MCIE CONTROL CENTRE 690V MOTOR CONTROL SWITCHBOARD OMCS 400 V LOW VOLTAGE SWITCHBOARD
FIRE WATER
PLANTROOM
DAMPER
CONTROL
PANEL A
SCIE INTRINSICALLY SAFE SUMP INSTRUMENTATION & CONTROLS
BARRIER CABINET MARSHALLING CABINET
DAMPER
CONTROL
PANEL B
MVAC
HYDROCARBON
SENSOR
FOAM
SUPPRESSION
SKID
AIR
HYDROCARBON COMPRESSOR
SENSORS STORMWATER STORMWATER STORMWATER STORMWATER GROUNDWATER GROUNDWATER
GROUND WATER PUMP PANEL PUMP PANEL PUMP PANEL PUMP PANEL PUMP PANEL PUMP PANEL
x2
STORM WATER TO WTP
QUALITY
VESSEL
pH LEVEL FLOAT
SENSORS SENSORS SWITCHES
x2 x6 x4
Legend:
Package #607
By others
Contractor
Control M4E-PR-FRM-PWD-00555-B-
Power Form 2 - Scope of Work -
Equipment Appendix 5 Page 1 of 15
Piping
Interface 17/02/2017
LOW LEVEL OUTPUT FROM FIRE SERVICES
HYDROCARBON SUCTION POINT AND VAPOUR NOTES:
CONTROL PANEL TO SHUT THE SLUICE
RETURN LINE TERMINATE EXTERNAL TO
GATES IN THE EVENT OF A FOAM DUMP 1. FOR FIRE SERVICES SCHEMATIC REFER TO
Supply cabling by others, terminated by others PLANTROOM WITH CAPPED DN80 CAMLOK
DRAWING No. M4E-NDY-DG-60-460-220093.
FITTINGS. ALL HYDROCARBON SUCTION AND
VAPOUR RETURN PIPES 316 STAINLESS STEEL
Legend 2. TANK IS LOCATED WITHIN EASTBOUND
PLANTROOM BREAKDOWN LANE, AT CHAINAGE 4800.
Contractor scope
Ground Water Supply cabling by others, terminated by others MONORAIL FOR REMOVAL OF PUMPS. REFER 3. TANK SHOWN IS SERVING EASTBOUND AND
BL TO DESIGN LOT 10-340-335 FOR DETAILS WESTBOUND TUNNELS.
STORMWATER PUMP
STORMWATER PUMP
STORMWATER PUMP
STORMWATER PUMP
Storm Water
4. PH SENSORS LOCATED IN PIPEWORK MOUNTED
CONTROL PANEL
CONTROL PANEL
CONTROL PANEL
CONTROL PANEL
GROUNDWATER
PUMP CONTROL
GROUNDWATER
PUMP CONTROL
TO TANK WALLS.
Hydrocarbon
PANEL
PANEL
5. FOR DETAILS ON POWER SUPPLY AND LOCATION
INSTRUMENT POWER PMCS R I/O OF I/O REFER TO LV PACKAGE 60-06.
AND IS PANEL PANEL
6. TRANSDUCERS FOR PH SENSORS AND LEVEL
SENSORS LOCATED IN ELECTRICAL CONTROLS
UST11001
UST11003
PHT11001
BOARDS.
UST11004
PHT11002
UST11005
UST11006
UST11002
GWV11002
GWV11003
CKV11006 GWV11004
CKV11001 SWV11001
CKV11002 SWV11002
SWV11003
CKV11003 SWV11004
SWV11005
CKV11004 SWV11006
PSV11001
PSV11002
PSV11003
PSV11004
S S S S
PDL140
DN110
VR100
DISCHARGE LINE DRAIN DOWN. COMPRESSOR
GWV110005 NORMALLY LOCKED CLOSED RECEIVER DRYER
PAC11001
BL AP AP AP AP AP AP AP AP AP AP AP AP
PUMP RISING MAIN CONTINUED
ON DESIGN LOT 10-360-400 LVT LVT LVT LVT LVT LVT ULTRASONIC LEVEL SENSOR
PDL355
A
DN110
Rising mains by others By contractor including USL11001 USL11002 USL11003 USL11004 USL11005 USL11006
final flange makeup OPEN ENDED DN110 PIPE FOR PUMP
PENSTOCK ACTUATOR DISCHARGE LINE DRAIN DOWN.
PSA11001 SWV110005 NORMALLY LOCKED CLOSED
PUMP RISING MAIN CONTINUED
ON DESIGN LOT 10-360-400
21.7 L/s
100 L/s
100 L/s
100 L/s
100 L/s
DESIGN LOT 10-360-400 FOR DETAILS
STORAGE 50,000L
HYDROCARBON
PDL110
PDL200
PDL200
PDL200
PDL200
REFER TO CIVIL DRAWING
SU100
PHS11001 PHS11002
GWP11001
GWP11002
SWP11001
SWP11002
SWP11003
SWP11004
GROUND WATER DISCHARGE PUMPS
DUTY / STAND-BY
C:\Windows\system32\config\systemprofile\Documents\M4E-NDY-MD-60-000-MHF_SCHEMATICS_gevorgm.rvt
STORMWATER PUMPOUT/STORAGE
70
HYDROCARBON
CHAMBER FOR FIRE DELUGE/RAINWATER INGRESS.
FOR DETAIL REFER TO DESIGN LOT 10-360-400
PROTECTION OF PENSTOCK
PTS11001
PROTECTION OF PENSTOCK
PTS11002 M4E-PR-FRM-PWD-00555-B-
Form 2 - Scope of Work -
40
Appendix 5 Page 2 of 15
30
CHECKED BY:
C_00 ISSUED FOR SUBSTANTIAL DETAILED DESIGN 16/12/2016 DB
HEIGHT DATUM:
TUNNEL SUMP HYDRAULIC SCHEMATIC
A3 ORIGINAL
A.H.D. BC
REV AMENDMENT / REVISION DESCRIPTION DATE APPROVAL NOT TO SCALE CLIENT DRAWING NO.:
PROJECT COMPANY DOCUMENT ZONE DISCIPLINE LOT NO. DOC No. REV
THIS DRAWING MAY BE PREPARED USING COLOUR AND MAY BE INCOMPLETE IF COPIED M4E NDY DG 60 400 120 022 C_00
0
Hydrocarbon
DN140-PE100-PN16 DN355-PE100-PN16
SWV11001
SWV11002
SWV11003
SWV11004
SWV11005
SWV11006
GWV11001
GWV11002
GWV11003
GWV11004
PSV11001
PSV11002
PSV11003
PSV11004
S
S
CKV11005
CKV11001
CKV11006
CKV11002
CKV11003
CKV11004
DN140-PE100-PN16
DN110-PE100-PN16
DN355-PE100-PN16
DN110-PE100-PN16
PAC SU VR
11001
DRAIN DOWN
DRAIN DOWN
DN100-S/S-316L-SCH40
Rising mains by others BL LVTUSL LVTUSL
LVTUSL LVTUSL LVTUSL LVTUSL
11005 11006
11001 11002 11003 11004
TREATMENT PLANT
PSA PSA
By contractor including 11001 11002
final flange makeup
QUALITY POND
DN100-S/S-316L-SCH40
PUMP 3 START
DN200-PE100-PN16
DN200-PE100-PN16
DN200-PE100-PN16
DN200-PE100-PN16
RL -40.18
DN110-PE100-PN16
DN110-PE100-PN16
PTS11002
PSG11001
PSG11002
PHS PHS
80
70
60
50
Appendix 5 Page 3 of 15
30
A.H.D. BC
REV AMENDMENT / REVISION DESCRIPTION DATE APPROVAL NOT TO SCALE CLIENT DRAWING NO.:
PROJECT COMPANY DOCUMENT ZONE DISCIPLINE LOT NO. DOC No. REV
THIS DRAWING MAY BE PREPARED USING COLOUR AND MAY BE INCOMPLETE IF COPIED M4E NDY DG 60 400 120 023 C_00
0
PTAOIP PTAOIP
By contractor including
final flange makeup BL Rising mains by others
MAIN LINE
GWV11009 GWV11010
CKV11011 CKV11012
USL USL
1 L/s
1 L/s
11011 11012
DN65-PE100-PN16
DN65-PE100-PN16
80
PUMP STOP
RL -23.4
C:\Windows\system32\config\systemprofile\Documents\M4E-NDY-MD-60-000-MHF_SCHEMATICS_gevorgm.rvt
70
60
GWP11007 GWP11008
SUMP BASE
RL -23.9
50
M4E-PR-FRM-PWD-00555-B-Form 2
- Scope of Work - Appendix 5
40
Page 4 of 15
30
CHECKED BY:
C_00 ISSUED FOR SUBSTANTIAL DETAILED DESIGN 16/12/2016 DB
HEIGHT DATUM:
P AND ID
A3 ORIGINAL
A.H.D. BC
REV AMENDMENT / REVISION DESCRIPTION DATE APPROVAL NOT TO SCALE CLIENT DRAWING NO.:
PROJECT COMPANY DOCUMENT ZONE DISCIPLINE LOT NO. DOC No. REV
THIS DRAWING MAY BE PREPARED USING COLOUR AND MAY BE INCOMPLETE IF COPIED M4E NDY DG 60 400 120 024 C_00
0
PTAOIP PTAOIP
By contractor including
final flange makeup BL Rising mains by others
MAIN LINE
GWV11005 GWV11006
CKV11003 CKV11004
USL USL
1 L/s
1 L/s
11007 11008
DN65-PE100-PN16
DN65-PE100-PN16
80
PUMP STOP
RL -41.2
C:\Windows\system32\config\systemprofile\Documents\M4E-NDY-MD-60-000-MHF_SCHEMATICS_gevorgm.rvt
70
60
GWP11003 GWP11004
SUMP BASE
RL -41.7
50
M4E-PR-FRM-PWD-00555-B-Form 2
- Scope of Work - Appendix 5
40
Page 5 of 15
30
CHECKED BY:
C_00 ISSUED FOR SUBSTANTIAL DETAILED DESIGN 16/12/2016 DB
HEIGHT DATUM:
P AND ID
A3 ORIGINAL
A.H.D. BC
REV AMENDMENT / REVISION DESCRIPTION DATE APPROVAL NOT TO SCALE CLIENT DRAWING NO.:
PROJECT COMPANY DOCUMENT ZONE DISCIPLINE LOT NO. DOC No. REV
THIS DRAWING MAY BE PREPARED USING COLOUR AND MAY BE INCOMPLETE IF COPIED M4E NDY DG 60 400 120 025 C_00
0
PTAOIP PTAOIP
By contractor including
final flange makeup BL Rising mains by others
MAIN LINE
GWV11010 GWV11009
CKV11010 CKV11009
USL USL
1 L/s
1 L/s
11010 11009
DN65-PE100-PN16
DN65-PE100-PN16
80
PUMP STOP
RL -43.2
C:\Windows\system32\config\systemprofile\Documents\M4E-NDY-MD-60-000-MHF_SCHEMATICS_gevorgm.rvt
70
60
GWP11006 GWP11005
SUMP BASE
RL -43.7
50
M4E-PR-FRM-PWD-00555-B-Form 2
- Scope of Work - Appendix 5
40
Page 6 of 15
30
CHECKED BY:
C_00 ISSUED FOR SUBSTANTIAL DETAILED DESIGN 16/12/2016 DB
HEIGHT DATUM:
P AND ID
A3 ORIGINAL
A.H.D. BC
REV AMENDMENT / REVISION DESCRIPTION DATE APPROVAL NOT TO SCALE CLIENT DRAWING NO.:
PROJECT COMPANY DOCUMENT ZONE DISCIPLINE LOT NO. DOC No. REV
THIS DRAWING MAY BE PREPARED USING COLOUR AND MAY BE INCOMPLETE IF COPIED M4E NDY DG 60 400 120 026 C_00
0
PTAOIP PTAOIP
By contractor including
final flange makeup BL Rising mains by others
MAIN LINE
GWV11011 GWV11012
CKV11013 CKV11014
USL USL
1 L/s
1 L/s
11013 11014
DN65-PE100-PN16
DN65-PE100-PN16
80
PUMP STOP
RL -7.6
C:\Windows\system32\config\systemprofile\Documents\M4E-NDY-MD-60-000-MHF_SCHEMATICS_gevorgm.rvt
70
60
GWP11009 GWP11010
SUMP BASE
RL -8.1
50
M4E-PR-FRM-PWD-00555-B-Form 2
- Scope of Work - Appendix 5
40
Page 7 of 15
30
CHECKED BY:
C_00 ISSUED FOR SUBSTANTIAL DETAILED DESIGN 16/12/2016 DB
HEIGHT DATUM:
P AND ID
A3 ORIGINAL
A.H.D. BC
REV AMENDMENT / REVISION DESCRIPTION DATE APPROVAL NOT TO SCALE CLIENT DRAWING NO.:
PROJECT COMPANY DOCUMENT ZONE DISCIPLINE LOT NO. DOC No. REV
THIS DRAWING MAY BE PREPARED USING COLOUR AND MAY BE INCOMPLETE IF COPIED M4E NDY DG 60 400 120 027 C_00
0
PTAOIP PTAOIP
By contractor including
final flange makeup BL Rising mains by others
MAIN LINE
GWV11014 GWV11013
CKV11016 CKV11015
USL USL
1 L/s
1 L/s
11016 11015
DN65-PE100-PN16
DN65-PE100-PN16
80
PUMP STOP
RL -6.7
C:\Windows\system32\config\systemprofile\Documents\M4E-NDY-MD-60-000-MHF_SCHEMATICS_gevorgm.rvt
70
60
GWP11012 GWP11011
SUMP BASE
RL -7.2
50
M4E-PR-FRM-PWD-00555-B-Form 2
- Scope of Work - Appendix 5
40
Page 8 of 15
30
CHECKED BY:
C_00 ISSUED FOR SUBSTANTIAL DETAILED DESIGN 16/12/2016 DB
HEIGHT DATUM:
P AND ID
A3 ORIGINAL
A.H.D. BC
REV AMENDMENT / REVISION DESCRIPTION DATE APPROVAL NOT TO SCALE CLIENT DRAWING NO.:
PROJECT COMPANY DOCUMENT ZONE DISCIPLINE LOT NO. DOC No. REV
THIS DRAWING MAY BE PREPARED USING COLOUR AND MAY BE INCOMPLETE IF COPIED M4E NDY DG 60 400 120 028 C_00
0
Legend
Contractor scope
Gas detection & foam suppression
Ø32 Ø40
1620
1280
Ø50 Ø50 Ø50 Ø40 Ø32
FOAM TEST DRAIN DISCHARGE FROM ABOVE. FOAM SYSTEM FROM ABOVE. FOR CONTINUATION REFER TO SUMP PLANT ROOM
FOR CONTINUATION REFER TO SUMP PLANT ROOM FIRE SUPPRESSION SYSTEM LAYOUT
FIRE SUPPRESSION SYSTEM DETAIL
SUMP FIRE SUPPRESSION SYSTEM
SCALE : 1 : 100
DUPLICATED
HYDROCARBON
SENSORS MOUNTED IN 600 x 600 x 600 DELUGE
DUCTWORK. VALVE ASSEMBLY.
Ø65
250
Ø25 CONDUIT MOUNTED ON
PLANTROOM ROOF
80
SCIE
1
220091 1300 x 1300 x 250H PLINTH. 250H PLINTH PROVIDED
70
60
By contractor including
Ø65 INCOMING WATER
SUPPLY AT L/L. PIPEWORK TO final coupling makeup
600 x 600 x 600 DELUGE VALVE
ASSEMBLY.
Ø65 FOAM SYSTEM TO DROP INTO SUMP.
FOR CONTINUATION REFER TO SUMP FIRE
SECTION 1 M4E-PR-FRM-PWD-00555-B-
RISE TO PLANTROOM LEVEL SUPRESSION SYSTEM SCALE : 1 : 50 220091
Form 2 - Scope of Work -
40
A.H.D. JD
REV AMENDMENT / REVISION DESCRIPTION DATE APPROVAL PROJECT COMPANY DOCUMENT ZONE DISCIPLINE LOT NO. DOC No. REV
CLIENT DRAWING NO.:
THIS DRAWING MAY BE PREPARED USING COLOUR AND MAY BE INCOMPLETE IF COPIED 1:100 FULL SIZE AT A3 M4E NDY DG 60 460 220 091 C_00
0
K011
011 500A SS MAIN CONT. MAIN CONTACTOR
K011
K017 E-STOP K011
RESET NO NC
012 010
K028
021
F014B
K015
TBC
TBC
TBC
Battery limit
021 INDICATOR LAMP
KEYPAD (IP54) TEST H024
DOOR MOUNTED EARTH BAR A
022 SS RUNNING
K017 H024
RUNNING
023 JBXxxxxx
INDICATOR LAMP
JUNCTION BOX
R
024 RUNNING RELAY
V1 U2 K026 K026
NO NC
025 044
6
8
W1 V2
1
5
X23
K062
THERMAL
MOISTURE SWITCH
PE1
PE2
W1
W2
U1
U2
V1
V2
DEVICE TERMINAL
WATER IN OIL SENSOR
031
FIELD MARSHALLING
60
M4E-PR-FRM-PWD-00555-B-Form 2 -
RTD
033
SWPxxxxx
034
168kW
FLC 172A Page 10 of 15 DISCONNECT TERMINAL
FUSE TERMINAL
40
CHECK PRINT
30
20
V IS DISCIPLINE
ORIGINAL SIZE: DRAWN BY:
MECHANICAL AND ELECTRICAL
RE ROGR
A3 MH
DISCIPLINE
CO-ORDINATE SYSTEM: DESIGNED BY:
ELECTRICAL DESIGN
IN P TYPICAL STORMWATER PUMP SOFT STARTER
DISCIPLINE
MGA ZONE 56 MH
10
A3 ORIGINAL
C_00 ISSUED FOR SUBSTANTIAL DETAIL DESIGN 10/08/2016 GL NOT TO SCALE DISCIPLINE
HEIGHT DATUM: CHECKED BY: SCHEMATIC DIAGRAM - SHEET 01
A.H.D. MS
DATE APPROVAL BACKDRAFTED/CORRECTED PROJECT COMPANY DOCUMENT ZONE DISCIPLINE LOT NO. DOC. No. REV
REV AMENDMENT / REVISION DESCRIPTION
CLIENT DRAWING NO. :
THIS SHEET MAY BE PREPARED USING COLOUR AND MAY BE INCOMPLETE IF COPIED DO NOT SCALE FROM THIS DRAWING CONFIRMED M4E NDY DG 60 500 270 271 C_00
0
Battery limit
K005 X31 CONTROL SWITCHBOARD.
2 1 DI-xx:yy/zz p PLCxxxxx SWPxxxxx
040 xx:yy/zz PUMP PANEL 5. 24 VOLT DC POWER SUPPLIED TO BE SUPPLIED FROM
SUPPLY HEALTHY THE INTRINSICALLY SAFE BARRIERS AND
INSTRUMENT MARSHALLING PANEL
041 6. PLANT AND MONITORING CONTROL SYSTEM
K018 INTERFACE POINT TERMINALS TO BE COORDINATED
3 2 DI-xx:yy/zz p PLCxxxxx SWPxxxxx
042 xx:yy/zz PUMP PANEL WITH DESIGN LOT 60-540-416
PROTECTION TRIP
043
K026
4 3 DI-xx:yy/zz p PLCxxxxx SWPxxxxx
044 xx:yy/zz PUMP
RUNNING
S007
045 OFF
MAN AUTO
046
048
049
050
051
052
053
054
055
056
057 PMCSxxxxx
LOCATION TBC
X30 X6
REFER TO PMCS DESIGN LOT 60-540-416 1 1
0V-IO
058
Battery limit
061 RESET RELAY
K062
X32 X5 K062
PLCxxxxx SWPxxxxx p DI-xx:yy/zz 6 9 NO NC
062 xx:yy/zz PUMP PANEL
LOCATION: W:\S307xx\S30776\011\E-\07_Drawings\60_06 Electrical LV\001 - Clone Drawings\M4E-NDY-DG-60-500-270272_C_01.dwg
RESET 029
LOCAL TERMINAL
064
DRAWING DEFINED TERMINAL
70
065
DEVICE TERMINAL
068
Scope of Work - Appendix 5 DISCONNECT TERMINAL
CHECK PRINT
30
20
V IS DISCIPLINE
ORIGINAL SIZE: DRAWN BY:
MECHANICAL AND ELECTRICAL
RE ROGR
A3 MH
DISCIPLINE
CO-ORDINATE SYSTEM: DESIGNED BY:
ELECTRICAL DESIGN
IN P TYPICAL STORMWATER PUMP SOFT STARTER
DISCIPLINE
MGA ZONE 56 MH
10
A3 ORIGINAL
C_00 ISSUED FOR SUBSTANTIAL DETAIL DESIGN 10/08/2016 GL NOT TO SCALE DISCIPLINE
HEIGHT DATUM: CHECKED BY: SCHEMATIC DIAGRAM - SHEET 02
A.H.D. MS
DATE APPROVAL BACKDRAFTED/CORRECTED PROJECT COMPANY DOCUMENT ZONE DISCIPLINE LOT NO. DOC. No. REV
REV AMENDMENT / REVISION DESCRIPTION
CLIENT DRAWING NO. :
THIS SHEET MAY BE PREPARED USING COLOUR AND MAY BE INCOMPLETE IF COPIED DO NOT SCALE FROM THIS DRAWING CONFIRMED M4E NDY DG 60 500 270 272 C_00
0
023
V1 U2
Battery limit
024
W1 V2
1
025
U1
W2
EARTH BAR M4E-PR-FRM-PWD-00555-B-Form 2 -
026
Scope of Work - Appendix 5
027
Page 12 of 15
LOCATION: W:\S307xx\S30776\011\E-\07_Drawings\60_06 Electrical LV\001 - Clone Drawings\M4E-NDY-DG-60-500-270273_C_01.dwg
SUMP AREA
MOISTURE SWITCH
THERMAL
028
PE1
PE2
W1
W2
U1
U2
V1
V2
TERMINAL
029 BOX LOCAL TERMINAL
DEVICE TERMINAL
WATER IN OIL SENSOR
031
FIELD MARSHALLING
60
PTC
032 PMCS MARSHALLING TERMINAL
033
EX
DISCONNECT TERMINAL
034
FUSE TERMINAL
40
CHECK PRINT
30
20
V IS DISCIPLINE
ORIGINAL SIZE: DRAWN BY:
MECHANICAL AND ELECTRICAL
RE ROGR
A3 MH
DISCIPLINE
CO-ORDINATE SYSTEM: DESIGNED BY:
ELECTRICAL DESIGN
IN P TYPICAL MAIN SUMP GROUNDWATER PUMP DOL
DISCIPLINE
MGA ZONE 56 MH
10
A3 ORIGINAL
C_00 ISSUED FOR SUBSTANTIAL DETAIL DESIGN 10/08/2016 GL NOT TO SCALE DISCIPLINE
HEIGHT DATUM: CHECKED BY: SCHEMATIC DIAGRAM - SHEET 01
A.H.D. MS
DATE APPROVAL BACKDRAFTED/CORRECTED PROJECT COMPANY DOCUMENT ZONE DISCIPLINE LOT NO. DOC. No. REV
REV AMENDMENT / REVISION DESCRIPTION
CLIENT DRAWING NO. :
THIS SHEET MAY BE PREPARED USING COLOUR AND MAY BE INCOMPLETE IF COPIED DO NOT SCALE FROM THIS DRAWING CONFIRMED M4E NDY DG 60 500 270 273 C_00
0
Battery limit
5. 24 VOLT DC POWER SUPPLIED TO BE SUPPLIED FROM
040 THE INTRINSICALLY SAFE BARRIERS AND
INSTRUMENT MARSHALLING PANEL
K005 X31
041 2 1 DI-xx:yy/zz p PLCxxxxx GWPxxxxx 6. PLANT AND MONITORING CONTROL SYSTEM
xx:yy/zz AUX SUPPLY
HEALTHY INTERFACE POINT TERMINALS TO BE COORDINATED
042 WITH DESIGN LOT 60-540-416
RUNNING
K015
043 3 2 DI-xx:yy/zz p PLCxxxxx GWPxxxxx
xx:yy/zz PUMP
RUNNING
044
TRIP
K015
045 4 3 DI-xx:yy/zz p PLCxxxxx GWPxxxxx
xx:yy/zz MPR
TRIPPED
046
S007
047 OFF
MAN AUTO
048
051
052
053
PMCSxxxxx
LOCATION: TBC
054 REFER TO PMCS DESIGN LOT 60-540-416 K055
X32 X6
PLCxxxxx SWPxxxxx p 1
055 xx:yy/zz PUMP PANEL PMCS SEAL FAILURE RESET
RESET K055
NO NC
015
056
K057 PMCS RUN RELAY
X32
PLCxxxxx GWPxxxxx p 1 2 K057
Battery limit
057 xx:yy/zz PUMP NO NC
RUN
010
058
X30 X6
0V-IO 1 3
059
060
By Contractor By Others (includes supply cabling)
061
062
LOCATION: W:\S307xx\S30776\011\E-\07_Drawings\60_06 Electrical LV\001 - Clone Drawings\M4E-NDY-DG-60-500-270274_C_01.dwg
063
TERMINAL LEGEND
80
DEVICE TERMINAL
066
FIELD MARSHALLING
60
067
M4E-PR-FRM-PWD-00555-B-Form 2 - PMCS MARSHALLING TERMINAL
FIELD TERMINAL
50
068
Scope of Work - Appendix 5 DISCONNECT TERMINAL
CHECK PRINT
30
ION ESS
SELF CHECK
20
V IS DISCIPLINE
ORIGINAL SIZE: DRAWN BY:
MECHANICAL AND ELECTRICAL
RE ROGR
A3 MH
DISCIPLINE
CO-ORDINATE SYSTEM: DESIGNED BY:
ELECTRICAL DESIGN
IN P TYPICAL MAIN SUMP GROUNDWATER PUMP DOL
DISCIPLINE
MGA ZONE 56 MH
10
A3 ORIGINAL
C_00 ISSUED FOR SUBSTANTIAL DETAIL DESIGN 10/08/2016 GL NOT TO SCALE DISCIPLINE
HEIGHT DATUM: CHECKED BY: SCHEMATIC DIAGRAM - SHEET 02
A.H.D. MS
DATE APPROVAL BACKDRAFTED/CORRECTED PROJECT COMPANY DOCUMENT ZONE DISCIPLINE LOT NO. DOC. No. REV
REV AMENDMENT / REVISION DESCRIPTION
CLIENT DRAWING NO. :
THIS SHEET MAY BE PREPARED USING COLOUR AND MAY BE INCOMPLETE IF COPIED DO NOT SCALE FROM THIS DRAWING CONFIRMED M4E NDY DG 60 500 270 274 C_00
0
009
H013 TEST
010
H013
011 CONTACTOR MPR HEALTHY LAMP
K012 H015 TEST
xxxA
012 FWD.
RESET K015 H015
S013 FWD. RUNNING LAMP
013
014 K015
K015 ELECTRONIC MOTOR
NO NC PROTECTION RELAY
015 013 005
045
043
016
017
PMCS INTERFACE
ETHERNET
1
018
/022
/022
/022
MODBUS /
X3
1
3
/019
/019
/022
/022
EARTH BAR
X1
ETHERNET IP
FIELD BUS
019
021
Battery limit
022
023
024 GROUNDWATER
PUMP
GWPxxxxx
025
M4E-PR-FRM-PWD-00555-B-Form 2 -
026
Scope of Work - Appendix 5
027
Page 14 of 15
LOCATION: W:\S307xx\S30776\011\E-\07_Drawings\60_06 Electrical LV\001 - Clone Drawings\M4E-NDY-DG-60-500-300610_C_00.dwg
028
TERMINAL LEGEND
80
POWER
1
/030
/030
/030
/030
/030
/030
X21
X23
DEVICE TERMINAL
031
PE
W
FIELD MARSHALLING
U
V
60
CHECK PRINT
30
20
V IS DISCIPLINE
ORIGINAL SIZE: DRAWN BY:
MECHANICAL AND ELECTRICAL
RE ROGR
A3 MH
DISCIPLINE
CO-ORDINATE SYSTEM: DESIGNED BY:
ELECTRICAL DESIGN
IN P TYPICAL AUX SUMP GROUNDWATER PUMP DOL
DISCIPLINE
MGA ZONE 56 MH
10
A3 ORIGINAL
DISCIPLINE
Battery limit
5. NOT USED.
24 VOLT DC POWER SUPPLIED TO BE SUPPLIED FROM
040 THE INTRINSICALLY SAFE BARRIERS AND
INSTRUMENT MARSHALLING PANEL
K005 X31
2 1 DI-xx:yy/zz p PLCxxxxx GWPxxxxx 6. PLANT AND MONITORING CONTROL SYSTEM
041 xx:yy/zz AUX SUPPLY
HEALTHY INTERFACE POINT TERMINALS TO BE COORDINATED
WITH DESIGN LOT 60-540-416
042 RUNNING 7. ALL PUMPING SYSTEM INSTRUMENTS TO BE WIRED
K015 LOCALLY TO EITHER A COMMON MARSHALLING BOX
3 2 DI-xx:yy/zz p PLCxxxxx GWPxxxxx
043 xx:yy/zz PUMP OR TO THE LOCAL CONTROL STATION
RUNNING
044 TRIP
K015
4 3 DI-xx:yy/zz p PLCxxxxx GWPxxxxx
045 xx:yy/zz MPR
TRIPPED
046
S007
047 OFF
MAN AUTO
048
050
051
052
053
054 PMCSxxxxx
LOCATION: TBC
055 REFER TO PMCS DESIGN LOT 60-540-416
056
K057 PMCS RUN RELAY
Battery limit
X32
PLCxxxxx GWPxxxxx p 1 9 K057
057 xx:yy/zz PUMP NO NC
RUN
010
058
X30 X6
0V-IO 1 1
059
By Contractor By Others (includes supply cabling)
060
061
062
LOCATION: W:\S307xx\S30776\011\E-\07_Drawings\60_06 Electrical LV\001 - Clone Drawings\M4E-NDY-DG-60-500-300611_C_00.dwg
LOCAL TERMINAL
064
DRAWING DEFINED TERMINAL
70
065
DEVICE TERMINAL
FIELD TERMINAL
50
CHECK PRINT
30
20
V IS DISCIPLINE
ORIGINAL SIZE: DRAWN BY:
MECHANICAL AND ELECTRICAL
RE ROGR
A3 MH
DISCIPLINE
CO-ORDINATE SYSTEM: DESIGNED BY:
ELECTRICAL DESIGN
IN P TYPICAL AUX SUMP GROUNDWATER PUMP DOL
DISCIPLINE
MGA ZONE 56 MH
10
A3 ORIGINAL
DISCIPLINE