Professional Documents
Culture Documents
France Air - Plafon Filtrant BVX3
France Air - Plafon Filtrant BVX3
➤ options
•O
ther dimensions or position of the air inlet sleeve possible.
- Special low height version under slab : H = 350 mm.
- Diffusion grilles in stainless steel 304 matt.
- Stainless steel version.
- Wall version for horizontal flow.
• Plenum :
-S
tainless steel sheet (10/10th) with white epoxy paint
RAL 9010.
- Pressure tap (diam. 3 mm) on one of the vertical sides.
- Return of 25 mm at inferior part for fitting of false-ceiling.
-A
ngle bracket supplied with fixing holes (diam. 10 mm every
60 cm) at superior part for fixing of the slab.
- L ateral air inlet made of a rigid sleeve (height 200 mm -
bvx 3
BVX 3 wall for horizontal flow. Ophthalmology office Blondeau, Château d’Olonne (85).
Guide created by France Air 2010 – All rights reserved. www.france-air.com 911
filtration
technical description
➤ Dimensions, reservation and weight
Type Dimensions Overall dimensions Dimensions Amount of Total weight (Nber) Types
BVX 3 reservation (mm) L x l x H (mm) sleeve pieces at (with filters of filters and grilles
L x H x P (mm) delivery and grilles) (kg)
1,5 x 1,5 1 340 x 1 280 1 390 x 1 330 x 450 900 x 200 x 150 1 100 (2 x) 12.6
2x1 2 010 x 1 280 2 060 x 1 025 x 450 900 x 200 x 1 300 1 100 (3 x) 9.6
2 x 1,5 2 010 x 1 280 2 060 x 1 330 x 450 1 550 x 200 x 150 1 180 (3 x) 12.6
2,5 x 1,5 2 560 x 1 340 2 610 x 1 390 x 450 2 100 x 200 x 150 1 210 (4 x) 12.6
2x2 2 010 x 1 950 2 060 x 2 000 x 450 1 550 x 200 x 150 1 240 (6 x) 9.6
3 x 1,5 2 925 x 1 340 2 975 x 1 390 x 450 2 100 x 200 x 150 1 300 (6 x) 9.6
2,5 x 2 2 560 x 2 010 2 610 x 2 060 x 450 2 100 x 200 x 150 2 360 (6 x) 12.6
3x2 2 925 x 2 010 2 975 x 2 060 x 450 2 350 x 200 x 150 2 400 (9 x) 9.6
2,5 x 2,5 2 680 x 2 560 2 730 x 2 610 x 450 2350 x 200 x 150 2 360 (8 x) 12.6
1330
2060
2060
1390 2060
2000
• Type 2,5 x 1,5 • Type 2,5 x 2,5 • Type 3 x 1,5 • Type 2,5 x 2 • Type 3 x 2
1390
1390
2060
2060
2730
2610 2975
2610 2975
2610
selection accessories
Selection of a BVX 3 for an operation room : ➤ FR EFI MPL H14-U15 (p. 898)
3 criterias must be taken into account for the selection
of a filtering ceiling : • Filters very high efficiency.
912 www.france-air.com Guide created by France Air 2010. All rights reserved.