade is complete. The BIM
upgrade is finished through the CIM backend. The CIM ensures the successful upgrade of the BIM
through retransmitting and flow control.

Figure 3-31 shows the CIM front view, and Figure 3-32 shows the CIM rear view.

Figure 3-31 CIM front view

(1) –48 V 0.5 A port (power (2) PoE port (3) COM_IN port (RS485
input) communication input)
(4) COM_OUT port (RS485 (5) DI and DO ports (6) HALL_1–HALL_8 current
communication output) monitoring ports
(7) RF_Z antenna port (8) BCB_1–BCB_4 (9) BCB_OUT and BCB_IN
ports ports
(10) Networking switch (11) PWR indicator (12) RUN indicator
(13) ALM indicator (14) RF_Z indicator (15) Delivered antenna

Ports support the security mechanism.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 57


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-32 CIM bottom view

(1) Fastener (2) Micro SD card (3) Default button


slot (IP reset)
(4) ADDR dual in-line package (DIP) switch (5) 12 V 2 A port
(RS485 communication address) (power input)

BIM
The BIM (BIM01C3) is a battery monitoring module that supports 12 V power input and
monitors the voltages, internal resistances, and pole temperatures of batteries.
 Monitors the voltages, internal resistances, and pole temperatures of batteries.
 Provides the hibernation function (when it detects that the battery voltage is low, it turns
the battery to low-consumption mode).
 Uploads battery data to CIM through wireless communication.
Figure 3-33 show the front and bottom views of a BIM.

Figure 3-33 BIM front view

(1) RUN/ALM indicator (2) Networking switch

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 58


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

(3) Panel port (4) Fastener

3.4.14 External Camera (optional)


An external camera IPC6211 is deployed outside a container. The camera has the following
features:
 Intelligent infrared lamp power adjustment and a maximum infrared radiation distance of
30 meters
 Built-in motorized zoom and focus lens that supports manual, automatic, OnePush, and
synchronous focus
 An aspect ratio of 9:16
 Region of Interest (ROI) encoding
 Defogging
 Stream smoothing parameter configuration, adaptive bandwidth, MTU configuration,
and QoS configuration
 IP address filtering, stream AES encryption, and 802.1x access authentication
 Quick configuration of ISP and stream packages
 ISP package plan setting
 Ultra wide operating voltage range and ultra wide operating temperature range
 DC, AC, PoE power supply modes
 Dual system backup, ensuring faster upgrade and higher security
Figure 3-34 shows the appearance of IPC6211. Table 3-32 describes its technical
specifications.

Figure 3-34 Appearance of IPC6211

Table 3-32 Technical specifications of IPC6211

Parameter Value
Camera Image sensor 1/2.8" 2.0-megapixel progressive scan CMOS
Effective pixels 1920 (H) x 1080 (V)
Minimum  Multicolor: 0.01 lux (F1.4, AGC ON, 1/30s shutter speed,
illumination and 50 IRE) and 0.007 lux (F1.2, AGC ON, 1/30s shutter
speed, and 50 IRE)
 B/W (infrared lamp enabled): 0 lux

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 59


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Parameter Value
Day/Night Automatic ICR, multicolor, or B/W
mode
Shutter speed 1/16,000s to 1/25 (1/30)s
Gain control Automatic
Backlight Supported
compensation
(BLC)
Wide dynamic Digital WDR
range
White balance Manual/Auto/Indoor/Outdoor/Fixed sodium lamp/Fluorescent
lamp 1/Fluorescent lamp 2/Incandescent lamp/OnePush
Noise Self-adaptive to 2D or 3D DNR
reduction
Defogging Supported
Maximum 30 m
infrared
radiation
distance
Lens Lens type Built-in Φ14 motorized zoom lens with an IR-CUT filter
Focal length 2.8 mm to 12 mm (support for automatic focus)
Iris DC automatic iris; a maximum iris of F1.4
Angle of view Horizontal angle of view: 11.3°to 33.8°
Zoom 4.3x optical zoom
Functio Video H.264 Main Profile/Baseline Profile (support for Profile
n compression switchover) and MJPEG
standard
Video 1920 x 1080, 1280 x 720, 720 x 576, 720 x 480, 352 x 288,
resolution and 352 x 240 (H.264: 30 fps, 25 fps, 1 fps to 20 fps; MJPEG: 1
frame rate fps to 5 fps)
Video bit rate 100 kbit/s to 8 Mbit/s
ROI encoding Supported
Corridor Support for an aspect ratio of 9:16
format
Multi-channel Three types of streams (can encode one channel of primary
video encoding streams and two channels of secondary streams at the same
time); maximum resolution for primary streams: 1080p;
maximum resolution for secondary streams: D1

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 60


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Parameter Value
Stream Four preset stream packages and four customized stream
package packages
ISP package Four preset ISP packages and eight customized ISP packages;
support for daily and monthly ISP package plans
Bit rate type Constants Bit Rate (CBR) or Variable Bit Rate (VBR)
Dynamic bit Supported
rate
Image quality H.264: CBR controlled by streams and VBR controlled by
adjustment stream upper limit (selectable image quality); MJPEG: JPEG
quality (QP) control
IP address IP address filtering by blacklist or whitelist
filtering
Communicatio One RJ-45 10M/100M adaptive Ethernet interface and one
n interface RS-485 interface (PELCO-P/D)
Alarm interface 2-channel alarm input and 2-channel alarm output (phoenix
connector)
Analog video BNC interface (1.0 Vp–p and 75 ohms); 1-channel hybrid
output analog video output through the CVBS interface
Audio G.711a/G.711u/G.726
encoding
format
Audio interface Support for 1-channel audio input and 1-channel audio output
through 3.5 mm audio interfaces
Voice Voice intercom (sound pickup required), voice broadcast, and
communication channel-associated voice
Motion Supported
detection
Privacy mask Supported
Image Vertical, horizontal, or both
mirroring
PU access ONVIF 2.4 and HUAWEI SDK
protocol
Network TCP, UDP, IPv4, DHCP, DNS, ICMP, IGMP, HTTP, HTTPS,
protocol SFTP, RTP, RTSP, RTCP, SIP, ARP, SSL, NTP, SNMP,
802.1x, and QoS
Stream mode Unicast and multicast
Maximum 10 (allows users to obtain a maximum of two channels of
number of 1080p video streams at the same time)
concurrent
login users

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 61


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Parameter Value
Local storage Micro SD card (configured additionally) with a maximum
capacity of 32 GB and at least class 4 speed
Security mode User name and password authentication, 802.1x (MD5
Challenge), and PKI digital certificate
Media security Stream encryption using the AES128/192/256 encryption
algorithm
Data Stream smoothing parameter configuration, adaptive
transmission bandwidth, MTU configuration, and QoS configuration
optimization
Alarm linkage Alarm source: motion detection alarm/lens block
alarm/Boolean value input; linkage target: Boolean value
output
Browser 32-bit Windows XP Internet Explorer 8, 32- or 64-bit
Windows 7 Internet Explorer 8/9/10/11, 32- or 64-bit
Windows 8 Internet Explorer 10/11; 32-bit Internet Explorer
General Power supply 9 V DC to 15 V DC, 18 V DC to 30 V DC, 18 V AC to 30 V
parame AC, PoE 802.3at; power adapter and PoE in hot standby mode
ters
Power Typical power consumption: 9.5 W; maximum power
consumption consumption: 12.5 W
Operating Operating temperature: –40°C to +60°C; relative humidity:
environment 5% RH to 95% RH (noncondensing)
Protection rate IP66
Net weight 1.4 kg
Physical 120 mm x 353.6 mm x 128.1 mm (including the shield)
dimensions (H
x W x D)

3.5 Fire Extinguishing System


3.5.1 Overview
A CE or standard fire extinguishing system can be used. The CE system complies with the
EU's CE certification, and the standard system complies with China's CCC certification.
If the container catches fire, smoke and heat will trigger the smoke detectors and heat
detectors, which will send fire alarm signals to the extinguishant control panel. Upon
receiving the fire alarm signals, the extinguishant control panel counts down and then opens
the solenoid valve on the fire extinguisher so that the fire cylinder discharges extinguishant to
the protection zone. At the same time, the extinguishant control panel automatically reports
alarms.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 62


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-35 shows the conceptual diagram of the CE fire extinguishing system, and Figure
3-36 shows the conceptual diagram of the standard fire extinguishing system.

Figure 3-35 Conceptual diagram of the CE fire extinguishing system

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 63


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-36 Conceptual diagram of the standard fire extinguishing system

Figure 3-37 shows the layout of the fire extinguishing system.

Figure 3-37 Layout of fire extinguishing components

(1) Fire control pipe (2) Smoke detector (3) Heat detector
(4) Indoor horn strobe (5) Fire alarm bell (6) Fire control box
(7) High-pressure hose (8) Fire cylinder

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 64


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

3.5.2 CE Fire Extinguishing System


3.5.2.1 Extinguishant Control Panel
The extinguishant control panel provides the following functions:
 Two zones supported, a third zone configurable
 Serial status connection and timer display
 Low pressure input with the indicator
 Programmable for I.S. barriers
 Standard exhaust fan control
 Hold activated indication and disablement indication
 Test mode
 Two first stage sounder outputs
 One second-stage audible and visual alarm output
 First- and second-stage relay contacts
 Auxiliary 24 V DC output
 Monitored manual release input and output
 Monitored release pneumatic switch input
 (Optional) Mode select key switch on the front panel
 (Optional) Manual release on the front panel

Figure 3-38 Extinguishant control panel

Table 3-33 lists the technical specifications of the extinguishant control panel.

Table 3-33 Extinguishant control panel specifications

Item Specifications
Input AC input frequency: ≤ 120 W

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 65


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Item Specifications
AC input voltage and frequency: 230 V AC (tolerance ±10%), 50
Hz
DC backup power voltage: 24 V DC
24 V power output 3A
Capacit Number Three loops. Loops 1 and 2 respectively connect to smoke detectors
y of and heat detectors. Loop 3 is reserved by default.
detection
loops
Number ≤ 24 PCS
of
detectors
connecte
d to each
loop
Output loop current Output loop for the solenoid valve driver: 1 A
limiting Output loops for other drivers: 1 A

The extinguishant control panel is equipped with two 12 V batteries and the required cables.

3.5.2.2 Heptafluoropropane Fire Extinguisher


When the FusionModule1000 catches fire, a lot of smoke is generated and the temperature
rises sharply. The smoke detector and heat detector send fire alarm signals to the
extinguishant control panel, which generates an electrical actuator start voltage to start the
electrical actuator of the fire cylinder. Then the fire cylinder valve is opened, and
extinguishant is released into the protected zone.
Heptafluoropropane (HFC-227ea) is a colorless, odorless, non-conductive, and secondary
pollution-free gas extinguishant. It features cleanness, low toxicity, good electrical insulation,
high fire extinguishing efficiency, zero threat to the ozonosphere (ODP = 0), and short
residual time (ATL = 34Y).

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 66


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-39 Fire extinguisher

Table 3-34 lists the technical specifications of the Heptafluoropropane fire extinguisher.

Table 3-34 Heptafluoropropane fire extinguisher specifications

Item Specifications
Dimensions Outer diameter of the steel cylinder: 406 mm
Startup current 0.25 A
Startup voltage 24 V DC
Startup mode Electromagnetic startup
Maximum operating 50°C: 3.4 MPa
pressure
Storage pressure 20°C: 2.5 MPa
Cylinder volume 52 L

The CE-certified fire extinguishing system supports the customized copper fluoride
(NOVEC1230) extinguishant.
Copper fluoride (NOVEC1230) is a new-generation extinguishant that has been favored like
Heptafluoropropane (HFC-227ea) for recent years. Copper fluoride (NOVEC1230) has been
widely proved to be eco-friendly and safe. It can be used to extinguish fire caused by
flammable liquid, gas, and electrical equipment. Physical and chemical actions are combined
during extinguishing. Generally copper fluoride (NOVEC1230) is a colorless and odorless
liquid. It does not contain bromine or chlorine, does no harm to the ozonosphere (ODP = 0),
and resides for a short time in the atmosphere (ATL = 0.014Y).

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 67


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

3.5.3 Standard Fire Extinguishing System


3.5.3.1 Fire Alarm Control Panel
The fire alarm control panel provides the following functions:
 Detects and reports composite fire alarm signals in dual loops. It can be connected to the
emergency start/abort switch, which ensures that the system operation is under control in
case of an emergency or during onsite equipment maintenance. It restarts automatically
after a fault is rectified.
 Provides a port for the gas release confirmation signal (reporting pressure values).
 Generates single fire and double fire alarms; drives the gas release indicator, alarm fire
alarm horn/strobe, and alarm fire alarm sounder.
 Provides an independent output port for the electromagnetic valve driver and supports 3
A, 24 V electromagnetic valve (electric detonator) startup voltage.
 Detects an open circuit fault of the input loop and a short or open circuit of the output
loop (in active output mode).
 Provides intelligent monitoring as well as overcharge and overdischarge protection for
backup batteries.
 Adopts the low-power consumption design, and supports at least 48-hour consecutive
operation with the backup power.
 Provides password lock protection for the keypad to prevent misoperations.

Figure 3-40 Fire alarm control panel

Table 3-35 Fire alarm control panel specifications

Item Specifications
AC input power ≤ 120 W

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 68


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Item Specifications
AC input voltage 220 V AC±20%
DC backup Voltage 24 V DC
power
Electric energy 7.0 Ah
Capacity Number of detection Two loops: one loop connected to the common
loops heat fire detector and the other connected to
the smoke detector
Number of detectors ≤ 20 (common detectors)
connected to each loop
Wire system of the detector loop Two-wire system
Length of the detector loop ≤ 1000 m
Relay contact capacity 7 A, 24 V DC for all relays
Output loop current limiting for the ≤3A
solenoid valve
Output loop current limit for other drivers ≤1A

3.5.3.2 Heptafluoropropane Fire Extinguisher


The fire extinguisher consists of a fire cylinder, pressure announciator, electromagnetic valves,
and other components.
When the FusionModule1000 catches fire, a lot of smoke is generated and the temperature
rises sharply. The smoke detector and heat fire Detector send fire alarm signals to the fire
alarm control panel, which generates a electromagnetic valve start voltage to start the
electromagnetic valve of the fire cylinder. Then the fire cylinder valve is opened, and
extinguishant is released into the protected zone.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 69


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-41 Heptafluoropropane fire extinguisher

Table 3-36 Heptafluoropropane fire extinguisher specifications

Item Specifications
Dimensions Outer diameter of the steel cylinder: 364
mm
Maximum operating pressure 50°C: 3.4 MPa
Storage pressure 20°C: 2.5 MPa
Cylinder volume 70 L
Heptafluoropropane filling density ≤ 1120 kg/m3
Startup current 1.2 A
Startup voltage 24 V DC

3.5.4 VESDA (Optional)


Composition
The VESDA consists of a VLF-250 detection unit and meshed air sampling pipes.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 70


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-42 VESDA

(1) VESDA detection unit (2) Sampling pipes (3) Air sampling pipe plugs

Working Principle
The detection unit includes the suction pump, filter, high-sensitive smoke detector, and
precision electrical analyzer. The air detector of the VESDA can detect fire in the initial phase
and generates alarms at an early time.
The detection unit of the VESDA sucks air samples from the monitored environment through
the air sampling tube to the smoke detector and works out the dust density in the air. If the
dust density exceeds the preset alarm threshold, the VESDA blinks and sends an alarm signal
to the monitoring module.

Features
 High sensitivity
The VESDA features extremely high sensitivity and wide sensitivity adjustment range
(0.005%–20% obs/m). It can detect both potential fire in the early phase and particles
released by the softened insulation layer of an overloaded power cable.
 Precise detection result
The VESDA works in active air sampling mode. The efficient aspirator continuously
sends air samples from the protected area to the detection chamber for analysis. The
detection result and response time are less influenced by air flow compared with a
traditional fire detection method.
 Flexible installation
The VESDA detection unit is compact and easy to install. The air sampling pipes can be
deployed depending on site requirements. The air sampling pipes are made of PVC and
can be installed on or under the ceiling, under the floor, at air return vents of air
conditioners, and in locations that need special protection. For example, the sampling
capillaries can be installed in a cabinet to monitor equipment in the cabinet.
 Easy maintenance
The VESDA is equipped with a special filter that filters air for cleaning the laser
measuring chamber, ensuring that the laser detector has a long lifespan. The filter can be
easily maintained and replaced, and cleaned by blowing air into the air sampling pipes.
Therefore, you do not have to replace any other components.
 Efficient auto-diagnosis system

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 71


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

The VESDA is designed with an efficient auto-diagnosis system for monitoring the
working status of itself, the network, and the air sampling pipes in real time. If a fault is
detected, the system generates an alarm and indicates the fault location for
troubleshooting.

3.6 Surge Protection and Grounding


3.6.1 Surge Protection
Power Ports
 First-level surge protection: A class I SPD with the capacity Imax of at least 100 kA (8/20
µs) should be deployed at the AC power inlet for the container.
 Second-level surge protection: An SPD with the recommended capacity Imax of 60 kA
(8/20 μs) should be deployed at the PDB.
 Third-level surge protection: An SPD with the recommended capacity Iin of 20 kA (8/20
μs) should be deployed at the power input port of the downstream equipment such as the
air conditioner or UPS.

Signal Ports
 Indoor signal ports are protected to 1 kV for common mode.
 Signal ports for routing cables out of the container pass the 3 kA impulse current test.

3.6.2 Grounding
Internal Grounding
The main earthing terminal (MET) is installed in the container and connects to the external
ground grid over ground downleads.
Devices in the container connect to the ground busbar over ground cables and are insulated
from other metal parts.

External Grounding
M12 bolt ground points are evenly located on the container exterior. Ensure that the two
diagonal ground points are connected to the ground grid. The FusionModule1000 provides
two external ground points, as shown in Figure 3-43. The ground resistance is within 10
ohms.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 72


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-43 Ground point of the container (unit: mm)

3.7 Integrated Cabling


Integrated cabling of the FusionModule1000 involves cable trays and various cables. Cable
trays on the tops of containers are separate from cabinets, and can be moved horizontally
along the width direction on the tops of containers. Strong- and weak-current cables are
routed separately.
Cables of the FusionModule1000 include power cables, monitoring cables, fire extinguishing
cables, signal cables, and ground cables.

Figure 3-44 Cable routes

(1) L2 signal cables (2) L1 power cables


(3) Mains inlet port (4) Cables for air conditioner indoor and outdoor units

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 73


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 3 System Architecture

Figure 3-45 Cable routes on cable trays

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 74


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 4 Key Technical Specifications

4 Key Technical Specifications

Table 4-1 lists the key technical specifications of the FusionModule1000.

Table 4-1 Key technical specifications

Item Specifications
Power supply Power input Two 250 A inputs, three-phase four-wire + PE,
and 380 V AC/400 V AC/415 V AC 50 Hz/60 Hz
distribution
Surge protection Class I, 100 kA (8/20 µs), 20 kA (10/350 µs)
level
Load power Total power ≤ 40 kW; single cabinet power ≤ 8
kW
Battery backup time 60 min
Cooling Cooling capacity 25 kW for each air conditioner, 3+1 mode
Refrigerant R410A
Fire Type Fire extinguishing system with the automatic fire
extinguishing detection and emergency gas release functions
Alarm Audible and visual alarming with automatic
monitoring and detection
Monitoring The analog addressable system releases the
gaseous extinguishant if fire alarms are generated
from dual detector loops.
Extinguishing agent Heptafluoropropane. Copper fluoride
(NOVEC1230) can be used in the CE version if
required.
Monitoring IP camera Dual-resolution IP cameras installed in the
container.
Management Monitors the temperature and humidity control
functions system, fire detection and control system, access
control system, and cooling system inside the
FusionModule1000 in real time

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 75


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 4 Key Technical Specifications

Item Specifications
O&M using the mobile APP, remote unattended
control
(Optional) The NetEco supports monitoring over
emails and Simple Network Management Protocol
(SNMP) short messages.
All backup power supplies are connected over
programmable dry contacts or fast Ethernet (FE)
ports. The AC/DC power system adopts the FE
port, and the DG supports the RS485 port and dry
contacts.
Structure Container 40 ft standard ISO shipping container (40 ft x 8 ft
x 9.5 ft)
Container heat The thermal transmission coefficient of the
insulation container is 0.4 W/(m2 x K) or less.
performance
Integrated cabling Power cables and signal cables are routed
separately.
Protection level IP55/IP65 (optional)
Installation mode Directly installed on the ground
NOTE
The container can be installed on a concrete platform,
with four 300 mm high steel bases connected to the
concrete platform using M16 bolts.

Dimensions (H x W 2896 mm x 2438 mm x 12,192 mm


x D)
Overall weight Empty container (excluding CT equipment):
16,000 kg; fully-loaded container: < 25,000 kg
Typical cabinet Eight cabinets; dimensions (H x W x D) of each
capacity CT cabinet (user-supplied): 2200 mm x 600 mm x
800 mm
Bullet-proof Performance The container bullet-proof function passed the 10
(optional) m rifle test.
Operating Cold aisle 18–27°C
specifications temperature
Humidity 20%–80% RH
Environmental Ambient –40°C to +55°C
requirements temperature
Storage temperature –40°C to +70°C
Ambient humidity 5%–95% RH

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 76


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview 4 Key Technical Specifications

Item Specifications
Altitude 0–4000 m
 The cooling capacity of the air conditioner is
derated when the altitude is from 1000 m to
4000 m. For the derating details, contact
Huawei technical support.
 The PDB is derated when the altitude is from
2000 m to 4000 m. For the derating details,
contact Huawei technical support.

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 77


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview A Acronyms and Abbreviations

A Acronyms and Abbreviations

A
ATS automatic transfer switch

C
CE Conformite Europende

M
MCB miniature circuit breaker
MCCB molded case circuit breaker

N
NetEco network ecosystem

T
TCP/IP Transmission Control Protocol/Internet Protocol

P
PUE power usage effectiveness

S
SNMP Simple Network Management Protocol

U
UPS uninterruptible power system

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 78


Copyright © Huawei Technologies Co., Ltd.
FusionModule1000A40 CT Solution
Product Overview A Acronyms and Abbreviations

V
VCN video cloud node

Issue Draft B (2017-01-10) Huawei Proprietary and Confidential 79


Copyright © Huawei Technologies Co., Ltd.