Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Triconex™

Product Specification

9791043-001

Safety Intelligent Enclosure

The EcoStruxure Triconex Safety Intelligent Enclosure (SIE) provides an integrated solution designed to be
mounted close to field instrumentation to reduce cabling. The SIE includes Tricon CX Universal Input/Output
(UIO) modules, power supplies, and External Termination Panels (ETPs) that are pre-installed and tested, and
can be connected to a wide range of field devices. The factory-manufactured SIE supports Schneider
Electric’s Flexible Lean Execution strategy, which shortens project schedules and reduces the risk of startup
delays. (Note that images are for illustrative purposes. Your product may look slightly different.)

OVERVIEW The SIE provides:


The Safety Intelligent Enclosure (SIE) consists of a  Simplified ordering
wall-mounted stainless steel enclosure, Tricon CX I/O  Standard cabinet design
Expansion Chassis, Universal Input/Output (UIO)  Flexible and scalable I/O deployment without
modules, power supplies, fans, and termination rewiring
panels.
 Indoor/outdoor and local/remote installation
Using TriStation™ 1131 Workbench software, you
support
can configure each Triple Modular Redundant (TMR)
UIO point as one of the following:  Support for a maximum of 64 user-configurable
points
 Supervised Digital Input, 24 VDC, with 1 ms
Sequence of Events (SOE) capability  Early-stage I/O wiring and late-stage project
changes
 Supervised Digital Output, 24 VDC
The SIE has ETPs for termination of field device
 Analog Input, 0-20 mA, configurable: with or
signals. Each ETP point comes pre-configured with a
without HART pass-through
pass-through signal conditioning module. A range of
 Analog Output, 4-20 mA, configurable: with or other signal conditioning types is available.
without HART pass-through
9791043-001
Page 2

FEATURES POWER DISTRIBUTION ARCHITECTURE


 Protection against harsh environments and The SIE uses two independent 24 VDC power
hazardous locations: architectures to operate. One set of dual redundant
power supplies provides logic power to the I/O
• NEMA® 4X/IP66 rated
chassis and another set of dual power supplies
• Corrosion resistance:
provides power to the field instruments. This power
– Electronics: ISA-71.04, G3 level architecture provides protection against power
failures.
– Enclosure: UL 50E and ASTM B117
• ATEX Zone 2 I/O BUS CONNECTION
• Class I, Division 2 The SIE supports a TMR I/O bus connection with
 Support for up to four Triconex 3902X UIO special interface modules:
Modules  Triconex 4701X IMSS – Serial RS-485
 Input/output types that are software configurable (up to 100 ft (30 m))
 Support for up to 64 TMR I/O points  Triconex 4703X IMFF – Fiber (up to 12.4 mi (20
 Wall-mounted km))
 Available in 24 VDC, 120 VAC, and 240 VAC The small form-factor pluggable (SFP) modules used
incoming power options with the IMFF are selected based on the application,
and are supplied separately.
 Redundant power supplies
 Redundant fans (available with no fans)
 Supports star and daisy chain network topologies
for the I/O bus
 Modular architecture allowing sections to be
fitted/removed separately for phased installation

P H Y S I C A L S P E C I F I C AT I O N S

Size Weight Range


31.50 in (800 mm) width, 15.75 in (400 mm) depth, 300 to 350 lb. (136 to 159 kg) (depending on
47.24 in (1200 mm) height configuration)

E N V I R O N M E N TA L S P E C I F I C AT I O N S

Operating Temperature Relative Humidity


WITHOUT INTERNAL FANS 5% to 95% (non-condensing)
–4° F to 113° F (–20° C to 45° C) Certifications
WITH INTERNAL FANS ATEX, FM (U.S. and Canada), CE, RoHS 2, NEMA
–4° F to 131° F (–20° C to 55° C) 4X/IP66
Contaminant Severity Level Hazardous Area Classification
ELECTRONICS II 3 G Ex ec nC nR IIB T4 Gc
ISA-71.04, G3 level II 3 G Ex nA nC nR IIB T4 Gc
ENCLOSURE Class I, Division 2, Groups A, B, C, D; T4
UL 50E and ASTM B117
9791043-001
Page 3

Figure 1. SIE Layout with Left-Side, Front, and Right-Side Views

Legend

A Primary External Power, PTB1 K Divider Plate U Field External Termination


Connectors (FETs)

B ESD Bonding Point L Field Power Terminals, 24 VDC V Tricon CX I/O Expansion Chassis
C Secondary External Power, PTB2 M I/O Expansion Chassis Sub- W Universal I/O (UIO) Modules
Panel Assembly

D Fiber Optic Patch Panel (customer N Functional Earthing Bar (Shield X Fan Tray Assembly
supplied) Ground)

E Protective Earthing Bar (Safety Ground) O Field Wire Duct Y Wall-Mounting Bracket

F Power Sub-Panel Assembly P ETP Sub-Panel Assembly Z Door Switch

G Alarm Terminals Q Signal Conditioning Modules AA Auxiliary Sub-Panel Assembly

H System Power Terminals, 24 VDC R External Termination Panel (ETP) BB External Field Power Termination
(optional)

I Power Supply Units (System and Field) S Lifting Ring CC Multi-cable Transit Frames
(optional)

J Wire Duct T I/O Bus Interface Modules


9791043-001
Page 4

D E L I V E RY O P T I ON S

The Schneider Electric BuyAutomation website To access the tool, sign in to the BuyAutomation
provides a tool to configure an SIE to your website, type “TCX” in the Configure model box, and
requirements. then click the double-arrow button next to the box.

Table 1. Supported Modules

Triconex
Model Number Description

3902X Universal I/O Module (UIO Module)


4701X I/O Bus Interface Module Serial-Serial (IMSS), RS-485 Serial Communication
4703X I/O Bus Interface Module Fiber-Fiber (IMFF), Single Mode (SM) or Multi-Mode (MM) Fiber
Optic Communication

Table 2. Supported Optional Third-Party Products

Manufacturer Product Description Part Number

Phoenix Contact IOA-PSR-PS22-1NO-1NC-24DC-SC IOA, SIL3 Pluggable Coupling 2702971


Relay
Phoenix Contact QUINT-ORING/24VDC/2x10/1x20/CO Diode ORing Module 2320173

Schneider Electric © 2019 Schneider Electric


38 Neponset Avenue All rights reserved.
Foxborough, MA 02035-2037
United States of America
http://www.schneider-electric.com Schneider Electric, EcoStruxure,
Triconex, Tricon, and TriStation are
trademarks and the property of Schneider
Electric SE, its subsidiaries and affiliated
companies. All other trademarks are the
property of their respective owners.
Global Customer Support
Website: https://pasupport.schneider-electric.com 0519

You might also like