Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

GE Digital Energy

Multilin

GE Multilin instruction sheet


Connecting the side-mounted UR-V
Enhanced Front Panel to a vertically-
mounted horizontal UR-series device
GE publication number: GEK-113182
GE Multilin part number: 1601-9083-A1

Connecting the side-mounted UR-V Enhanced Front Panel to a vertically-mounted horizontal UR-series device

Overview
The following procedures describe how to connect the side-mounted UR-V enhanced front
panel to a vertically-mounted UR-series horizontal device.

GE MULTILIN INSTRUCTION SHEET – CONNECTING THE UR-V ENHANCED PANEL TO A HORIZONTAL UR-SERIES DEVICE 1
Dimensions
There are two cutouts required to attach the UR-V enhanced front panel and the vertically-
mounted horizontal UR-series device.
Figure 1: Horizontal UR-series device mounting hole dimensions
4.000

Panel shown for


reference only

18.850

Ø 0.210
4 places 843707A1.CDR

Figure 2: UR-V enhanced front panel mounting holes and cutout dimensions

4.000
Panel shown for
reference only

1.000 3.000

1.000 10.656

13.906
RJ45 1.000
connector
cutout

1.500

Ø 0.210
4 places

4.000 843708A1.CDR

2 GE MULTILIN INSTRUCTION SHEET – CONNECTING THE UR-V ENHANCED PANEL TO A HORIZONTAL UR-SERIES DEVICE
ATTACHING THE UR-V ENHANCED FRONT PANEL TO THE CUSTOMER PANEL

Procedures
Attaching the UR-V The procedure to attach the UR-V enhanced front panel to the customer panel is as
enhanced front panel follows.
to the customer panel 1. Feed the RJ45 connector cable on the UR-V front panel through the RJ45 connector
cutout on the customer panel.
2. Using the four #10-32 × ⅜” screws (part number 1410-0006), four #10 zinc washers
(part number 1430-0006), and four nylock zinc nuts (part number 1422-1032), attach
the UR-V front panel to the customer panel.

1422-1032
Quantity: 4

1430-0006
Quantity: 4

1410-0006
Quantity: 4

834709A1.CDR

GE MULTILIN INSTRUCTION SHEET – CONNECTING THE UR-V ENHANCED PANEL TO A HORIZONTAL UR-SERIES DEVICE 3
ATTACHING THE UR-V ENHANCED FRONT PANEL TO THE CUSTOMER PANEL

3. Tighten the screws using a tightening torque of 20 lb.-in, ensuring the UR-V enhanced
front panel is snug to the panel.

843710A1.CDR

4 GE MULTILIN INSTRUCTION SHEET – CONNECTING THE UR-V ENHANCED PANEL TO A HORIZONTAL UR-SERIES DEVICE
ATTACHING THE MOUNTING BRACKETS AND VERTICAL MOUNT COVER TO THE HORIZONTAL UR-SERIES DEVICE

Attaching the The second step in connecting the side-mounted UR-V enhanced front panel to a
mounting brackets horizontal UR-series device is to attach the mounting brackets and vertical mount cover to
and vertical mount the chassis. If your chassis already has the mounting brackets and vertical mount cover
cover to the attached, then proceed to Attaching the horizontal UR-series device to the customer panel
on page 8.
horizontal UR-series
device 1. Using four #8-32 × ¼” screws (part number 1418-0107), attach the mount bracket
(part number 1001-0042) to the top of the chassis (tightening torque 17 lb.-in).

1001-0042 1418-0107

843719A1.CDR

2. Using four #8-32 × ¼” screws (part number 1418-0107), attach the mount bracket
(part number 1001-0042) to the bottom of the chassis (tightening torque 17 lb.-in).

1001-0042

1418-0107 843722A1.CDR

GE MULTILIN INSTRUCTION SHEET – CONNECTING THE UR-V ENHANCED PANEL TO A HORIZONTAL UR-SERIES DEVICE 5
ATTACHING THE MOUNTING BRACKETS AND VERTICAL MOUNT COVER TO THE HORIZONTAL UR-SERIES DEVICE

3. Plug the RJ45 cable into the RJ45 connector on the CPU unit.
4. Plug the ground cable from the UR-series device to the ground clip on the cover.

843725A1.CDR

5. Using two #8-32 × ¼” screws (part number 1412-0015) and two lock washers (part
number 1435-0002), attach the assembled side-mount cover to the top of the chassis
as shown (tightening torque 17 lb.-in).

1412-0015
1435-0002

1003-0083

843731A1.CDR

6 GE MULTILIN INSTRUCTION SHEET – CONNECTING THE UR-V ENHANCED PANEL TO A HORIZONTAL UR-SERIES DEVICE
ATTACHING THE MOUNTING BRACKETS AND VERTICAL MOUNT COVER TO THE HORIZONTAL UR-SERIES DEVICE

6. Using two #8-32 × ¼” screws (part number 1412-0015) and two lock washers (part
number 1435-0002), attach the assembled side-mount cover to the bottom of the
chassis as shown (tightening torque 17 lb.-in).

1003-0083

1412-0015
1435-0002

843732A1.CDR

GE MULTILIN INSTRUCTION SHEET – CONNECTING THE UR-V ENHANCED PANEL TO A HORIZONTAL UR-SERIES DEVICE 7
ATTACHING THE HORIZONTAL UR-SERIES DEVICE TO THE CUSTOMER PANEL

Attaching the The third step is to attach the horizontal UR-series device to the customer panel.
horizontal UR-series 1. Using the four #10-32 × ⅜” screws (part number 1410-0006), four #10 zinc washers
device to the (part number 1430-0006), and four nylock zinc nuts (part number 1422-1032), attach
customer panel the horizontal UR-series device to the customer panel starting at the bottom.

1422-1032
Quantity: 4

1430-0006
Quantity: 4 1410-0006
Quantity: 4

843712A1.CDR

8 GE MULTILIN INSTRUCTION SHEET – CONNECTING THE UR-V ENHANCED PANEL TO A HORIZONTAL UR-SERIES DEVICE
ATTACHING THE HORIZONTAL UR-SERIES DEVICE TO THE CUSTOMER PANEL

2. Tighten the screws using a tightening torque of 20 lb.-in, ensuring the UR-series
device is snug to the customer panel.

843714A1.CDR

GE MULTILIN INSTRUCTION SHEET – CONNECTING THE UR-V ENHANCED PANEL TO A HORIZONTAL UR-SERIES DEVICE 9
ELECTRICAL CONNECTIONS

Electrical connections The final step in connecting the side-mounted UR-V enhanced front panel to a horizontal
UR-series device is to complete the electrical connections.
1. Connect one end of the RJ45 cable (part number 0804-0177) to the UR-series device
as shown below.
2. Connect one end of the ground cable (part number 0804-0178) to the UR-series device
as shown below.

0804-0177

0804-0178

843715A1.CDR

3. Connect the other end of the ground cable through the cutout on the panel and
attach to the rear of the UR-V enhanced front panel as shown below.

843716A1.CDR

10 GE MULTILIN INSTRUCTION SHEET – CONNECTING THE UR-V ENHANCED PANEL TO A HORIZONTAL UR-SERIES DEVICE
COMPLETED INSTALLATION

4. Connect the other end of the RJ45 cable to the RJ45 cable on the UR-V front panel
with the RJ45 straight-through coupler (part number 1104-0259) as shown below.

1104-0259

843717A1.CDR

Completed When complete, the UR-V enhanced front panel is connected to a vertically-mounted
installation horizontal UR-series device as shown below.

843718A1.CDR

GE MULTILIN INSTRUCTION SHEET – CONNECTING THE UR-V ENHANCED PANEL TO A HORIZONTAL UR-SERIES DEVICE 11