Professional Documents
Culture Documents
PTS 20.161C - LPG Design and Engineering Practice Manual PDF
PTS 20.161C - LPG Design and Engineering Practice Manual PDF
MANUAL
PTS 20.161C
JUNE 1986
PREFACE
PETRONAS Technical Standards (PTS) publications reflect the views, at the time of publication,
of PETRONAS OPUs/Divisions.
They are based on the experience acquired during the involvement with the design, construction,
operation and maintenance of processing units and facilities. Where appropriate they are based
on, or reference is made to, national and international standards and codes of practice.
The objective is to set the recommended standard for good technical practice to be applied by
PETRONAS' OPUs in oil and gas production facilities, refineries, gas processing plants, chemical
plants, marketing facilities or any other such facility, and thereby to achieve maximum technical
and economic benefit from standardisation.
The information set forth in these publications is provided to users for their consideration and
decision to implement. This is of particular importance where PTS may not cover every
requirement or diversity of condition at each locality. The system of PTS is expected to be
sufficiently flexible to allow individual operating units to adapt the information set forth in PTS to
their own environment and requirements.
When Contractors or Manufacturers/Suppliers use PTS they shall be solely responsible for the
quality of work and the attainment of the required design and engineering standards. In
particular, for those requirements not specifically covered, the Principal will expect them to follow
those design and engineering practices which will achieve the same level of integrity as reflected
in the PTS. If in doubt, the Contractor or Manufacturer/Supplier shall, without detracting from his
own responsibility, consult the Principal or its technical advisor.
Subject to any particular terms and conditions as may be set forth in specific agreements with
users, PETRONAS disclaims any liability of whatsoever nature for any damage (including injury
or death) suffered by any company or person whomsoever as a result of or in connection with the
use, application or implementation of any PTS, combination of PTS or any part thereof. The
benefit of this disclaimer shall inure in all respects to PETRONAS and/or any company affiliated
to PETRONAS that may issue PTS or require the use of PTS.
Without prejudice to any specific terms in respect of confidentiality under relevant contractual
arrangements, PTS shall not, without the prior written consent of PETRONAS, be disclosed by
users to any company or person whomsoever and the PTS shall be used exclusively for the
purpose they have been provided to the user. They shall be returned after use, including any
copies which shall only be made by users with the express prior written consent of PETRONAS.
The copyright of PTS vests in PETRONAS. Users shall arrange for PTS to be held in safe
custody and PETRONAS may at any time require information satisfactory to PETRONAS in order
to ascertain how users implement this requirement.
CONTENTS
03.01.00.00 GENERAL
03.02.01.01 General
03.02.01.04 Separation
03.02.01.05 Confinement
03.02.01.06 Piping
03.02.02.01 General
03.02.02.04 Fabrication
03.02.02.06 Supports
03.02.02.07 Anchorage
03.02.02.08 Foundation
03.02.02.09 Painting
03.02.03.00 Instrumentation
03.02.03.01 General
03.02.04.00 Valves
03.02.04.01 General
03.02.04.02 Remote-operated Shut Down Valves and Emergency Shut Down (ESD) Valves
03.02.05.00 Piping
03.02.05.01 General
03.02.08.00 Electrical
03.02.10.01 General
03.03.01.01 General
03.03.02.04 Supports/Foundation
03.03.03.00 Instrumentation
03.03.03.01 General
03.03.04.00 Valves
03.03.04.01 General
03.03.04.02 Capacity of Pressure Relief Valves (for Mounded/Buried Pressurised LPG Storage)
03.03.05.01 General
03.03.06.00 Piping
03.03.09.00 Electrical
03.01.00.00 General
The principles of design set out herewith, are based on present knowledge with
respect to the standards of technique and experience in the engineering and
operation of pressurised LPG storage facilities.
• that the greatest care is taken in the selection of only those materials with the
properties required for the handling of the product concerned over the range of
operating conditions to be expected;
In addition, the number of connections on vessels below the maximum liquid level
should be reduced to the minimum.
The recommendations contained in this Manual are applicable to new facilities and
can also be appropriate for extension/modification of existing ones -thus they are not
seen as necessarily needing to be applied retroactively. It is recommended however
that all Operating Companies review their LPG facilities in the light of the revised
standards set by this section of the Manual and assess the significance of any
deficiency that may exist. Operating Companies should take appropriate action to
rectify major deficiencies.
Note: Throughout this section reference is made to LPG and propane/butane but the
design principles laid down apply to all pressurised liquefied gases.
03.02.00.00 ABOVE-GROUND STORAGE OF LPG IN PRESSURE VESSELS
03.02.01.01 General
LPG pressure vessels should preferably be grouped in rows and not in blocks.
However, horizontal vessels shall be placed in parallel and not in line or at right
angles to one another as the possibility exists that, if involved in a fire, vessels may
be displaced along their longitudinal axis.
All LPG facilities shall, whenever practicable, be grouped in the same area and when
locating them, the following aspects must be considered:
• The maximum number of tanks in any above-ground group shall be six. Any one
group of tanks shall be separated from any other group of tanks by a minimum of
15 m between adjacent vessel shells.
• The site's topographical nature with particular reference to its effect on the flow of
escaped liquid and vapour to possible ignition sources/important work areas etc.
or its dispersal/dilution.
• The direction of the prevailing wind, i.e. the location of storage downwind of other
facilities is preferable.
• The current and future use of the adjoining land, e.g. whether residential,
industrial etc.
(c) Leakage
The rate of leakage and its duration used in 03.02.01.02(b) shall be based on
identified possible leak sources in the system.
Leakages from the vessel shell, or all welded connections to the vessel shell,
are not considered likely where Group practice is followed in respect to
design, engineering, construction, operation and maintenance of the storage
vessel.
When considering radiation from a relief valve(s) fire, the valve(s) shall be
assumed to be discharging at maximum design flow rate and with
atmospheric conditions relevant to the site.
(e) Distances From LPG Handling Facilities to Fixed Sources of Ignition
Fixed sources of ignition are defined as plant furnaces and boilers, offices,
laboratories, fixed engines and similar facilities.
To minimise the chance of ignition of a leak, all sources of ignition within the
site fence shall be controlled.
LPG pressure storage vessels greater than 135 m3 capacity, pump bays and
loading/discharge facilities shall be located to ensure the following minimum
distances to fixed sources of ignition, irrespective of the requirements of
03.02.01.02(a):
Deflection walls may be used to extend the vapour travel path to meet these
safety distances. Such walls should be so located as to minimise the risk of
flame engulfment of storage vessels, in the event of ingition of escaped
product, and also so as to ensure free ventilation of the storage area from at
least three directions, taking account of prevailing winds
kW/m2
Equipment
Filling/discharge points 8
Plant Boundary
Notes:
In siting pressure storage vessels with respect to refrigerated product tanks, the
(1)
acceptable radiation flux level on the pressure vessel shell must be limited to 8 kW/m².
Special consideration shall be given to the location of floating roof tanks containing
(4)
volatile products, since effective water cooling of their roof structures is impracticable.
(7) An open area or small (e.g. temporary) building without shielded means of escape.
This is either an unshielded area of critical importance where personnel, not equipped
with protective clothing, may be required at all times, including during emergencies, or
(8)
a place difficult or dangerous to evacuate at short notice (e.g. plant entrance, hospital,
sports stadium).
Distances relating to vessels exceeding 135 m3 capacity are to be verified by a radiation assessment.
(Refer 03.02.01.02(a)) for smaller vessels used in marketing companies.)
- laboratories, control rooms, main offices, Related to the size of above-ground storage vessel.
other buildings where people are Refer Figures 03.02.01.04 and 03.02.01.05.
concentrated, and site boundary.
- the external retention wall of atmospheric 1.5 diameters of the outer tank of a refrigerated product
pressure refrigerated product storage storage tank, i.e. 1.5 times the diameter of a possible
tanks. pool fire.
Notes:
Safety distances are to be measured from the periphery of the vessel nearest to the
(1)
hazard.
Definition of product class being in accordance with the 'Refining Safety Code' and the
(3)
'Marketing Safety Code' issued by the Institute of petroleum.
Minimum
3
* Vessels exceeding 2.5 m capacity shall not be located less than two tank diameters from
the solid wall of a building.
3
Note: Distances for vessels exceeding 135 m shall be verified by a radiation assessment,
refer 03.02.01.02.(a).
FIGURE 03.02.01.05 TYPICAL MINIMUM SAFETY DISTANCES FOE ABOVE-GROUND LPG
PRESSURE STORAGE VESSELS
(1) The minimum distance to fixed sources of ignition for vessels of over 500m3 is 30m.
Note: All distances other than those to fixed sources of ignition are to be verified by radiation
assessment (refer 03.02.01.02 (a)). Safety distances for storage vessels up to 135 m3 capacity are
given in section 07.
03.02.01.03 Grading and Ground Finish
When vessels are installed immediately adjacent to one another, product escape
from one must be prevented from flowing under another, e.g. by suitably
grading/provision of low deflection walls (maximum height 0.6m)
The slope shall be away from the piping manifold or other important areas, e.g.
processing units, etc.
To facilitate the flow of escaped product and prevent its penetration into the ground,
the ground under and within 5m of the periphery of a vessel or group of vessels shall
be smooth, well compacted, e.g. paved, and be free from any vegetation or debris.
03.02.01.04 Separation
03.02.01.05 Confinement
Bund walls around pressure storage interfere with the ventilation of the site and
impede the vaporisation/dispersion of escaped products and shall not be used.
In areas where stored products may be below their atmospheric boiling point at
prevailing ambient temperatures(e.g. butane in winter), a collection pit/retaining
system, remote from the LPG vessels, incorporating a waterlock as illustrated in
Figures 03.02.01.06 and 03.02.01.07 may be used.
For such a retaining system, the ground slope as mentioned in 03.02.01.03 may have
to be extended, and pump-out facilities may be required. A drainage pump could also
be used for product pump-out (see Figure 03.02.01.06). A retaining system shall be
located at a safe distance from site boundary, work areas, etc.
FIGURE 03.02.01.06 TYPICAL LAYOUT LPG PRESSURE STORAGE WITH COLLECTION
PIT/RETAINING SYSTEM.
03.02.01.06 Piping
Only piping directly associated with the storage vessels shall be located within the
storage area. Such piping for product and water shall be fire protected in the vicinity
of the vessels (refer 03.02.02.05 and Figures 03.02.02.02, 03.02.02.03, 03.02.02.04).
The surface water drainage system serving the LPG storage area shall in general be
designed in accordance with PTS 34.14.20.31. and the following conditions.
The drainage system shall be designed, such that it is capable of handling the
aggregate quantities of fire water, cooling water and rain water falling in the area,
without causing flooding of the open trenches.
A sand-catcher shall be placed between the open trench and the underground piping
system, in order to prevent ingress of solids.
A sump provided with a waterlock shall be combined with the sand-catcher, in order
to prevent the dispersion of LPG and the possible spread of fire to adjacent areas.
If this sump is directly connected to an underground piping system, then the sump
shall always be water-filled to an elevation of at least 100mm above the inside top of
the pipe.
If the open trench is also taken into account for containment purposes and the
promotion of evaporation of LPG (refer 03.02.01.05), the waterlock shall be designed
such that it is capable of preventing the escape of a spill of liquid LPG, as referred to
in 03.02.01.05.
In the event that the above-mentioned conditions cannot be met, e.g. in dry areas or
locations subject to freezing, PETRONAS shall be consulted in order to arrive at an
acceptable and safe solution.
FIGURE 03.02.01.07 TYPICAL RAIN/FIRE WATER DRAINING SYSTEM FOR LPG PRESSURE
STORAGE AREA
03.02.02.01 General
• At 20°C (68°F) 1 tonne (1 000 kg) of liquid propane occupies 2.00 m3.
•
3
At 20°C (68°F) 1 tonne (1 000 kg ) of liquid butane occupies 1.75 m .
They are site erected from pre-formed plates and shop fabricated sub-
assemblies.
(a) General
The design and construction must be in accordance with Group requirements, but
where national and/or local regulations are more stringent, then they must be
adhered to unless modifications can be negotiated.
The design, fabrication, erection, inspection and testing of LPG storage vessels
for manufacturing/chemical installations shall conform to the following
requirements:
The above also applies to individual LPG storage vessels for marketing
depots/consumer installations exceeding 265 m3 capacity.
(i) General
The design pressure of a vessel is related to the product for which the
vessel is to be designed, e.g. butane or propane.
The assessed temperatures used in the Group are 35°C 40°C and 45°C
for temperate, tropical and desert climates respectively (refer Table
03.02.02.03 (a))
The lowest of either 0°C, or LODMAT (Lowest One Day Mean Ambient
Temperature) or ABP (Atmospheric Boiling Point) + 50°C (refer PTS
30.10.02.31 , which refers to this lower design temperature as 'Reference
temperature').
The design pressure to be used for the top of the vessel shall be equal to the
vapour pressure of the product concerned (ref Table 03.02.02.03 (a))
corresponding to the maximum temperature covered under 03.02.02.03 (c) (2)
above, plus an allowance to ensure that in normal operation pressure relief
valves (PRV) do not open (refer PTS 31.22.10.32.). This allowance shall, for
manufacturing/chemical installations, be 10 per cent of the vapour pressure
(gauge) referred to above, or 1.7 bar, whichever is the greater. However, for
marketing depots/consumer installations, in view of the usually different
operating conditions, the allowance for vessels with capacities up to and
3
including 265 m shall be 10 per cent.
If such systems are not used, then the design pressure referred to above shall
be increased to cover the back pressures generated when filling.
Vapour pressure
Storage vessels in: Maximum (bar gauge)
design
Comm Comm
Temperature
butane propane
(ºC)
Temperate Climates 35 4.5 13.8
Tropical Climates 40 5.2 15.7
Desert Climates 45 6.0 17.8
In order to establish the design pressure for the top of the vessel, the applicable
allowance must be added.
The design pressure is defined for the top of the vessel and, therefore, the liquid
static head has to be added for the lower part of the vessel.
-5 0.80
- 10 0.66
- 15 0.56
- 20 0.46
03.02.02.04 Fabrication
For field erected large vessels, all manholes, nozzles and major structural
attachments (e.g. column stubs) shall be welded into the shell plates in the workshop
and all these prefabricated sub-assemblies shall be stress-relieved. In addition, they
shall be fully inspected by the Magnetic Particle method and preferably be
ultrasonically tested. This inspection shall be carried out after stress-relieving, but
before the hydrostatic test.
All gussets and lugs to be welded to the vessel shall be of the same material quality
as the shell plate concerned.
If the entire vessel is to be stress-relieved, welding of gussets and lugs shall be done
before stress-relieving
If the shell plate thickness exceeds 32mm, the entire vessel shall be thermally stress-
relieved after erection, in addition to the above requirements.
03.02.02.05 Vessel Connections
(a) General
The number of connections on vessels, particularly below the liquid level, shall be
minimised.
In the storage area, spiral wound gaskets shall be used and all nozzle/pipe
flanges shall be suitable to accommodate these.
All piping connected to a vessel shall be adequately supported, in such a way that
forces and bending moments on the vessel are kept within acceptable limits.
There shall be only one product line connection at the bottom of the vessel, which
may be used for filling, discharging and draining. This line shall be provided with a
remote operated fail-safe and fire-safe-type emergency valve (refer 03.02.04.02
and Section 02).
In this case, the product line shall be welded flush with the inside of the vessel
and be:
For those vessels which require site stress-relieving of the entire vessel (the
aperture at the bottom must be left large enough for entry/exit of the stress-
relieving equipment), the bottom aperture should be connected to the piping
system using tapered joints as necessary and all welds in this connection
must be radiographed and locally stress-relieved.
• Provided with a water drain system upstream of the shut-off valve at the
manifold (refer 03.02.02.05(c)).
• Fire protected with a water spray system between the vessel and the
separation/deflection wall.
(iii) Internally-mounted Emergency Valve
• Fire protected with a water spray system between the vessel and the
separation/deflection wall.
FIGURE 03.02.02.02 BOTTOM CONNECTION AT LPG PRESSURE STORAGE VESSELS
WITH EMERGENCY VALVE AT THE MANIFOLD SIDE
OF THE SEPARATION WALL
A drain connection shall be provided for each storage vessel, but the drain
location will depend on the design of the bottom connection.
It shall consist of a nozzle not larger than 50 mm nominal size (Schedule 80),
welded to the line (see Fig. 03.02.02.02/03) or vessel (see Fig. 03.02.02.04), to
which a valve, again not larger than 50 mm nominal size (upstream drain valve),
is connected.
The upstream and downstream drain valves must be positioned relative to one
another to allow simultaneous operation of both by a single operator.
The downstream drain valve shall be a hand-operated, quick acting, spring loaded
type (spring-to-close) which will operate as a dead man's handle. The
downstream drain valve should be followed by a 20 mm pipe of sufficient length to
protect the operator from flashed vapours, but such that, in case the drain effluent
discharges outside the periphery of the vessel, it can also be observed by the
operator controlling the drain system (refer also 03.02.04.05).
At locations where freezing can occur, the drain valves and lines shall be
adequately traced and/or insulated. If the drain facilities are connected to the
product discharge line, the latter should also be traced and/or insulated.
Note: In order to avoid spot corrosion (e.g. by caustic), steam tracing lines or
other heating systems shall never be tack-welded to the product/drain line
or be contact with them.
Liquid and vapour lines may be flange connected to the top of the vessel.
These connections shall be provided with an emergency valve, e.g. a remote
operated fail-safe and fire-safe shut-off valve, which is required arrangement
if the line extends below the maximum liquid level, or a combination of a non-
return valve and a shut-off valve which may be of the remote operated type.
(ii) Manhole
There shall preferably be only one manhole. It shall have an internal diameter
of at least 500 mm. The manhole cover may be utilised for the location of
connections/fittings, e.g. instruments.
PRVs must be connected to the vapour space of the vessel. For further
details refer 03.02.04.08.
(e) Instrument Connections
03.02.02.06 Supports
(a) General
These shall be supported on skirts or on leg supports of tubular steel. The inside
space of skirts shall be adequately ventilated.
For spheres, tubular steel supports are to be used in accordance with PTS
34.28.00.31.
(e) Fire-proofing
Steel legs and skirts of vertical vessels and spheres shall be fire-proofed up
to the shell of the vessel, irrespective of the height.(Refer Standard
Specification G-8-1.)
A rain deflector shall be installed at the top of each fire-proofed leg or skirt, to
prevent moisture and dirt from accumulating between the fire-proofing and
the supporting structure.
Galvanised grating used for stair treads and for covering platforms as per
PTS 34.28.00.31 and Standard Drawing S28022.
FIGURE 03.02.02.05 SUPPORT/SADDLE FOR HORIZONTAL LPG PRESSURE STORAGE
VESSELS
03.02.02.07 Anchorage
03.02.02.08 Foundation
The foundation shall be designed for the vessel full of water (refer PTS 34.00.01.30.
and PTS 34.19.20.31.).
03.02.02.09 Painting
03.02.03.00 Instrumentation
03.02.03.01 General
-The possibility of datum setting shall be considered on at least one level indicator.
(a) General
Also, low level alarm, low-low level (emergency) alarm or a combination of these
may be considered, e.g. for pump protection.
(i) Small vessels, which are batch filled (e.g. by rail/road cars) and closely
supervised during filling, as is typical for marketing depots, may be
equipped with minimum ullage gauges. These gauges must be set to
ensure that product filled at the lowest temperature will, after expansion,
still leave a minimum ullage space of 1 per cent of the gross vessel
capacity. Where meteorological data is not available for guidance, a 30°C
temperature rise should be allowed for.
(ii) Vessels, which are only filled by continuous low flow rate rundown
streams from process units, and other vessels which are operated
relatively unsupervised and are provided with PRVs discharging to a
flare/vent system, shall be equipped at least with a high level
indicator/alarm (LIA/H) and high-high level alarm (LA/HH), refer Note 1
and Figure 03.02.03.03.The LIA/H and LA/HH must be set at 90 per cent
and 95 per cent respectively of the gross vessel capacity, refer Note 2.
(iii) Vessels which are filled at high flow rates must be equipped with a LA/H
and two high-high level emergency alarms (LZA/HH), refer Note 1 and
Figure 03.02.03.04. Both LZA/HHs shall independently stop the filling
operation by closing the filling valve(s) and/or stopping
pumps/compressors. Measures shall be provided to protect upstream
facilities, e.g. the filling valve shall be closed slowly to avoid pressure
surges.
In order to ensure a safe operating margin, the LZA/HH shall be set not
higher than 95 per cent.
The LA/H shall be set at a level to allow sufficient time (10 minutes
minimum) to take action before the liquid level reaches the LZA/HH
setting
.
FIGURE 03.02.03.01 TYPICAL PRESSURISED LPG LIQUID VOLUME CORRECTION GRAPH
FIGURE 03.02.03.02 GRAPH TO DETERMINE THE SETTING OF LEVEL ALARM/ULLAGE
GAUGES FOR OVERFILL PROTECTION OF HORIZONTAL
AND SPHERICAL LPG PRESSURE VESSELS OF
VARIOUS DIAMETERS
FIGURE 03.02.03.03 PROTECTION SYSTEM FOR SITUATION IN WHICH FILLING/DELIVERY
RATES ARE BASED ON ALARMS AND CORRECTIVE ACTIONS ARE
MANUALLY IMPLEMENTED.
(Applicable to storage facility connected to a flare system - situation e.g. in process plants and
installations where filling rates are low)
FIGURE 03.02.03.04 PROTECTION SYSTEM FOR SITUATIONS IN WHICH FILLING/DELIVERY
RATES ARE HIGH AND CORRECTIVE ACTIONS ARE AUTOMATICALLY
IMPLEMENTED
Notes:
- For location of emergency shut-off valve (s): See figure 03.02.02.02 / 03 / 04.
- This figure indicates a number of instrument signal connections and read-outs that may not be
required in particular practical applications
- This figure only indicates suggested protection instruments; the LZA's and the PIZA
arrangements are shown in simplified form - refer PTS 31.10.03.10.
Note 1: LA/H, LA/HH and LZA/HH must be independent measurements. They
may, however, be combined and mounted on the main and auxiliary
gauges, provided these are of a (servo-operated) high accuracy type
(refer 03.02.03.02) and have power transmission and read-outs
completely separated to ensure that failure of both level indicators and
thus the associated transmitters/alarms at the same time is unlikely.
Note 2: The level at LIA/H is the normal maximum working level before allowing
for thermal expansion. The variation in temperature experienced in
practice, may allow a higher level or necessitate a lower level to be used.
Refer also (b)(i) above.
The pressure sensors shall be connected to the vapour space of the vessel. The
indicator shall be readable locally.
High or low pressure, and possibly even vacuum, can develop when vessels, without
vapour return and without spray/splash filling systems, are involved in high rate
transfer operations (e.g. as discussed in 03.02.03.03 (b) (iii)). In these cases
consideration may be given to installing a high and low pressure alarm and a high
and low pressure emergency alarm, with appropriate automatic trip actions.
The high pressure emergency alarm shall be set 5 per cent below the opening
pressure of the lowest PRV setting.
For the use and application of these facilities, reference is made to Section 02.
03.02.04.00 Valves
03.02.04.01 General
The various functions of valves are discussed in the following paragraphs in relation
to the systems in which they are used.
03.02.04.02 Remote Operated Shut Down Valves (ROVs) and Emergency Shut Down (ESD)
Valves
ESD valves close automatically when the power source for the actuator is cut off.
They shall be fail-safe and fire-safe to BS 5146.ESD valves are generally
hydraulically or pneumatically actuated.
Careful attention should be given to the location of the remote controls for ESD
valves, and to the number of ESD valves included in a single shut down system, e.g.
in a small depot, it may be considered safer to include all ESD valves in a single
system, such that all ESD valves in the system are closed simultaneously, whereas in
other plants it may be necessary to use several ESD systems. The shut down
controls shall be located at various positions over the site and shall be clearly
indicated with an appropriate notice. The location of the ESD valves' opening controls
will depend on the manner in which the plant is supervised and operated, but the
number of positions from which the ESD system can be opened shall be limited to the
minimum required for safe operation.
ESD valves shall not be provided with hand wheels or operating levers, unless there
are specific local requirements to provide manual override. Refer 03.02.04.02 (a) for
ESD valves on vessel connections.
Motorised (i.e. electrically activated) valves (MOVs) usually fulfill the requirements
specified above, under ROVs used for operational convenience. MOVs may be
operated from control rooms/centres with provision for local operation/override, e.g.
during maintenance.
The bottom outlet of each LPG storage vessel shall be fitted with an ESD valve.
Depending on the type of installation and its location, this ESD valve is either
located near themanifold and just downstream of the separation/deflection wall,
or internally in the bottom outlet nozzle (refer 03.02.02.05 (b)). Under no
circumstances is this valve to be provided with a handwheel/lever override.
This valve, which may be of the hydraulic, pneumatic or electric type, shall
satisfy the following criteria:
• It shall form an integral part of the storage vessel, i.e. it shall always be of
material of piping class 117 (refer 03.02.05.01 Note 3) and field
(preferably butt) welded to the bottom pipe, subsequently stress-relieved
and thereafter radiographed (the valve need not be dismantled for the
latter purposes).
• The valve and actuator assembly shall be protected from fire by a spray
water system (refer 03.02.02.05 (b)) In addition, the actuator shall be
protected by fire insulation.
• The valve and actuator assembly shall comply with the hazardous area
classification.
The product liquid and vapour lines on jetties shall be equipped with an ESD
system. This system shall consist of ESD valves in series and a logic control
system. The two valves, installed at approximately 0.5m distance from each
other, shall be fire-safe. Ball valves are to be selected in view of their rather
smooth closure characteristics. Closure time should be set at approximately
10 seconds, since high surge pressures could be expected when flow is
reduced suddenly.
The logic control system shall close the valves in case an emergency action is
initiated:
• Manually, by pushing one of the dedicated buttons located at various
strategic locations on the shore and on the ship (pendant box or ship-to-
shore link).
Check valves are designed to prevent the reverse flow of liquid or gaseous products.
In view of their possible unreliability, in particular when not adequately maintained
and tested, these valves should not be relied upon for positive shut-off.
Excess flow valves are designed to shut when flow conditions are in excess of design
flow rates, e.g. in case of a hose burst. They are not generally recommended for
refinery or depot emergency shut down applications for storage vessels, loading
points or multi-product systems, since their reliability in providing positive shut-off is
doubtful.
All vessels shall be provided with a double valve drain system for operational
drainage (refer 03.02.02.05 (c)) which, for manufacturing/chemical installations,
should preferably be lined up to flare.
At low points in pipelines and equipment, drain points shall be provided with a valve
which must be plugged when not in use.
Equipment and pipeline sections shall be provided with vent valves which enable a
final check on proper depressurisation. They can also be used for air removal during
purging operations. Vent valves shall be plugged when not in use.
03.02.04.07 Depressurising Valves/Provisions for Depressurising
(a) General
In the petroleum industry the following two types of PRV are commonly used:
A 'pilot operated PRV' is a type of PRV in which the major relieving device is
combined with, and is controlled by, a self-actuated auxiliary PRV. Typical
application is on storage vessels containing refrigerated product at its boiling point
at near atmospheric pressure (i.e. where the difference between system pressure
and ambient is very small). Although the pilot operated PRV has the advantage of
opening fully at its set point, the design features of the pilot system and any fail-
safe mechanism that may be incorporated may give rise to a fail open condition
and therefore render the valve doubtful for applications in pressurised systems.
The consequences of PRVs failing open on pressurised storage are considerably
greater than in atmospheric pressure systems.
As a consequence of the above, only direct acting, spring loaded type safety relief
valves are to be installed on LPG pressure vessels according to the ASME Code,
div 1 (part UG, Section VIII) and-to BS 5500, Appendix J.
• Fire exposure.
In view of the generally large difference in relief capacities (required for the above-
mentioned process and fire duties) and the different set pressures, separate
PRVs should preferably be provided for each duty. For manufacturing/chemical
installations the PRVs should preferably be lined up to a flare system. Where a
flare system is not practicable, disposal of released vapour via a remote vent
system to a safe location must be considered. Only in the event a remote vent
system not being possible, direct discharge to atmosphere is acceptable in
manufacturing/chemical installations.
FIGURE 03.02.04.01 TYPICAL ARRANGEMENTS FOR PRESSURE RELIEF VALVES WITH
SIDE OUTLET
With the above in mind, PRVs shall be installed in accordance with one of
the three following systems:
(i) All PRVs discharging to flare.
PRVs to cope with abnormal operating conditions, discharging into a
(ii) flare or remote vent system, and additional PRVs to cope with fire
exposure, discharging to remote vent or directly to atmosphere.
PRVs discharging directly to atmosphere if a flare or vent system is
(iii) absent, e.g. in marketing installations, or if linking to a flare system
would be impracticable.
(b) Installation Requirements
(i) PRVs must be connected to the vapour space of the vessel. The
nozzle(s) shall have an internal cross-sectional area at least equal to
the total inlet areas (connections) of all the PRVs. The cross-sectional
area of the discharge pipe from any PRV must not be less than the
outlet area of the PRV.
The line shall be self-draining towards the knock-out drum and must
be protected against mechanical damage. Its supports shall be fire-
proofed to prevent it from collapsing in a fire and being 'pinched shut'.
(iv) The stack pipes on side outlet PRVs shall be adequately supported on
the vessel shell/platform to minimise bending moments on the
nozzles, resulting from the reaction forces of relief discharge. In the
case of PRVs discharging to flare both the inlet and outlet lines shall
be self-draining.
(v) Isolating valves shall be fitted between PRVs and the vessel if it is
required to replace PRVs without taking the vessel out of service.
Where small vessels in consumer service can easily be emptied and
depressurised, isolating valves are not required.
Adequate protection must be provided to prevent incorrect/accidental
closure of isolating valves. These valves shall be interlocked and be
installed such that they cannot fail closed, e.g. if gate valves are used,
their spindles shall be horizontal. (Refer PTS 80.46.30.11.)
(vi) Spare PRVs shall be installed to fulfill the requirement that if PRVs
are removed, e.g. for maintenance, the PRVs remaining connected for
service ensure full protection of the vessel.
A vent shall be provided between the PRV and upstream block valve
to allow a check for tightness of the block valve, and to allow for in-
situ testing of the PRV.
If PRVs discharge to flare (or vent) the spare PRV shall also
discharge to flare (or vent).
(viii) Flare and vent systems shall incorporate adequate means to deal with
hydrate and ice formation, and operating procedures shall take the
occurrence of hydrate/ice formation into account
• Setting
• Sizing
PRVs for abnormal operating conditions shall be sized for the maximum
filling rate (either the maximum pumping rate of the supply pump(s), or
the maximum liquid capacity of the selected control valves in the supply
line, whichever can admit the largest flow into the vessel). The high-high
level cut-out controlling flow into the vessel (if present) shall not be taken
into account when sizing the PRVs.
• Setting
PRVs intended to deal only with fire exposure shall be set to open at a
pressure of not more than 110 per cent of the design pressure of the
vessel, and shall prevent it from rising above 120 per cent of that
pressure, i.e. in accordance with ASME and API.
• Sizing
It is suggested that when applying API RP 520 to spheres, the liquid level
to be taken into account should be the highest of that corresponding to 8
m above grade level, or at the vessel's half-full mark.
For very small spheres installed at grade, this generally means that the
vessel shall be assumed to be full of liquid; while big spheres having their
equator higher than 8 metres above grade shall be assumed to be half
full.
A TEV is a PRV actuated by inlet static pressure which opens, for the relief of liquid,
in proportion to the increase in pressure over the opening pressure. They are
required on sections of piping and equipment in which liquid product can be trapped,
to prevent overpressurisation caused by the thermal expansion of the liquid when
the temperature increases.
Means of static pressure relieving is also required to protect a pump where liquid
can be locked in between shut-off valves. It is recommended that a TEV is installed
in the pump suction piping between the pump and its suction valve.
The aim shall be to minimise the number of shut-off valves in a pipeline system,
thereby minimising the need to install too many TEVs, bearing in mind operational
and emergency requirements.
• It is permissible to omit TEVs in lines shorter than 10 m or if line contents are less
than 500 litres, as excessive amounts of associated small bore piping, required at
complex manifolds, could in itself create a hazardous situation.
• TEVs need not normally be installed at sampling/drain points and control or block
valves arrangements etc., where proper operating/maintenance procedures will
avoid blocking-in of liquid product.
• Through 'cascade' system back to the storage vessel (by-passing shut-off valves)
or to flare (via a knock-out vessel) or, if impracticable, to atmosphere at a safe
location (see Notes 1 and 2 and Figure 03.02.04.02).
• Through a separate header back to the storage vessel or to flare (via a knock-out
vessel) or, if impracticable, to atmosphere at a safe location.
• Higher than the maximum vapour pressure of the product in the line.
• Lower than the piping design pressure, decreased by 'N' bar. 'N' being the
number of cascading TEVs (refer Note 2).
• Higher than the pump shut-in pressure, but lower than the piping design
pressure.
Note 1: The discharge of the TEVs should preferably be against the normal direction
of flow, subject to the location of the final relieving facility.
• Combine TEVs located close together, relieving into a header and by-
pass more than one shut-off valve, or.
• Increase the piping design pressure, ultimately up to its full service limit
rating.
FIGURE 03.02.04.02 ARRANGEMENT OF THERMAL EXPANSION VALVES IN CASCADE
SYSTEM
03.02.05.00 Piping
03.02.05.01 General
Piping, and piping components, for liquid and gaseous propane, butane and mixtures
shall be in accordance with PTS 31.38.01.11. and PTS 31.38.01.12. Reference is
also made to Table 03.02.05.01 (a).
Note 1: Class 111 for liquid and gas at a temperature range from 0°C to
40°C. Class 111 may also be applied at locations where ambient
temperatures are never sub-zero, but when, due to depressurising,
the liquid or gas in the line may reach a sub-zero temperature,
followed by repressurising only when the temperature has risen to
above zero.
Note 2: Class 117 for liquid and gas at a temperature range from -50°C to
150°C.
Note 3: The bottom pipe of a pressure storage vessel including the first
valve at the manifold, thus forming an integral part of the storage
vessel, shall always be Class 117.(Refer 03.02.02.05 (b) (i).)
Butt-welded connections are preferred for all sizes, but where flanges are
unavoidable or necessary, raised face flanges shall be fitted. For reasons of
mechanical strength product transfer piping for refinery and depot storage shall be
minimum 50 mm nominal size.
The pressure rating of the pump suction valve as well as the piping between this
valve and the pump shall be the same as that selected for the discharge piping.
TABLE 03.02.05.01 (a) PIPING CLASSES FOR LIQUEFIED AND GASEOUS PROPANE, BUTANE AND MIXTURES
(According to PTS 31.38.01.11)
Service Temperature º C
Piping Service Piping Class limits Pipe material Remarks
Class Experience
Medium State Minimum Maximum*
Hydrocarbons
Non-Corrosive
Butane and Gas 101 340 max 0 340/400 Carbon Steel (Pipe forming integral part of
lighter
(vessel. For service up to 200 º C
(use Class 102 if ball valves are
(required.
Liquid-Gas 102 190 0 200 Carbon Steel
Liquid/Gas 111 40 max 0 40/100 Carbon Steel
Liquid/Gas 117 65 max -50 150/100 Carbon Steel )
max (fire grain) )Bottom pipe forming an integral
Liquid 218 -80 to 0 -80 150 3,5 Ni steel )part of pressure storage
Liquid 309 -170 to 0 -200 150/100 Stainless steel )vessel. See PTS 30.10.02.31
TP 304 )
Other Liquid/Gas 101 400 max 0 340/400 Carbon Steel
hydrocarbons
* Where two maximum temperature limits are shown different piping pressure ratings apply.
Threaded connections are not accepted in manufacturing/ chemical plants. As,
however, small equipment as used in marketing depots/consumer installations may
only be readily available with threaded connections, these are accepted in such
installations up to and including 50 mm nominal size (refer Section 07).
Piping for instruments, sampling points, etc. may be minimum 12 mm nominal size
(schedule 80) when protected by an isolation valve at the nozzle (refer
03.02.02.05(e)), and if protected against impact, e.g. by bracing. This piping shall be
as short as possible and extended branching should be avoided.
All pump suction lines shall slope continuously downwards from storage vessel to
pump suction.
Table 03.02.05.01(b)
Equivalent nominal pipe sizes
inch mm
0.5 15
0.75 20
1 25
1.5 40
2 50
3 80
4 100
6 150
8 200
10 250
12 300
14 350
16 400
18 450
20 500
22 550
24 600
Piping systems for propane and butane should preferably be segregated to prevent
propane from entering butane systems or vice versa.
If this is impracticable, it shall be ensured that in case of a faulty operation the system
will not be endangered and the faulty operation will be evident, e.g. by use of
pressure emergency alarms or trips.
Piping systems for handling more than one grade of LPG should either meet (i) or (ii)
below.
(i) The total system should either be designed for propane unless all connections
between the propane and butane systems are so designed as to allow only one
system to be connected at a time by either of the following:
• Swivel joints, when changing of connections occurs regularly, e.g. one liquid
and vapour line being used for more than one grade.
The system shall ensure that in case more than one connection has to be
switched, they shall all be switched simultaneously, e.g. by interlocks.
An ESD valve, preferably remote operated, with a non-return valve, shall be fitted
close to the termination of all piping to which flexible arms/hoses are connected for
loading and discharging. Refer also Section 02.
Note: Excess flow valves are not recommended for emergency shut down duties in
refineries or depots.
All lines should be painted with the correct colour recognition bands and lettering.
The recommendations for LPG colour coding and the location of such coding is as
follows:
(iii) Whatever additional marking is used to suit local conditions (use of mixtures,
names of brands, etc.) the marking indicated in the last column of (i) should
also be applied.
(iv) Common lines shall have a clear indication of the products handled,
adjacent to control valves, cross-over connections and offtake filling points
etc.
Separate purging connections shall not be provided if use can be made of existing
drains, vents and sampling points.
03.02.08.00 Electrical
All electric power, lighting installations and equipment must be in accordance with the
area classification requirements as defined in IEC 79.
03.02.10.01 General
LPG used for most commercial purposes, e.g. as a fuel gas, must possess a
distinctive and preferably an unpleasant odour to assist its detection in case of
leakage. However, odorisation is not required if harmful in the use of, or further
processing of, the LPG, e.g. for certain particular applications, such as feedstocks
and aerosols, or if it will serve no useful purpose as a warning agent in such use.
The odorant used shall be non-corrosive, shall have the lowest practicable sulphur
content and shall have a boiling point as near as possible to that of LPG.
Care is necessary in handling those odorants which are toxic in concentrated form.
Many odorants tend to be absorbed to some degree by the steel walls of storage and
transport vessels so that increased doses may be necessary when new units are first
introduced into the system.
The recommended and most commonly used odorant is entyl mercaptan (C2 H5 S H).
Possible alternatives are dimethyl sulphide [ (CH 3) 2 S] or tetrahydrothiophene (THT),
[ (CH 2) 4 S]. In Japan, two product known under their trade names of AL-741 and
CP-380 are generally used. Relevant physical properties of these products are given
in Table 03.02.10.02
Table 03.02.10.02
Physical properties of LPG odorants
(mainly based on suppliers' data)
As shown in Table 03.02.10.02 the odorising agents are generally volatile, highly
flammable liquids, the vapours of which are heavier than air and may spread over the
ground. Obviously all odorants possess a very strong, obnoxious odour and in
addition some exhibit certain toxic properties, particularly ethyl mercaptan.
The latter is a moderately toxic substance in the event of ingestion and inhalation,
leading to temporary effects to the nervous system. It is an irritant to the skin and
mucous membranes, and it is irritating to the eyes. Its threshold limit value (TLV) -
time weighted average (TWA) concentration for a normal eight hour working day or
40 hours work week - is 0.5 ppm (1 mg/m3).The TLV - short term exposure limit
(STEL) which is the maximum concentration to which workers can be continuously
exposed for a period up to 15 minutes without suffering irritation, chronic or
irreversible tissue change or narcosis - is 2 ppm (4 mg/ m3).
Every plant must have copies of the odorant manufacturers safety data sheet readily
available at all times.
The storage and handling facilities for odorising agents shall be designed with due
regard for the above properties, refer 03.02.10.05.
Small odorant spills should be chemically neutralised with ordinary household bleach
solution (5 per cent) and subsequently washed away with water. Solid bleach (active
component sodium hypochlorite) shall never be used as it may produce a violent
reaction with the odorant. The use of bleach solution is less effective with sulphide
type odorants which are far more oxidation-resistant than the mercaptans.
The obnoxious smell accompanying a small spill may be counteracted with masking
agents. It must be appreciated, however, that the masking agent does not destroy the
odorant but merely counteracts the odour.
If concentrations are higher than the TLV (0.5 ppm) self-contained respiratory
equipment should be worn. Protective clothing shall include chemical type safety
goggles, PVC/special rubber type gloves and cotton overalls or laboratory coats.
The recommended injection rates vary according to the type of odorant used.
Sometimes a certain concentration of odorant is required by the product specification.
In all other cases the recommended injection rate shall be applied. These are based
on NFPA or suppliers' recommendations as shown in Table 03.02.10.04.
Table 03.02.10.04
Recommended injection rates
Type of odorant Basis 1b/10 000 USG of g/m3 LPG cc/m3 mg/kg
LPG
Ethyl mercaptan NFPA 58 1.0 12 14 20-25
ed 1983
Dimethyl sulphide No value available
Tetrahydrothiophene NFPA 58 6.4 77 77 130-160
(THT) ed 1983
AL- 741 Supplier 40-60
CP-380 Supplier > 40
As some odorants, e.g. ethyl mercaptan react with iron oxide which is normally
present in newly built installations, vessels, pipelines, etc. in the form of rust, a
substantial quantity of odorant can initially be lost during the commissioning stage of
new installations
Bulk storage tanks for odorants shall be fabricated in accordance with Group
requirements and national/local regulations, refer 03.02.02.03. The design pressure
shall take into account any pressure applied to the vessel for operational reasons,
e.g. transfer of the odorant.
Vent lines from tanks/containers and relief valve outlets must be lined up to flare. If
this is impossible the vented fumes must be scrubbed through a bed of activated
carbon in order to remove the obnoxious odour.
FIGURE 03.02.10.01 DETAILS OF ODORANT STORAGE
NOTES:
1. Odorant drum
3. Drain
4. Sight glass
(a) General
All pipe work and vessels shall be thoroughly cleaned before putting them into
odorant service because of possible damage to fine tolerance metering, pumping
and control units.
Figure 03.02.10.02 shows a typical layout where the odorant measuring vessel
can be filled with sufficient odorant for, say, one bulk load. The odorant is injected
into the LPG line by the pressure of the blanketing gas. Injection takes place
gradually during loading as controlled by the needle valve. In either in one shot
shortly after the start of loading or the latter case, the injection rate may be
checked by isolating the bottom of the sight glass and connecting it to the LPG
line. To prevent the blanketing gas from entering the LPG line, the odorant valves
must be closed immediately after completion of the LPG loading operation.
Automation of this shut-off may be considered, e.g. by using the no-flow signal
from the LPG line.
This simple injection method is suitable for very constant LPG flows or for single
batch bulk loads but requires proper supervision for this manual operation. In the
case of bulk loads, a single injection early during loading ensures proper mixing
with the LPG, owing to the turbulence created in the receiving tank by the
incoming LPG.
FIGURE 03.02.10.02 INJECTION SYSTEM-USING PRESSURE INJECTION
NOTES:
3. Needle valve
NOTE A:
The odorant flow rate is independent of the LPG flow. A timer stops the injection
automatically upon completion of odorant injection. A pump 'running' visual signal
may be used to indicate the correct operation of the system.
In this system (see Figure 03.02.10.04) the LPG flow controls the operation of the
odorant injection pump, in order to maintain the required odorant injection ratio at
all LPG flows. Control may be by on-off operation (in case of small, solenoid-
operated pumps), by pump stroke frequency and/or stroke volume. In all cases
the pump is stopped when the LPG flow ceases. Additional provisions (such as a
pump 'running' visual signal) may be included to indicate proper operation of the
system. The complete system is available commercially as a package.
Although pure and dry odorants have, generally, little corrosive effect on mild steel,
for general use stainless steel is recommended, in particular where intermittent
exposure to liquid odorant and air is unavoidable.
At all times care must be taken to avoid any mixing of water with ethyl mercaptan in
particular, e.g. the system must be thoroughly dried before the introduction of
odorant, in view of corrosion problems.
FIGURE 03.02.10.03 INJECTION SYSTEM - USING METERING PUMP
NOTES:
1. Odorant drum
3. Metering/Injection pump
4. Electric motor
5. Sight glass
FIGURE 03.02.10.04 FLOW PROPORTIONAL INJECTION SYSTEM
NOTES:
1. Odorant drum
3. Metering/Injection pump
4. Electric motor
5. Sight glass
03.03.00.00 UNDERGROUND AND MOUNDED STORAGE OF LPG IN PRESSURE VESSELS
03.03.01.01 General
Vessel(s) shall be located such that they do not affect other nearby underground
structures, e.g. foundations, pipelines, sewers, or are themselves (the vessels) not
subjected to loads from vehicular traffic or other hazards like power cables, etc.
unless designed for these conditions.
(a) Plant Storage - Spacing of Underground and Mounded LPG Pressure Vessels
Vessels not completely mounded shall, as far as the uncovered portions are
concerned, be treated as above-ground vessels.
The radiation flux levels referred to in 03.03.01.02(a) above shall be based on the
ignition of product discharging from the vessel relief valve(s), as well as escaping
from the vessel or its appurtenances, or from other flammable storage systems
and possibly forming a pool.
(c) Leakage
The rate of leakage and its duration used in 03.03.01.02(b) shall be based on
identified possible leak sources in the system.
When considering radiation from a relief valve(s) fire, the valve(s) shall be
assumed to be discharging at maximum design flow rate and with atmospheric
conditions relevant to the site.
(e) For distances from LPG handling facilities to fixed sources of ignition,
03.02.01.02(e) refers.
Buried/mounded pressure vessels shall be in direct contact with their cover, i.e. the
installation of vessels in open underground vaults is not acceptable
The minimal thickness of the soil cover shall be 1 m so that adequate protection
exists against fire radiation, flying objects and frost penetration.
For mounded vessels the covering layer shall be finished to prevent erosion by rain or
wind, e.g. by seeding with grass.
The location of buried vessels shall be clearly marked at ground level. The back filling
of the pit must be done with material which will not damage the vessel or its
protective coating; this also applies for the surrounding layer of mounded vessels.
- Protected (1)
44
- Unprotected (2)
8
The external retention wall of refrigerated produce storage
tanks, storage tanks containing other flammable products
(3) and process:
Facilities:
- Protected (1)
32
- Unprotected (2)
8
The above-ground connections, including PRVs of 8
buried/mounded LPG storage vessels
Filling/discharge points
8
Personnel inside boundary
Process area (4) 8
Protected work area (5) 8
Work area (6) 5
Critical area (7) 1.5
Plant boundary
Remote area (8) 13
Urban area (9) 5
Critical area (7) 1.5
FIGURE 03.03.01.01
NOTES:
Special consideration should be given to the location of floating roof tanks containing
(3)
volatile products, since effective water cooling of their roof structures is impracticable.
A permanent building where personnel inside are shielded and/or have shielded means
(5)
of escape.
(6) An open area or small (e.g. temporary) building without shielded means of escape.
This is either an unshielded area of critical importance, where personnel not equipped
with protective clothing may be required at all times, including during emergencies, or a
(7)
place difficult or dangerous to evacuate at short notice (e.g. plant entrance, hospitals,
sports stadium).
• Laboratories, control rooms, main offices, other Related to the size of the
buildings where people are concentrated and site buried/mounded storage vessel. Refer
boundary Figure 03.03.01.03
• The external retention wall of atmospheric pressure The diameter of the outer tank of a
refrigerated product storage tanks refrigerated product storage tank =
diameter of a possible pool fire
APPENDIX 03.03.01.02
NOTES:
Safety distances are to be measured from exposed nozzles, tank fittings, etc. of the
(1)
vessel nearest to the hazard.
Consideration may need to be given to restricting the movement of traffic during draining
(2)
operations.
Definition of product class being in accordance with the Refining Safety Code and the
(3)
Marketing Safety Code issued by the Institute of Petroleum.
(4) Distance required for safe operation of earth moving and other maintenance equipment.
FIGURE 03.03.01.03 BURIED/MOUNDED LPG PRESSURE STORAGE VESSELS MINIMUM
SAFETY DISTANCES AS REFERRED TO IN FIGURE 03.03.01.01
(1) The minimum distance to fixed sources of ignition for vessels over 500 m3 is 30m
(2) Dr 2 diameter of the outer tank
(3) Vapour deflection walls may be required where this distance is used to a building etc
considered a source of ignition
Note: All distances other than those to fixed sources of ignition are to be verified by radiation
assessment (refer 03.03.01.02) Safety distances for strange vessels up to 135 m3 capacity
are given in section 07
03.03.02.00 Pressure Storage Vessels
Horizontally placed cylindrical vessels are normally used for buried/mounded storage.
(a) General
Reference is made to 03.02.02.03 (b), with the provision that PTS 31.22.10.36. is
not applicable for mounded/buried pressure vessels.
Due to the external asymmetrical loading, stiffening rings may need to be applied
in order to avoid uneconomical wall thicknesses.
(i) General
In general, frost will not penetrate through the earth cover and consequently
the temperature of the vessel's contents will not fall below the product's ABP.
When appropriate pressure equalisation facilities between vessels are
provided there is generally no need to take vacuum conditions into account.
(a) General
03.02.02.05 (a) applies with the following additions: connections for buried
vessels shall preferably be on the top and shall be extended to a level above the
soil cover. Fittings at or above ground level must be protected against accidental
damage, e.g. impact.
For mounded vessels bottom liquid inlet and outlet connections may have
advantages. For manufacturing/chemical installations all bottom connections shall
be welded to the vessel and to the vessel's valves, i.e. no flanges shall be present
on the vessel side, i.e. 03.02.02.05 (b) (i) and (ii) apply. Similarly all instrument
connections in the bottom shall be equipped with a valve which shall be welded
on the vessel side.
03.02.02.05 (c) applies with the following supplement. For underground and
mounded storage vessels draining will normally require the installation of a dip
pipe with top connected drain valves.
03.03.02.04 Supports/Foundation
Depending on the soil conditions, vessels may be placed on a compacted sand bed
or on a piled supporting structure.
3
For storage vessels exceeding 50 m capacity, a foundation design based on a soil
investigation is recommended. The expected overall and differential settlements,
requirements for mound stability and drainage shall be considered.
Overall settlements, based on the measurements taken immediately prior to
commissioning, exceeding 0.5m are not acceptable, although their effects on vessel
and connected piping shall be considered. Settlement after installation may be
reduced by preloading of the support area before installation. Maximum permitted
differential settlements must be determined at the project design stage and
procedures must be established to regularly monitor these settlements throughout the
life of the vessel(s).
The angle of circumference over which a sand bed supports the vessel shall be
assumed not to exceed 120°. The beneficial effect of lateral soil support is not to be
taken into account in the design of mounded vessels.
The vessel should preferably be placed at least 0.6 m above ground water level and
both site and backfill material should preferably be chosen to limit the possibility of
water levels reaching the vessel. Adequate precautions must be taken to prevent
flotation.
The vessel shall be sloped a minimum of 0.25 per cent to facilitate drainage.
If under operational conditions the temperature of the vessel can drop below 0°C,
measures must be taken to prevent frost-heave, e.g. by applying a surrounding layer
of course sand and by reducing the water ingress in the mound/buried tank area, e.g.
by applying a top layer of clay. In such a case the vessel shall be placed at least 1 m
above the original ground level.
(a) General
Vessels shall be adequately protected to resist the local soil/cover corrosion and a
combination of coatings and cathodic protection may be used.
(b) Coating
Coating shall be able to resist frictional forces between the vessel and the
surrounding soil under all operational conditions, i.e. also when the soil is frozen.
In case a primer is used, this shall be a thin film epoxy paint. Primers of the
inorganic or organic zinc type should not be used for this application.
03.03.03.00 Instrumentation
03.03.03.01 General
03.03.04.00 Valves
03.03.04.01 General
(a) General
The total relief capacity required shall cover the greater of either the relief required
for abnormal operating conditions or for fire exposure.
The relief capacity for fire exposure shall be determined as specified by the IP
Model code of safe practice (Part 9, Volume 1, LPG):
•
3
For vessels larger than 135m , the relief capacity shall be according to API
RP520.
• For vessels smaller than and equal to 135m3, the relief capacity shall be 30
per cent of the requirement for an uninsulated above-ground pressure vessel
of the same capacity (in accordance with NFPA 58).
03.03.05.01 General
The status of the level of cathodic protection has to be checked once per year in the
case of scarificial anode protection, and once per three months for that of impressed
current protection. The results of the survey are to be recorded and filed. Any
discrepancy in the protective level has to be corrected before the next survey.
Once every 3 years a survey has to be performed showing the status of the coating of
the vessel. For such a survey, the 'Pierson method', by using the Pierson holiday
detector, is accepted. Corrective action is only required when the location of coating
defects coincides with a deterioration of the cathodic protection.
Detailed records shall be kept with respect to all periodic inspection, testing and
maintenance.
Pressure testing may replace all of the above vessel inspection requirements.
For more details on pressure vessel inspection refer to SIPM Report MF 85-0330.
For mounded LPG vessels, overall and differential settlement over the length of the
vessel must be measured and recorded. The reference for the measurements shall
be the initial data recorded prior to commissioning. The applicable intervals for
subsequent measurements are:
• Every three (3) months during the first year of operation.
• Every six (6) months during the second and third year of operation.
• Every twelve (12) months thereafter.
03.03.06.00 Piping Refer 03.02.05.00
This type of storage is not yet extensively applied, and detailed information on the
various types is not readily available.
Information is being collected and is intended to be published in the next issue of this
manual.