6 PDF

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Correction factors fg1 fg2 Gw fg1·fg2·Gw

1.45
Total heat loss coefficient through the ground Ht,ig = (Sk Ak·Uequiv,k)·fg1·fg2·Gw 0.00
Heat losses to spaces heated at different temperatures
Code Building fij Ak (mІ) Uk (W/mІK) fij·Ak·Uk (W/K)
Element
Total heat loss coefficient through spaces at different temperature Ht,ij = Sk fij·Ak·Uk 0.00
Total transmission heat loss coefficient Ht,i = Ht,ie + Ht,iue + Ht,ig + Ht,ij W/K 25.14
Temperature data
Design external temperature иe °C -18
Design internal temperature иint,i °C 20
Design temperature difference иint,i-иe °C 38
Total transmission heat loss Phit,i = Ht,i·(tint,i - te) W 956
Increment % 20
Total design transmission heat loss with increment 1147

Ventilation heat loss calculation


Room internal volume Vi m3 42.15
Outdoor Temperature иe °C -18
Internal temperature иint,i °C 20
Minimum hygienic air exchange rate nmin,i 1/h 0.5
Minimum hygienic air flow rate Vmin,i m3/h 21.08
Air exchange rate/hour at 50 Pa (n50) n50 1/h 5
Shielding coefficient e 0.02
Height correction factor е 1.00
Infiltration air flow rate Vinf,i m3/h 8.43
Selected value for calculation Vi m3/h 21.08
Design ventilation heat loss coefficient Hv,i W/K 7.17
Temperature difference иint-иe °C 38
Design ventilation heat loss Цv,i W 272.3 272.3

Calculation of heating-up capacity


Reheat factor fRH W/mІ 23
Floor area Ai mІ 14.05
Heating-up capacity ЦRH,i W 0.00 0.00

Total design heat load


Total heat load ЦHL,i W 1419

Level : prv kat Space : 4

Transmission heat loss calculation


Heat losses directly to the exterior
Code Building Ak (mІ) Uk (W/mІK) ek Ak·Uk·ek
Element (W/K)
W2 Outer Wall 1 9.25 0.70 1.000 6.47
O1 Reg. Glass 1.68 2.3 1.000 3.86
(Wood.Frame)
W7 Outer Wall 10 1.22 0.35 1.000 0.43
W2 Outer Wall 1 1.62 0.70 1.000 1.13
W7 Outer Wall 10 0.18 0.35 1.000 0.06
Total of building elements Sk Ak·Uk·ek W/K 11.95
Code Thermal bridge Шk (W/mK) lk (m) ek Шk·lk·ek (W/K)
O1- L- 5 0.550 1.40 1.000 0.77
O1- L- 5 0.550 1.40 1.000 0.77
W2- H - 10 (50%) 0.225 4.05 1.000 0.91
W2- H - 10 (50%) 0.225 4.05 1.000 0.91
W2- H - 10 (50%) 0.225 0.60 1.000 0.13
W2- H - 10 (50%) 0.225 0.60 1.000 0.13
Total of thermal bridges Sk Psik·lk·ek W/K 3.63
Total heat loss coefficient directly to the exterior Ht,ie = Sk Ak·Uk·ek + Sk Psik·lk·ek 15.58
Heat losses through unheated spaces