Dryer Heat Exchanger Manual

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Klingenburg GmbH

Boystraße 115
D - 45968 Gladbeck
Telefon 0 20 43/96 36 0
Telefax 0 20 43/7 23 62
E-Mail: klingenburg@klingenburg.de
www.klingenburg.de
Regenerative Systeme
Rekuperative Systeme
Klingenburg GmbH · Boystraße 115 · D-45968 Gladbeck
DEC-Systeme
Befeuchter

Cleaning of Counterflow Plate Heat Exchanger GS

We advise to take a hot water - high pressure cleaning device for cleaning device for cleaning of
counterflow plate heat exchanger.

These units should have following parameters:

Nozzle: Plane jet nozzle


Pressure: up to 20 bar
Amount of water: up to 450 l/h
Temperature of warm water: up to 70°C
Distance to the plate: min. 30 cm
Cleaning direction: 90° offset to the embossed foil from
exhaust air to extract air side.

Cleaning direction: in air direction (from outside air to supply air respect. from exhaust air to extract
air side)

The a.m. data must not exceeded, as otherwise the surface and the plate heat exchangers can be
damaged.

For very strong resisting dirt you can also use detergent (like biological detergent, washing
detergents, etc..). Remark: In this case you need to clean up finally with fresh water.

NOTE: Do not use aluminium cleaner ! These cleaner contain acid and threfore are not usable for
the surface of our plate heat exchanger.

Geschäftsführer: Kai Klingenburg · Amtsgericht: Gelsenkirchen HRB 4214 · Gerichtsstand Gladbeck