Tek 10-02C1
Tek 10-02C1
At pilasters and
changes in wall Adjacent to lintel and through
thickness opening if not crossing
vertical reinforcement
Related TEK: Keywords: bond beams, construction details, control joints, crack
7-1C, 10-1A, 10-3, control, joint reinforcement, reinforcing bars, reinforced concrete masonry,
shrinkage, wall movement
10-4
Control joint with load transfer Control joint with load transfer
capability to adjacent panel capability to adjacent panel
Lintel
Lintel
Slip plane to permit relative movement Slip plane to permit relative movement in
in the plane of the wall. No vertical the plane of the wall. No vertical
reinforcement permitted to cross control reinforcement permitted to cross control
joint. joint.
24-in. (610-mm) long joint reinforcement at lintel 24-in. (610-mm) long joint
bearing and two courses below lintel bearing reinforcement at lintel bearing and two
courses below lintel bearing, each side
2a—Openings less than 6 ft (1,829 mm) 2b—Openings wider than 6 ft (1,829 mm)
Vertical reinforcement,
Joint as required Joint reinforcement,
reinforcement, as required
as required
Vertical
Stop joint Stop joint reinforcement, as
reinforcement reinforcement required
at control Preformed at control
joint gasket joint Ceramic fiber felt
Concrete masonry sash unit (alumina-silica fiber)
Joint reinforcement,
Joint reinforcement,
as required
as required
Vertical Vertical
Stop joint reinforcement, Stop joint
reinforcement reinforcement,
reinforcement as required
at control joint as required
at control joint
Raked mortar
Building
joint
paper
or other
bond break
Sealant Backer rod Sealant Backer rod
3c—Discontinuous Horizontal Reinforcement 3d—Formed Paper Joint (4-Hour Fire Rated*)
* See TEK 7-1C, Fire Resistance Rating of Concrete Masonry Assemblies (ref. 5), for more information on fire ratings.
3e—Special-Shaped Units (4-Hour Fire Rated*) 3f—Doweled Joint (for Shear Transfer)
Control joint backer rod and sealant continuous with control joint in wall
3g—Control Joint Through a Bond Beam—Continuous Horizontal Reinforcement
Control joint backer rod and sealant Terminate one bar short of
continuous with control joint in wall control joint
3h—Control Joint Through a Bond Beam—Lapped Horizontal Reinforcement
Sealant
4a—Round backer, 4b—Square backer or
common application raked mortar, may
reduce sealant stresses
NCMA and the companies disseminating this technical information disclaim any and all responsibility and liability for the accuracy
and the application of the information contained in this publication.
To order a complete TEK Manual or TEK Index, contact NCMA Publications (703) 713-1900