(1989) - Goldberg PDF

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

586 IEEE Transactions on Power Delivery,Vol. 4, No.

1, January 1989

A COMPUTER MODEL OF THE SECONDARY ARC IN SINGLE PHASE OPERATION OF TRANSMISSION LINES

by
Saul Goldberg, Member, IEEE William F . Horton, Senior Member, IEEE
California Polytechnic State University
San Luis Obispo, California
Demetrios Tziouvaras, Member, IEEE
Pacific Gas and Electric Company
San Francisco, California

Abatract The particular contribution made by this


paper is the development of a secondary arc
The secondary arc phenomenon associated with computer model using the widely applied
single phase autoreclosure (SPAR) procedures Electromagnetics Transients Program (EMTP)
in transmission lines has been modeled by A. [8J. EMTP is a powerful computer program
T. Johns, eta1 161. Johns’ mathematical and its wide use gives the arc model
model, based on empirical data, represents immediate utility. The paper describes the
the arc conduction characteristics and also mathematical model (Johns), the computer
the arc withstand voltage characteristic. model (EMTP) and simulation results.
This paper describes a computer model Simulation results are compared with the
developed from Johns’ mathematical model. results from another simulation and with
The computer model utilizes the widely used results from field tests.
Electromagnetic Transients Program (EMTP).
Block diagrams of the computer model as well The Hathematical Model
as a listing are provided. Simulation
results utilizing the computer model compare There are two characteristics to be
favorably with a previous simulation and considered in the model of the secondary
field test results. arc. The arc conduction characteristic
applies when the arc is conducting current.
Introduction Conduction occurs when the magnitude of the
voltage across the arc exceeds the arc with-
Single phase autoreclosure (SPAR) procedures stand voltage. The second characteristic,
have been adopted by a number of utilities the arc withstand voltage characteristic,
to clear single phase faults from three applies when the arc is not conducting.
phase high voltage overhead transmission k c Conducstion -act eriatic.
lines [1,2,31. A critical aspect of SPAR
operation is the extinction of the secondary The volt ampere characteristics of the arc
arc since the secondary arc must extinguish model are described in [SI. Over a range of
before successful reclosure can occur. The arc currents from 1 to 55 amps the arc
extinction time depends on a number of cyclogram of Figure 1 applies. The value of
factors including primary arc current, vp is given by:
interphase coupling, system voltage and
atmospheric conditions [4,51. For vp = 15Ip-.‘ vol ts/ cm ,
simulation purposes it is quite useful to
have a computer model of the secondary arc where Ip is the peak value of secondary arc
phenomenon. Such a model allows users to current, assuming zero arc resistance. The
carry out realistic computer studies of model is hysteretic and the equivalent
various SPAR procedures. resistances of the ascending and descending
paths are functions of arc length and thus
This paper describes a computer model of the time varying.
secondary arc which has been developed for
use in system simulation studies. The This model of the conducting arc is somewhat
computer model is based on the mathematical more realistic than the simpler model in
model described by Johns et a1 [ 6 , 7 ] . which the arc voltage gradient has the value
Johns’ mathematical model is largely vp for all values of arc current. However
empirical and was obtained by fitting the simpler version is often used [ I ] .
mathematical equations to experimental data.
It is the most realistic mathematical model For the computer simulation reported here, a
of the secondary arc known to the authors. model between the two versions has been
programmed. This model is shown in Figure
2. On this cyclogram, which is not
hysteretic, the path from the origin to vp
depends on time from initiation of the
88 WM 073-9 A paper recommended and approved secondary arc (RUNTIM). In Figure 2 , the
by the IEEE Transmission and Distribution Committee path labeled (a) is for RUNTIM = 250
of the IEEE Power Engineering Society for presentat- milliseconds and the path labeled (b) is for
ion at the IEEE/PES 1988 Winter Meeting, New York, RUNTIM = 1000 millisecond for a particular
-
New York, January 31 February 5, 1988. Manuscript value of Ip as described below.
submitted August 20, 1987; made available for printing
November 6, 1987.

0885-8977/89/0100-0586$01 .WO1989 IEEE


587

The Computer Model


The EMTP computer model of the secondary arc
is shown in block form in the arc simulation
diagram of Figure 3 . We assume a single
phase fault on Phase A and that the phase is
subsequently isolated at a time designated
in the simulation as ISOTIM. The switch
( 1 3 ) is normally closed and arc current is
conducted to ground through the Arc
Conduction Circuit shown in Figure 4 . A 200
52 resistor is put in series with the fault
0 .15 .38 1.0 2.0 and serves to damp high frequency
MULTIPLES OF Ip oscillations. It should be noted that this
ARC CYCLOGRAM resistance is small compared to line to line
FIGURE 1 capacitive reactance at 60 Hz.
The switch (13) is opened on each fault
current zero. The actual arc voltage (TBlA)
is compared with the computed arc withstand
voltage (VARCW) from Furrent zero forward to
the next current zero. If lTBlAl > VARCW,
the LOGIC CIRCUIT causes the switch ( 1 3 ) to
close. The process is then repeated on the
next current zero. However, if ITBlAl <.
VARCW, the switch (13) remains open and the
0.1 .4 1 .o 2.0 fault clears.
MULTIPLES OF Ip
SIMULATION ARC CYCLOGRAM Detailed descriptions of the functional
FIGURE 2 blocks of Figure 3 are given below.

As.,JA tbAmd- ~ ~ ~ - ~ ~ iec - _ ~ ~ ~ ~ ~ ~ ” ~ ~ ~ ~ $ . ~

The withstand voltage of the arc is given in


FAULT ISOLATION
I71 as: FAULT INITIATION
SMTCH
SWITCH

PHASE A SOURCE
Jvr(tr)J = [ 5 + 1620Te/(2.15+1~) I *
( t r-T e ) h ( t r-Te kV/cm 1 DAMPING
RESISTOR (zoon) -
SWITCHING nME
ISOTIM , ,
Further, the length of the arc is given by:
VARCW
1 for 5. 0.1 second
l(tr)/lo = { 10tr
for
tr

tr > 0.1 second


In these equations:
ARC
vr(tr) = withstand voltage, kV/cm CONDUCTION
CIRCUIT
I

Te = time from initiation of


secondary arc to current zero, seconds
t ISOTIM

ARC SIMULATION DIAGRAM


nc.3
Is = Ip/J2 amps, rms
tr = time from initiation of
secondary arc, secs -Arc .._Conductionarcu-it
-_”

1 for (tr - Te) > 0 A realization of the Arc Conduction Circuit


is shown in Figure 4 . Here the magnitude of
h(tr) = 0 for (tr - Te) < 0 the arc conduction voltage (TBBA) is
essentially clamped at the voltage D1.
l(tr) = length of arc, cm
10 = initial length of arc, cm (75*XIP-.4)*GAPLEN, RUNTIM < 100 ms
D1={
The arc withstand voltage is given by: (75*XIP-.4)*GAPLEN*.01*RUNT1M,
RUNTIM > 100 ms
Varcw(tr) = Ivr(tr) l*l(tr), kV.
Arc extinction occurs when the arc withstand D1 is in volts.
voltage exceeds the actual open circuit arc
voltage.
588

whcrt. T h e ARC ZRO var i a b 1 c is d ii'f e r e n 1. i a L e d t o


p r o d u c e t h e v a r i a b 1 . e LEAD. LEAD h a s a p e a k
x 1. I' = p e a k val.i.re o f s e c o n d a r y a r c val11c. o f a b o u t 5 v0.Lt.s. Four. ..-its a r c
c u r r e n t ( I p assumi riq zcii-o a r c siit)t.rac:tctf from LFXI) to product the v a r i a b l c
r e s i s t a n c e i n amiss R A M W T . which resets a n Accumulator (ti51 i n
t h e Arc W i t h s t a n d V o l t a g e C i r c u i t .
GAPLEN = i n j . t i a l l e n g t h o f a r c i n cm (lo)
AJ-c Wi t l l s t a n d V o l t a g e C i r c u i t
RUNTIM = time f r o m i r r j t i a t i o n o f
s e c o n d a r y arc: i n n i i llisecorrcis T h e A r c W i t h s t a n d VCJLI.~:~. C i r c u i t c o m p u t e s
(t,*103) the. a r c k i t h s t a i i d v o l t a q e e a c h half cyc-1 e ,
following a n arc c u r r e n t z e r o . T h i s is
Note t h a t D Z = - D l . shown i n F i g u r e 6 . N o t e t h a t DELTAT a n d
TIMEX a r e internal EW" variables, the
T h e 5168 Q r e s i s t o r p r o v i d e s t h e p a t h s from siniujation time step and running time
t h e o r i g i n t o v p shown i n F i g u r e 2 . respectively.

The c o n t p u t a t i o n o f t h e a r c w i I hsl a n d v o l t a g e

r* (VARCW) i s g i v e n by:

VARCW

where,
= [5+1.62*R~NTIM/(2.15t~~~~/~~)~~
.Ol*GAPLEN*RUNTIM*RAMP

RAMP = Time From L a s t C u r r e n t Zero I n


Milliseconds

= ( t r - Te)*1O3

I t can be seen that computed v a l u e of


the
VARCW s t a r t s a t z e r o when HUNTIM i s z e r o .

-
0-1 1 VARCk i s l e s s t h a n V a r c ( t
srcorid but e c ~ u a l sV r
t r > 0.1 second.
( i I' 1 ,
VARCW i s
r ) f o r t r < 0.1
given above, for
p a s s e d on t o t h e
L o g i c C i r c u i t a', e x ~ ~ l a t n e tble l o w .

1
ARC CONDUCTION CIRCUIT
FIG. 4
VARCI

.4rc Z e r o C i r c u i t
-----?-I I
As shown i n F i q i r r e 5 . t t i i a r c c u r r e n t (Tk324)
is s c a J e d by t h e f a c t o r ( 1 0 0 / I , , ) t o p r o d u c e
A H C I A , a v a r i a b l c whickj is t h e n t r u n c a t e d .
E a c h t i m e t h e t r u n c a t e d v a r i a b l e A R C l T goes
t h r o u g h h e r o , the I F c i rrii i t ( 60 1 p r o d w c s
a n outj'ut o f t 1 . T h i s o u t p u t (ARCZRO) i s a n OPERATED

i n d i c a t i o n o f a zero o f t h e arc c u r r e n t .
a r e s u l t of t h e s c a l i n g t h i s v a l u e o f arc
As
S W T - 0. ISOTIM(TIMEX
INPUT. ISDTIU>TIMEX
LCPU is accurate t o a b o u t 0 . 0 1 r a d i a n o r 0.6
degrees.
ISDllM nMEX
ARC MTHSTAND MLTAGE URCUIT
FIG 6

L G ~ I CC i r c u i t

The Logic Circuit, shown in Figure 7,


p r o \ l d e s t h e s i g n a l (SWDRV) t o open t h e
s w i t c h ( 1 3 ) on e a c h h a l f c y c l e . In addition
i t m a k e s t h e c o m p a r i s o r i b e t w e e n VARCW arid
the absolutc v a l u e of t h e arc v o l t a g e .
ABS(TB1A). I f

DVARC -= \'ARCW - ABS(TB1A)


TACS TRANSFER
RAMRST
,001s = LEAD - 4 i s n e g a t j v e , SWDRV = + 1 a n d t h e s w i t c h ( 1 3 )
.ooozs + 1 is r e c l o s e d . IS
ARC ZERO CIRCUIT
FIG. 5
DVARC > 0,
t h e n SWDH\: = -1 a n d t h e s w i t c h ( 1 3 ) i s h e l d
open.
589

EMTP simulation of the system shown in


Figure 8 .
In this simulation, fault initiation
DVARC occurred 2 0 milliseconds into the simulation
and fault isolation (ISOTIM) occurred 50
milliseconds into the simulation. DELTAT
was selected to be 0 . 0 5 milliseconds, a
compromise between computation time and
ARC ZRO
accuracy.
The simulation of the system of Figcie 8
LCUC CIRCUIT
utilizes a 4 section PI model of the
FIG. 7 transmission line. A preliminary simuldtion
with a bolted single phase fault yielded a
Application of the Computer Model value for I p of 35 amperes. The simulation
program, including the arc model program, is
The computer model of the secondary arc was listed in Appendix A.
utilized to represent a secondary arc in an
The simulation was executed using a DEC VAX
11/750 computer, requiring approximately 5
FAULT INIPAPON minutes of CPU time for each run. An IBM AT
FAULT IsounoN compatible computer was used as a smart
terminal for these simulation runs utilizing
VTlOO and Tektronix Graphics Terminal
emulation software.

M W V LINE
System simulation results are shown in
ROUND UUN Figures 9 and 10. Extinction time is seen to
MOUNTAIN
be 16.0 cycles. Extinction times are
measured from ISOTIM to the time at which

Y
SECONDARY
the secondary arc current becomes zero.
The wave forms are quite similar to those
reported by Johns and Ritchie in Reference
URCUA M I L E 3 94
z, -
SYSTEM IMPEDANCES AT Y N J N
msin
b- ~ 0 4 . 3 0 ~ 1
171. A figure from [7] is shown as Figure
11 of this paper. Plots of arc current and
arc voltage versus time from Figure 11 may
be compared with those of Figures 9 and 10.
It should be noted that the wave forms of
Figure 11 begin at the initiation of the
secondary arc (ISOTIM).

100

In

-G4
z

W
a
a
U
=I

U
4

-100

J
80,000

2
d>
-
z
W

5g
3
U

F i g u r e 10: Arc Voltage Versus Time i n Seconds


-80,000

Comparison of S i m u l a t i o n R e s u l t s W i t h S t a g e d
Tests [ZJ The a r c current. withstand voltage
(VARCV), as computed in the
I n O c t o b e r 1 9 8 6 , PGandE: s t a g e d a number o f siniulation, increases with time,
secondary arc tests on the Malin-Round s t a r t i n g a t zero when t = 1SOT1?1.
M o u n t a i n # 2 , 500 kV L i n e . The t e s t r e s u l t s w h e r e ISOTlM is 1,hc t i m e at. w h i c h
a r e g i v e n i n R e f e r e n c e 191. A comparison f a u l t, isolation occurs. The
w i t h t h e s i m u l . a t i o n r e s u l t s m u s t b e made n i n t . h c ~ m a t i c a l model. for the arc
with caution s i n c e t h e e f f e c t of primary with>;t,and v o l t a g e has an initial
f a u l t current is not represented i n these value of jvr)*lo. I t h o l d s this
tests. value for 0.1 seconds and then
increases with t i m e . The s i m u l a t i o n
Of t h e 2 0 t e s t s r e p o r t e d i.n 1 9 1 , t e s t s 12-18 a n d m:il,hcmatic:al m o d e l s f o r t,he a r c
are a p p l i c a b l e for comparison since for wi thstiind v o l t a g e c o i n c i d e f o r t >
t h e s e t e s t s s e r i e s c a p a c i t o r s were by p a s s e d ISO'I'IM t 0 . 1 s e c o n d .
and l i n e r e a c t o r s were taken off line.
Osc:illograms f o r t e s t s 13-17 are a c t u a l l y The underJ y i n q r e a s o n f o r t . h e s r d i f f e r e n c e s
shown i n f 9 1 . i s t h a t , EMTP i s a somewhat r i g i d t o o l w h i c h
l a c k s many o f the useful features of a
A comparison of t h e wave f o r m s o f s e c o n d a r y modern p r o g r a m m i n g l a n g u a g e , s u c h as FORTRAN
arc c u r r e n t s between t h e s i m u l a t i o n r e s u l t s 77. H o w e v e r , t h e s i n i u l a t i o n model ajrpc~ars
and test results shows r e a s o n a b l y close to represent the mathematical model
correlation. Of t h e f i v e t e s t s ( 1 3 - 1 7 ) , adequate1.y i n a l l import.ant a s p e c t s .
extinction t i m e s ranged from 5.5 to 17
cycles. The c o m p a r a b l e s i m u l a t i o n v a l u e i s Comparison of siniulut.ion results with
16.0 cycles. published simulation results show close
correlation. I n addition a reasonably close
Discussion correlation is Sound with results from
staged tests.
T h i s p a p e r p r e s e n t s a n EMTP s i m u l a t i o n m o d e l
o f t h e s e c o n d a r y arc: w k t i c;h i s hased on t h e Conclusion
m a t h e m a t i c a l model o f J o h n s e t a l . The m o d e l
d i f f e r s f r o m t h e m a t h e m a t i c a l model i n t . w o S i m u l . a t i o r i o f SI-TAtt proc:edures arc made morr
d e t a i Is: re a 1 i s t i c if the secondary arc
c h a r a c t e r i s t i c s a r e i n c l u d e d as part o f t h e
111 The f o r w a r d c o n d u c t i o n c h a r a c t e r i s t i c simulation. This paiwr dcssc-1-i b e s a
of the s i m u l a t i o n model is non- sjmulation model of the secondary arc
h y s t e r e t i c , as d i s c u s s e d e a r l - i e r . u t . i l i . z i n g EM'L'P, ii widely used computer
p r o g r a m f o r power s y s t e m s a n a l y s i s . Through
t h i s paper., t. he modc.1 b e c o m e s a v a j 1 a b I e to A
I.arge segment of t h e i n d u s t r s - . .
t I t

-100-
r
U
8
0
-1%-
U

- 0-1 . 0.2 - 0 - 3
TIME I N SECONDS TIME I N SECOND'S

FIGURE 11: SIMULATION OF FAULT ON SHORT UNCOMPENSATED L I N E


T H I S FIGURE IS REPRODUCED FROM REFERENCE C71

Appendix A
LISTING OF EMTP SPAR MODEL
c ..........................................................................
C * MODEL E IS THE NOMINAL MODEL *
c ..........................................................................
C * THIS MODEL DEVELOPED BY POWER SYSTEMS CONSULTANTS (805)544-2154 *
C * 3220 FLORA STREET SAN LUIS OBISPO, CA 93401 *
C
C
** ON PG&E CONTRACT 210-5-295-85
AND MODEL IS BASED ON JOHNS IEEE PAPER RUN 2/19/87
**
C * USES EMTP TACS CAPABILITY MODEL E *
*
C
c .*. . .SIMULATION
. . . . . . . . . . .BASED
. . . . . .ON
. . . FOUR
. . . . . .SECTION
. . . . . . . .PI
. . .MODEL
.................................
BEGIN NEW DATA CASE
C *****
FIRST MISCELLANEOUS DATA CARD
C **DELTAT** **TMAX** **XOPT** COPT** **
0.5E-4 400.E-3 6 0 . 0 0.0
C *****
SECOND MISCELLANEOUS DATA CARD (PRINT EVERY Kth POINT)
C 1 IN COLUMN 64 GENERATES AUTOMATIC VAX PLOT FILE
C **IOUT** **IPLOT**
99 01 1
C *****
TACS SECTION OF SIMULATION
TACS HYBRID
C
C *****
EMTP VOLTAGES AND CURRENTS BROUGHT INTO TACS
C *****
TYPE 90 IS VOLTAGE AT TBlA (VOLTAGE ACROSS THE ARC)
9OTBlA
C *****
TYPE 91 IS CURRENT THRU BREAKER TBlA TO TB2A (FAULT CURRENT)
91TB2A
C
C ....................... INPUT CONSTANTS FOR TACS ...........................
G
C ** FORTRAN STATEMENT TO DEFINE XIP ........................
C ** XIP = PEAK VALUE OF FAULT CURRENT ASSUMING BOLTED.FAULT - IN AMPS *******
99XIP = 35.0
C ***** FORTRAN STATEMENT TO DEFINE GAPLEN **************
C ** GAPLEN = INITIAL ARC LENGTH - IN CENTIMETERS
99GAPLEN = 400.
C ***** FORTRAN STATEMENT TO DEFINE ISOTIM
C ** ISOTIM = TIME OF ISOLATION OF FAULTED PHASE - IN SECONDS *****
99ISOTIM = .05
C
c .........................................................................
C
C ***** FORTRAN STATEMENT TO SCALE ARC1
592

APPENDlX A CONTINUED
99ARCIA = (lOO.O/XIP)*TBZA
C ***** FORTRAN STATEMENT TO TRUNCATE ARC1 (ARCT = FAULT CURRENT)
Y9ARCIT = TRUNC(ARCIA1
C ***** FORTRAN STATEMENT TO GENERATE INPUT SIGNAL DELTAT IN MILLISECS
99INPUT = DELTAT*1000
C *****
TACS TRANSFER FUNCTION DEVICE TO GENERATE PULSE SIGNAL (DIFFERENTIATOR)
C
0 1LEAD +ARCZRO .001
0 .o 1 .0
1 .o .0002
C
C ***** TYPE 60 INPUT IF DEVICE
C
99ARCZR060tZERO +PLUS1 +ZERO 0.0 ARCIT
C
C *****FORTRAN STATEMENT TO GENERATE FLAG SIGNAL FOR SWITCH DRIVE
C
99DRVFL = ARCZRO - DVARQ
C
C ***** TYPE 60 IF DEVTCE TO GENERATE SWITCH DRIVER SIGNAL
C
98SWDRV 6O+PLUS1 +PLUS1 +MINUS1 0.0 DRVFL
C
C *****RELAY OPERATED SWITCH TYPE 51
C **
SWOUT IS TIME FROM PHASE ISOLATION - IN MILLISECONDS
C
99SWOUT 51tINPUT 1.0 0.0 0.0 ISOTIMTIMEX
C
C ***** TYPE 65 ACCUMULATOR AND COUNTER
C ***** RUNTIM IS TIME FROM INITIATION OF SECONDARY ARC CURRENT IN MILLISECONDS
98RUNTIMG5+SWOUT
C
C *****
FORTRAN STATEMENT TO GENERATE RESET SIGNAL FOR RAMP
C
99RAMRST = +LEAD - 4 . 0
C ***** TYPE 65 ACCUMULATOR AND COUNTER
C *****
RAMP 1s TIME FROM LAST CURRENT ZERO IN MILLlSECONDS
98RAMP 65+INPUT 0.0 RAMRST
C
C ***** TYPE 60 IF DEVICE TO GENERATE INTERMEDIATE SlGNAL DVARQ
C
99DVARQ 6OtTWOV +ZERO +ZERO 0.0 DVARC
c
C ***** FORTRAN STATEMENT TO GENERATE ARC WITHSTAND VOLTAGE
C
98VARCW = (5.0 + 1.62*RUNTlM/(Z.15+ XIP/SQRT(2) ))*.Ol*GAPLEN*RUNTIM*RAMP
C
C *****
FORTRAN STATEMENTS TO CALCULATE VARlOUS CONSTANTS AND CONTROL SIGNALS
99DVARC = -ABS(TBlA) t VARCW
99TWOV = P.O*PLUSl
99MINUS2 = 2.0*MINUS1
C
c ............................................................................
C
C OUTPUT VARIOUS TACS SIGNALS A "1" IN COL 2 OU'PPUTS ALL TACS SIGNALS
C
1
C
c ............................................................................
C
BLANK CARD ENDING TACS OUTPUT REQUESTS
593

APPENDIX A CONTINUED
C ***** EMTP SIMULATION FOLLOWS
C **********BRANCH DATA IN EMTP SECTION OF SIMULATION **********
C
C ****FOLLOWING IS FOUR PI SECTION MODEL OF THE TRANSMISSION LlNE ****
C ****SECTION 1***
1RM A BUSl A 2.421 25.145.372
2RM B BUSl B 1.857 10.269-.05172.421 25.145.372
3RM C BUSl C 1.857 10.269-.05171.857 10.269-.05172.421 25.145.372
C ***SECTION 2***
lBUSl ABUSZ ARM A BUSl A
2BUSl BBUS2 B
3BUS1 CBUS2 C
C ***SECTION 3***
lBUS2 ABUS3 ARM A BUSl A
2BUS2 BBUS3 B
3BUS2 CBUSJ C
C ***SECTION 4***
1BUS3 AMAL A RM A BUSl A
2BUS3 BMAL B
3BUS3 CMAL C
MAL A BKR 3A .05
BKR 4AGENlA 0.0 48.04 0.0
MAL B GENlB 0.0 48.04 0.0
MAL C GENlC 0.0 48.04 0.0
RM A BKR 1A .05
BKR 2ATBlA 200 6

B1A B2A .05


TB2A B1A 1.0
TB2A 5168.
C
c ............................................................................
C
BLANK CARD TERMINATING BRANCH CARDS
C *****
SWITCH CARDS
C ***** TIME VARYING (DlODE SWITCH) NONLINEAR RESISTOR TO CLAMP ARC VOLTAGE
llBlA Rl
llD2 B2A
C *****
END OF NONLINEAR RESISTOR
C *********************ISOTIM***
BKR 3ABKR 4A -1.0 .050
c ..............................
BKR lABKR 2A .02 .500
C *****TACS OPERATED SWITCH
13TBlA TBZA SWDRV 11
BLANK CARD TERMINATING SWITCH CARDS
C *****SOIJRCE CARDS
C *****THREE PHASE GENERATION LOCATED AT MALIN
14GENlA 428661. 60.0 0.0 0. -1.
14GENlB 428661. 60.0 -120. 0. -1.
14GENlC 426661. 60. -240. 0. -1.
C ***** BACK TO BACK DIODES SOURCE VOLTAGES FOR NONLINEAR RESISTOR SIMULATION
C ***** D10 =(75*XIPA-.4)*GAPLEN IN VOLTS AT ISOTIM
C ***** D2 = -D1 IN VOLTS
C **********NUMl****h*****
C ******* D10 ************* To ******
D11 T1*** TSTART **TSTOP ***
c **
13D1 t7235. 0. t7235. 15 * 05 e15
13D1 +1235. 0. t72350. .90 .15 1.05
13D2 -7235. 0. -7235. * 15 ,05 615
13D2 -7235. 0. -72350. .90 .15 1.05
C ***** END OF SOURCE DEFINITIONS
BLANK CARD TERMINATING SOURCE CARDS
C *****
NODE VOLTAGE OUTPUT
TBlA D1
BLANK CARD TERMINATING NODE VOLTAGE OUTPUT
BLANK CARD TERMINATING THE CASE
594

References Saul Gpldberg (M) was born in New York and


received the B.S.E.E. degree from Fairleigh
I11 Single-Pole Switching f o r Stability and Dickinson University, and the M.E. and Ph.D.
Reliability, Panel Discussion Report, degrees from the University of Florida. He
IEEE Transactions on Power Systems VOL joined the faculty of the Electronic and
PWRS-1, No. 2 , May 1986. Electrical Engineering Department,
California Polytechnic State University in
r21 Hasibar, Legate, Brunke and Peterson, 1970. He currently holds the rank of
The Application of High-speed Grounding Professor of Electronic and Electrical
Switches For Single-Pole Reclosing on
500 kV Power Systems, IEEE Transactions
Engineering .
He is a principal of Power
Systems Consultants, a consulting company.
on Power Apparatus and Systems VOL PAS-
100, No. 2, April 1981. W$Jliam . F . Korton ( S M ) was born in North
Carolina and received the B.S. and M.S.
Haun, R. K., 13 Years Experience with degrees from the California Institute of
Single-phase Reclosing at 345 kV, IEEE Technology and the Ph.D. degree from UCLA.
Transactions on Power Apparatus and He joined the faculty of the Electronic and
Systems VOI, PAS-97, No. 2 , March/April E1ect, r ica1 Engineering Department,
1978. California Polytechnic State University in
1968. He currently holds the rank of
Kapperman, Sweezy, Koschik and Professor of Electronic and Electrical
Mustaphj, Staged Fault Tests With Engineering. He is a principal of Power
Single-phase Reclosing on the Winnipeg- Systems Consultants, a consulting company.
Twin Cities 500 kV Interconnection,
IEEE Transactions on Power Apparatus ( M 1 was born in Greece
J)g.?e.t;rjosJkiouvaras
and Systems VOL PAS-101, No. 3, March and immigrated to the U.S.A. in 1977. He
1982. received the B.S.E.E. and M.S.E.E. degrees
from the University of New Mexico and Santa
Shperling, Fakheri, Shin and Ware, Clara University, respectively. He joined
Analysis of Single-phase Switching Pacific Gas and Electric Company in 1980 and
Field Tests on the AEP 765 kV System, is currently a Senior Protection Engineer.
IEEE Transactions on Power Apparatus He is responsible for the protection of
and Systems, VOL PAS-100, No. 4 , April generators, transformers, HV and EHV
1981. transmission lines.
Johns, A. T. and Al-Rawi, A. M.
Developments in the Simulation of long-
distance single-pole-swi tched EHV
Systems, IEE Proceedings Vol 131, Part
C , No 2 , March 1984.
Discussion
Johns, A. T. and Ritchie, W. M.,
Applications of an Improved Technique B. R. Shperling (New York Power Authority, New York, NY): A
for Assessing the Performance of h n d a r y arc model based on experimental results by T. E.Browne and A.
Single-Pole Reclosing Schemes, IEEE P. Strom, and further modificationsby A. T. Johns and W.M. Ritchie, was
Transactions on Power Apparatus and implemented in the electromagnetic transient program (EMTP) by the
Systems, Vol PAS-103, No 12, December authors. To validate. the model, the authors calculatedsecondary arc current
1984. and voltage in single-phase switching operations for a line without shunt
compensation and compared their results with the calculationspublished by
181 EMTP Rule Book, Bonneville Power A. T. Johns and W.M. Ritchie. It should be noted that there was no reason
Administration, Portland, Oregon, to expect any noticeable difference between these two sets of calculations
Revised June 1984. since both of them utilized the same data base, including the arc model. The
real validation of the arc model requires adirect unnparison with field
191 PGandE Report, Secondary Arc Tests on measurements. Therefore, the authors should compare their calculations
the Ma.Zin-Round Mountain #2, 500 kV with the secondary arc current and voltage oscillograms from the single-
Line, October 5 and 6, 1986, Test phase switching tests performed by the PG&E Company on a 5WkV line,
Report by Demetrios A. Tziouvaras. and referred to in the paper. A comparison presented in the paper between
595
the extinction times for PG&E tests (5.5 to 17 cycles) with the calculations System-Extinction Time for Large Secondary Arc Currents,” ZEEE
(16 cycles) cannot be considered convincing because of the relatively small Trans., PAS-102, No. 8, 1983, pp. 2775-2783.
secondary arc currents and large statistical deviation of the field test arc
Manuscript received February 24, 1988.
extinction times. Also, it would be useful to test the validity of the
secondary arc model for secondary arc currents greater than 50 A which
result in much longer extinction times. Finally, it i s quite important to
compare the arc model and the arc gap voltage withstand characteristics S. Goldberg, W. F. Horton, and D. Tziouvnms: We agree with Mr.
used by the authors, with the arc and gap characteristics measured during Shperling that there is no reason to expect any noticeable difference
staged fault tests on 765-kV transmission lines. These parameters, between our results and those published by A. T. Johns and W. M. Ritchie.
summarized in [l], include a full spectrum of arc characteristics, namely, In fact our objective was to develop an Electtomagnetic Transients Program
volt-ampere characteristic as a function of time, dynamic arc resistance, (EMTP) model based on the Johns model of the secondary arc.
secondary arc energy, as well as the arc gap withstand voltage characteristic Our next objective is to utilize the EMTP secondary arc model in
after the secondary arc extinction. conjunction with PGandE’s simulation of a 500-kV transmission line. The
results of this study can then be compand with those from staged tests
performed on this line. We expect to publish our results in a later paper.
We thank Mr. Shperliig for his comments and his suggestions with
Reference regard to the Fakheri paper.
[l] A. J. Fakheri, et al., “Single Phase Switching Tests on the AEP 765 kV Manuscript received April 6, 1988.

You might also like