This document summarizes the design calculation of an isolated footing at Point 18 for a proposed building with the following key details:
1. The footing has a dead load of 42.78 kips and live load of 6.9 kips. An assumed footing size of 3.5 feet by 3.5 feet is used for the initial calculation.
2. Calculations are shown to determine the effective bearing pressure, upward soil pressure, and punching and one-way shear values.
3. The one-way shear value of 14.86 kips is found to be less than the required value of 19.11 kips, indicating the assumed footing size is not correct for this design.
This document summarizes the design calculation of an isolated footing at Point 18 for a proposed building with the following key details:
1. The footing has a dead load of 42.78 kips and live load of 6.9 kips. An assumed footing size of 3.5 feet by 3.5 feet is used for the initial calculation.
2. Calculations are shown to determine the effective bearing pressure, upward soil pressure, and punching and one-way shear values.
3. The one-way shear value of 14.86 kips is found to be less than the required value of 19.11 kips, indicating the assumed footing size is not correct for this design.
This document summarizes the design calculation of an isolated footing at Point 18 for a proposed building with the following key details:
1. The footing has a dead load of 42.78 kips and live load of 6.9 kips. An assumed footing size of 3.5 feet by 3.5 feet is used for the initial calculation.
2. Calculations are shown to determine the effective bearing pressure, upward soil pressure, and punching and one-way shear values.
3. The one-way shear value of 14.86 kips is found to be less than the required value of 19.11 kips, indicating the assumed footing size is not correct for this design.
COMPUTATION OF THE RESULTS OF ISOLATED FOOTINGS FOR
PROPOSED BUILDING
4.1. Design Calculation of Isolated Footing At Point 18 (Assume footing size)
This design is saturated in Shwe Pyi Thar Township, Yangon District. The required data for the proposed building is described in Table 3.1.The foundation has 21 footings. Among footings, point (18) footing has dead load 42.78 kip and live load 6.9 kip. Therefore, design calculation of isolated footing is as follow.
D.L=42.78k, L.L=6.9k
4ʹ
(1) Design information,
fcʹ = 3000 psi fy = 60000 psi column size = 12ʹʹ x 12ʹʹ foundation depth = 4ʹ By soil test result, ɤ = 123.51 lb/ft3 Allowable soil bearing pressure, qu = 1.7 t/ft2 = 3808 psf = 3.808 ksf (2) Design procedure (a) Depth of fill = 4 -1 = 3ʹ weight of fill = 3 x 123.51 = 370.53 psf weight of footing = 12/12 x 150 = 150 psf 520.53 psf 31
Effective bearing pressure, qe = qa – 520.53psf
= 3808 – 520.53 = 3287.5 psf = 3.288 ksf (b) Compute required footing area and choose footing Assume footing size 3.5'x3.5' (3) To find upward soil pressure, footing size = 3.5ʹ x 3.5ʹ Pu qu = A act 1.4 D. L+1.7 L . L = BxB 1.4 x 42.78+ 1.7 x 6.9 = 3.5 x 3.5 = 5.85 ksf (4) (a) Punching shear, Vu = Bearing capacity x (Footing area – Punching area) ( 12+ d )2 2 = 5.85( 3.5 – ) 144 Nominal punching shear length, ∅Vc = ∅ 4 √ fc' bo d d = 0.85 x 4 x√ 3000 x 4(12 + d) x 1000 ∅Vc = Vu d 2 ( 12+ d )2 0.85 x 4 x√ 3000 x 4(12 + d) x = 5.85(3.5 - ) 1000 144 d = 3.8ʹʹ (b) Check one-way shear, L−c Vu = qu x B x ( −d ) 2 12 3.5− = 5.85 x 3.5 x 12 3.8 ( − ) 2 12 = 19.11 k Nominal one-way shear length, ∅ Vc=∅ 2 √ fc ' B d 1 = 0.85 x 2 x √ 3000 x 3.5 x 12 x (-17.4) x 1000 32
= 14.86 k ≯ Vu (NOT OK!)
This design calculation of isolated footing with assume footing size is not right.