3. Depress the temperature select switch (increase) (2) and the temperature select switch
(decrease) (5) on the control panel at the same time. Hold both switches down for at least three
seconds.
4. The diagnosis procedure shall start. If any error is memorized, the smallest error code is
displayed on display (1) . If no problems exist, "E-.-" is displayed.
5. When the temperature select switch (increase) (2) is depressed, error codes are displayed. The
error codes are displayed in ascending order from "E11" to "E51". When the temperature select
switch (decrease) (5) is depressed, error codes are displayed. The error codes are displayed in
descending order from "E51" to "E11".
Note: When only one error code exists, the same display is repeated. A flashing display means
that the error code is continuing from the past. A non-flashing display means that the error code
was found in the past, but the error code is not found now.
6. When the fault diagnosis is running, the control of each function is altered.
◦ All outputs from the control panel except error codes are turned OFF.
7. Clear the error codes. Depress the following two switches on the control panel at the same time:
recirculation switch (3) and "DEF" switch (4) . Hold both switches down for at least three
seconds.
Note: Clear any error codes when the equivalent problems have been repaired. Make sure that
the same error code is not displayed again. When a problem has not yet been repaired, the
equivalent error code should be displayed again.
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisw... 09/02/2011
PDF created with pdfFactory Pro trial version www.pdffactory.com
330D L Excavators B6H00001-UP (MACHINE) POWERED BY C9 Engine(SEBP486... Página 3 de 4
Error Codes
Table 1
Error Codes for the Automatic Temperature Control (ATC)
Code Problem Area Problem
"E11" Sensor for recirculated air Open circuit
"E12" Sensor for recirculated air Short circuit
"E13" Sensor for fresh air Open circuit
"E14" Sensor for fresh air Short circuit
"E15" Water temperature sensor Open circuit
"E16" Water temperature sensor Short circuit
"E21" Sensor at evaporator Open circuit
"E22" Sensor at evaporator Short circuit
"E43" Damper for air outlet Incorrect movement
"E44" Damper for air inlet Incorrect movement
"E51" Refrigerant pressure High/low error
ReferenceRefer to Schematic, "Air Conditioning Electrical System" for the correct electrical
schematic.
1. Turn the battery disconnect switch key and the key start switch to the OFF position.
Note: A separate electrical wire must be used to perform an open circuit test. Any harness wire
can be used.
2. Install a jumper (connecting wire) between the two electrical wires at one end of the harness.
3. Use a multimeter in order to check for continuity across the two electrical wires at the other end
of the harness.
4. Turn the multimeter dial to the 200 ohm range and measure the electrical resistance.
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisw... 09/02/2011
PDF created with pdfFactory Pro trial version www.pdffactory.com
330D L Excavators B6H00001-UP (MACHINE) POWERED BY C9 Engine(SEBP486... Página 4 de 4
Note: If there is continuity between the electrical wires, the multimeter will have a reading of less
than 5 ohms. If there is not continuity, the electrical wire is faulty. The electrical wire should be
replaced with another wire of the same gauge.
1. Turn the battery disconnect switch key and the key start switch to the OFF position.
3. Turn the multimeter dial to the 200 ohm range and measure the electrical resistance.
4. Use one multimeter probe in order to make contact with the connector of the faulty electrical
wire.
5. Use the other probe from the multimeter to check for continuity across all other electrical wires
in the same harness.
6. If there is continuity between any of the electrical wires, the multimeter will have a reading of
less than 5 ohms.
Note: If there is not continuity, the electrical wire is faulty. The electrical wire should be replaced
with another wire of the same gauge.