Professional Documents
Culture Documents
Simulation of Mho Type Phase Comparator From The Output of System Analysis Programs
Simulation of Mho Type Phase Comparator From The Output of System Analysis Programs
Simulation of Mho Type Phase Comparator From The Output of System Analysis Programs
net/publication/318199574
CITATIONS READS
0 245
2 authors:
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Jose Antonio González - Cueto Cruz on 05 July 2017.
1
Centro de Estudios Electroenergéticos. UCLV. CUBA
C E E
Expression (5) may also be written as: This protection requires polarization signal S2
to provide a reliable reference angle. Self-
Z −B Z polarization is not suited when a bolted fault is
θ1 − λ ≤ arg = arg S1 ≤ θ2 − λ (7) too close to this signal therefore adaptive
Z
Z − A S2 polarization is used. This may be cross,
combined or memory polarization [16, 18]. The
where Z S1 = Z − B and
first two fail on bold three-phase short circuits,
Z S2 = Z − A (8) only memory polarization solves the problem.
In the case of a mho with combined or dual
The form and dimensions of the characteristics polarization, the S2 signal is given by
of a phase comparator in the complex Z-plane S 2 = V + k pV p (11)
are given by the threshold operating conditions,
which are determined by the equality conditions while for the cross or simple polarization, the S2
in (7). This equality conditions are defined by signal is
the values of k, θ1 and θ 2 . Constants A and B are S 2 = k pV p (12)
the impedance values determining the
The mho threshold operating conditions in the
characteristic in the complex plane, A = Z − Z S 2
complex plane are:
and B = Z − Z S1 . Thus the operation zone of the
Z −Z r
comparator in the complex plane is not affected
θ1 − λ ≤ arg = arg Z − B ≤θ −λ (13)
by the amplitude and phase variations of the Z Z −Ap 2
S2
alternating currents and voltages, while the
values of current and voltage can be measured In the mho Ap and B are also impedance values
by the comparator. determining the circle diameter in the complex
plane.
2.2 Mho phase comparator.
B = Zr (14)
In combined polarization
2
Centro de Estudios Electroenergéticos. UCLV. CUBA
C E E
3
Centro de Estudios Electroenergéticos. UCLV. CUBA
C E E
Table 1
Unit S1 S2 Arg(S1/ S2) Zr Zp AP B
4
Centro de Estudios Electroenergéticos. UCLV. CUBA
C E E
The program can do a modal analysis and find The program editor can show plots of the
the eigenvalues of the reduced matrix JR with the impedance measured curves and all the zone
variable values of the critical state. The characteristics of mho phase comparators in the
participation factors of nodes, branches and complex plane. This can also be done for each
generators can be found for the smaller end of all selected lines.
eigenvalues and the critical elements of the
network. This analysis is a measure of the
vicinity to the critical point and the branches 3.2 Mid-term synchronous stability.
with high participations are either weak links or
are heavy loaded. [20]. The line with the highest The numerical method used in the mid-term
percent of active power transferred is determined stability program for the solutions of the
by equation (23). These elements are useful for differential equations is the implicit trapezoidal
contingency selection and to identify the integration method with a ZBus load flow for the
protections closer to their reach threshold values network solution [8, 24]. The principal system
in the critical state. elements and its interrelationships are shown in
Fig. 3. The figure shows the interchange
PMax = YSRVS VR − G RRVR2 (23) between the network with:
The currents of the branches are found by
i. Generators and its controls. The network
I S Y SS − Y SR V S and generators interactions are dq-ri
=
Y RR V R
(24)
I R − Y RS variable transformations, Tdq -Tri.; and
reference and feedback signals, RS, FS,
The results in this program are balanced three for the controls. The synchronous
phase and the impedance measured values are generators may be represented from the
given by voltages on each end of the line simplest flux model, constant emf, to d
Z SM = V S /[Y SH V S + Y SER (V S − V R )] (25) and q sub-transient effects with
saturation. The prime motors may be
Z RM = V R /[Y SH V R + Y SER (V R − V S )] (26) steam, gas and hydraulics turbines and
internal combustion motors. Also may
Hence a curve in the complex plane can be be simulated eolic turbines with
plotted with the impedance values above for induction generators and photovoltaic
each stable stage of the solution procedure from generation.
the initial condition to the critical point.
ii. Active protections, with input signals
The characteristics of the mho phase and tripping signals, IS and TS. These
comparators in the complex plane are given at protections during simulation may sense
point B by equation (14) and at point Ap by values of frequency, frequency
equations (15) to (18). Depending on the variation, voltage, active and reactive
polarization type, B and Ap can also be found by power, impedances and inversion of
the voltages of both ends of each line for the active power.
balanced conditions in the critical state. These
characteristics are circles with center in iii. Breaker operations and simulated faults,
C = (B + A p ) / 2 (27) with matrix modification and-or load
variation, MtxMod and LV.
and radio
iv. Loads, with its current injections Ii
R = (B + A p ) / 2 (28) under variations of voltage |V|,
5
Centro de Estudios Electroenergéticos. UCLV. CUBA
C E E
6
Centro de Estudios Electroenergéticos. UCLV. CUBA
C E E
The effect of mutual inductance of zero The voltages for each node i and stage k are
sequence in transmission lines may be simulated obtained from the voltage sub-vector
in cases of asymmetrical faults involving
ground. [V i ]abc = [TS ][V i ]012 (33)
The program results are given in graphical of the network voltage vector of the kth stage
form and in tabular form with optional solution
configurations. One of the graphic shows the
variation curves of the impedance measured [V BUS ]012 = [Z BUS ]012 [I BUS ]012 (34)
modules and the angle measured of the apparent
power phasors versus time, in both ends of the And the currents for a line SR by the matrix
lines. The objective is to detect those
relation
protections, which can measure impedances or
oscillatory values near their reach. These values [I ]abc [Y ]012 [Y ]012 [V ]012
judge against the value of the line impedance in S = [T s ] SS SR
S (35)
each simulation instant. The phase difference [I R ]
abc [Y RS ] [Y RR ] [V R ]012
012 012
Table 2
Unit S2 Self S2 Combined S2 Combined S2 Simple S2 Simple S2 Sec pos
AB V ab V ab + k p V c ∠ − 90 0
V ab + k p V ca ∠ − 120 0
k p V bc ∠ − 120
0
k p V c ∠ − 90
0
V ab1
A V a + k p V bc ∠ + 90 V a + k p V c ∠ − 120 k p V bc ∠ + 90 0
0 0 0
Va k p V b ∠ − 120 V a1
7
Centro de Estudios Electroenergéticos. UCLV. CUBA
C E E
V1MEM [ k ] is the present memorized positive α is the time constant of the memory.
Then for each line selected, with a mho phase
sequence voltage, which must be used in the step
comparator, the values of S1, S2, Ap y B are
k as polarization voltage.
calculated for each distance unit protection
V1[ k ] is the actual positive sequence voltage selected, for the reach given to each zone, the
value. type of polarization of the unit and output values
V1MEM [ k −1] is the previous memorized positive of voltage and current given by the program,
which uses the relations (33) to (35).
sequence voltage value.
Fig. 7 Complex plane and related reactance curve. (a)Impedance measured curves and mho
characteristcs, (b) Reactance versus time, (c) Arg. (S1/ S2) versus time.
8
Centro de Estudios Electroenergéticos. UCLV. CUBA
C E E
Example1. The total initial load of the system Protections of the line L20 with higher
is 2850 MW and 580 MVAr. Loads were percentage of active power transfer can be
increased with the voltage stability program in observed with the impedance measured curve by
proportion to their initial values and was them, from the initial condition to the critical
obtained a total load 1,603 times greater than the point, in Fig. 8(b).
initial, for a critical network condition. The The protections of the receiving end are shown,
smallest eigenvalue was 0.0033 determined by a because its third zone is the closest to the critical
modal analysis. The node B106, the line L35 and point impedance. The mho characteristics in this
the generator G10 were the elements with case are three forward zones, first 80, second
highest participation factor, for this operation 120 and third 250 % of the line L20 and a third
mode. The voltage vs active power curve in the inverted zone with 120% of impedance of the
critical node B106 is shown in Fig. 8(a). line L20, all with self-polarization.
9
Centro de Estudios Electroenergéticos. UCLV. CUBA
C E E
conditions in the mid-term stability program. The impedance measured curves and mho
G210 has the greater participation factor in the operation zones are shown in the complex plane
aforementioned operation mode. in Fig. 10(a). Mho protections in sending and
Power oscillations were detected with receiving ends of the line L35 have the same
consequent variations of the impedance zones as L20 in example 1 but with positive
measured in multiple lines in the vicinity of sequence polarization in all the analyzed period.
critical node B6. Line L35 power oscillations are
The graph time interval is from 0 to 4.13
shown in Fig.9 in the vicinity of 4 seconds.
seconds just when impedance measured values
Impedance measured values were below the
value of the impedance line and the angle values get out of all protection zones.
of the apparent power vectors SS and SR were in
the first quadrant in Fig 9.
10
Centro de Estudios Electroenergéticos. UCLV. CUBA
C E E
Fig. 10 (a) Impedance measured curves and operation zones. (b)Input and (c)Output Z point in operation
zones.
The input and output points in the complex time of minimum Zab impedance module in Fig.
plane to operation zones are observed with better 9.
accuracy in the vicinity of the protections. The The environment of operation zones in the
input point indicated by the lines drawn from the complex plane and impedance measured curves
sending and receiving ends of the line to Z in sending and receipt are shown in Fig. 11(a)
curves in Fig. 10(b), corresponds to 3.75 sec. for a time interval between 3.7 and 4.16 seconds.
The output point in Fig. 10(c) corresponds to The curves of θ, for each phase and line mho
4.13 sec. The time intervals of the impedance zones are shown in Fig. 11 (b) in the same time
measured within operation zones vary from 4.8 interval. Mho operation zones in the complex
cycles for the first zones up to 22.8 cycles for plane and θ versus time curves are the same in
third zone of the receiving end. The intersection the three phase units and the three line units as it
of the impedance measured with the straight line is balanced conditions. Hence reference is only
representing the impedance of the transmission made to the sending and receiving zones.
line is at 4.02 seconds in Fig. 10 just exactly
Fig. 11 From 3.7 to 4.16 sec. (a) Impedance measured curves. (b)Arguments of S1/S2.
11
Centro de Estudios Electroenergéticos. UCLV. CUBA
C E E
Mho operation zones with positive sequence operation zones around the complex plane
polarization behave in same way as mho with origin. The sequence of successive changes is
self-polarization in Fig. 11. Impedance Zp has onset of fault at 0.2sec, faulted phases opening at
value for all zones but there is not displacement 0.27 sec and a successful re-closure at 0.37 sec.
from the complex plane origin because All phase and line protections overlap in both
measuring voltages and polarization voltages are zones under pre-fault conditions Fig. 12(a). Also
identical and in balanced conditions Z = Zp. all load impedance measured are equal as shown
Equations (16) and (18) are confirmed by the by the straight line from receiving end line to
coincidence of time and sequencing of input and load impedance value. At 0.2 sec fault onset,
output into each protection zone of impedance three line protections practically overlap and
curve in the complex plane, with crossing θ
therefore two zones are only witnessed while the
curve of each protection zone the values of 900
six phase operation zones are offset one from
and -900. Intersections of θ curves in 00 and 1800
for activated and non-activated zones another Fig. 12 (b). All zones operate except the
respectively at 4.02 seconds coincide with time two zones of phase A because all impedance
instant in which the impedance measured measured are very close from the end of the line.
intercept the straight line representing L35 in the Twelve zones are discriminated very subtly at
complex plane. 0.27 sec end of the fault time interval and all
Example3. Fault BC to earth at the receiving zones have moved with respect the beginning of
end of the line L20 is analyzed with only first the fault Fig. 12 (c). All zones remain triggered
and second mho operation zones but with except the two zones of phase A. The voltage
memory positive sequence polarization in all and current values in all phases and memory
time intervals Fig. A-1, point F. The effect of output voltages have variations in the time
memory is shown on the displacement of mho interval.
Fig. 12 Impedance measured from receiving end before fault and mho operation zones in fault conditions.
12
Centro de Estudios Electroenergéticos. UCLV. CUBA
C E E
AB, CA and A zones are shown in Fig. 13 (a) have been used by manufacturer to avoid mho
when B and C phases open at 0.27 second and miss-operation in this conditions [18, 25].
impedance measured of this three zones are The θ curves of twelve operation zones with
outside of their areas. Same six areas have polarized positive sequence using memory in
reduced their dimensions at 0.37 second Fig. 13 this last example are shown in Fig. 14 for the
(b) and their impedance measured are out of interval from 0.15 to 0.4 seconds. The mho
their reach. Phases B and C are closed at 0.37 zones behavior in the complex plane from Fig.
second and balanced conditions are restored Fig. 11 and 12 agree with results given by θ curves in
13 (c). The two zones of the six protections
the pre-fault, fault and post-fault conditions. The
coincide but they are displaced from the end of
the line, because voltages still are not constants. mho zones displacement equations in the
These voltages and frequency variations produce
also output memory voltages variations. The complex plane are tested again in this example
adaptive short or not memory vs long memory conditions.
Fig. 13 Mho operation zones with B and C open and post fault conditions.
13
Centro de Estudios Electroenergéticos. UCLV. CUBA
C E E
5 Conclusions.
The mho phase comparator was modeled in
the complex plane using the results of a static
voltage stability program. This simulation
detects unit distance elements with impedance
values measured near their reach threshold.
The critical system elements also detected can
be used for contingency analysis in dynamic
disturbances.
Fig. 14 θ curves of mho operation zones.
The dynamic behavior of mho phase
comparators can be modelled using the
method described for results of a mid-term
stability digital program as input. The
simulation of effects of polarization type and
memory usage were tested successfully with
the most important types of disturbances in
two numerical examples. Short circuit
programs achieve similar results for a fault in
an instant of time as it is a particular case of
dynamic simulation.
14
Centro de Estudios Electroenergéticos. UCLV. CUBA
C E E
Appendix 1
System IEEE-24. One-line diagram
15
Centro de Estudios Electroenergéticos. UCLV. CUBA
C E E
16
Centro de Estudios Electroenergéticos. UCLV. CUBA
C E E
17
Centro de Estudios Electroenergéticos. UCLV. CUBA
C E E
18