COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-1

1C1 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 54.9 -0.3 0.9 49.8 0.7 -1.8
2 60.1 -0.5 0.9 55.0 1.0 -1.9
3 44.0 -0.3 0.6 38.9 0.6 -1.2
4 45.8 -0.1 0.9 40.7 0.2 -1.9
5 55.7 -0.3 0.8 50.6 0.6 -1.7
6 54.2 -0.2 0.9 49.1 0.5 -1.8
7 55.0 -0.3 0.9 49.9 0.7 -1.8
8 46.5 -0.2 0.9 41.4 0.3 -1.9
9 55.7 -0.3 0.8 50.6 0.7 -1.8
10 60.1 -0.5 0.9 55.0 1.0 -1.9
11 43.9 -0.3 0.6 38.8 0.6 -1.1
12 44.7 2.0 0.7 40.4 -1.6 -1.5
13 48.9 -2.6 0.8 44.5 2.8 -1.6
14 48.4 -0.5 2.8 44.1 0.8 -3.5
15 45.2 -0.1 -1.3 40.8 0.4 0.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 54.9 - 54.9
M1 (kN.m) 0.7 0.6 0.0
M2 (kN.m) -1.8 -0.6 -2.5 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.043 Le1/b1 = 8.6 < 15.0 225
Beta = 0.95 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.8 / 2.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.82 / 0.82 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.04 / 0.05 N/mm2
Links = Y8-175

2C1 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 10.7 -0.3 1.6 5.0 0.4 -1.0
2 10.5 -0.6 1.5 4.9 0.3 -1.0
3 9.8 -0.4 1.0 4.2 0.4 -0.7
4 9.9 0.2 1.7 4.3 0.1 -1.1
5 10.6 -0.4 1.5 5.0 0.5 -0.9
6 10.8 -0.3 1.6 5.2 0.4 -1.0
7 10.7 -0.4 1.6 5.1 0.4 -1.0
8 9.8 0.2 1.6 4.2 0.0 -1.0
9 10.6 -0.5 1.5 5.0 0.5 -0.9
10 10.5 -0.6 1.5 4.9 0.3 -1.0
11 9.8 -0.3 1.0 4.1 0.4 -0.7
12 8.9 0.0 1.3 4.1 0.0 -0.9
13 9.3 -0.6 1.3 4.5 0.6 -0.9
14 9.3 -0.3 1.5 4.5 0.3 -1.1
15 8.9 -0.3 1.1 4.1 0.3 -0.6
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 10.7 - 10.7
M1 (kN.m) 0.4 0.1 0.0
M2 (kN.m) 1.6 0.1 2.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.008 Le1/b1 = 9.6 < 15.0 225
Beta = 0.99 Le2/b2 = 9.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.4 / 0.8 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.02 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-2

1C2 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 154.4 -1.5 1.1 149.3 3.0 -2.2
2 124.8 -0.6 1.2 119.7 1.3 -2.5
3 139.5 -1.5 0.5 134.4 3.0 -1.0
4 147.6 -1.8 1.1 142.5 3.6 -2.2
5 155.6 -1.4 1.0 150.5 3.0 -2.1
6 157.3 -1.5 1.0 152.2 3.2 -2.1
7 154.2 -1.5 1.1 149.1 3.0 -2.2
8 144.8 -1.7 1.1 139.7 3.4 -2.3
9 155.7 -1.5 1.0 150.6 3.0 -2.1
10 124.8 -0.6 1.2 119.7 1.3 -2.5
11 139.5 -1.4 0.5 134.4 2.9 -0.9
12 132.4 1.1 0.8 128.0 0.2 -1.8
13 129.4 -3.6 0.9 125.0 4.8 -1.9
14 132.1 -1.5 3.0 127.7 2.7 -3.8
15 129.7 -1.0 -1.2 125.3 2.3 0.1
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 154.4 - 154.4
M1 (kN.m) 3.0 1.7 4.8
M2 (kN.m) -2.2 -1.7 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.122 Le1/b1 = 8.6 < 15.0 225
Beta = 0.86 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.3 / 0.4 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.84 / 0.87 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.01 N/mm2
Links = Y8-175

2C2 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 14.5 -2.6 1.1 8.9 1.7 0.0
2 13.3 -1.0 1.3 7.7 0.8 0.0
3 14.5 -2.6 0.4 8.9 1.8 0.0
4 13.7 -3.0 1.2 8.1 1.9 0.0
5 14.3 -2.7 1.2 8.7 1.8 0.0
6 14.4 -2.8 1.1 8.8 1.8 0.0
7 14.3 -2.6 1.1 8.7 1.7 0.0
8 13.9 -2.8 1.2 8.3 1.8 0.0
9 14.5 -2.7 1.2 8.9 1.9 0.0
10 13.3 -1.0 1.3 7.7 0.8 0.0
11 14.5 -2.6 0.4 8.9 1.7 0.0
12 12.6 -1.8 1.0 7.8 1.0 0.0
13 12.3 -2.6 0.9 7.5 1.9 0.0
14 12.5 -2.2 1.1 7.7 1.5 0.0
15 12.5 -2.2 0.7 7.7 1.4 0.0
Critical Combination:4 - ((G+Q)P21 *F)
Min Design
N (kN) 13.7 - 13.7
M1 (kN.m) -3.0 -0.2 -4.2
M2 (kN.m) 1.2 0.2 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.011 Le1/b1 = 9.5 < 15.0 225
Beta = 0.99 Le2/b2 = 10.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.5 / 0.4 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.04 / 0.01 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-3

1C3 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 108.9 -0.2 -0.1 103.8 0.5 0.1
2 109.4 -0.2 0.0 104.3 0.5 0.0
3 92.7 -0.2 0.3 87.6 0.5 -0.5
4 99.7 -0.2 -0.2 94.6 0.5 0.4
5 91.9 -0.2 -0.4 86.8 0.4 0.7
6 108.8 -0.2 -0.1 103.7 0.4 0.1
7 108.9 -0.2 -0.1 103.8 0.5 0.1
8 99.7 -0.3 -0.2 94.6 0.5 0.4
9 91.9 -0.2 -0.4 86.8 0.4 0.7
10 109.4 -0.2 0.0 104.3 0.5 0.0
11 92.7 -0.2 0.2 87.6 0.5 -0.4
12 92.3 1.4 -0.1 87.9 -0.4 0.1
13 92.7 -1.8 0.0 88.4 1.2 0.0
14 92.8 -0.3 2.1 88.5 0.5 -2.0
15 92.2 -0.1 -2.2 87.8 0.4 2.2
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 108.9 - 108.9
M1 (kN.m) 0.5 1.2 0.0
M2 (kN.m) 0.1 1.2 2.3 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.086 Le1/b1 = 10.3 < 15.0 225
Beta = 0.90 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.6 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.84 / 0.79 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.00 N/mm2
Links = Y8-175

2C3 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 9.8 0.4 -0.6 4.2 0.0 0.6
2 10.0 0.4 -0.5 4.3 0.0 0.6
3 9.3 0.4 0.1 3.6 0.0 0.2
4 9.8 0.4 -0.8 4.2 0.0 0.7
5 9.4 0.4 -1.0 3.8 0.0 0.9
6 9.8 0.4 -0.5 4.2 0.0 0.6
7 9.8 0.4 -0.6 4.2 0.0 0.6
8 9.8 0.5 -0.8 4.2 0.0 0.7
9 9.4 0.4 -1.0 3.8 0.0 0.9
10 10.0 0.4 -0.5 4.3 0.0 0.6
11 9.3 0.4 0.1 3.6 0.0 0.2
12 8.4 -0.4 -0.5 3.6 0.0 0.5
13 8.5 1.1 -0.5 3.7 0.0 0.5
14 8.5 0.4 -0.1 3.7 0.0 0.2
15 8.4 0.3 -0.9 3.6 0.0 0.9
Critical Combination:1 - (G+Q *F)
MinDesign
N (kN) 9.8 - 9.8
M1 (kN.m) 0.4 0.1 0.0
M2 (kN.m) 0.6 0.1 1.0 225
N-max (kN) 0.0
Concrete Cover 25.0
= mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.008 Le1/b1 = 10.8 < 15.0 225
Beta = 0.99 Le2/b2 = 9.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.3 / 0.6 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.01 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-4

1C4 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 158.6 0.0 -0.1 153.5 0.0 0.3
2 156.7 0.0 -0.1 151.6 0.0 0.2
3 129.5 0.0 0.4 124.4 0.0 -0.8
4 149.5 0.0 -0.3 144.4 0.0 0.6
5 133.2 0.0 -0.6 128.1 0.0 1.1
6 158.7 0.1 -0.1 153.6 0.0 0.3
7 158.6 0.0 -0.1 153.5 0.0 0.2
8 149.4 0.0 -0.3 144.3 0.0 0.5
9 133.2 0.0 -0.6 128.1 0.0 1.0
10 156.7 0.0 -0.1 151.6 0.0 0.2
11 129.5 0.1 0.3 124.4 0.0 -0.7
12 133.8 1.1 -0.1 129.5 0.2 0.2
13 133.7 -1.1 -0.1 129.3 -0.3 0.2
14 134.0 -0.1 2.1 129.6 0.0 -2.0
15 133.5 0.1 -2.3 129.1 0.0 2.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 158.6 - 158.6
M1 (kN.m) 0.0 1.8 0.0
M2 (kN.m) 0.3 1.8 3.3 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.125 Le1/b1 = 10.3 < 15.0 225
Beta = 0.85 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.3 / 0.3 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.83 / 0.90 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.01 N/mm2
Links = Y8-175

2C4 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 5.6 0.0 0.0 0.0 0.0 0.0
2 5.6 0.0 0.0 0.0 0.0 0.0
3 5.6 0.0 0.0 0.0 0.0 0.0
4 5.6 0.0 0.0 0.0 0.0 0.0
5 5.6 0.0 0.0 0.0 0.0 0.0
6 5.6 0.0 0.0 0.0 0.0 0.0
7 5.6 0.0 0.0 0.0 0.0 0.0
8 5.6 0.0 0.0 0.0 0.0 0.0
9 5.6 0.0 0.0 0.0 0.0 0.0
10 5.6 0.0 0.0 0.0 0.0 0.0
11 5.6 0.0 0.0 0.0 0.0 0.0
12 4.8 0.3 0.0 0.0 0.0 0.0
13 4.8 -0.3 0.0 0.0 0.0 0.0
14 4.8 0.0 0.3 0.0 0.0 0.0
15 4.8 0.0 -0.3 0.0 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 5.6 - 5.6
M1 (kN.m) 0.0 -0.1 0.0
M2 (kN.m) 0.0 -0.1 -0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.004 Le1/b1 = 10.8 < 15.0 225
Beta = 0.99 Le2/b2 = 10.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 0.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.76 / 0.76 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-5

1C5 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 44.6 0.0 -0.9 39.5 0.1 1.7
2 50.7 -0.3 -0.8 45.6 0.6 1.6
3 46.0 0.0 -0.8 40.9 0.1 1.6
4 33.5 0.2 -0.8 28.4 -0.3 1.5
5 34.6 0.0 -0.7 29.5 0.1 1.2
6 44.8 0.0 -0.9 39.7 0.0 1.7
7 44.8 0.0 -0.8 39.7 0.1 1.7
8 33.2 0.1 -0.8 28.1 -0.2 1.5
9 34.5 0.0 -0.7 29.4 0.1 1.2
10 50.7 -0.3 -0.8 45.6 0.6 1.6
11 45.9 0.0 -0.8 40.8 0.1 1.7
12 36.3 2.3 -0.8 31.9 -2.1 1.5
13 40.1 -2.4 -0.7 35.7 2.3 1.4
14 36.5 -0.1 1.3 32.1 0.2 -0.5
15 39.9 0.1 -2.8 35.5 0.0 3.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 44.6 - 44.6
M1 (kN.m) 0.1 0.5 0.0
M2 (kN.m) 1.7 0.5 2.2 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.035 Le1/b1 = 8.6 < 15.0 225
Beta = 0.96 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 2.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.76 / 0.81 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.05 N/mm2
Links = Y8-175

2C5 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 9.9 1.6 -2.1 4.3 -1.0 1.6
2 9.8 1.3 -2.1 4.2 -1.0 1.5
3 9.7 1.5 -2.0 4.1 -0.9 1.4
4 9.2 1.9 -1.9 3.6 -1.1 1.5
5 9.2 1.4 -1.6 3.6 -0.8 1.3
6 10.0 1.4 -2.1 4.4 -0.8 1.5
7 9.9 1.6 -2.1 4.3 -1.0 1.6
8 9.1 2.1 -1.9 3.5 -1.3 1.5
9 9.2 1.4 -1.6 3.6 -0.8 1.3
10 9.8 1.3 -2.1 4.2 -1.0 1.5
11 9.7 1.5 -2.0 4.1 -0.9 1.4
12 8.2 1.7 -1.8 3.4 -1.3 1.4
13 8.7 1.0 -1.8 3.9 -0.5 1.3
14 8.2 1.4 -1.6 3.4 -0.9 1.1
15 8.6 1.4 -2.0 3.8 -0.9 1.6
Critical Combination:8 - ((G+Q)P41 *F)
MinDesign
N (kN) 9.1 - 9.1
M1 (kN.m) 2.1 0.1 4.0
M2 (kN.m) -1.9 -0.1 0.0 225
N-max (kN) 0.0
Concrete Cover 25.0
= mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.007 Le1/b1 = 9.6 < 15.0 225
Beta = 0.99 Le2/b2 = 9.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.0 / 1.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.03 / 0.03 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-6

1C6 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 171.3 -2.5 -0.6 166.2 5.1 1.2
2 138.8 -1.6 -0.7 133.7 3.2 1.4
3 173.3 -2.4 -0.5 168.2 5.0 1.1
4 158.1 -2.6 -0.5 153.0 5.4 1.0
5 157.6 -2.4 -0.3 152.5 5.0 0.4
6 171.2 -2.4 -0.6 166.1 5.0 1.2
7 171.0 -2.5 -0.6 165.9 5.1 1.2
8 158.2 -2.7 -0.5 153.1 5.5 1.0
9 157.7 -2.4 -0.3 152.6 5.0 0.4
10 138.8 -1.6 -0.7 133.7 3.2 1.4
11 173.5 -2.4 -0.6 168.4 5.0 1.2
12 146.4 0.3 -0.5 142.0 1.9 1.0
13 144.5 -4.5 -0.5 140.1 6.7 1.0
14 143.8 -2.2 1.6 139.4 4.4 -1.0
15 147.1 -2.0 -2.6 142.7 4.2 3.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 171.3 - 171.3
M1 (kN.m) 5.1 1.9 6.7
M2 (kN.m) 1.2 1.9 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.135 Le1/b1 = 8.6 < 15.0 225
Beta = 0.84 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.5 / 0.7 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.85 / 0.90 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.02 N/mm2
Links = Y8-175

2C6 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 13.9 -2.8 -1.2 8.3 1.0 0.0
2 12.6 -0.9 -1.3 7.0 -0.1 0.0
3 13.8 -2.8 -1.1 8.2 1.0 0.0
4 13.2 -3.2 -1.0 7.6 1.4 0.0
5 13.8 -3.0 -0.6 8.2 1.2 0.0
6 13.8 -3.0 -1.2 8.2 1.3 0.0
7 13.8 -2.8 -1.2 8.2 1.0 0.0
8 13.2 -3.0 -1.0 7.6 1.1 0.0
9 13.8 -3.0 -0.6 8.2 1.2 0.0
10 12.6 -0.9 -1.3 7.0 -0.1 0.0
11 13.9 -2.9 -1.1 8.2 1.1 0.0
12 12.0 -1.8 -1.0 7.2 0.3 0.0
13 11.9 -2.9 -1.0 7.1 1.4 0.0
14 11.9 -2.4 -0.8 7.1 0.9 0.0
15 11.9 -2.3 -1.2 7.1 0.8 0.0
Critical Combination:4 - ((G+Q)P21 *F)
Min Design
N (kN) 13.2 - 13.2
M1 (kN.m) -3.2 -0.1 -4.2
M2 (kN.m) -1.0 -0.1 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.010 Le1/b1 = 9.5 < 15.0 225
Beta = 0.99 Le2/b2 = 10.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.4 / 0.4 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.03 / 0.01 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-7

1C7 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 194.0 0.3 1.2 188.9 -0.7 -2.4
2 167.7 -0.7 1.3 162.6 1.3 -2.6
3 179.5 0.3 0.7 174.4 -0.6 -1.3
4 170.3 1.1 1.1 165.2 -2.3 -2.3
5 194.0 0.4 1.1 188.9 -0.8 -2.3
6 170.9 1.2 1.2 165.8 -2.4 -2.5
7 193.1 0.3 1.2 188.0 -0.7 -2.4
8 193.5 0.3 1.1 188.4 -0.6 -2.2
9 195.1 0.4 1.1 190.0 -0.7 -2.3
10 167.7 -0.7 1.3 162.6 1.3 -2.6
11 179.4 0.4 0.6 174.3 -0.7 -1.2
12 163.8 2.6 1.0 159.5 -2.9 -2.0
13 165.1 -2.1 1.0 160.7 1.7 -2.0
14 166.0 0.1 3.2 161.6 -0.3 -4.0
15 162.9 0.5 -1.2 158.5 -0.8 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 194.0 - 194.0
M1 (kN.m) -0.7 -2.2 0.0
M2 (kN.m) -2.4 -2.2 -4.2 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.153 Le1/b1 = 8.6 < 15.0 225
Beta = 0.82 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 0.4 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.90 / 0.88 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.01 N/mm2
Links = Y8-175

2C7 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 21.5 1.7 1.2 15.9 -1.9 -0.1
2 19.9 -0.2 1.4 14.3 -0.9 -0.1
3 21.4 1.6 0.5 15.8 -1.8 -0.1
4 20.1 3.4 1.2 14.5 -2.8 -0.1
5 20.6 1.6 1.2 15.0 -1.8 -0.1
6 20.4 3.2 1.3 14.8 -2.7 -0.1
7 20.5 1.7 1.2 14.9 -1.8 -0.1
8 21.2 1.9 1.1 15.6 -2.0 -0.1
9 21.6 1.6 1.3 16.0 -1.9 -0.1
10 19.9 -0.2 1.4 14.3 -0.9 -0.1
11 21.4 1.7 0.5 15.8 -1.8 -0.1
12 18.4 1.8 1.0 13.6 -2.1 -0.1
13 18.5 1.1 1.0 13.7 -1.2 -0.1
14 18.5 1.4 1.4 13.7 -1.6 -0.1
15 18.4 1.5 0.6 13.6 -1.7 -0.1
Critical Combination:4 - ((G+Q)P21 *F)
Min Design
N (kN) 20.1 - 20.1
M1 (kN.m) 3.4 0.2 4.6
M2 (kN.m) 1.2 0.2 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.016 Le1/b1 = 9.6 < 15.0 225
Beta = 0.98 Le2/b2 = 10.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.9 / 0.5 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.78 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.04 / 0.01 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-8

1C8 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 186.8 -5.0 -0.4 181.7 10.2 0.9
2 184.5 -5.1 -0.5 179.4 10.3 1.0
3 161.2 -5.1 0.1 156.1 10.4 0.0
4 162.4 -2.8 -0.4 157.3 5.7 0.8
5 168.5 -5.0 -0.8 163.4 10.2 1.6
6 186.2 -5.0 -0.4 181.1 10.2 0.9
7 187.5 -5.1 -0.4 182.4 10.2 0.9
8 163.0 -2.9 -0.4 157.9 5.8 0.9
9 168.4 -5.0 -0.8 163.3 10.2 1.5
10 184.5 -5.1 -0.5 179.4 10.3 1.0
11 160.5 -5.0 0.0 155.4 10.3 0.1
12 156.5 -1.9 -0.4 152.2 6.4 0.8
13 158.0 -6.5 -0.4 153.6 10.7 0.8
14 156.8 -4.4 1.9 152.4 8.7 -1.5
15 157.8 -4.1 -2.7 153.4 8.4 3.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 186.8 - 186.8
M1 (kN.m) 10.2 2.1 11.9
M2 (kN.m) 0.9 2.1 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.148 Le1/b1 = 8.6 < 15.0 225
Beta = 0.83 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 5.7 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.94 / 0.89 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.14 / 0.00 N/mm2
Links = Y8-175

1C9 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 160.1 6.0 -0.3 155.0 -12.0 0.6
2 142.8 4.1 -0.3 137.7 -8.3 0.6
3 146.0 6.0 -0.4 140.9 -12.0 0.9
4 157.1 5.9 -0.3 152.0 -11.9 0.6
5 140.6 5.9 -0.2 135.5 -11.9 0.3
6 160.4 6.0 -0.3 155.3 -12.1 0.7
7 144.7 6.0 -0.4 139.6 -12.0 0.9
8 156.9 5.9 -0.3 151.8 -11.9 0.5
9 139.4 5.9 -0.2 134.3 -11.9 0.2
10 142.8 4.1 -0.3 137.7 -8.3 0.6
11 162.5 5.9 -0.3 157.4 -11.9 0.7
12 136.0 7.3 -0.3 131.7 -12.3 0.6
13 134.7 2.8 -0.2 130.4 -8.1 0.5
14 135.6 4.9 2.0 131.2 -10.1 -1.7
15 135.2 5.2 -2.5 130.8 -10.3 2.8
Critical Combination:12 - (G+Q+Nx)
Min Design
N (kN) 136.0 - 136.0
M1 (kN.m) -12.3 -1.5 -13.6
M2 (kN.m) 0.6 1.5 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.107 Le1/b1 = 8.6 < 15.0 225
Beta = 0.87 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 6.5 / 0.3 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.91 / 0.90 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.16 / 0.01 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-9

1C10 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 92.6 2.4 1.4 87.4 -4.9 -2.8
2 95.0 2.7 1.4 89.9 -5.5 -2.7
3 92.8 2.4 1.5 87.7 -4.9 -2.9
4 73.8 1.2 1.3 68.7 -2.5 -2.6
5 80.9 2.5 0.9 75.8 -5.0 -1.9
6 74.4 1.4 1.5 69.3 -2.7 -2.9
7 92.5 2.4 1.5 87.4 -4.9 -2.9
8 92.0 2.3 1.3 86.9 -4.8 -2.5
9 81.1 2.5 1.0 76.0 -5.0 -2.0
10 95.0 2.7 1.4 89.9 -5.5 -2.7
11 92.6 2.5 1.4 87.5 -4.9 -2.8
12 79.8 4.3 1.2 75.4 -6.3 -2.4
13 77.6 -0.2 1.2 73.2 -2.1 -2.4
14 81.0 1.9 3.5 76.6 -4.0 -4.5
15 76.4 2.3 -1.1 72.0 -4.4 -0.2
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 92.6 - 92.6
M1 (kN.m) -4.9 -1.0 -7.5
M2 (kN.m) -2.8 -1.0 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.073 Le1/b1 = 8.7 < 15.0 225
Beta = 0.91 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 3.5 / 2.7 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.85 / 0.86 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.09 / 0.06 N/mm2
Links = Y8-175

2C10 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 12.7 5.1 2.1 7.1 -3.0 -1.0
2 12.7 5.6 2.0 7.1 -3.0 -1.0
3 12.8 5.0 2.3 7.2 -2.9 -1.2
4 11.4 3.1 2.0 5.7 -2.0 -0.9
5 11.9 5.1 1.2 6.3 -3.0 -0.6
6 11.4 3.0 2.2 5.8 -1.9 -1.1
7 12.7 5.2 2.0 7.1 -3.0 -1.0
8 12.6 5.3 1.9 7.0 -3.1 -0.8
9 11.9 5.1 1.4 6.3 -2.9 -0.7
10 12.7 5.6 2.0 7.1 -3.0 -1.0
11 12.7 5.1 2.1 7.1 -2.9 -1.1
12 11.0 4.6 1.7 6.2 -2.8 -0.9
13 10.8 4.2 1.8 6.0 -2.2 -0.9
14 11.3 4.4 2.2 6.5 -2.5 -1.4
15 10.5 4.4 1.3 5.7 -2.5 -0.4
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 12.7 - 12.7
M1 (kN.m) 5.6 0.1 7.6
M2 (kN.m) 2.0 0.1 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.010 Le1/b1 = 9.9 < 15.0 225
Beta = 0.99 Le2/b2 = 9.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.6 / 1.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.06 / 0.03 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-10

1C11 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 183.4 2.4 -0.8 178.3 -4.8 1.6
2 172.0 2.4 -0.8 166.9 -5.0 1.7
3 181.0 2.4 -0.7 175.9 -4.9 1.5
4 133.5 1.1 -0.8 128.4 -2.3 1.8
5 176.1 2.4 -0.5 171.0 -4.8 1.0
6 187.6 2.5 -0.7 182.5 -4.9 1.5
7 181.6 2.4 -0.7 176.5 -4.9 1.6
8 129.2 1.1 -0.9 124.1 -2.2 1.9
9 175.6 2.4 -0.5 170.4 -4.8 0.9
10 172.0 2.4 -0.8 166.9 -5.0 1.7
11 183.3 2.4 -0.8 178.2 -4.8 1.6
12 153.4 4.4 -0.7 149.0 -6.3 1.4
13 155.2 -0.4 -0.7 150.9 -1.6 1.4
14 152.3 1.8 1.6 147.9 -3.8 -0.8
15 156.3 2.2 -2.9 151.9 -4.2 3.5
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 183.4 - 183.4
M1 (kN.m) -4.8 -2.1 -6.5
M2 (kN.m) 1.6 2.1 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.145 Le1/b1 = 8.6 < 15.0 225
Beta = 0.83 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.4 / 0.9 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.84 / 0.89 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.02 N/mm2
Links = Y8-175

2C11 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 -16.2 8.7 -2.1 -21.8 -9.2 1.2
2 -17.0 8.9 -2.1 -22.6 -9.2 1.2
3 -16.6 8.8 -1.9 -22.3 -9.3 1.0
4 -15.0 6.3 -2.2 -20.6 -7.6 1.3
5 -12.8 8.2 -1.5 -18.4 -8.5 0.9
6 -14.1 8.4 -2.0 -19.7 -8.9 1.1
7 -16.6 8.9 -2.2 -22.2 -9.3 1.2
8 -17.2 6.6 -2.3 -22.8 -8.0 1.4
9 -13.2 8.3 -1.3 -18.8 -8.6 0.8
10 -17.0 8.9 -2.1 -22.6 -9.2 1.2
11 -15.8 8.6 -2.0 -21.5 -9.1 1.1
12 -14.3 7.9 -1.8 -19.1 -8.4 1.0
13 -13.4 6.9 -1.8 -18.2 -7.4 1.0
14 -14.1 7.3 -1.3 -18.9 -7.8 0.5
15 -13.6 7.5 -2.2 -18.4 -7.9 1.5
Critical Combination:7 - ((G+Q)P32 *F)
Min Design
N (kN) -22.2 - -22.2
M1 (kN.m) -9.3 0.2 -11.5
M2 (kN.m) -2.2 0.2 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.018 Le1/b1 = 9.5 < 15.0 225
Beta = 1.00 Le2/b2 = 9.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 5.5 / 1.1 kN As (Required): %0.86 433.96 mm2 4Y16
vc'(1/2)= 0.73 / 0.72 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.13 / 0.03 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-11

1C12 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 170.7 -0.9 3.6 165.6 1.8 -7.2
2 163.0 -1.0 3.6 157.9 2.0 -7.3
3 147.3 -0.8 2.2 142.2 1.7 -4.2
4 158.7 -0.5 3.6 153.6 0.9 -7.2
5 165.5 -0.9 3.6 160.3 1.8 -7.3
6 149.1 -0.4 3.7 144.0 1.0 -7.4
7 147.2 -0.8 2.2 142.1 1.7 -4.2
8 180.5 -0.9 3.6 175.4 1.7 -7.1
9 165.0 -0.9 3.5 159.9 1.8 -7.1
10 163.0 -1.0 3.6 157.9 2.0 -7.3
11 171.2 -0.8 3.7 166.1 1.7 -7.4
12 146.0 1.7 3.0 141.6 -0.8 -6.1
13 144.7 -3.1 3.0 140.3 3.9 -6.1
14 146.3 -0.9 5.3 141.9 1.7 -8.1
15 144.4 -0.6 0.8 140.0 1.3 -4.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 170.7 - 170.7
M1 (kN.m) 1.8 1.9 0.0
M2 (kN.m) -7.2 -1.9 -8.9 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.135 Le1/b1 = 8.6 < 15.0 225
Beta = 0.84 Le2/b2 = 8.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.3 / 4.5 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.94 / 0.93 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.06 / 0.11 N/mm2
Links = Y8-175

2C12 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 66.5 -8.2 6.3 60.9 15.8 -2.9
2 66.0 -8.4 6.3 60.4 16.0 -2.9
3 65.5 -8.1 3.8 59.9 15.7 -2.0
4 61.0 -6.8 6.2 55.3 14.3 -3.0
5 60.4 -7.5 6.1 54.8 14.2 -2.7
6 61.9 -7.1 6.4 56.3 14.4 -3.1
7 65.3 -8.0 3.4 59.7 15.6 -1.6
8 65.7 -7.8 6.1 60.1 15.7 -2.8
9 61.1 -7.6 6.3 55.4 14.4 -3.1
10 66.0 -8.4 6.3 60.4 16.0 -2.9
11 66.0 -8.1 6.4 60.4 15.7 -3.0
12 57.4 -6.5 5.2 52.6 13.1 -2.5
13 56.5 -7.5 5.3 51.7 14.0 -2.5
14 57.0 -7.1 5.7 52.2 13.7 -3.0
15 56.8 -6.9 4.8 52.0 13.5 -2.0
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 66.0 - 66.0
M1 (kN.m) 16.0 0.7 21.9
M2 (kN.m) 6.3 0.7 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.052 Le1/b1 = 9.5 < 15.0 225
Beta = 0.94 Le2/b2 = 9.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 7.4 / 2.8 kN As (Required): %1.18 594.88 mm2 4Y16
vc'(1/2)= 0.82 / 0.82 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.18 / 0.07 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-12

1C13 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 83.1 1.9 3.0 78.0 -3.9 -6.0
2 83.4 1.9 3.0 78.3 -3.9 -6.0
3 67.2 1.9 2.1 62.1 -3.8 -3.9
4 71.1 1.3 3.0 65.9 -2.6 -6.0
5 83.8 2.0 3.0 78.7 -3.9 -6.1
6 71.5 1.4 3.1 66.4 -2.7 -6.1
7 67.5 1.9 2.0 62.3 -3.8 -3.9
8 82.6 1.9 3.0 77.5 -3.8 -6.0
9 82.9 2.0 2.9 77.8 -3.9 -5.9
10 83.4 1.9 3.0 78.3 -3.9 -6.0
11 83.8 2.0 3.1 78.7 -3.9 -6.2
12 71.8 4.0 2.6 67.4 -5.5 -5.1
13 69.3 -0.7 2.5 64.9 -1.1 -5.1
14 71.5 1.5 4.9 67.1 -3.2 -7.3
15 69.6 1.8 0.2 65.2 -3.5 -2.9
Critical Combination:12 - (G+Q+Nx)
Min Design
N (kN) 71.8 - 71.8
M1 (kN.m) -5.5 -0.8 -10.3
M2 (kN.m) -5.1 -0.8 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.057 Le1/b1 = 8.6 < 15.0 225
Beta = 0.93 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 3.2 / 4.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.84 / 0.84 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.08 / 0.10 N/mm2
Links = Y8-175

1C14 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 146.4 3.2 -1.3 141.2 -6.3 2.7
2 146.4 3.0 -1.3 141.3 -6.1 2.7
3 126.6 3.1 -0.3 121.5 -6.3 1.0
4 127.9 2.1 -1.2 122.8 -4.1 2.6
5 134.3 3.2 -1.7 129.2 -6.3 3.4
6 145.6 3.2 -1.3 140.5 -6.4 2.7
7 122.7 3.1 -0.5 117.6 -6.2 1.3
8 128.6 2.0 -1.2 123.5 -4.1 2.6
9 149.9 3.2 -1.2 144.8 -6.3 2.5
10 146.4 3.0 -1.3 141.3 -6.1 2.7
11 134.7 3.2 -1.5 129.6 -6.3 3.2
12 125.5 5.0 -1.0 121.1 -7.6 2.2
13 122.4 0.3 -1.1 118.1 -3.1 2.3
14 123.8 2.6 1.4 119.5 -5.2 -0.2
15 124.1 2.7 -3.5 119.7 -5.4 4.7
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 146.4 - 146.4
M1 (kN.m) -6.3 -1.6 -8.6
M2 (kN.m) 2.7 1.6 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.116 Le1/b1 = 8.6 < 15.0 225
Beta = 0.86 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.2 / 2.7 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.91 / 0.91 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.10 / 0.07 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-13

1C15 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 259.1 -2.4 -1.2 254.0 4.9 2.4
2 236.7 -2.5 -1.5 231.6 5.1 3.0
3 225.9 -2.4 0.1 220.8 4.9 0.0
4 238.7 -1.4 -1.1 233.6 2.9 2.4
5 242.2 -2.4 -1.6 237.1 4.9 3.2
6 257.6 -2.3 -1.2 252.5 4.8 2.5
7 221.0 -2.4 -0.1 215.9 5.0 0.4
8 240.4 -1.5 -1.1 235.3 3.0 2.4
9 262.7 -2.4 -1.1 257.6 4.9 2.2
10 236.7 -2.5 -1.5 231.6 5.1 3.0
11 243.5 -2.4 -1.4 238.4 4.9 3.0
12 217.7 0.3 -0.9 213.3 1.9 2.0
13 220.1 -4.4 -1.0 215.7 6.4 2.0
14 219.9 -2.1 1.4 215.6 4.2 -0.4
15 217.9 -1.9 -3.4 213.5 4.1 4.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 259.1 - 259.1
M1 (kN.m) 4.9 2.9 7.1
M2 (kN.m) 2.4 2.9 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.205 Le1/b1 = 8.6 < 15.0 225
Beta = 0.76 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.5 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.89 / 0.87 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.00 N/mm2
Links = Y8-175

2C15 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 22.0 -0.9 -2.0 16.4 0.1 0.4
2 21.1 -1.1 -2.5 15.4 0.1 0.7
3 21.1 -1.0 0.3 15.5 0.1 -0.9
4 20.8 0.2 -2.1 15.2 0.0 0.5
5 19.6 -1.2 -3.0 14.0 0.0 1.2
6 21.5 -1.1 -2.1 15.9 0.1 0.5
7 21.5 -0.9 -0.3 15.9 0.1 -0.4
8 21.4 0.5 -2.0 15.8 0.0 0.4
9 21.1 -1.1 -1.8 15.5 0.1 0.4
10 21.1 -1.1 -2.5 15.4 0.1 0.7
11 20.2 -1.0 -2.5 14.5 0.1 0.7
12 19.0 -0.5 -1.7 14.2 0.0 0.3
13 18.8 -1.0 -1.7 14.0 0.1 0.4
14 19.1 -0.7 -0.9 14.2 0.0 -0.4
15 18.7 -0.7 -2.5 13.9 0.1 1.1
Critical Combination:5 - ((G+Q)P22 *F)
Min Design
N (kN) 19.6 - 19.6
M1 (kN.m) -1.2 -0.2 0.0
M2 (kN.m) -3.0 -0.2 -4.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.016 Le1/b1 = 10.6 < 15.0 225
Beta = 0.98 Le2/b2 = 9.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.4 / 1.3 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.03 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-14

1C16 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 212.7 -3.1 0.6 207.6 6.4 -1.2
2 158.0 -1.9 0.7 152.8 3.9 -1.3
3 212.9 -3.1 0.7 207.8 6.4 -1.3
4 201.5 -3.2 0.6 196.4 6.5 -1.3
5 203.5 -3.1 0.3 198.4 6.3 -0.6
6 212.7 -3.0 0.6 207.6 6.3 -1.2
7 212.3 -3.2 0.7 207.2 6.5 -1.3
8 201.6 -3.2 0.6 196.5 6.6 -1.2
9 204.5 -3.0 0.3 199.4 6.2 -0.7
10 158.0 -1.9 0.7 152.8 3.9 -1.3
11 212.3 -3.1 0.6 207.2 6.4 -1.2
12 182.4 -0.2 0.5 178.0 3.1 -1.0
13 177.1 -5.0 0.5 172.7 7.7 -1.1
14 181.7 -2.7 2.8 177.3 5.5 -3.2
15 177.7 -2.5 -1.7 173.4 5.3 1.1
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 212.7 - 212.7
M1 (kN.m) 6.4 2.4 8.3
M2 (kN.m) -1.2 -2.4 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.168 Le1/b1 = 8.6 < 15.0 225
Beta = 0.81 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.2 / 0.7 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.97 / 0.93 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.10 / 0.02 N/mm2
Links = Y8-175

2C16 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 19.2 1.0 1.0 13.6 -5.5 -0.1
2 17.1 2.9 1.0 11.4 -6.2 -0.1
3 19.2 0.9 1.1 13.6 -5.6 -0.1
4 17.9 0.1 1.0 12.3 -4.6 -0.1
5 18.8 0.3 0.6 13.2 -4.6 -0.1
6 19.2 0.7 1.0 13.6 -5.2 -0.1
7 19.3 1.0 1.0 13.6 -5.6 -0.1
8 17.8 0.6 1.0 12.2 -5.0 -0.1
9 18.5 0.4 0.7 12.9 -4.6 -0.1
10 17.1 2.9 1.0 11.4 -6.2 -0.1
11 19.5 0.8 1.1 13.8 -5.4 -0.1
12 16.4 1.4 0.9 11.6 -5.2 -0.1
13 16.5 0.4 0.9 11.7 -4.3 -0.1
14 16.3 0.9 1.3 11.5 -4.7 -0.1
15 16.5 1.0 0.5 11.7 -4.8 -0.1
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 17.1 - 17.1
M1 (kN.m) -6.2 -0.2 -7.2
M2 (kN.m) 1.0 0.2 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.013 Le1/b1 = 9.5 < 15.0 225
Beta = 0.98 Le2/b2 = 10.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.8 / 0.4 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.07 / 0.01 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-15

1C17 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 32.6 -0.2 -0.6 27.5 0.4 1.2
2 43.1 -0.2 -0.5 38.0 0.5 1.0
3 27.8 -0.2 -0.2 22.7 0.4 0.5
4 27.3 0.0 -0.6 22.2 0.2 1.2
5 24.9 -0.1 -0.8 19.8 0.4 1.6
6 32.6 -0.1 -0.6 27.5 0.4 1.2
7 20.7 -0.2 -0.4 15.6 0.5 0.8
8 27.3 -0.1 -0.6 22.2 0.2 1.2
9 40.7 -0.1 -0.5 35.6 0.2 1.0
10 43.1 -0.2 -0.5 38.0 0.5 1.0
11 24.0 -0.2 -0.7 18.9 0.5 1.4
12 25.5 2.2 -0.5 21.1 -1.9 1.0
13 30.6 -2.5 -0.5 26.2 2.6 1.0
14 28.1 -0.2 1.8 23.7 0.4 -1.2
15 28.0 -0.1 -2.7 23.6 0.2 3.2
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 32.6 - 32.6
M1 (kN.m) 0.4 0.4 0.0
M2 (kN.m) 1.2 0.4 1.6 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.026 Le1/b1 = 8.5 < 15.0 225
Beta = 0.97 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.7 / 2.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.80 / 0.79 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.04 / 0.05 N/mm2
Links = Y8-175

1C18 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 89.3 0.2 1.9 84.2 -0.3 -3.9
2 100.5 0.1 1.9 95.4 -0.2 -3.8
3 61.3 0.1 1.2 56.2 0.0 -2.2
4 82.7 0.3 1.9 77.6 -0.5 -3.9
5 83.0 0.2 1.9 77.9 -0.3 -4.0
6 88.7 0.2 1.9 83.6 -0.3 -3.8
7 90.5 0.2 2.0 85.4 -0.3 -3.9
8 83.1 0.2 1.9 78.0 -0.5 -3.9
9 61.5 0.1 1.0 56.4 0.0 -2.0
10 100.5 0.1 1.9 95.4 -0.2 -3.8
11 81.6 0.2 2.1 76.4 -0.2 -4.2
12 73.1 2.5 1.6 68.7 -2.5 -3.2
13 78.4 -2.2 1.6 74.1 2.0 -3.3
14 75.0 0.1 3.9 70.6 -0.2 -5.4
15 76.5 0.2 -0.6 72.1 -0.2 -1.1
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 89.3 - 89.3
M1 (kN.m) -0.3 -1.0 0.0
M2 (kN.m) -3.9 -1.0 -4.8 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.071 Le1/b1 = 8.5 < 15.0 225
Beta = 0.92 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 3.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.79 / 0.85 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.07 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-16

1C19 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 192.2 -2.5 -0.7 187.1 5.2 1.5
2 145.9 -1.6 -0.7 140.8 3.3 1.4
3 190.3 -2.6 -0.6 185.1 5.4 1.4
4 183.6 -2.6 -0.7 178.5 5.4 1.4
5 183.0 -2.4 -0.6 177.9 5.0 1.1
6 195.3 -2.5 -0.7 190.2 5.3 1.4
7 192.4 -2.5 -0.7 187.3 5.2 1.4
8 180.3 -2.6 -0.7 175.2 5.4 1.5
9 181.1 -2.5 -0.6 176.0 5.2 1.1
10 145.9 -1.6 -0.7 140.8 3.3 1.4
11 191.9 -2.5 -0.7 186.8 5.2 1.4
12 164.2 0.3 -0.6 159.8 2.1 1.2
13 160.8 -4.6 -0.6 156.4 6.8 1.2
14 160.2 -2.2 1.6 155.9 4.4 -0.9
15 164.7 -2.1 -2.8 160.3 4.4 3.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 192.2 - 192.2
M1 (kN.m) 5.2 2.2 7.0
M2 (kN.m) 1.5 2.2 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.152 Le1/b1 = 8.6 < 15.0 225
Beta = 0.82 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.6 / 0.7 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.86 / 0.91 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.02 N/mm2
Links = Y8-175

2C19 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 13.4 13.3 -1.0 7.8 -27.6 -0.1
2 12.2 14.9 -1.0 6.6 -28.2 -0.1
3 13.3 13.3 -0.9 7.7 -27.6 -0.1
4 12.7 11.4 -1.0 7.1 -24.7 -0.1
5 13.6 11.0 -0.8 8.0 -23.4 -0.1
6 14.2 12.6 -1.0 8.6 -26.7 -0.1
7 13.4 13.3 -1.1 7.8 -27.5 -0.1
8 11.4 12.4 -1.0 5.8 -25.9 -0.1
9 12.9 11.4 -0.7 7.3 -24.0 -0.1
10 12.2 14.9 -1.0 6.6 -28.2 -0.1
11 14.1 12.9 -1.0 8.5 -27.0 -0.1
12 11.2 12.1 -0.9 6.4 -24.2 -0.1
13 11.7 10.9 -0.9 6.9 -23.1 -0.1
14 11.4 11.5 -0.5 6.6 -23.7 -0.1
15 11.5 11.4 -1.3 6.7 -23.6 -0.1
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 12.2 - 12.2
M1 (kN.m) -28.2 -0.1 -29.2
M2 (kN.m) -1.0 -0.1 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.010 Le1/b1 = 9.5 < 15.0 225
Beta = 0.99 Le2/b2 = 10.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 13.1 / 0.4 kN As (Required): %2.06 1044.26 mm2 8Y16
vc'(1/2)= 0.96 / 0.96 N/mm2 As (Provided): %3.18 1608.50 mm2
v (1/2)= 0.32 / 0.01 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-17

1C20 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 340.2 2.9 2.7 333.4 -5.7 -5.4
2 303.4 1.3 3.0 296.6 -2.7 -6.0
3 311.6 3.0 0.9 304.8 -5.8 -1.3
4 311.2 3.6 2.8 304.4 -7.1 -5.5
5 317.6 2.7 3.2 310.8 -5.4 -6.7
6 315.9 3.7 2.7 309.1 -7.3 -5.4
7 347.0 2.9 2.7 340.2 -5.7 -5.2
8 336.8 2.8 2.8 330.0 -5.5 -5.5
9 300.8 2.8 0.8 294.0 -5.5 -1.6
10 303.4 1.3 3.0 296.6 -2.7 -6.0
11 321.5 2.9 3.3 314.7 -5.7 -6.7
12 287.3 5.6 2.3 281.4 -7.9 -4.6
13 288.5 -0.7 2.3 282.7 -1.8 -4.5
14 287.0 2.4 7.6 281.2 -4.8 -9.4
15 288.8 2.5 -3.0 282.9 -4.9 0.3
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 340.2 - 340.2
M1 (kN.m) -5.7 -3.8 -8.7
M2 (kN.m) -5.4 -5.1 0.0 300
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.202 Le1/b1 = 8.6 < 15.0 225
Beta = 0.77 Le2/b2 = 6.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.4 / 1.1 kN As (Required): %0.40 (min) 270.00 mm2 4Y16
vc'(1/2)= 0.78 / 0.87 N/mm2 As (Provided): %1.19 804.25 mm2
v (1/2)= 0.01 / 0.02 N/mm2
Links = Y8-175

2C20 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 72.8 -16.8 3.5 65.3 51.0 -0.3
2 71.3 -19.7 4.1 63.8 52.4 -0.6
3 71.2 -16.7 0.5 63.7 50.9 0.5
4 66.4 -13.8 3.7 58.9 45.6 -0.6
5 64.2 -13.7 4.4 56.8 42.9 -0.6
6 70.0 -15.1 3.4 62.5 48.8 -0.2
7 72.2 -16.9 3.1 64.7 51.0 -0.3
8 70.6 -16.0 3.8 63.2 48.9 -0.7
9 66.4 -14.2 0.3 58.9 44.5 1.1
10 71.3 -19.7 4.1 63.8 52.4 -0.6
11 69.7 -16.2 5.0 62.2 49.3 -1.3
12 62.7 -13.8 3.0 56.2 43.1 -0.3
13 62.1 -15.1 2.9 55.7 44.3 -0.3
14 62.3 -14.4 3.9 55.9 43.7 -1.4
15 62.5 -14.6 2.0 56.1 43.8 0.8
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 71.3 - 71.3
M1 (kN.m) 52.4 0.8 55.2
M2 (kN.m) 4.1 1.1 0.0 300
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.042 Le1/b1 = 9.7 < 15.0 225
Beta = 0.95 Le2/b2 = 7.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 21.9 / 0.0 kN As (Required): %2.87 1940.61 mm2 10Y16
vc'(1/2)= 0.98 / 0.85 N/mm2 As (Provided): %2.98 2010.62 mm2
v (1/2)= 0.40 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-18

1C21 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 116.8 1.3 1.1 111.6 -2.6 -2.2
2 120.7 1.6 1.1 115.6 -3.2 -2.2
3 99.2 1.3 0.6 94.1 -2.6 -0.9
4 100.4 0.5 1.2 95.3 -0.9 -2.3
5 106.8 1.4 1.3 101.7 -2.7 -2.7
6 101.3 0.5 1.1 96.2 -0.9 -2.2
7 122.0 1.3 1.2 116.9 -2.6 -2.2
8 115.8 1.3 1.2 110.7 -2.6 -2.3
9 95.8 1.4 0.5 90.7 -2.6 -0.9
10 120.7 1.6 1.1 115.6 -3.2 -2.2
11 104.9 1.3 1.4 99.8 -2.6 -2.7
12 100.4 3.5 1.0 96.0 -4.4 -1.9
13 97.4 -1.2 0.9 93.1 0.1 -1.8
14 98.6 1.1 3.4 94.2 -2.2 -4.3
15 99.2 1.1 -1.5 94.9 -2.2 0.5
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 116.8 - 116.8
M1 (kN.m) -2.6 -1.3 -4.6
M2 (kN.m) -2.2 -1.3 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.092 Le1/b1 = 8.6 < 15.0 225
Beta = 0.89 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.6 / 2.6 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.88 / 0.88 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.06 / 0.06 N/mm2
Links = Y8-175

1C22 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 150.0 3.1 -0.6 144.9 -6.2 1.2
2 150.0 2.9 -0.6 144.9 -6.0 1.3
3 129.3 3.1 0.2 124.2 -6.2 -0.2
4 131.6 2.1 -0.5 126.5 -4.1 1.2
5 137.4 3.1 -1.1 132.2 -6.2 2.1
6 149.0 3.2 -0.6 143.9 -6.2 1.3
7 137.0 3.1 -0.8 131.9 -6.2 1.7
8 132.7 2.0 -0.5 127.6 -4.0 1.2
9 127.7 3.1 -0.1 122.6 -6.1 0.2
10 150.0 2.9 -0.6 144.9 -6.0 1.3
11 152.0 3.1 -0.6 146.9 -6.2 1.3
12 128.6 5.0 -0.4 124.2 -7.5 1.0
13 125.5 0.2 -0.5 121.1 -2.9 1.1
14 127.5 2.7 2.0 123.1 -5.3 -1.4
15 126.6 2.6 -2.9 122.2 -5.2 3.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 150.0 - 150.0
M1 (kN.m) -6.2 -1.7 -7.6
M2 (kN.m) 1.2 1.7 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.119 Le1/b1 = 8.6 < 15.0 225
Beta = 0.86 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.2 / 2.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.91 / 0.92 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.10 / 0.05 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-19

1C23 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 254.3 -2.2 -0.5 249.2 4.7 1.1
2 233.1 -2.4 -0.8 228.0 4.9 1.7
3 219.0 -2.2 0.6 213.9 4.7 -1.1
4 234.8 -1.2 -0.5 229.7 2.6 1.1
5 237.8 -2.2 -1.0 232.7 4.7 2.0
6 252.6 -2.2 -0.5 247.5 4.6 1.1
7 236.9 -2.2 -0.7 231.8 4.7 1.7
8 236.5 -1.3 -0.5 231.4 2.7 1.0
9 217.6 -2.2 0.3 212.5 4.7 -0.7
10 233.1 -2.4 -0.8 228.0 4.9 1.7
11 256.6 -2.2 -0.5 251.5 4.7 1.1
12 213.4 0.5 -0.4 209.0 1.7 0.9
13 215.9 -4.3 -0.4 211.6 6.2 0.9
14 214.5 -1.8 2.0 210.1 3.9 -1.5
15 214.8 -1.9 -2.8 210.5 4.0 3.2
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 254.3 - 254.3
M1 (kN.m) 4.7 2.9 6.9
M2 (kN.m) 1.1 2.9 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.201 Le1/b1 = 8.6 < 15.0 225
Beta = 0.77 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.4 / 0.4 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.87 / 0.98 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.01 N/mm2
Links = Y8-175

2C23 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 14.0 -2.0 -1.3 8.4 0.1 0.8
2 12.7 -2.4 -1.9 7.1 0.2 1.1
3 13.5 -2.0 0.9 7.9 0.1 -0.4
4 13.7 -0.8 -1.3 8.1 0.1 0.8
5 13.2 -2.0 -2.4 7.6 0.1 1.5
6 13.6 -2.1 -1.4 8.0 0.1 0.9
7 12.8 -2.0 -2.1 7.1 0.1 1.4
8 14.1 -0.7 -1.2 8.5 0.1 0.8
9 14.0 -2.1 0.5 8.4 0.1 -0.3
10 12.7 -2.4 -1.9 7.1 0.2 1.1
11 13.9 -2.0 -1.2 8.3 0.1 0.7
12 12.1 -1.5 -1.1 7.3 0.1 0.7
13 12.0 -1.9 -1.1 7.1 0.1 0.7
14 12.0 -1.7 -0.4 7.2 0.1 0.0
15 12.0 -1.7 -1.8 7.2 0.1 1.4
Critical Combination:5 - ((G+Q)P22 *F)
Min Design
N (kN) 13.2 - 13.2
M1 (kN.m) -2.0 -0.1 0.0
M2 (kN.m) -2.4 -0.1 -4.4 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.010 Le1/b1 = 10.6 < 15.0 225
Beta = 0.99 Le2/b2 = 9.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.8 / 1.2 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.03 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-20

1C24 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 94.2 0.2 -1.7 89.1 -0.4 3.4
2 107.5 0.1 -1.7 102.4 -0.2 3.4
3 65.6 0.2 -0.7 60.5 -0.2 1.5
4 87.7 0.4 -1.7 82.6 -0.6 3.4
5 85.9 0.2 -2.0 80.8 -0.3 3.9
6 94.2 0.3 -1.7 89.1 -0.4 3.4
7 86.3 0.2 -1.8 81.2 -0.3 3.7
8 87.7 0.3 -1.7 82.6 -0.6 3.4
9 64.2 0.1 -0.9 59.1 -0.1 1.8
10 107.5 0.1 -1.7 102.4 -0.2 3.4
11 95.1 0.3 -1.7 90.0 -0.5 3.4
12 77.1 2.6 -1.4 72.8 -2.6 2.9
13 82.9 -2.2 -1.4 78.6 2.0 2.9
14 80.9 0.3 0.8 76.5 -0.4 0.7
15 79.2 0.1 -3.7 74.8 -0.2 5.1
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 94.2 - 94.2
M1 (kN.m) -0.4 -1.1 0.0
M2 (kN.m) 3.4 1.1 4.4 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.074 Le1/b1 = 8.5 < 15.0 225
Beta = 0.91 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.7 / 0.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.87 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.04 / 0.00 N/mm2
Links = Y8-175

1C25 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 213.6 -2.9 0.2 208.5 5.9 -0.4
2 158.9 -1.7 0.3 153.8 3.5 -0.7
3 205.0 -2.9 0.1 199.9 6.1 -0.1
4 202.4 -2.9 0.2 197.3 6.0 -0.4
5 212.8 -2.8 0.1 207.7 5.9 -0.3
6 213.6 -2.8 0.2 208.5 5.9 -0.4
7 212.8 -2.8 0.2 207.7 5.9 -0.4
8 202.4 -3.0 0.2 197.3 6.1 -0.4
9 212.7 -2.9 0.1 207.6 6.1 -0.3
10 158.9 -1.7 0.3 153.8 3.5 -0.7
11 205.9 -2.8 0.0 200.8 5.9 0.0
12 183.1 0.0 0.2 178.8 2.7 -0.3
13 177.7 -4.8 0.2 173.4 7.3 -0.3
14 182.4 -2.3 2.4 178.0 4.9 -2.4
15 178.5 -2.5 -2.0 174.1 5.1 1.8
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 213.6 - 213.6
M1 (kN.m) 5.9 2.4 7.9
M2 (kN.m) -0.4 -2.4 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.169 Le1/b1 = 8.6 < 15.0 225
Beta = 0.80 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.9 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.89 / 0.86 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-21

2C25 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 21.1 -0.7 0.0 15.5 -4.7 0.1
2 19.7 1.2 0.2 14.1 -5.6 0.1
3 20.6 -1.0 -0.1 14.9 -4.5 0.1
4 19.6 -1.3 0.1 14.0 -4.0 0.1
5 20.6 -1.0 0.0 15.0 -4.1 0.1
6 21.1 -0.8 0.0 15.5 -4.6 0.1
7 21.1 -0.6 0.0 15.4 -4.8 0.1
8 19.6 -1.1 0.0 14.0 -4.1 0.1
9 20.7 -1.1 0.1 15.1 -4.1 0.1
10 19.7 1.2 0.2 14.1 -5.6 0.1
11 20.5 -0.8 -0.2 14.9 -4.4 0.1
12 18.1 0.0 0.0 13.3 -4.5 0.1
13 18.1 -1.0 0.0 13.3 -3.6 0.1
14 18.3 -0.5 0.4 13.5 -4.2 0.1
15 17.9 -0.6 -0.3 13.1 -4.0 0.1
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 19.7 - 19.7
M1 (kN.m) -5.6 -0.2 -5.9
M2 (kN.m) 0.2 0.2 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.016 Le1/b1 = 9.5 < 15.0 225
Beta = 0.98 Le2/b2 = 10.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.1 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.76 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.05 / 0.00 N/mm2
Links = Y8-175

1C26 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 51.0 -0.3 0.0 45.9 0.8 0.1
2 57.4 -0.4 0.0 52.3 0.9 0.1
3 47.6 -0.2 -0.2 42.5 0.7 0.5
4 41.5 -0.2 0.0 36.4 0.6 0.1
5 47.7 -0.3 0.1 42.6 0.8 -0.3
6 50.6 -0.2 -0.1 45.5 0.7 0.1
7 42.6 -0.3 0.1 37.5 0.9 -0.2
8 41.8 -0.3 0.0 36.7 0.7 0.1
9 62.8 -0.2 -0.1 57.7 0.6 0.1
10 57.4 -0.4 0.0 52.3 0.9 0.1
11 40.8 -0.3 -0.2 35.7 0.8 0.4
12 40.4 2.1 0.0 36.1 -1.6 0.1
13 47.4 -2.7 0.0 43.1 3.0 0.1
14 43.6 -0.2 2.2 39.2 0.6 -2.1
15 44.3 -0.4 -2.3 39.9 0.8 2.3
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 51.0 - 51.0
M1 (kN.m) 0.8 0.6 1.4
M2 (kN.m) 0.1 0.6 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.040 Le1/b1 = 8.6 < 15.0 225
Beta = 0.95 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.9 / 1.5 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.82 / 0.82 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.05 / 0.04 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-22

2C26 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 31.8 0.2 -0.4 26.2 -0.2 0.3
2 31.9 -0.2 -0.4 26.3 0.0 0.3
3 30.6 0.3 -0.5 25.0 -0.3 0.0
4 28.7 0.1 -0.4 23.0 -0.1 0.3
5 28.7 0.3 -0.1 23.1 -0.3 0.4
6 32.2 0.1 -0.3 26.6 -0.1 0.3
7 32.1 0.1 -0.2 26.5 -0.1 0.2
8 28.2 0.3 -0.4 22.6 -0.3 0.3
9 28.2 0.5 -0.4 22.6 -0.5 0.5
10 31.9 -0.2 -0.4 26.3 0.0 0.3
11 30.8 0.2 -0.4 25.2 -0.2 0.0
12 26.6 0.6 -0.3 21.8 -0.6 0.2
13 27.9 -0.3 -0.3 23.1 0.3 0.2
14 27.2 0.2 0.5 22.4 -0.2 -0.5
15 27.3 0.1 -1.1 22.5 -0.2 1.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 31.8 - 31.8
M1 (kN.m) -0.2 -0.4 0.0
M2 (kN.m) -0.4 -0.4 -0.7 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.025 Le1/b1 = 9.5 < 15.0 225
Beta = 0.97 Le2/b2 = 9.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.2 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.78 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

1C27 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 157.8 -1.0 0.0 152.7 2.2 0.0
2 134.3 -0.7 0.0 129.2 1.4 0.0
3 148.6 -0.9 0.3 143.5 2.1 -0.4
4 152.0 -1.1 0.0 146.9 2.5 0.0
5 148.5 -1.0 -0.3 143.4 2.2 0.4
6 159.8 -1.0 0.0 154.7 2.3 0.0
7 156.8 -1.0 0.1 151.7 2.2 -0.1
8 150.0 -1.1 0.0 144.9 2.4 0.0
9 150.2 -0.9 -0.2 145.1 2.1 0.4
10 134.3 -0.7 0.0 129.2 1.4 0.0
11 147.9 -1.0 0.2 142.8 2.2 -0.3
12 137.1 1.6 0.0 132.7 -0.5 0.0
13 131.7 -3.3 0.0 127.4 4.3 0.0
14 134.5 -0.8 2.3 130.1 1.8 -2.3
15 134.3 -1.0 -2.3 129.9 2.0 2.3
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 157.8 - 157.8
M1 (kN.m) 2.2 1.8 3.8
M2 (kN.m) 0.0 1.8 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.125 Le1/b1 = 8.6 < 15.0 225
Beta = 0.85 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.5 / 1.5 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.92 / 0.95 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.06 / 0.04 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-23

2C27 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 13.5 -1.2 -0.2 7.9 0.7 0.0
2 12.0 -0.8 -0.2 6.4 0.5 0.0
3 13.6 -1.2 0.2 8.0 0.7 0.0
4 12.4 -1.7 -0.2 6.8 1.1 0.0
5 13.6 -1.2 -0.4 7.9 0.7 0.0
6 13.0 -1.5 -0.2 7.4 0.9 0.0
7 13.2 -1.3 -0.2 7.6 0.8 0.0
8 12.9 -1.4 -0.2 7.3 0.9 0.0
9 14.0 -1.1 -0.3 8.4 0.6 0.0
10 12.0 -0.8 -0.2 6.4 0.5 0.0
11 13.4 -1.2 0.1 7.8 0.7 0.0
12 11.8 -0.5 -0.1 7.0 0.1 0.0
13 11.3 -1.6 -0.1 6.5 1.2 0.0
14 11.5 -1.1 0.4 6.7 0.6 0.0
15 11.5 -1.1 -0.6 6.7 0.7 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 13.5 - 13.5
M1 (kN.m) -1.2 -0.2 -1.4
M2 (kN.m) -0.2 -0.2 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.011 Le1/b1 = 9.5 < 15.0 225
Beta = 0.99 Le2/b2 = 10.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.9 / 0.2 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.00 N/mm2
Links = Y8-175

1C28 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 226.7 0.5 -0.2 221.6 -0.8 0.6
2 193.9 -0.3 -0.2 188.8 0.7 0.5
3 214.9 0.5 -0.5 209.8 -0.8 1.3
4 203.9 1.1 -0.2 198.8 -2.0 0.6
5 215.8 0.5 0.1 210.7 -0.8 -0.4
6 206.7 1.1 -0.2 201.6 -2.1 0.6
7 208.6 0.5 0.2 203.5 -0.8 -0.2
8 223.9 0.4 -0.2 218.7 -0.8 0.6
9 239.1 0.5 -0.3 234.0 -0.8 0.5
10 193.9 -0.3 -0.2 188.8 0.7 0.5
11 209.7 0.5 -0.5 204.6 -0.8 1.1
12 191.4 2.9 -0.2 187.0 -3.1 0.5
13 192.7 -2.0 -0.2 188.3 1.7 0.5
14 192.1 0.5 2.2 187.7 -0.8 -1.8
15 191.9 0.3 -2.6 187.6 -0.6 2.8
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 226.7 - 226.7
M1 (kN.m) -0.8 -2.5 0.0
M2 (kN.m) 0.6 2.5 4.6 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.179 Le1/b1 = 8.6 < 15.0 225
Beta = 0.79 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.4 / 0.2 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.96 / 0.95 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.01 / 0.01 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-24

2C28 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 18.4 2.4 -0.7 12.8 -2.5 0.3
2 16.8 0.6 -0.6 11.2 -1.3 0.2
3 16.7 2.4 -1.1 11.1 -2.5 0.3
4 17.7 3.3 -0.7 12.1 -2.7 0.3
5 16.8 2.4 -0.1 11.2 -2.5 0.2
6 19.1 3.3 -0.7 13.4 -2.8 0.3
7 17.2 2.5 -0.1 11.6 -2.6 -0.1
8 17.0 2.4 -0.6 11.4 -2.5 0.2
9 17.4 2.4 -0.6 11.8 -2.4 0.3
10 16.8 0.6 -0.6 11.2 -1.3 0.2
11 17.4 2.4 -1.2 11.7 -2.5 0.6
12 15.9 2.6 -0.6 11.1 -2.6 0.2
13 15.5 1.5 -0.6 10.7 -1.6 0.2
14 15.7 2.1 0.1 10.9 -2.1 -0.5
15 15.7 2.0 -1.3 10.9 -2.1 0.9
Critical Combination:4 - ((G+Q)P21 *F)
Min Design
N (kN) 17.7 - 17.7
M1 (kN.m) 3.3 0.2 4.0
M2 (kN.m) -0.7 -0.2 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.014 Le1/b1 = 9.8 < 15.0 225
Beta = 0.98 Le2/b2 = 9.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.8 / 0.7 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.78 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.04 / 0.02 N/mm2
Links = Y8-175

1C29 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 116.1 0.4 2.3 111.0 -0.6 -4.6
2 129.1 0.2 2.3 124.0 -0.4 -4.7
3 107.4 0.4 2.6 102.3 -0.6 -5.1
4 109.6 0.5 2.3 104.5 -0.9 -4.6
5 78.4 0.2 1.0 73.3 -0.3 -2.2
6 116.1 0.5 2.3 111.0 -0.7 -4.6
7 116.8 0.4 2.3 111.7 -0.7 -4.7
8 109.6 0.5 2.3 104.5 -0.8 -4.6
9 76.9 0.3 1.1 71.8 -0.3 -2.3
10 129.1 0.2 2.3 124.0 -0.4 -4.7
11 108.2 0.3 2.5 103.1 -0.5 -5.0
12 95.4 2.8 1.9 91.0 -2.8 -3.9
13 101.2 -2.1 1.9 96.8 1.8 -3.9
14 97.7 0.5 4.2 93.3 -0.7 -6.1
15 98.9 0.2 -0.4 94.5 -0.3 -1.6
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 116.1 - 116.1
M1 (kN.m) -0.6 -1.3 0.0
M2 (kN.m) -4.6 -1.3 -5.8 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.092 Le1/b1 = 8.5 < 15.0 225
Beta = 0.89 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.9 / 3.4 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.89 / 0.87 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.05 / 0.08 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-25

1C30 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 211.0 -2.6 -0.1 205.9 5.5 0.3
2 157.9 -1.6 -0.3 152.8 3.2 0.6
3 211.1 -2.6 0.0 206.0 5.5 0.2
4 199.8 -2.6 -0.2 194.7 5.6 0.4
5 201.2 -2.7 -0.1 196.1 5.7 0.0
6 211.0 -2.6 -0.1 205.9 5.4 0.3
7 211.0 -2.6 -0.1 205.9 5.5 0.2
8 199.7 -2.7 -0.1 194.6 5.7 0.3
9 201.1 -2.7 0.0 196.0 5.7 0.0
10 157.9 -1.6 -0.3 152.8 3.2 0.6
11 211.1 -2.7 -0.1 206.0 5.6 0.3
12 181.0 0.2 -0.1 176.6 2.3 0.3
13 175.5 -4.7 -0.1 171.2 7.0 0.3
14 176.6 -2.0 2.1 172.2 4.5 -1.8
15 179.9 -2.4 -2.3 175.6 4.8 2.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 211.0 - 211.0
M1 (kN.m) 5.5 2.4 7.4
M2 (kN.m) 0.3 2.4 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.167 Le1/b1 = 8.6 < 15.0 225
Beta = 0.81 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.7 / 0.3 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.88 / 0.92 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.01 N/mm2
Links = Y8-175

2C30 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 21.2 -1.1 -0.3 15.6 -4.2 -0.1
2 19.8 0.7 -0.5 14.2 -5.1 -0.1
3 21.3 -1.0 -0.2 15.7 -4.4 -0.1
4 19.7 -1.6 -0.3 14.0 -3.5 -0.1
5 20.0 -1.7 -0.1 14.4 -3.3 -0.1
6 21.2 -1.3 -0.3 15.5 -4.1 -0.1
7 21.1 -1.2 -0.4 15.5 -4.1 -0.1
8 19.7 -1.5 -0.3 14.1 -3.6 -0.1
9 20.1 -1.6 0.0 14.5 -3.4 -0.1
10 19.8 0.7 -0.5 14.2 -5.1 -0.1
11 21.3 -1.0 -0.3 15.7 -4.3 -0.1
12 18.2 -0.4 -0.3 13.4 -4.1 -0.1
13 18.2 -1.4 -0.3 13.4 -3.1 -0.1
14 18.0 -0.9 0.1 13.2 -3.6 -0.1
15 18.4 -0.9 -0.6 13.6 -3.7 -0.1
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 19.8 - 19.8
M1 (kN.m) -5.1 -0.2 -5.6
M2 (kN.m) -0.5 -0.2 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.016 Le1/b1 = 9.5 < 15.0 225
Beta = 0.98 Le2/b2 = 10.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.8 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.76 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.04 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-26

1C31 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 290.7 -2.9 1.8 285.6 6.0 -3.6
2 269.2 -3.1 2.0 264.1 6.3 -4.1
3 274.5 -2.8 2.3 269.4 6.0 -4.4
4 265.4 -1.5 1.8 260.3 3.3 -3.6
5 244.7 -2.9 0.3 239.6 6.1 -0.8
6 289.1 -2.8 1.8 284.0 5.9 -3.7
7 292.4 -2.8 1.9 287.3 6.0 -3.6
8 267.0 -1.6 1.8 261.9 3.4 -3.6
9 242.4 -2.9 0.5 237.3 6.0 -1.0
10 269.2 -3.1 2.0 264.1 6.3 -4.1
11 275.1 -2.9 2.1 270.0 6.0 -4.2
12 243.7 0.0 1.5 239.3 2.8 -3.0
13 246.2 -4.8 1.5 241.9 7.3 -3.0
14 244.9 -2.2 3.9 240.5 4.9 -5.4
15 245.0 -2.6 -0.9 240.7 5.2 -0.7
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 290.7 - 290.7
M1 (kN.m) 6.0 3.3 8.7
M2 (kN.m) -3.6 -3.3 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.230 Le1/b1 = 8.6 < 15.0 225
Beta = 0.73 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.9 / 0.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.93 / 0.80 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.00 N/mm2
Links = Y8-175

2C31 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 12.8 -3.6 3.0 7.2 0.1 -1.3
2 11.6 -4.0 3.5 5.9 0.2 -1.6
3 11.6 -3.6 4.0 6.0 0.1 -2.0
4 12.5 -1.8 3.0 6.9 0.1 -1.4
5 13.1 -3.6 0.2 7.5 0.1 0.2
6 12.4 -3.7 3.0 6.8 0.1 -1.3
7 12.8 -3.6 2.8 7.2 0.1 -1.2
8 12.9 -1.7 3.0 7.3 0.1 -1.4
9 13.4 -3.6 0.6 7.8 0.1 -0.1
10 11.6 -4.0 3.5 5.9 0.2 -1.6
11 11.3 -3.6 3.7 5.7 0.1 -1.8
12 11.1 -2.8 2.5 6.3 0.1 -1.1
13 11.0 -3.2 2.5 6.2 0.1 -1.1
14 11.1 -3.0 3.2 6.2 0.1 -1.8
15 11.1 -3.0 1.8 6.2 0.1 -0.4
Critical Combination:3 - ((G+Q)P12 *F)
Min Design
N (kN) 11.6 - 11.6
M1 (kN.m) -3.6 -0.1 0.0
M2 (kN.m) 4.0 0.1 7.5 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.009 Le1/b1 = 10.6 < 15.0 225
Beta = 0.99 Le2/b2 = 9.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.3 / 1.8 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.77 / 0.77 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.03 / 0.04 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-27

1C32 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 188.7 3.9 1.9 183.6 -7.7 -3.7
2 188.6 3.7 1.8 183.5 -7.5 -3.7
3 176.8 4.0 2.3 171.7 -7.8 -4.4
4 164.8 2.5 1.9 159.7 -4.9 -3.8
5 155.3 3.9 0.7 150.1 -7.7 -1.5
6 187.9 4.0 1.9 182.8 -7.8 -3.8
7 189.9 4.0 1.9 184.8 -7.8 -3.8
8 165.7 2.5 1.9 160.6 -4.9 -3.7
9 153.5 3.9 0.8 148.4 -7.7 -1.7
10 188.6 3.7 1.8 183.5 -7.5 -3.7
11 177.4 3.9 2.1 172.3 -7.7 -4.2
12 160.8 5.7 1.6 156.4 -8.8 -3.2
13 157.6 0.9 1.6 153.3 -4.2 -3.1
14 159.3 3.5 4.1 155.0 -6.7 -5.6
15 159.1 3.1 -0.9 154.7 -6.3 -0.7
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 188.7 - 188.7
M1 (kN.m) -7.7 -2.1 -10.8
M2 (kN.m) -3.7 -2.1 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.149 Le1/b1 = 8.6 < 15.0 225
Beta = 0.83 Le2/b2 = 8.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 3.9 / 0.1 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.92 / 0.79 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.09 / 0.00 N/mm2
Links = Y8-175

1C33 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 143.7 1.8 -0.2 138.6 -3.5 0.4
2 145.8 1.8 -0.2 140.7 -3.7 0.5
3 132.9 1.8 -0.3 127.8 -3.5 0.9
4 121.3 1.0 -0.1 116.2 -1.8 0.4
5 130.5 1.8 0.1 125.4 -3.5 -0.3
6 127.7 1.0 -0.2 122.6 -1.9 0.4
7 128.7 1.8 0.2 123.6 -3.5 -0.1
8 137.3 1.8 -0.1 132.2 -3.4 0.4
9 149.5 1.9 -0.2 144.4 -3.6 0.4
10 145.8 1.8 -0.2 140.7 -3.7 0.5
11 128.9 1.8 -0.4 123.8 -3.4 0.8
12 123.8 3.9 -0.1 119.4 -5.1 0.3
13 121.0 -0.9 -0.2 116.6 -0.7 0.4
14 122.4 1.6 2.3 118.0 -3.0 -2.0
15 122.4 1.4 -2.6 118.0 -2.8 2.7
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 143.7 - 143.7
M1 (kN.m) -3.5 -1.6 -4.9
M2 (kN.m) 0.4 1.6 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.114 Le1/b1 = 8.6 < 15.0 225
Beta = 0.87 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 0.2 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.78 / 0.87 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-28

2C33 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 51.3 3.0 0.7 45.7 0.1 -2.1
2 51.3 2.9 0.7 45.7 0.1 -2.1
3 48.7 3.0 -0.2 43.1 0.1 -0.5
4 46.2 1.8 0.5 40.6 0.1 -1.8
5 44.9 3.1 1.5 39.3 0.0 -3.4
6 51.3 1.8 0.6 45.7 0.1 -2.1
7 49.7 3.0 1.8 44.1 0.1 -4.3
8 46.3 3.0 0.6 40.6 0.1 -1.9
9 46.4 3.1 0.4 40.7 0.0 -1.3
10 51.3 2.9 0.7 45.7 0.1 -2.1
11 48.9 3.0 -0.3 43.3 0.1 -0.3
12 44.0 2.8 0.6 39.2 0.0 -1.8
13 44.0 2.4 0.6 39.2 0.1 -1.8
14 44.0 2.6 1.1 39.2 0.1 -1.9
15 44.0 2.5 0.0 39.2 0.1 -1.7
Critical Combination:7 - ((G+Q)P32 *F)
Min Design
N (kN) 49.7 - 49.7
M1 (kN.m) 3.0 0.6 0.0
M2 (kN.m) -4.3 -0.6 -7.2 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.039 Le1/b1 = 10.6 < 15.0 225
Beta = 0.95 Le2/b2 = 9.5 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.9 / 1.9 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.79 / 0.80 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.02 / 0.04 N/mm2
Links = Y8-175

1C34 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 95.9 -1.0 -4.8 90.8 2.4 9.7
2 97.6 -1.3 -4.8 92.5 2.7 9.8
3 96.2 -1.0 -4.7 91.1 2.3 9.7
4 83.3 -0.3 -4.8 78.2 1.0 9.8
5 72.6 -1.2 -3.0 67.5 2.6 5.9
6 95.8 -1.0 -4.8 90.7 2.3 9.8
7 95.9 -1.0 -4.8 90.8 2.3 9.7
8 83.5 -0.4 -4.8 78.4 1.0 9.8
9 72.6 -1.1 -2.9 67.5 2.5 5.8
10 97.6 -1.3 -4.8 92.5 2.7 9.8
11 96.3 -1.1 -4.8 91.2 2.4 9.8
12 79.7 1.5 -4.1 75.3 -0.3 8.2
13 82.4 -3.3 -4.0 78.1 4.3 8.2
14 80.1 -0.6 -1.9 75.8 1.7 6.2
15 82.0 -1.1 -6.2 77.6 2.2 10.2
Critical Combination:15 - (G+Q-Ny)
Min Design
N (kN) 82.0 - 82.0
M1 (kN.m) 2.2 0.9 0.0
M2 (kN.m) 10.2 0.9 12.2 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.065 Le1/b1 = 8.6 < 15.0 225
Beta = 0.92 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.5 / 5.5 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.86 / 0.85 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.06 / 0.13 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-29

1C35 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 148.6 0.0 0.0 143.5 0.2 0.0
2 125.7 0.2 0.0 120.6 -0.3 0.0
3 148.6 0.1 0.1 143.5 0.2 0.0
4 125.1 -0.4 0.0 120.0 1.2 0.0
5 146.2 0.1 0.0 141.1 0.1 0.0
6 153.0 0.0 0.0 147.9 0.3 0.0
7 148.7 0.0 0.1 143.6 0.2 0.0
8 120.7 -0.5 0.0 115.6 1.1 0.0
9 146.1 0.1 0.0 141.0 0.1 0.0
10 125.7 0.2 0.0 120.6 -0.3 0.0
11 148.6 0.0 0.0 143.5 0.3 0.0
12 125.8 2.5 0.0 121.4 -2.2 0.0
13 125.6 -2.5 0.0 121.3 2.7 0.0
14 125.7 0.2 1.5 121.3 0.0 -0.6
15 125.8 -0.3 -1.5 121.4 0.5 0.6
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 148.6 - 148.6
M1 (kN.m) 0.2 1.7 0.0
M2 (kN.m) 0.0 1.7 3.1 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.117 Le1/b1 = 8.6 < 15.0 225
Beta = 0.86 Le2/b2 = 10.3 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.79 / 0.76 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

2C35 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 24.4 11.5 -0.1 18.8 -22.4 -0.1
2 23.6 12.0 -0.1 18.0 -22.6 -0.1
3 24.3 11.6 -0.1 18.7 -22.5 -0.1
4 22.3 9.6 -0.1 16.7 -20.2 -0.1
5 23.4 10.4 -0.1 17.8 -20.3 -0.1
6 25.9 10.6 -0.1 20.3 -21.5 -0.1
7 24.4 11.4 -0.1 18.8 -22.3 -0.1
8 20.8 10.5 -0.1 15.2 -21.1 -0.1
9 23.4 10.5 0.0 17.8 -20.4 -0.1
10 23.6 12.0 -0.1 18.0 -22.6 -0.1
11 24.4 11.5 -0.1 18.7 -22.4 -0.1
12 20.5 10.4 -0.1 15.7 -19.8 -0.1
13 21.3 9.2 -0.1 16.5 -18.6 -0.1
14 20.9 9.9 -0.7 16.0 -19.2 -0.1
15 20.9 9.8 0.5 16.1 -19.1 -0.1
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 23.6 - 23.6
M1 (kN.m) -22.6 -0.3 -22.8
M2 (kN.m) -0.1 -0.3 0.0 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.019 Le1/b1 = 9.5 < 15.0 225
Beta = 0.98 Le2/b2 = 10.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 10.5 / 0.0 kN As (Required): %1.48 748.21 mm2 4Y16
vc'(1/2)= 0.78 / 0.76 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.25 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-30

1C36 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 215.4 0.0 -4.4 210.3 0.3 9.0
2 199.6 -0.6 -4.5 194.5 1.3 9.2
3 216.0 0.0 -4.4 210.9 0.3 9.1
4 190.6 0.6 -4.4 185.5 -0.9 9.0
5 182.1 0.0 -2.5 177.0 0.3 5.0
6 187.9 0.6 -4.5 182.8 -0.9 9.1
7 215.3 0.0 -4.3 210.2 0.3 8.9
8 218.1 0.0 -4.3 213.0 0.3 8.8
9 182.0 0.0 -2.5 176.9 0.3 5.0
10 199.6 -0.6 -4.5 194.5 1.3 9.2
11 216.2 -0.1 -4.5 211.1 0.4 9.1
12 182.1 2.5 -3.7 177.7 -2.2 7.5
13 182.2 -2.5 -3.7 177.8 2.7 7.6
14 180.8 0.2 -1.4 176.4 0.0 5.4
15 183.5 -0.3 -5.9 179.1 0.5 9.6
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 215.4 - 215.4
M1 (kN.m) 0.3 2.4 0.0
M2 (kN.m) 9.0 2.4 10.9 225
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.170 Le1/b1 = 8.6 < 15.0 225
Beta = 0.80 Le2/b2 = 8.7 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 5.2 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.89 / 0.97 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.13 N/mm2
Links = Y8-175

2C36 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 36.1 -10.9 -8.2 30.5 22.8 3.8
2 35.1 -11.8 -8.3 29.5 23.4 3.9
3 36.0 -10.8 -8.0 30.4 22.7 3.6
4 33.3 -9.1 -8.2 27.7 20.6 3.8
5 32.8 -9.9 -4.9 27.2 20.5 2.6
6 32.2 -9.8 -8.4 26.6 21.3 4.0
7 36.2 -11.0 -8.3 30.5 22.9 4.0
8 37.2 -10.2 -8.0 31.6 22.1 3.6
9 32.7 -9.8 -4.6 27.1 20.4 2.2
10 35.1 -11.8 -8.3 29.5 23.4 3.9
11 36.1 -10.8 -8.2 30.5 22.7 3.8
12 31.3 -8.7 -6.9 26.5 18.9 3.2
13 30.5 -9.9 -6.9 25.7 20.1 3.2
14 30.7 -9.3 -6.5 25.9 19.4 2.7
15 31.1 -9.4 -7.3 26.3 19.6 3.7
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 35.1 - 35.1
M1 (kN.m) 23.4 0.4 31.4
M2 (kN.m) -8.3 -0.4 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.028 Le1/b1 = 9.6 < 15.0 225
Beta = 0.97 Le2/b2 = 9.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 10.6 / 3.8 kN As (Required): %2.13 1076.41 mm2 8Y16
vc'(1/2)= 0.99 / 0.99 N/mm2 As (Provided): %3.18 1608.50 mm2
v (1/2)= 0.26 / 0.09 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-31

1C37 Storey: 1 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 103.3 2.4 -4.0 98.2 -4.6 8.1
2 104.5 2.3 -4.0 99.4 -4.6 8.2
3 104.0 2.5 -3.9 98.9 -4.7 8.1
4 86.4 1.5 -3.9 81.3 -2.8 8.1
5 80.8 2.3 -2.5 75.7 -4.5 4.9
6 86.7 1.5 -4.0 81.6 -2.8 8.2
7 103.2 2.4 -3.9 98.1 -4.6 8.0
8 102.9 2.4 -3.9 97.8 -4.6 7.9
9 80.9 2.4 -2.4 75.8 -4.6 4.9
10 104.5 2.3 -4.0 99.4 -4.6 8.2
11 104.0 2.4 -4.0 98.9 -4.6 8.3
12 88.5 4.4 -3.3 84.1 -6.2 6.8
13 85.8 -0.4 -3.4 81.5 -1.6 6.9
14 86.3 2.3 -1.0 81.9 -4.1 4.6
15 88.0 1.8 -5.7 83.6 -3.6 9.0
Critical Combination:12 - (G+Q+Nx)
Min Design
N (kN) 88.5 - 88.5
M1 (kN.m) -6.2 -1.0 0.0
M2 (kN.m) 6.8 1.0 12.4 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.070 Le1/b1 = 8.6 < 15.0 225
Beta = 0.92 Le2/b2 = 8.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 3.5 / 4.9 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.87 / 0.86 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.09 / 0.12 N/mm2
Links = Y8-175

2C38 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 -0.1 0.0
M2 (kN.m) 0.0 0.1 0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.8 < 15.0 225
Beta = 1.00 Le2/b2 = 9.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-32

2C39 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 -0.1 0.0
M2 (kN.m) 0.0 0.1 0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.8 < 15.0 225
Beta = 1.00 Le2/b2 = 9.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

2C40 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 -0.1 0.0
M2 (kN.m) 0.0 -0.1 -0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.8 < 15.0 225
Beta = 1.00 Le2/b2 = 9.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-33

2C42 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 0.1 0.0
M2 (kN.m) 0.0 0.1 0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.8 < 15.0 225
Beta = 1.00 Le2/b2 = 9.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

2C43 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 0.1 0.0
M2 (kN.m) 0.0 0.1 0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.8 < 15.0 225
Beta = 1.00 Le2/b2 = 9.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-34

2C44 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 0.1 0.0
M2 (kN.m) 0.0 0.1 0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.7 < 15.0 225
Beta = 1.00 Le2/b2 = 9.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

2C45 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 0.1 0.0
M2 (kN.m) 0.0 -0.1 -0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.7 < 15.0 225
Beta = 1.00 Le2/b2 = 9.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-35

2C46 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 0.1 0.0
M2 (kN.m) 0.0 0.1 0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.7 < 15.0 225
Beta = 1.00 Le2/b2 = 9.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

2C47 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 -0.1 0.0
M2 (kN.m) 0.0 -0.1 -0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.8 < 15.0 225
Beta = 1.00 Le2/b2 = 9.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-36

2C48 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 0.1 0.0
M2 (kN.m) 0.0 0.1 0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.7 < 15.0 225
Beta = 1.00 Le2/b2 = 9.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

2C49 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 32.6 10.0 0.0 27.0 -3.7 0.4
2 32.2 7.3 0.0 26.6 -2.9 0.4
3 31.5 10.0 0.0 25.9 -3.7 0.1
4 30.8 9.8 0.0 25.2 -3.6 0.5
5 30.5 9.7 0.0 24.8 -3.5 0.7
6 32.6 9.8 0.0 27.0 -3.5 0.4
7 32.1 10.0 -0.1 26.5 -3.8 0.2
8 30.9 10.1 0.0 25.3 -3.8 0.6
9 31.1 9.7 0.0 25.5 -3.5 0.9
10 32.2 7.3 0.0 26.6 -2.9 0.4
11 31.4 9.9 0.0 25.8 -3.6 0.1
12 28.1 8.9 0.0 23.3 -3.6 0.4
13 27.9 8.1 0.0 23.1 -2.7 0.3
14 28.0 8.4 0.0 23.2 -3.1 0.0
15 28.0 8.5 -0.1 23.2 -3.2 0.8
Critical Combination:8 - ((G+Q)P41 *F)
Min Design
N (kN) 30.9 - 30.9
M1 (kN.m) 10.1 0.3 10.6
M2 (kN.m) 0.6 0.3 0.0 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.024 Le1/b1 = 9.8 < 15.0 225
Beta = 0.97 Le2/b2 = 9.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.2 / 0.3 kN As (Required): %0.49 250.14 mm2 4Y16
vc'(1/2)= 0.79 / 0.78 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.10 / 0.01 N/mm2
Links = Y8-175

Project: Sani_commercial
OkeBen (*1LX-CWX8-822F-L6MU)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-37

2C50 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 -0.1 0.0
M2 (kN.m) 0.0 -0.1 -0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.9 < 15.0 225
Beta = 1.00 Le2/b2 = 9.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

2C51 Storey: 2 (Con.:C20/25 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 0.0 0.0 0.0 -5.6 0.0 0.0
2 0.0 0.0 0.0 -5.6 0.0 0.0
3 0.0 0.0 0.0 -5.6 0.0 0.0
4 0.0 0.0 0.0 -5.6 0.0 0.0
5 0.0 0.0 0.0 -5.6 0.0 0.0
6 0.0 0.0 0.0 -5.6 0.0 0.0
7 0.0 0.0 0.0 -5.6 0.0 0.0
8 0.0 0.0 0.0 -5.6 0.0 0.0
9 0.0 0.0 0.0 -5.6 0.0 0.0
10 0.0 0.0 0.0 -5.6 0.0 0.0
11 0.0 0.0 0.0 -5.6 0.0 0.0
12 0.0 0.0 0.0 -4.8 0.0 0.0
13 0.0 0.0 0.0 -4.8 0.0 0.0
14 0.0 0.0 0.0 -4.8 0.0 0.0
15 0.0 0.0 0.0 -4.8 0.0 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) -5.6 - -5.6
M1 (kN.m) 0.0 -0.1 0.0
M2 (kN.m) 0.0 0.1 0.1 225
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = -0.004 Le1/b1 = 9.8 < 15.0 225
Beta = 1.00 Le2/b2 = 9.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.0 kN As (Required): %0.40 (min) 202.50 mm2 4Y16
vc'(1/2)= 0.69 / 0.69 N/mm2 As (Provided): %1.59 804.25 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-175

Project: Sani_commercial