(1994) - Kizilcay - Numerical Fault Arc Simulation Based On PDF

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

ElEP

Numerical Fault Arc Simulation


Based on Power Arc Tests
M. Kizilcay, K.-H. Koch

Abstract
More than 200 power arc tests were carried out with original arrangements of overhead line insulators and
arcingfittings for 20 kC: 110 kV and 220 kV With an adequately modelled network, short-circuit currents in
the range of 2 kA to 12.5 kA can be realized. Analysis of the measurements shows that a typical arc voltage
rime function can be attributed to each insulator type and arrangement. Using the measured variables, which
were digitally recorded and stored on optical media, an existing numerical arc model has been enhanced, which
can be applied in an electromagnetic transients program to reproduce the dynamic and random behaviour of
power arcs for any insulator arrangement, current and system voltage.

1 Introduction arrangements of insulators for overhead lines with arc-


ing fittings for 20-kV, 1 10-kV and 220-kV lines. In these
In the case of short-circuits occurring on lines with- tests the input signals relevant to the distance protection,
in medium- and high-voltage networks the distance pro- the line voltage and the line current, and in addition the
tection has to locate precisely the fault point for a selec- arc voltage were measured (voltages by fast capacitive
tive interruption of the faulty line. The exact distance of dividers, current by shunt or Rogowski coil), and they
the fault point is measured by evaluating the impedance were digitized by a transient recorder of high resolution
resulting from line voltage and line current at the begin- ( 12 bit) and high sampling rate (6 ms).
ning of the h e . In most cases, however, short circuits in As the main task of this investigation, all the digi-
a network are power fault arcs so that an impedance eval- tized variables were stored on magneto-optical discs
uation is disturbed by the arc voltage arising at the fault and are thus available for developing or testing dis-
point. The fault arc has not only a non-linear current/ tance protection algorithms. In addition, using the re-
voltage characteristic but also is its length time-varying corded arc voltages and currents of various configura-
due to forces acting on it. Electrodynamical force, ther- tions of insulators tested, numerical fault arc models
mal buoyancy and wind cause the arc to elongate can be developed. With these models, transient input
between its roots or to move along the line conductor signals required for the distance protection can be cal-
with one of its rooks. Abrupt changes in the arc voltage culated numerically for any configuration of the
are caused by a breakdown between arc sections. electric power system. Furthermore, using these calcu-
The arc voltage also depends on how the insulators lated signals the distance protection algorithms can be
for overhead lines and the arcing fittings are arranged. It developed or tested.
also depends on how much space is disposable, i. e.
whether the space is unlimited or limited by insulating
material as is in the case of cables. If the space is unlim- 3 Test Arrangements and Test Circuits
ited, the arc voltage is definitely higher than within a
cable. Therefore, in this investigation only tests with With the 20-kV arrangement 102 power arc tests
configurations of insulators for overhead lines and arc- were performed. Two configurationsof the insulator with
ing finings were performed. the arcing horns (one solid-core insulator, horn distance
In electric power supply networks the use of digital 0.17 m) were tested, namely the suspension insulator
protection relays is growing. By means of microproces- (vertical arrangement) and the tension insulator (nearly
sors and distinct algorithms, these relays evaluate volt- horizontal arrangement). Simulated was a overhead line
age and current vectors from the measured input signals of 95/15 m2ACSR with three different lengths corre-
and suppress effectively disturbing external effects, sponding to the prospective short-circuit currents (rms
such as the superimposed arc voltage. values) off, = 2.0 kA, 3.2 kA and 5.5 kA.
With the 110-kV arrangement 115 power arc tests
were performed in the vertical and the horizontal posi-
2 Power Arc Tests tion of the insulator (one long rod insulator, ring distance
1 .O m). Simulated were single circuit lines 120/20 mm2
For testing the above-mentioned protection algo- and 240/40 mm' ACSR with four lengths corresponding
rithms power arc tests were performed in a high-power to the prospective short-circuit currents (rms values) of
test laboratory. These tests were performed on original I , = 5.0 kA to 12.5 kA in 2.5 kA steps. Also double cir-

ETEP Vol. -1. No. 3, May/June 199.1 I77


ETEP

P
FT 1059.MH

Fig. 2. Test circuit for power arc tests with insulators for
overhead lines
R,+j X, supply impedance BS breaking switch
R,, + jX, series line impedance MS making switch
Fig. 1. Power arc test with the 220-kV arrangement in ten- ce line-to-earth capacitance
sion position ( I, = 7.5 kA): double exposure

Although the model reproduces the short-circuit


cuit lines 120120 mm' ACSR with different fault points current and the arc voltage quite realistically, the line
in one circuit were simulated. voltage of the distance protection can be only approxi-
With the 220-kV arrangement 16 power arc tests mately reproduced. In this case the line voltage can be
were performed only in the horizontal position of the in- calculated by means of a transient program with an im-
sulator (two long-rod insulators, ring distance 1.0 m plemented arc model as shown in the second part of this
each, total distance 2.5 m). Simulated was the same paper.
240/40 line with the same short-circuit currents as in the
110-kV tests. Fig. 1 shows a power arc test with the
220-kV arrangement and I , = 7.5 kA.
The test circuit shown in Fig. 2 comprises all essen- 4 Arc Voltage During Arcing Time
tial components to reproduce the distance protection
input signals and the arc voltage as realistically as re- The evaluation of the arc voltage peak in each half-
quired. With the 20-kV and the 1 10-kV test circuits dou- period shows the movement of the arc during the arc-
ble earth faults were simulated, with the 220-kV test cir- ing time of 290 ms. Tab. 1shows the measured arc volt-
cuit single-phase short circuits were simulated. The sup- ages at arc initiation and the highest voltages that oc-
ply circuits were represented with their short-circuit curred during the arcing time for all arrangements test-
power and their capacitive earth fault current. By these ed. Oscillograms of some power arc tests are shown in
means the relatively slow transients, induced by a short chapter 6.
circuit, were realized. The overhead lines were repre-
sented only with their lead and return series impedance
of the faulty phase. The relatively fast transients deriv- 4.1 The 20-kV Arrangement
ing from the line were not realized, but they are not rel-
evanfto the digital distance protection with its relative- At arc initiation, i. e. immediately after melting and
ly low sampling frequencies of 2 kHz for instance. evaporation of the fusible wire, the arc voltage starts
The tests with the 20-kV arrangements were per- with values of 0.5 kV ...0.75 kV and increases in the
formed with full supply voltage, the network was repre- first instance to values near 2 kV. In tests with the low
sented with scale 1 : 1. In view of the required high power, short-circuit current (2.0 kA) the arc voltage generally
the tests with the 110-kV and 220-kV arrangement could maintains this value. The higher currents (3.2 kA and es-
not be performed with full supply voltage. The suppiy pecially 5.5 kA)cause the arc to elongate due to the high-
voltage can be reduced as long as the short-circuit cur- er electrodynamical force and the thermal buoyancy.
rent maintains its sinusoiw wave-
form, i. e. is not influenced by the arc
voltage. In the case of the intended Test arrangement
longest horn distance of 2.5 m and
20 kV llOkV 220 kV
the highest short-circuit current of Insulator
12.5 kA,the required sinusoidal cur- position Arc Maximum Arc Maximum Arc Maximum
rent can be obtained with 20-kV sup- initiation initiation initiation
in kV in kV in kV in kV in kV in kV
ply voltage. Network elements, re-
actances. resistances and capaci- Suspension 6.0 9.5 no tests
tances must be converted with the re- insulator
0.5 ...0.75 0.8... 1.4
' 2.3 ...3.3
specti.ve scale: for the double earth Tension
2.0 6.0 9.0
insulator
fault at I LO kV. the scale is 20: I LO
= 1 :5.5, for the single-phase short- Tab. 1. Arc voltage of the three investigated test arrangements immediately after arc
circuit at 220 kV, the scale is initiation and highest measured value during the arcing time of 290 ms for the suspen-
20: 2201t3 = I :6.35. sion and the tension insulator

I78 ETEP Vol.4, No.3,MayNune 1994


E TEP
8 For the three tested ar-
kV rangements of insulators
7 in the tension position and
for a short-circuit current
6 of 5.5 kA,Fig. 3 shows for
each case the maximum
5 arc voltage of each half-
A
period during the arcing
I
14
time of 290 ms. For each
u, arrangement, this figure
indicates clearly the char-
3 acteristic voltage range at
arc initiation. Also, during
2 the entire arcing time the
arc voltage remains in a
1 range which is character-
istic for each arrange-
0
ET IOSY.03H
I
50
1
100
-I50
rare
1
200 250 rns

Fig. 3. Maximum arc voltage of each half-period during the arcing time; insulator in the
ment, although temporary
300 overlaps of adjacent rang-
es are possible.
Fig. 4 shows the max-
tension position and I, = 5.5 kA imum voltage ofeach half-
I five tests with the 20-kV arrangement period for the 20-kV ar-
2 six tests with the 110-kV arrangement rangement (1, = 5 kA) and
3 three tests with the 220-kV arrangement for the 110-kV arrange-
ment ( I , = 12 kA), both in
the suspensionposition. In
Therefore the arc voltage time function depends in prin- both arrangements the arc voltage at arc initiation is in the
ciple on the position of the insulators: same range as in the tension position. In the further course
of arcing time, in eight out of ten tests with the 20-kV ar-
- In the srispensionposirion of the insulator. the upper rangement, and in all seven tests with the 1 10-kV arrange-
arcing horn is directed downwards to the line con- ment, the arc voltages rise steadily and, for both arrange-
ductor. Therefore the arc can move with its lower ments, have the same voltage values in the time interval
root along the line conductor, the arc voltagecan rise from about I 0 0 ms to 250 ms. Coincidentally,in this time
up to values of 6 kV, but if the arc root jumps back interval abrupt voltage breakdowns occur on the arcs with
to the horn, the arc voltage diminishes to values the 20-kV arrangement, so that at the end of arcing time
below 2 kV. in all ten tests the arc voltage has again values below 2 kV.
- In contrast to the suspension position, in the rension With the 110-kV arrangement the arc voltage also shows
position the insulator is rotated by 90". Therefore a breakdowns but they are less severe.
movement of the corresponding arc root along the line
conductor is impossible. Consequently the arc bums
steadily between the arcing horns, the arc voltage re- 5 Numerical Arc Simulation
mains at values below 2 kV even at higher currents.
The goal of developing a fault arc model is to repro-
4.2 The 110-kV Arrangement duce the dynamic interaction between the arc and the
power system during a short-circuit through air with an
At arc initiation the arc voltage starts with values of acceptable accuracy. Once a general arc model is estab-
0.8 kV ...I .4 kV. During the arcing time, in the suspen- lished and its parameters are determined for various in-
sion position the arc voltage rises to values up to 9.5 kV, sulator arrangements, digital simulation of transients
especially at the higher currents (10.0 kA and 12.5 kA). can substitute for the demanding power arc tests. The
Because of the considerably large horn distance in signals produced numerically can be used to test and im-
comparison to the 20-kV arrangement, the arc elongates prove distance protection algorithms implementedin the
also in the tension position. Maximum values up to 6 kV digital protective relays for desired configurations of
were measured. power networks.

4.3 The 220-kV Arrangement 5.1 Dynamic Arc Model

With the 220-kV arrangement only tests in the ten- Based on the prior work [ 5 ] of the same author, the
sion position were canied out. At arc initiation the arc dynamic fault arc model has been improved to take the
voltage starts with values of 2.3 kV ...3.4 kV. Because random behaviour of the arc into consideration. The arc
of the large horn distance in comparison to the I 10-kV parameters are obtained automatically by numerical
arrangement, the arc voltage rises to values up to 9 kV analysis of the time functions of arc current and arc
during the arcing time. voltage.

ETEP Vol. 4, No. 3, MayIJune 1994 17Y


ETEP
10 ,i instantaneous arc
current,
kV
I, time-varying arc
8 length.
The stationary arc
7 conductance follows as:
6

urn
t* (3)

4 The current-depen-
dent portion of the sta-
3 tionary arc voltage can be
attributed physically to
2 the partial time-varying
arc elongation in each
I
half-period because of the
0 I I magnetic force due to the
50 100 I50 200 250 ms 300 short-circuit current. It in-
!
3 I(HY.04H I,- fluences the arc behavi-
Fig. 4. Maximum arc voltage of each half-period during the arcing time; insulator in the our significantly for long
suspension position arcs ( 1 10-kV and 220-kV
I ten tests with the 20-kV arrangement and I , = 5.5 kA insulator arrangements)
2 seven tests with the I 10-kV arrangement and I , = 12.5 kA as will be shown later.

As explained in [5], the dynamic behaviour of the 5.2 Determination of Arc Parameters
fault arc through air is described by the power balance
relation between the electric input power and the heat The basic arc parameters h,ro and 7are determined
dissipation to the surrounding air. Based on the theory of by means of computer programs automatically using the
black box models of the switching arc [6],it is assumed digitally recorded time functions of arc current and arc
that the arc channel is at a constant temperature, which voltage. The instantaneous arc conductance is cornput-
is independent of the arc current. An increase of the en- ed additionally from the arc current and arc voltage using
ergy of the arc column causes an increase of the cross- the relation
section of the arc. Whereas the stationary electric field
strength is supposed to be constant, the stationary arc
(4)
voltage varies with the continuously changing arc
length. These assumptions allow to describe the electric
arc by a first order differential equation, where the arc based on the assumption that the arc has purely resistive
conductance is expressed as a function of the heat con- characteristics.
tent of the arc column. The arc equation of Hochruiner A numerical method that involves the integration of
[7]is used to describe the dynamic behaviour of a fault the measured time functions has to be preferred to deter-
arc through air: mine the arc parameters UO, ro and 7,since the arc shows
rather random behaviour depending on the surrounding
conditions, such as wind velocity, buoyancy, vertical or
horizontal position of insulators, etc.
where It is assumed that the arc parameters are constant
during a half-period of arc current and voltage. First
g instantaneous arc conductance, the unknown parameters uo and ro are determined by
G stationary arc conductance, solving the following two linear eqs. ( 5 ) and (6),
7 arc time constant. which are derived from eq. (1) by integration with
Deviating from the switching arc black box models, the limits as indicated in Fig. 5 for the arc conduc-
the stationary arc voltage is assumed to be not constant tance:
for fault arcs burning in air freely, but it depends on the 1.

arc length and partly on the short-circuit current flowing


through the arc. It is expressed as follows (5)

u,t = (ub + r(li,l )I, (2)


where I*

u,, stationary arc voltage,


u,', characteristic arc voltage per arc length,
4, characteristic arc resistance per arc length,

I xo ETEP Vol. 4, No. 3, Mny/June 1994


ETEP
A a) 1.4
g l
kV
1 .o
0.8
4 1
0.6
0.4
0.2
0
b) 1.4
t - kV
I .o
Fig. 5. Integration limits in a half-period of the arc conduc- 0.8
tance 4 1
0.6
0.4
Eqs. ( 5 ) and (6)are approximate in the sense that the 0.2
integral of Glr within the stated limits is assumed to be I I

constant.
The arc time constant ris calculated with the known
4and ro through integration in the time intervals either
1
from t l to t3 or from t3 to r5
‘3 ‘I
Gdt - gdt

The trapezoidal rule of integration is used to com-


pute the integrals ineqs. ( 5 ) to (7).This method is repeat-
ed successively fora sequence of half-periods in the time
interval selected, where no significant elongation of the
arc can be observed visually from the time function of d ) 3.0 I I
I
the arc voltage. This way the basic arc parameters can be 1
kV
obtained, which are representative for each insulator ar-
rangement of voltage levels 20 kV, 110 kV and 220 kV. ,2.0
As given in Fig. 6 and 7 for all insulator m g e - I
I .5
ments tested, the stationary arc characteristics (us(ver- %I

sus),i and arc time constant robtained by evaluation 1.o


of the measurements scatter in a wide range (shaded
area in Fig. 6)depending on the time-varying, random
behaviour of the arc. The physically non-realistic val-
ues of arc parameters due to the high distortion of wave-
forms of arc voltages as a result of rush elongation and e ) 5.0
kV
partial breakdown of the arc were eliminated. In Fig. 6
4.0
the intercept on the y-axis gives uo and rorepresents the 3.5
slope of the lines. The lines drawn in Fig. 6 indicate the
mean regression curves belonging to the arc tests car-
1 3.0
2.5
ried out for various prospective short-circuit currents us
2.0
stated in chapter 3. 1.5
The characteristic arc resistance rocannot be deter- 1.o
mined reliably from the measurements of the 20-kV arc
0.5
tests, because of the relatively small value of the resis-
tance, which is drowned by the random behaviour of
the arc. For this reason, the 20-kV arc measurements
were evaluated using a simplified formula with the as-
ET 11)59.(bH
0 2 4 6 8
‘arc

Fig. 6. Stationary arc characteristics


- 1
10
I
12 14 16kA18

sumption of ro = 0. Fig. 6a and 6b show therefore rang- a) 20-kV insulator arrangement in suspension position
es of a constant stationary arc voltage for the 20-kV arc b) 20-kV insulator arrangement in tension position
tests. c ) I IO-kV insulator arrangement in suspension position
The range of the variation of the arc time constant in d) 1 10-kV insulator arrangement in tension position
Fig. 7 is indicated by error bars, where the markers point e ) 220-kV insulator arrangement in suspension position

ETEP Vol. 4, No. 3. May/June 1994 181


ETEP
a) 0.9 { A suspension position
eters uo. to,sand the arc length 1 are represented using
rns MODELS [9], which is a general-purpose simulation
0.7 language interfaced to the ATP-EMTP. The dynamic
0.6 interaction between the electric circuit and MODELS
A 0.5
for the simulation of a fault arc as a time-varying re-
I 0.4
sistance is very similar to what has been sufficiently
r 0.3
0.2 described in [6] and [9].
0. I The arc eq. ( 1) including the expressions for tiQ and

b) 1.4
0
1.5 2.0 2.5 3.0 3.5
1, -
4.0 4.5 5.0 kA 6.0
G given in eqs. (2) and (3) is solved at each time step
using the library function Laplace of MODELS [9]
through the equation:

rns
I .o
A
0.8
where sdoes not need to be a constant coefficient.
r 0.6 The random behaviour of the arc length, which influ-
0.4 ences the stationary arc voltage us[according to eq. (2), is
0.2 realized in MODELS through a sophisticated algorithm,

-
01 I I I which was developed by analysingthe arc measurements.
2.5 5.0 7.5 10.0 12.5 kA 15.0 The length variation of the arc simulatedusing MODELS
ET 1059 07H 1, in the first numerical example is given in section 6.1.
Fig. 7. Arc time constant obtained from arc tests with differ- The variation of the arc parameters tio, ro and 7dur-
ent short-circuit currents ing arcing time within the range given in Fig. 6 and 7 is
a) 20-kV insulator m n g e m e n t considered by a random signal, which is filtered using a
b) 1 10-kV and 220-kV insulator arrangement third-order, low-pass Butterworth filter with the comer
frequency of 100 Hz in order to create slowly varying arc
parameters.
to the mean values. Whereas the 20-kV arcs possess rel-
atively small time constants, which is an indication of a
briskarc behaviour,the timeconstants of the 110-kV and
220-kV arcs vary in the same range. 6 Comparison of Test and Simulation
In Fig. 8 the mean values of the characteristicarc pa- Results
rameters 4 and ro are plotted as a function of the horn
distance for the horizontal position of insulators. The 6.1 The 20-kV Insulator Arrangement
values for the 20-kV arcs were calculated by exmpola-
tion using constant stationary arc voltages given in Two power arc tests were selectedto comparethe test
Fig. 6a and 6b. and simulationresults. The measuredtime functionsof the
selected 20-kV arc test with a vertical insulator arrange-
ment and a prospectiveshort-circuitcurrent (rms value)of
5.3 Arc Simulation in the ATP-EMTP I, = 5.5 kA are given in Fig. 9a to 9c.The arc parameters
obtained by evaluating the half-periods according to the
Digital simulations of the power arc tests were method given in section5.2 are shown in Fig. 9d to 9e.As
performed using the royalty-free universal transients it can be deduced from Fig. 9c and 9d,the arc elongates
program ATP-EMTP [8]. The dynamics of the electric steadily startingfrom t = 100 ms until t = 200 ms and after
arc including the random behaviour of the arc param- reaching approximately five times of its initial length, it
breaks down abruptly to the initial length.
The simulation results of the same case with the
basic arc parameters determined from the measurements
are given in Fig. 10. The test circuit given in Fig. 2 was
modelled in the ATP-EMTPby lumped RLC-circuit ele-
ments. The 20-kV power source is representedby its no-
load voltage and short-circuitimpedance. Since the neu-
tral point was isolated, the equivalent line-to-earth ca-
pacitance was also modelled in the test circuit. The se-
ries impedancerepresentingthe transmissionline is cho-
sen such that the prospective short-circuit current (rms
value) I , = 5.5 kA flows through the circuit. The electri-
0 0.4 0.8 1.2 1.6 rn 2.0” cal data of the test circuit are given as follows:
ET 1059.08H 4mlnl-
€, = 20 k V / a (rms value),
Fig. 8. Mean value of arc parameters uo and ro determined
from the arc tests with the horizontal insulation arrangement Z5= R, +j X,= (0.05 +j0.92) R (corresponding
as a function of the horn distance dhom to Sr = 435 MVA),

I82 ETEP Vol. 4, No. 3, MayNune 1994


E TEF
a ) 10,

b) 30
kV
t
UllW
';
-15 -301" I I 1
-301" ' I 1 I I

I I

-8 I I
50 100 150 200 ms 250
t --c
400
mR
300

200 '
A e) 900
V
f 800
I
I r\ in\J
I

\A
0
' 7

100 Ul1 700


I
600- ____-
0
50 I50 200 ms 250
f --*

200 ms 250
ET 1059 IOH t-

Fig. 10. Numerical simulation of the power arc test with the
20-kV insulator
50 100 150 200 ms 250
ET IOS9.09H t- a) arccurrent
b) line voltage
Fig. 9. Power arc test with the vertical 20-kV insulator c) arcvoltage
arrangement (I, = 5.5 kA) d) arc length variation
a) measured arc current e) random variation of uo
b) measured line voltage f) random variation of ro
c) measured arc voltage
d) calculated arc parameters uo and ro
e) calculated arc time constant 6.2 The 110-kVInsulator Arrangement

This power arc test with a 110-kV insulator arrange-


C, = 13.7pF, ment is used to show the impact of the fault arc on the
line voltage of the equivalent real 110-kV network. This
Zwr = Rwr + j X,,r = (0.82 +j 1SO) R. selected arc test was performed in the vertical position
An additional resistance of 80 R is connected p a - of the 1 10-kV overhead line insulator with the series im-
allel to the supply reactance in the numerical model of pedance of the modelled single circuit overhead line
the circuit in order to reproduce the actual damping of I20/20 mm' ACSR corresponding the short-circuit cur-
the test circuit. rent (rms value) of 11.5 kA. The electrical data of the test
Besides the computed time functions of arc current, circuit given in Fig. 2 are given as follows
arc voltage and line voltage, the arc length variation with E, = 20.1 k V / G (rms values).
a superimposed random signal and time variation of the
arc parameters uoand r0 according to a random signal are 2,= R, + jX,= (0.04 + j0.67)R (corresponding
shown in Fig. 1Od to 1Of. to Sy = 600 MVA),

ETEP Vol. 4. No. 3. May/June 1994 I83


ETEP
and220 kV. A test circuit witha20-kV powersource was
modelled to achieve prospective short-circuit currents in
A the range of 2 kA to 12.5 kA (rms values). Arc tests have
' 0 been performed in the horizontal and vertical position of
UllK
-15 the insulators.
During the tests the input signals relevant to the dis-
-30'" I
tance protection, line voltage and line current as well as
b, k$ the arc voltage were measured. They were digitized by
4 a transient recorder of high resolution and high sampling
1 0 rate. The discrete measured data were stored on magne-
Uarc
-4 to-optical discs and are thus available for developing or
I I I
testing distance protection algorithms.
Using the recorded arc voltages and currents of var-
ious configurations of insulators tested, an existing nu-
merical arc model has been improved to take the random
behaviour of the arc into consideration. The arc param-
eters were determined by numerical analysis of record-
ed time functions. A general arc model has been estab-
lished, which allows the digital simulation of arcs of var-
ious insulator arrangements.
The numerical simulation of the selected two cases
shows a good agreement between the measured and
computed time functions. The numerical arc model is re-
alized in the universal electromagnetic transients pro-
gram ATP-EMTP, which allows the representation of
any network configuration to be investigated, so the dig-
ital simulation of arc faults through air can substitute for
demanding power arc tests. The signals produced by
ATP-EMTP can be used to test and improve distance
protection algorithms implemented in the modem digi-
-LU I I 1
tal protective relays.
0 50 100 150 200 ms 250
ETIll5Y I I H t -*
Fig. 11. Power arc test with the vertical I 10-kV insulator 8 List of Symbols and Abbreviations
arrangement ( I, = 12.5 kA)
a) measured line voltage 8.1 Symbols
b) measured arc voltage
c) simulated arc voltage ( 1 10-kV network model) line-to-earth capacitance
d) simulated line voltage ( I 10-kV network model) source voltage
e) simulated arc current ( I 10-kV network model) instantaneous arc conductance
stationary arc conductance
arc current
C, = 27.4 ,uF, prospective short-circuit current
arc length
& = R W r + jX,, = (0.1 17 +j 0.260) Q. characteristic arc resistance
In order to simulate the equivalent 110-kV power equivalent source resistance
network with the same short-circuit current all the im- series line resistance
pedances and the source voltage must be multiplied by Laplace operator
the scaling factor 5.5 as explained in chapter 3. Fig. 11 initial symmetrical short-circuit power
shows the measured line voltage and the arc voltage of time
the 20-kV test circuit as well as the computed voltages arc voltage
and currents of the equivalent 110-kV nework. It can line-to-earth voltage
be noticed that the distortion of the line voltage of the stationary arc voltage
110-kV network (Fig. 1Id) due to fault arc is signifi- characteristic arc voltage
cantly lower than of the measured line voltage in the equivalent source reactance
20-kV test circuit (Fig. 1la). series line reactance
arc time constant

7 Conclusions 8.2 Abbreviations

Extensive power arc tests were carried out with the ATP-EMTP Alternative Transients Program -
original arrangements of overhead line insulators and Electromagnetic Transients Program
arcing fittings of nominal voltage levels 20 kV, I10 kV ACSR Steel Reinforced Aluminium Conductor

I 84 ETEP Vol.4,No. 3, MaylJune 1994


E TEP
References The Authors
[ I ] IEC 36B (Sec.) I 16 (Draft): Insulators for Overhead Lines Dr.-Ing. Mustafa Kizilcay ( 1955).
with a Nominal Voltage above lo00 V, A.C. Power Arc VDE. received the B.S. degree in elec-
Tests on Insulator Sets. Frankfurt a. MXermany: Germ. trical engineering from Middle East
Electrotech. Commiss. (DKE), I993 Technical University in Ankarnur-
[2] Nelles, D.; Opperskalski. H.: Digitaler Distanzschutz: key in 1979. That same year, he joined
Verhalten der Algorithmen bei nicht idealen Eingangs- the Turkish Electricity Authority
signalen. Wiesbaden/Gemany: Dt. Univ.-Verl., 1991 (TEK) in Ankara as a research en-
131 Opperskalski. H.: Verhalten impedanzbestimmenderDis- gineer. In 1985. he received the Dip1.-
tanzschutzalgorithmen.Dusseldorf/Gerrnany: VDI, 199 I Ing. degree in electrical engineering
(Fortschr.-Ber. R. 6, no. 256) from the University of HannovedGer-
[4] Nilges. 1.:Die Anwendung des Distanzschutzprinzipszur many. From 1985 to 1990, he was a
KunschluBerfassung auf Drehstrom-Doppelleitungen. member of the scientific staff of “Institut fur Elektrische En-
Dusseldorf/Germany: VDI, 1990 (Fortschr.-Ber. R. 2 1, ergieversorgung”of the University of Hannover. After a short
no. 73) period with AEG’s Dept. of Protective Relay Development in
[ 5 ] Kizilcay, M.;Pniok, T : Digital Simulation of Fault Arcs Frankfurthi, Germany, early in 199I, he moved to his present
in Power Systems. ETEP Eur. Trans. on Electr. Power position with Lahmeyer International GmbH in FrankfurtfM
Engng. 1 (1991)no. l,pp.55-60 where, as a consulting engineer, he has responsibility for
[6] CIGRE Working Group 13.0I : Practical applicationof arc power system studies. In 1991, he was awarded his doctorate
physics in circuit breakers. Survey of calculation methods in electrical engineering from the University of Hannover. He
and application guide. Electra No. 118, 1988, pp. 65-79
[ 7 ] Hochruiner; A.: Eine regelungstechnische Betrachtung was a contributor to EiMTP development through the Leuven
des elektrischen Lichtbogens, kybernetische Theorie des EMTP Center in LeuvedBelgium. where he was a faculty
Lichtbogens. ETZ-A Elektrotech. Z. 92 (1971) no. 6, member of the 1989, 1991 and 1993 EMTP short courses.
pp. 367 - 37 1 (Lahmeyer International, RE 2, Lyoner Str. 22, D-60528
[8] Alternative Transients Program - Rule Book. Portland, FrankhidM. T +4969/6677-254, F a +4969/6677-322)
Oregon/USA: Canadian/American EMTP User Group. Karl-Heinrich Koch ( 1942) received
I992 the Dip1.-lng. degree in Electrical En-
191 Dub6 L.: Bonftnri, I.: MODELS: A New SimulationTool gineering from the Technical Univer-
in the EMTP. ETEP Eur. Trans. on Electr. Power Engng. 2 sity of DarmstadVGermany. After-
(1992) no. I. pp. 45-50
wards he joined the high power labor-
atory of FGH in MannheidGermany
as a Research Engineer. His fields of
interest are the transient performance
Acknowledgment of current transformers, the extinction
The authors would like to acknowledge the Ministry for Eco- of earth-fault current by compensation
nomic Affairs of the Federal Republic of Germany for finan- and power-system studies with the
cial assistance of the AiF-project 8507. EMTP. (Forschungsgerneinschaft fur Hochspannungs- und
Hochstromtechnik e.V.. Hallenweg 40, D-682 19 Mannheim,
Munuscripr received on November 16. I993 T +49 6 2 I / 8 04 72 60. Fax +49 6 2 1 / 8 047259)

ETEP Vol. 4. No. 3. May/.!une 1994 I85

You might also like