Focused Specs Requirements:

Number of units Required : 6 units of generator for 6 different sites

Electric Motor Specs: Danfoss / HOYER water mist High pressure pump
Number of motors 1
Starting and control circuit type Frequency converter: (1: 1) of rated power to start
Maximum power consumption 30 KW or less as per controller signal
Accessories (no starting current) 7 KW to 10 KW
Generator Specs Needed: Alternator
COO Europe , or equivalent as per preferred by local market
RPM 1500 (to be complied with alternator to generate 50 KVA, 50 HZ)
PHASE 380-415 V, 3 PHASES
FREQUENCY 50 HZ (Kindly make sure of Pump Frequency requirement)
Rated power at standby 50 KVA (operating load 37 KW Pump with accessories)
Rated power at prime 45 KVA + 10% overload any time
Cooling Water cooling
AutoStart Europe, or equivalent as per preferred by local market
Voltage regulation +0.9 : 1.1% acceptable
Generator Specs Needed: Engine
COO English, Perkins preferred
RPM 1500 (match with alternator) also alternator able to handle over speed 120%
Maximum Consumption / fuel 9.7: 12 L / Hour – Diesel
Number of cylinders 3 : 4 acceptable
Turbo charger Yes
Protection alarm sensors Yes
Water fuel separator Yes
Water jacket heater Not required
Battery charger Yes
Manual of trouble shooting Yes
ATS COO (local or higher) As preferred for local market
Sound proof Not Required
Diesel tank 50 L or Higher ( able to deliver 4 hour working in full duty )