Professional Documents
Culture Documents
Service Literature: Corp. 9728 L12 Revised 01 2002
Service Literature: Corp. 9728 L12 Revised 01 2002
Service Literature: Corp. 9728 L12 Revised 01 2002
Corp. 9728−L12
Service Literature Revised 01−2002
SPECIFICATIONS
Model No. 80UHG3/4(X)Ć100 80UHG4/5(X)Ć100 80UHG3/4(X)Ć120 80UHG4/5(X)Ć120
Input Btuh (kW) 100,000 (29.3) 120,000 (35.2)
Output Btuh (kW) 82,000 (24.0) 98,400 (28.8)
A.F.U.E. 80.1% 80.0% 80.0% 80.1%
California Seasonal Efficiency 76.5% 77.0% Not Available 75.5%
Flue size connection diameter Ċ in. (mm) round 4 (102)
Temperature rise range Ċ _F (_C) 45 Ć 75 (25 Ć 42) 35 Ć 65 (19 Ć 36) 45 Ć 75 (25 Ć 42)
High static certified by A.G.A./C.G.A. Ċ in wg. (Pa) .50 (125) .65 (162) .50 (125)
Gas Piping Size I.P.S. Natural or LPG/propane 1/2 (13)
Page 2
BLOWER DATA
80UHG2-45, 80UHG2-60 AND 80UHG2-75 BLOWER PERFORMANCE
External Static Air Volume at Various Blower Speeds
Pressure High MediumĆHigh MediumĆLow Low
in. w.g. Pa cfm L/s cfm L/s cfm L/s cfm L/s
0 0 1270 600 980 460 770 365 570 270
.05 12 1245 590 975 460 770 365 565 265
.10 25 1220 575 975 460 770 365 565 265
.15 37 1195 565 965 455 765 360 560 265
.20 50 1170 550 960 455 760 360 560 265
.25 62 1140 540 950 450 760 360 555 260
.30 75 1110 525 940 445 760 360 550 260
.40 100 1060 500 910 430 750 355 545 255
.50 125 990 465 880 415 740 350 540 255
.60 150 900 425 810 380 690 325 530 250
.70 175 800 380 740 350 630 295 520 245
NOTE Ċ All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished) in place. Also see Filter Air Resistance table
Page 3
BLOWER DATA
80UHG4/5Ć100 AND 80UHG4/5Ć120 BLOWER PERFORMANCE
External Static Air Volume at Various Blower Speeds
Pressure High MediumĆHigh Medium MediumĆLow Low
in. w.g. Pa cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
0 0 2450 1155 2160 1020 1970 930 1700 800 1500 710
.05 12 2440 1150 2155 1015 1965 925 1695 800 1500 710
.10 25 2430 1145 2150 1015 1960 925 1690 800 1495 705
.15 37 2415 1140 2135 1010 1950 920 1685 795 1495 705
.20 50 2400 1135 2120 1000 1940 915 1680 795 1490 705
.25 62 2380 1125 2105 995 1930 910 1675 790 1480 700
.30 75 2360 1115 2090 985 1915 905 1670 790 1470 695
.40 100 2310 1090 2050 965 1870 880 1650 780 1440 680
.50 125 2260 1065 2000 945 1810 855 1610 760 1410 665
.60 150 2180 1030 1950 920 1750 825 1560 735 1370 645
.70 175 2100 990 1890 890 1700 800 1520 715 1330 630
NOTE Ċ All air data is measured external to unit with 1 in. (25 mm) cleanable filter (not furnished) in place. Also see Filter Air Resistance table
Page 4
VENT ADAPTER
80UHG PARTS IDENTIFICATION CABINET TOP
HEAT EXCHANGER
ASSEMBLY
FLUE BOX
FRONT ACCESS
PANEL
BURNER
ASSEMBLY
TRANSFORMER
CONTROL
BOARD SECONDARY
LIMITS CABINET
BOTTOM
BLOWER ASSEMBLY
FIGURE 1
COMBUSTION AIR
PROVE SWITCH
MANIFOLD
Left
Bottom Back
BURNERS
Front
Top
Right
HEAT EXCHANGER
GAS VALVE
COMBUSTION AIR INDUCER
COLLECTOR
FIGURE 2
Page 5
80UHG BURNER ASSEMBLY (shown in upflow position)
-2 MODEL SHOWN
SURELIGHT ROLLOUT
IGNITOR SWITCHES
BURNER BOX
TOP
VEST PANEL
UPPER
BURNER
MOUNTING
RAIL
LOWER
BURNER
MOUNTING
RAIL
FLAME
BURNER
SENSOR HEAT EXCHANGER
PRIMARY LIMIT
Top
Back
ORIFICE Left
GAS VALVE
Right
Front
BURNER BOX
MANIFOLD
Bottom
FIGURE 3
I-UNIT COMPONENTS (Figures 1, 2, 3) 1- Control Transformer (T1)
80UHG unit components are shown in figure 1. The gas A transformer located on the blower housing provides
valve, combustion air inducer and burners can be acĆ power to the low voltage section of the unit. Transformers
cessed by removing the burner access panel. Electrical on all models are rated 30VA with a 120V primary and a
components are mounted to the blower housing. 24V secondary.
80UHG units are factory equipped with bottom return air panĆ 2-Door Interlock Switch (S51)
els in place. The panels are designed to be field removed as A door interlock switch rated 16A at 125VAC is wired in seĆ
required for bottom air return. Knockout panels are provided ries with line voltage. When the blower door is removed the
for side return air. unit will shut down.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures DANGER
CAUTION Shock hazard.
Spark related components contain high voltage.
Electrostatic discharge can affect electronic Disconnect power before servicing. Control is
components. Take precautions during furnace not field repairable. If control is inoperable, simĆ
installation and service to protect the furnace's ply replace entire control.
electronic controls. Precautions will help to Can cause injury or death. Unsafe operation will
avoid control exposure to electrostatic disĆ result if repair is attempted.
charge by putting the furnace, the control and
the technician at the same electrostatic potenĆ
tial. Neutralize electrostatic charge by touching
hand and all tools on an unpainted unit surface,
such as the gas valve or blower deck, before perĆ
forming any service procedure.
Page 6
3− Furnace Control (A3) a−Electronic Ignition (See Figure 5)
On a call for heat the SureLight control monitors the com8
80UHG−2, −3 Models
bustion air inducer pressure switch. The control will not be8
80UHG−2 and −3 model units are equipped with the Len8 gin the heating cycle if the prove switch is closed (by−
nox SureLight ignition system. The system consists of
passed). Once the prove switch is determined to be open,
ignition control board (figure 6 with control terminal desig8
nations in table 4) and ignitor (figure 7). The board and ig8 the combustion air inducer is energized. When the differ8
nitor work in combination to ensure furnace ignition and ential in the prove switch is great enough, the prove switch
ignitor durability. The SureLight integrated board controls closes and a 15−second pre−purge begins. If the prove
all major furnace operations. The board also features two switch is not proven within 2−1/2 minutes, the control goes
LED lights for troubleshooting and two accessory termi8 into Watchguard−Pressure Switch mode for a 5−minute re−
nals rated at (4) four amps. See table 3 for troubleshoot8 set period.
ing diagnostic codes. Table 1 and 2 show jack plug termi8
After the 15−second pre−purge period, the SureLight igni8
nal designations. Units equipped with the SureLight
board can be used with either electronic or electro−me8 tor warms up for 20 seconds during which the gas valve
chanical thermostats without modification. The Sur8 opens at 19 seconds for a 4−second trial for ignition. The
eLight ignitor is made of durable silicon−nitride. Ignitor ignitor stays energized for the first second of the 4−second
longevity is also enhanced by voltage ramping by the trial. 80UHG units equipped with control 10M9301: ignitor
control board. The board finds the lowest ignitor tempera8 remains energized during the 4 second trial until flame is
ture which will successfully light the burner, thus increas8 sensed. If ignition is not proved during the 4−second peri8
ing the life of the ignitor. Each time power is applied to the od, the control will try four more times with an inter purge
furnace, the SureLight board performs a selfcheck in8
and warm−up time between trials of 35 seconds. After a to8
cluding energizing the combustion air blower for a period
of 1 second. tal of five trials for ignition (including the initial trial), the
control goes into Watchguard−Flame Failure mode. After a
TABLE 1 60−minute reset period, the control will begin the ignition
SureLight BOARD J156 (J2) TERMINAL sequence again.
DESIGNATIONS The SureLight control board has an added feature that
PIN # FUNCTION
prolongs the life of the ignitor. After a successful ignition,
the SureLight control utilizes less power to energize the ig8
1 Combustion Air Inducer Line
nitor on successive calls for heat. The control continues to
2 Ignitor Line ramp down the voltage to the ignitor until it finds the lowest
3 Combustion Air Inducer Neutral amount of power that will provide a successful ignition.
4 Ignitor Neutral This amount of power is used for 255 cycles. On the 256th
call for heat, the control will again ramp down until the low8
TABLE 2 est power is determined and the cycle begins again.
SureLight BOARD J58 (J1) TERMINAL b−Fan Time Control
DESIGNATIONS The fan on time of 45 seconds is not adjustable. Fan off
PIN # FUNCTION time (time that the blower operates after the heat demand
1 Primary Limit / Pressure Switch Out has been satisfied) can be adjusted by flipping the dip
switches located on the SureLight integrated control. The
2 Secondary Limit
unit is shipped with a factory fan off setting of 90 seconds.
3 24V Fan off time will affect comfort and is adjustable to satisfy
4 Not Used individual applications. See figure 4.
5 Rollout Switch In
6 24V
7 Primary Limit In FANOFF TIME ADJUSTMENT
60sec. 90sec. 120sec. 180sec.
8 Ground
9 Gas Valve In
10 Pressure Switch In
11 Rollout Switch Out To adjust fan−off timing, flip dip switch to desired setting.
Page 7
The SureLight board is equipped with two LED lights for troubleshooting. The diagnostic codes are listed below in table 3.
TABLE 3
DIAGNOSTIC CODES
MAKE SURE TO ID LED’S CORRECTLY: REFER TO INSTALLATION INSTRUCTIONS FOR CONTROL BOARD LAYOUT.
Primary or Secondary limit open. Units with board 12L69: Limit must close within
5 trials for ignition or board goes into one hour limit Watchguard. Units with board
SLOW FLASH ON
56L84: Limit must close within 3 minutes or board goes into one hour limit Watch8
guard.
Pressure switch open or has opened 5 times during a single call for heat; OR:
OFF SLOW FLASH Blocked inlet/exhaust vent; OR: Condensate line blocked; OR: Pressure switch
closed prior to activation of combustion air blower.
ALTERNATING SLOW ALTERNATING SLOW
FLASH FLASH Watchguard − burners fail to ignite.
SLOW FLASH OFF Flame sensed without gas valve energized.
ON SLOW FLASH Rollout switch open. OR: 9 pin connector improperly attached.
ON ON
ON OFF Circuit board failure or control wired incorrectly.
OFF ON
FAST FLASH SLOW FLASH Main power polarity reversed. Switch line and neutral.
SLOW FLASH FAST FLASH Low flame signal. Measures below 0.2 microAmps. Replace flame sense rod.
ALTERNATING FAST ALTERNATING FAST Improper main ground or line voltage below 75 volts; OR: Broken ignitor; OR:
FLASH FLASH Open ignitor circuit.
NOTE − Slow flash equals 1 Hz (one flash per second). Fast flash equals 3 Hz (three flashes per second). Drop out flame sense current < 0.15 microAmps
ÉÉ
1 15 34 35 38 80 5 SEC
ÉÉ ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
ON Pre −Purge Ignitor Warmup Trial for Blower HOn" Post
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
OFF Ignition Delay Purge
ÉÉÉÉÉÉÉÉ
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
DEMAND
CA
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
ÉÉÉÉÉÉÉÉÉ
B
IGNITOR
GAS VALVE
INDOOR BLOWER
ÉÉÉÉÉÉÉÉÉ
*Blower on time will be 45 seconds after ignition. Blower off time will depend on HOFF TIME" Setting.
FIGURE 5
Page 8
SURELIGHT INTEGRATED CONTROL BOARD TABLE 4
TERMINAL DESIGNATIONS
COOL-H Blower - Cooling Speed (120VAC)
HEAT-H Blower - Heating Speed (120VAC)
EAC-H Electronic Air Cleaner (120VAC)
HUM-H Humidifier (120VAC)
XFMR-H Transformer (120VAC)
LINE-H Input (120VAC)
LINE-N Input (Neutral)
XFMR-N HUM-N Humidifier (Neutral)
EAC-N Electronic Air Cleaner (Neutral)
XFMR-N Transformer (Neutral)
CIR-N Not Used
PARK
(FLAME SENSE)
Flame
sense
SureLight Ignitor
SURELIGHT IGNITOR
FIGURE 6
4-Flame Sensor 80UHG -2 models
A flame sensor is located on the left side of the burner
support. See figure 8. The sensor is mounted on a
FIGURE 7
bracket in the burner support and the tip protrudes
into the flame envelope of the left-most burner. The NORMAL FLAME SIGNAL u 0.2 MICROAMPS
LOW FLAME SIGNAL v 0.2 MICROAMPS
sensor is fastened to burner supports and can be reĆ MINIMUM FLAME SIGNAL v 0.15 MICROAMPS
FIGURE 8
Page 9
5- Furnace Control (A3) 80UHG-1 Model when no voltage should be present, the control deĆenergizes
80UHG units are equipped with an integrated ignition/blower the combustion air inducer which terminates voltage to the
control (EGCĆ2) which controls ignition, safety circuits, valve. The system goes into hard lockĆout which is reset only
blower operation, fan off timing, and allows for thermostat by removing power to the unit.
connection and troubleshooting. The EGCĆ2 is a printed If flame is sensed when no flame should be present, the conĆ
circuit board which is divided into two sections, 120 and trol will energize the combustion and indoor blowers. The
24VAC. Line voltage comes into the board on the 120VAC unit will remain locked in this sequence until the flame is no
side. See figure 10. Terminal designations are listed in
longer sensed or the main power is turned off to reset the
tables 6 and 7.
control.
Ignition Control
The rollĆout circuit is also monitored by the EGCĆ2 control. If
80UHG units use the EGC-2 direct spark integrated the switch opens, the control will deĆenergize the gas
ignition control. The EGC-2 controls and monitors the valve, combustion air inducer, and indoor blower. The
entire sequence of operation. On a call for heat from the unit will remain deĆenergized until the switch is manualĆ
thermostat the control monitors the combustion air inĆ ly reset.
ducer prove switch. The control will not begin the heatĆ
ing cycle if the prove switch is closed (byĆpassed). Once
the prove switch is determined to be open, the combustion DANGER
air inducer is energized. When the differential in pressure
across the prove switch is great enough, the prove switch Shock hazard. Avoid personal injury. Make sure to
disconnect power before changing fan off" timing.
closes and a 15 second preĆpurge period begins. If the
prove switch does not close within 2 1/2 minutes, the conĆ
trol goes into 5 minute watchguard. After the preĆpurge peĆ Blower Operation / Fan Off Timings
riod, the gas valve will open and ignition (spark) will be atĆ Fan off" timing (time that the blower operates after the heat
tempted for 10 seconds. After ignition, the control initiates a demand has been satisfied) can be adjusted by moving the
ten second flame stabilization period. The flame stabiĆ jumper on the EGCĆ2 blower control board. Figure 9 shows
lization period allows the burners to heat up and the the various fan off" timings and how jumper should be posiĆ
flame to stabilize. Once flame is established, the control will tioned. To adjust fan off " timing, gently disconnect jumper
constantly monitor the burner flame using flame rectification. and reposition across pins corresponding with new timing.
Flame failure response time is 0.8 seconds. Unit is shipped with a factory fan off" setting of 180 seconds.
If the initial attempt for ignition fails, the sequence is reĆ Fan on" time is factory set at 45 seconds following the
peated up to five times. After the fifth trial, the control goes into opening of the main gas valve and is not adjustable.
Watchguard"*. During watchguard mode, the entire unit will Fan off" time will affect comfort and efficiency and is adĆ
be deĆenergized for one hour. After one hour the control will justable to satisfy individual applications. The fan off" timĆ
repeat the ignition sequence. Watchguard may be manually ing is initiated after a heating demand but not after a coolĆ
reset by breaking and remaking thermostat demand. ing demand.
*NOTE-If flame is established beyond the 10 second flame NOTEĊIf fan off" time is set too low, residual heat in
stabilization period then lost, the control resets for five more heat exchanger may cause primary limit S10 to trip, reĆ
ignition trials. The control can be reset five times during one sulting in frequent cycling of blower. If this occurs, adjust
blower to longer fan off" time setting.
unsatisfied thermostat demand, providing a maximum
of 25 trials for ignition. FANĆOFF TIME ADJUSTMENT
Safety Circuits TIMING To adjust fanĆoff timing:
JUMPER Remove jumper from EGCĆ2 and select
During the entire heating demand the control monitors the one of the other pin combinations to
safety circuits. If the primary or secondary heating limits achieve the desired time.
open, the control deĆenergizes the main gas valve and TIMING PINS
180
combustion air blower while the indoor blower remains enĆ 60 (seconds)
ergized. When the limit automatically resets, the ignition seĆ
quence also resets. If either of the limits trip five consecuĆ Leave jumper off for
tive times during one unsatisfied thermostat demand, the 240 second fanĆoff timing.
Page 10
Thermostat Connection TABLE 5
Thermostat wires are connected to the terminal strip EGCĆ2 DIAGNOSTIC CODES
found on the EGCĆ2 control board. DIAG #2 DIAG #1 DIagnostic Condition
Power ON". Normal Operation. InĆ
Troubleshooting Simultaneous Simultaneous creased flash rate indicates there
Flash Flash is a heating demand.
The EGCĆ2 control board is equipped with two diagnostic
Primary or Secondary
green LEDs to indicate the mode of failure. The LED lights On Flash Limit Switch Open.
are marked DIAG #1 and DIAG #2. The codes are given in AutoĆReset Switch.
Pressure Switch Watchguard,
table 5. Flash Off pressure switch opened during
operation.
A slotted edge connector is also provided for the Lennox
Alternate Alternate Flash Watchguard, burners
Diagnostic Module (part number 11K75). See figure 10. Flash failed to ignite.
When connected to the EGCĆ2 control board, the module disĆ Off Flash Flame sensed without
valve energized.
plays (in words) the diagnostic condition. RollĆout Switch Open.
Flash On ManualĆReset Switch.
Continuous Circuit board selfĆcheck failure or
On Continuous On ignition/blower control
is wired incorrectly.
7
6
5
4
DIAGNOSTIC LEDS
THERMOSTAT
TERMINAL STRIP
(DETACHABLE)
EDGE 1 4 7
CONNECTION
2 8
5
3 6 9
DIAGNOSTIC CODE ERASE JUMPER 3 2 1
24VAC (Remove power to control and short pins for
PLUG P20 10 seconds to erase previous code.)
FIGURE 10
Page 11
TABLE 6 SUPPLY AIR BLOWER
BLOWER CONTROL A15 TERMINAL DESIGNATIONS AND SECONDARY LIMITS SECONDARY
Terminal LIMITS (S21)
Designation Type Function
(See fig. 10)
R Screw Strip 24VAC to Thermostat (Red)
Manual Fan Input from Thermostat Top
G Screw Strip Back
(Green) Left
W Screw Strip Heat Demand Input from Thermostat Right
(White) Front
Cool Demand Input from Thermostat Bottom
Y Screw Strip (Yellow)
C Screw Strip Common Ground to Thermostat
1 1/4" Spade 24VAC Hot from Transformer
2 1/4" Spade 24VAC Return to Transformer
3 1/4" Spade 24VAC Ground
4, 5, 6 1/4" Spade 120VAC Return - 120VAC Common
120VAC Return - 120VAC Common BLOWER
7 1/4" Spade Input MOTOR
8 1/4" Spade Combustion Blower (Line Voltage)
MOTOR
9 1/4" Spade Heat Only Accessory (Line Voltage)
CAPACITOR
10 1/4" Spade 120VAC Hot to Transformer
11 1/4" Spade 120VAC Hot Input To Remove Blower From Unit: Remove Bolts and
12, 13 1/4" Spade Accessories (Line Voltage) Wiring Jackplugs. Then Slide Out Front of Unit.
14 1/4" Spade ACB Cool Speed (Line Voltage)
15 1/4" Spade ACB Heat Speed (Line Voltage)
FIGURE 11
7-Combustion Air Inducer (B6)
TABLE 7
All 80UHG units use a combustion air inducer to move air
EGCĆ2 CONTROL JACK/PLUG 20 TERMINAL DESIGNATIONS
through the burners and heat exchanger during heating
Pin # Function
operation. The blower uses a 120VAC motor. The motor
1 Rollout Switch Out
2 Spare operates during all heating operation and is controlled by
3 Gas Valve Common furnace control A3. The blower also operates for 15 seĆ
4 Pressure Switch Return conds before burner ignition (preĆpurge) and for 5 seconds
5 Hi Limit Return / Pressure Switch Out after the gas valve closes (postĆpurge)
6 Flame Sensor
7 Gas Valve Out A proving switch connected to the combustion air inducer
8 High Limit Out housing is used to prove combustion air inducer operation.
9 Rollout Switch Return The switch monitors air pressure in the blower housing. DurĆ
6-Blower Motors and Capacitors ing normal operation, the pressure in the housing is negaĆ
tive. If pressure becomes less negative (signifying an obĆ
All 80UHG units use direct drive blower motors. All motors
struction) the prove switch opens. When the prove switch
used are 120V permanent split capacitor motors to ensure
opens, the furnace control (A3) immediately closes the gas
maximum efficiency. See table 8 for ratings.
valve to prevent burner operation.
TABLE 8
80UHG BLOWER RATINGS 120V 1PH 8-Flame Rollout Switches (S47)
BLOWER MOTOR HP CAP Flame rollout switch is a high temperature limit located on
80UHG2 1/4 5MFD 370V top of the burner box. Each furnace is equipped with two
80UHG3 1/3 5MFD 370V
identical switches. One switch is located over the leftmost
80UHG3/4 1/2 7.5MFD 370V
80UHG4 1/2 7.5MFD 370V burner and the other switch is located over the rightmost
80UHG4/5 3/4 40MFD 370V burner. The limit is a N.C. SPST manualĆreset limit conĆ
80UHG5/6 3/4 40MFD 370V nected in series with the ignition control A3. When S47
Page 12
senses rollout, the ignition control immediately stops igniĆ Two limits are supplied in each furnace. 80UHG3, 80UHG4
tion and closes the gas valve. If unit is running and flame and 80UHG4/5 model units built prior to Apri 1999, will
rollout is detected, the gas valve will close and ignition conĆ have one each of style shown in figures 13 and 14. If stick
trol will be disabled. Rollout can be caused by a blocked limit (figure 14) suffers frm nuisance trips on the above
flue or lack of combustion air. The switch is factory set and model units and the furnace is in the horizontal position, reĆ
cannot be adjusted. The setpoint will be printed on the side of place with limit kit no. 50L98. All 80UHG2 model units will
the limit. The switch can be manually reset. To manually reĆ have one of each style shown in figures 13 and 14.
set a tripped switch, push the reset button located on the
SECONDARY LIMIT CONTROL (S21)
control. FOR 80UHG SERIES UNITS
THIS TYPE AUTOĆRESET LIMIT IS
INSULATING COVER
ROLLOUT SWITCH (S47) USED FOR THE LEFT SECONDARY
SPADE CONNECTORS
LIMIT (S21) (see FIGURE 11)
LIMIT
MANUAL
RESET BUTTON
LIMIT
FIGURE 12
INSULATING COVER (s)
9-Primary Limit Control (S10) FIGURE 14
LIMIT CONTROL FOR
80UHG SERIES UNITS 11-Spark Electrode and Flame Sensor
80UHG-1 Models
THIS TYPE AUTOĆRESET LIMIT
IS USED FOR THE PRIMARY LIMIT (S10) AND
Figure 17 shows the arrangement of flame sensor, spark
RIGHT SECONDARY LIMIT (S21) electrode and burners. The ignition control uses direct
(see FIGURE 11)
spark to ignite the rightmost burner and the burners crossĆ
FIGURE 13 light to the left. The flame sensor uses flame rectification to
sense combustion. A flame retention ring in the end of
The primary limit (S10) on 80UHG units is located in the
each burner is used to maintain correct flame length and
middle of the heating vestibule panel. When excess heat is
shape and to keep the flame from lifting off the burner
sensed in the heat exchanger, the limit will open. If the limit is
head.
tripped, the furnace control energizes the supply air blower
and closes the gas valve. The limit automatically resets when Figure 18 shows the gap between tip of the electrodes and
unit temperature returns to normal. The switch is factory set the burner surface, and the gap between the sensor and
and cannot be adjusted. The switch may have a different burner surface.
setpoint for each unit model number. However, the setpoint 12-Gas Valve
will be printed on the side of the limit. The 80UHG uses a gas valve manufactured by HoneyĆ
well or White Rodgers. The valve is internally redundant to
10-Secondary Limit Controls (S21)
assure safety shut-off. If the gas valve must be replaced,
The secondary limit (S21) on 80UHG units is located in the
the same type valve must be used.
blower compartment in the back side of the blower housing.
When excess heat is sensed in the blower compartment, the 24VAC terminals and gas control knob are located on top of
limit will open. If the limit is tripped, the furnace control enerĆ the valve. All terminals on the gas valve are connected to
gizes the supply air blower and closes the gas valve. The limit wires from the electronic ignition control. 24V applied to the
automatically resets when unit temperature returns to normal. terminals energizes the valve.
The switch is factory set and cannot be adjusted. The setĆ Inlet and outlet pressure taps are located on the valve. A reguĆ
point will be printed on the limit. lator adjustment screw (figures 15 and 16) is located on the
valve.
LPG changeover kits are available from Lennox. Kit s include
burner orifices and a gas valve regulator conversion kit.
Page 13
WHITE RODGERS 36E SERIES GAS VALVE HONEYWELL VR8205 SERIES GAS VALVE
MANIFOLD MANIFOLD
MANIFOLD PRESSURE PRESSURE
PRESSURE ADJUSTMENT OUTLET
ADJUSTMENT SCREW
SCREW
MANIFOLD ON
PRESSURE
OUTLET
OFF
FIGURE 15 FIGURE 16
Top
TYPICAL BURNER/ELECTRODE ORIENTATION 23/32 in.
80UHG-1 MODEL SHOWN (18 mm) Right Left
1/8"(+1/64") UPPER BURNER
BURNER MANIFOLD ORIFICE
MOUNTING RAIL Bottom
LOWER BURNER
SPARK ELECTRODE GROUND FLAME RETENTION RING MOUNTING RAIL FLAME SENSOR
FIGURE 17
FLAME SENSOR
FIGURE 18
Page 14
PROVE SWITCH B-Heating StartĆUp
COMBUSTION AIR INDUCER
PROVE SWITCH
Normally Open
Closes on Negative Pressure
WARNING
Shock and burn hazard.
80UHG-1 units are equipped with a direct spark igniĆ
tion system. Do not attempt to light manually.
1 - STOP! Read the safety information at the beginning
of this section.
Sensing Tube
Attaches to Top 2 - Set thermostat to lowest setting.
Side Of Blower 3 - Turn off all electrical power to appliance.
4 - This appliance is equipped with an ignition device
Top which automatically lights the burners. Do not try to
Back
Right light the burners by hand.
PROVE 5 - Remove top access panel.
SWITCH 6 - White Rodgers 36E Gas Valve -- Switch lever to
Left
Front OFF. See figure 15.
Bottom
Honeywell VR8205 Gas Valve -- Turn knob on gas
FIGURE 19 valve clockwise to OFF. Do not force. See figĆ
ure 16.
On startĆup, the switch senses that the combustion air 7 - Wait five (5) minutes to clear out any gas. If you then
blower is operating. It closes a circuit to the furnace control smell gas, STOP! Close manual main shut-off valve to
when pressure inside the combustion air blower deĆ the furnace. Immediately call your gas supplier from a
creases to a certain set point. Set points vary depending neighbor's phone. Follow the gas supplier's instructions.
on unit size. The pressure sensed by the switch is relative If you do not smell gas go to next step.
8 - White Rodgers 36E Gas Valve -- Switch gas valve lever
to atmospheric pressure. If the flue becomes obstructed to ON.
during operation, the switch senses a loss of negative Honeywell VR8205 Gas Valve -- Turn knob on gas
pressure (pressure becomes more equal with atmospherĆ valve counterclockwise to ON. Do not force.
ic pressure) and opens the circuit to the furnace control 9 - Replace access panel.
and gas valve. A bleed port on the switch allows dry relativĆ 10- Turn on all electrical power to unit.
ity air in the vestibule to purge switch tubing, to prevent 11- Set thermostat to desired setting.
condensate build up. The switch also has an internal inline NOTE–When unit is initially started, steps 1 through 11
orifice, designed to prevent nuisance shut downs due to may need to be repeated to purge air from pilot line.
erratic vent pressure fluctuations. 12- If the appliance will not operate, follow the instructions
The switch is factory set and is not field adjustable. It is a To Turn Off Gas To Unit".
safety shutĆdown control in the furnace and must not be Turning Off Gas To Unit
by-passed for any reason. If switch is closed or by-passed, 1 - Set thermostat to lowest setting.
the control will not initiate ignition at start up. 2 - Turn off all electrical power to unit if service is to be
II-PLACEMENT AND INSTALLATION performed.
Make sure unit is installed in accordance with installation 3 - Remove access panel.
instructions and applicable codes. 4 - Switch lever on White Rodgers gas valve to OFF; turn
III-STARTĆUP knob on Honeywell valve clockwise to OFF. Do not
force.
A-Preliminary and Seasonal Checks
5 - Replace access panel.
1 - Inspect electrical wiring, both field and factory installed
for loose connections. Tighten as required. C-Safety or Emergency Shutdown
2 - Check voltage at disconnect switch. Voltage must be Turn off unit power. Close manual and main gas valves.
within range listed on the nameplate. If not, consult the D-Extended Period Shutdown
power company and have voltage condition corrected Turn off thermostat or set to UNOCCUPIED" mode. Close
before starting unit. all gas valves (both internal and external to unit) to guaranĆ
tee no gas leak into combustion chamber. Turn off power
to unit. All access panels, covers and vent caps must be in
place and secured.
Page 15
IV-HEATING SYSTEM SERVICE CHECKS through Lennox under part number 31B2001. See Corp.
8411-L10, for further details.
A-A.G.A./C.G.A. Certification
Do not use matches, candles, flame or any other source of
All units are A.G.A. and or C.G.A. design certified without ignition to check for gas leaks.
modifications. Refer to the 80UHG Operation and InstallaĆ
tion Instruction Manual Information.
D-Testing Gas Supply Pressure
When testing supply gas pressure, connect test gauge to
B-Gas Piping inlet pressure tap (field provided). See figure 20. Check
Gas supply piping should not allow more than 0.5"W.C. gas line pressure with unit firing at maximum rate. Low
drop in pressure between gas meter and unit. Supply pressure may result in erratic operation or underfire. High
gas pipe must not be smaller than unit gas connection. pressure can result in permanent damage to gas valve or
Compounds used on gas piping threaded joints should be overfire. For 80UHG-45,60 and 75 BTUH natural gas
resistant to action of liquefied petroleum gases. units, operating pressure at the unit must be a minimum
4.5"W.C. For the 80UHG-100 and 120 BTUH units, the opĆ
C-Testing Gas Piping erating pressure must be a minimum of 5.0"W.C. For L.P.
gas units, operating pressure at unit gas connection must
IMPORTANT be a minimum of 11.0" W.C.
On multiple unit installations, each unit should be checked
In case emergency shutdown is required, turn off
the main shutĆoff valve and disconnect the main separately, with and without other units operating. Supply
power to unit. These controls should be properly pressure must fall within range listed in previous paraĆ
labeled by the installer. graph.
E-Check Manifold Pressure
When pressure testing gas lines, the gas valve must be After line pressure has been checked and adjusted, check
disconnected and isolated. Gas valves can be damaged if
manifold pressure. Move pressure gauge to outlet presĆ
subjected to more than 0.5psig (14" W.C.). See figure 20. If
sure tap located on unit gas valve (GV1). Checks of manĆ
the pressure is equal to or less than 0.5psig (14"W.C.), use ifold pressure are made as verification of proper regulator
the manual shut-off valve before pressure testing to isoĆ adjustment. Manifold pressure for the 80UHG can be meaĆ
late furnace from gas supply. sured at any time the gas valve is open and is supplying gas
GAS PIPING TEST PROCEDURE to the unit. Normal manifold pressure for natural gas units is
3.5 in. W.C. For LP/propane gas the correct manifold presĆ
MANUAL MAIN SHUT-OFF VALVE
sure is 9.5 in. W.C.
WILL NOT HOLD TEST PRESSURE
IN EXCESS OF 0.5 PSIG (14"W.C.)
IMPORTANT
For safety, connect a shutĆoff valve between the
manometer and the gas tap to permit shut off of
gas pressure to the manometer.
CAP
GAS VALVE TABLE 9
FIELD PROVIDED
GAS VALVE REGULATION
LINE PRESSURE TAP Unit (Fuel) Operating Pressure (outlet) in. W.C.
Natural 3.5 +0 -0.3
FIGURE 20 L.P. 9.5 + 0.5
When checking piping connections for gas leaks, use preĆ The gas valve is factory set and should not require adĆ
ferred means. Kitchen detergents can cause harmful corroĆ justment. All gas valves are factory regulated. See
sion on various metals used in gas piping. Use of a specialty table 9. See specifications section of this manual for
Gas Leak Detector is strongly recommended. It is available High Altitude manifold pressure settings.
Page 16
Manifold Adjustment Procedure: To Measure Flame Signal - Ignition Control:
1 - Connect a test gauge to outlet pressure tap on gas A transducer (Part
valve. Start unit and allow 5 minutes for unit to reach TRANSDUCER
#78H5401 available from
steady state. (PART #78H5401)
Lennox Repair Parts) is
2 - While waiting for the unit to stabilize, notice the flame. required to measure
Flame should be stable and should not lift from burner.
flame signal if meter used
Natural gas should burn blue. L.P. gas should burn
will not read a low micro
mostly blue with some orange streaks.
amp signal. ĂSeeĂfigĆ
3 - After allowing unit to stabilize for 5 minutes, record FIGURE 21
ureĂ21. The transducer
manifold pressure and compare to values given in
table 9. converts microamps to volts on a 1:1 conversion. Flame sigĆ
nal should for the EGC control should be 1.0 - 5.0 with a lock-
NOTE-Shut unit off and remove manometer as soon as
out signal of .45 nominal microamps, therefore a reading of
an accurate reading has been obtained. Take care to
1.0 - 5.0 nominal volts should be read on the meter. Flame
replace pressure tap plug.
signal for the SureLight control should read 0.7 microamps
F- Proper Gas Flow (Approximate) with a lockout signal of .15 microamps. A digital readout meter
Furnace should operate at least 5 minutes before must be used. The transducer plugs into most meters.
checking gas flow. Determine time in seconds for two See figure 22 for proper use of transducer.
revolutions of gas through the meter. (Two revoluĆ
1 - Set the volt meter to the DC voltage scale. Insert
tions assures a more accurate time.) Divide by two transducer into the VDC and common inputs. ObĆ
and compare to time in table 10 below. Adjust manĆ serve correct polarities. Failure to do so results in
ifold pressure on gas valve to match time needed. negative (-) values.
NOTE- To obtain accurate reading, shut off all other 2 - Turn off supply voltage to control.
gas appliances connected to meter. 3 - Disconnect ignition control flame sensor wire from the
TABLE 10 flame sensor.
GAS METER CLOCKING CHART 4 - Connect (-) lead of the transducer to flame sensor.
5 - Connect (+) lead of transducer to the ignition control senĆ
Seconds for One Revolution
sor wire.
80UHG Natural LP
6 - Turn supply voltage on and close thermostat contacts to
U it
Unit 1 cu ft 2 cu ft 1 cu ft 2 cu ft cycle system.
Dial Dial Dial DIAL
7 - When main burners are in operation for two minutes, take
-45 80 160 200 400 reading. Remember 1 DC volt = 1 DC microamp.
-60 60 120 150 300
NOTE-MUST USE DIGITAL METER
-100 36 72 90 180
-120 30 60 75 150
Natural-1000 btu/cu ft LP-2500 btu/cu ft
FIGURE 22
Page 17
C-External Static Pressure
WARNING 1 - Tap locations shown in figure 23.
Fire and explosion hazard. 2 - Punch a 1/4" diameter hole STATIC PRESSURE
These instructions MUST be followed exactly. TEST
in supply and return air pleĆ
Can cause a fire or explosion resulting in property
damage, personal injury or loss of life. nums. Insert manometer MANOMETER
hose flush with inside edge
V-TYPICAL OPERATING CHARACTERISTICS of hole or insulation. Seal
around the hose with perĆ
A-Blower Operation and Adjustment magum. Connect the zero 80UHG UNIT
NOTE- The following is a generalized procedure and end of the manometer to the FIGURE 23
does not apply to all thermostat controls. discharge (supply) side of the system. On ducted sysĆ
tems, connect the other end of manometer to the reĆ
1 - Blower operation is dependent on thermostat control
turn duct as above. For systems with non-ducted reĆ
system.
turns, leave the other end of the manometer open to
2 - Generally, blower operation is set at thermostat subĆ
the atmosphere.
base fan switch. With fan switch in ON position, blower
3 - With only the blower motor running and the evaporator
operates continuously on heating speed. With fan
coil dry, observe the manometer reading. Adjust blowĆ
switch in AUTO position, blower cycles with demand or
er motor speed to deliver the air desired according to
runs continuously while heating or cooling circuit cycles.
the job requirements.
3 - Depending on the type of indoor thermostat, blower
4 - External static pressure drop must not be more than
and entire unit will be off when the system switch is in
0.5" W.C.
OFF position.
5 - Seal around the hole when the check is complete.
B-Temperature Rise
D-Blower Speed Taps Leadless Motors
Temperature rise for 80UHG units depends on unit input,
blower speed, blower horsepower and static pressure as 80UHG-1 Models
marked on the unit rating plate. The blower speed must be Blower speed tap selection is accomplished by changing the
set for unit operation within the range of AIR TEMP. RISE taps at the blower motor harness connector. Disconnect harĆ
°F" listed on the unit rating plate. ness connector from motor to expose speed selectors.
To Measure Temperature Rise: Blower speed selections are listed in table 11.
To Change Blower Speed:
1 - Place plenum thermometers in the supply and return
1 - Turn off electric power to furnace.
air plenums. Locate supply air thermometer in the first
2 - Remove blower access door.
horizontal run of the plenum where it will not pick up raĆ
Disconnect blower motor harness from motor.
diant heat from the heat exchanger.
3 - Select desired speeds for heating and cooling. (Red =
2 - Set thermostat to highest setting.
heating, Black = cooling, White = common).
3 - After plenum thermometers have reached their highĆ 4 - Depress harness connector tab to release wire termiĆ
est and steadiest readings, subtract the two readings. nal. Select connector location for new speed (refer to
The difference should be in the range listed on the unit unit wiring diagram). Insert wire terminal until it is seĆ
rating plate. If the temperature is too low, decrease curely in place. See figure 24.
blower speed. If temperature is too high, first check 5 - Replace harness connector to motor.
the firing rate. Provided the firing rate is acceptable, inĆ TABLE 11
crease blower speed to reduce temperature. To
change blower speed taps see the Blower Speed Taps
section in this manual.
Page 18
BLOWER SPEED TAP SELECTION VI-MAINTENANCE
Leaded Motors HARNESS At the beginning of each heating season, the system
CONNECTOR should be checked as follows:
A-Filters
Return air filter is not supplied with unit. See Optional AcĆ
cessaries section in this manual for filter and rack size. A
filter must be used in order to ensure long life and proper
operation. The filter is located in the return air duct or return
air register. Filters must be cleaned or replaced when dirty
to assure proper unit operation.
B- Heat Exchanger and Burners
DEPRESS TAB TO RELEASE
WIRE TERMINAL. SELECT
Due to dimples designed in the heat exchanger, cleanĆ
CONNECTOR LOCATION ing is not recommended. Removal is for inspection
FOR NEW SPEED (REFER TO only.
UNIT WIRING DIAGRAM). INĆ
SERT WIRE UNTIL IT IS SEĆ NOTE-Use papers or protective covering in front of furĆ
MOTOR
CURELY IN PLACE. nace while cleaning furnace.
FIGURE 24 To clean burners:
1 - Remove screws holding upper burner mounting rail (figĆ
E-Blower Speed Taps Leaded Motors
ure 17). Remove rail.
80UHG-2 Models 2 - Slide burners off each orifice pull burners from heat exĆ
Blower speed tap changes are made on the SureLight changer.
control board. See figure 6. Unused taps must be secured
3 - Clean holes in burner head (retention ring) with a wire
on two dummy terminals labeled "PARK on the SureLight
board. The heating tap is connected to the "HEAT-H " terĆ brush. See figure 17.
minal and the cooling tap is connected to the "COOL-H" 4 - With a shop vacuum or rags, clean out soot and scale
terminal. The continuous blower tap is the same as the deposits from burners.
heating tap. 5 - Remove screws securing flue box to vestibule panel.
To change existing heat tap, turn off power then switch out Remove flue box from unit. Leave combustion air
speed tap on "HEAT-H" with tap connected to "PARK" .
blower attached to flue box.
See table 12 for blower motor tap colors for each speed.
TABLE 12 6 - With a shop vacuum or rags, clean out soot and scale
deposits from heat exchanger tubes and flue box. If turĆ
bulators are removed (figure 1) make sure they are reĆ
installed before reassembling units.
7 - Inspect heat exchanger for corrosion damage, holes or
cracks.
8 - Replace burners making sure to fully engage on orifice.
Resecure burner mounting rail and flue box. Inspect flue
box gasket. Replace gasket if necessary.
9 - Slide heat exchanger into cabinet and reĆsecure heat
exchanger screws.
10 - Reinstall filler piece making sure that there is a good
seal between the cabinet sides, blower and deck and
filler piece. Use silicon caulking to fill in any potential
gaps.
11 - ReĆsecure flue pipe, gas piping and access panels.
12 - Carefully check all piping connections (factory and
field) for gas leaks. Use a leak detecting solution or othĆ
er preferred means.
12 - Turn on gas and electrical supply.
Page 19
HEAT EXCHANGER REMOVAL (unit shown in horizontal position)
Left
Back
Bottom
Top
Right
FIGURE 25
D-Flue and Chimney
CAUTION Flue must conform to all AGA/GAMA venting requireĆ
Potential for gas leaks, fire or explosion. ments. Flue pipe deteriorates from the inside out and must
Some soaps used for leak detection are corrosive be disconnected in order to check thoroughly. Check flue
to certain metals. Carefully clean piping thorĆ pipe, chimney and all connections for tightness and to
oughly after leak detection has been completed. make sure there is no blockage or leaks.
Can cause damage to piping resulting in gas
leaks, fire or explosion. E-Electrical
1 - Check all wiring for loose connections.
C-Supply Air Blower 2 - Check for correct voltage.
1 - Check and clean blower wheel.
3 - Check amp-draw on blower motor.
2 - Motors used on the Lennox 80UHG series units are
permanently lubricated and need no further luĆ
brication.
Page 20
VII- Wiring and Sequence of Operation
80UHG-1 MODEL WITH EGC CONTROL (SEE FLOW CHARTS ON THE FOLLOWING TWO PAGES):
1 - When disconnect is closed, 120V is routed through door 5 - When S18 closes, assuming primary limit (S10) and
interlock switch (S51) to feed the line voltage side of the secondary limit (S21) are closed, a 15 second pre-purge
ignition control (A3) and transformer T1 primary. Door inĆ begins. After the pre-purge period the ignition control
terlock switch must be closed for A3 and T1 to receive starts ignition spark and opens main gas valve.
voltage. 6 - After 45 seconds, ignition control (A3) energizes the
2 - T1 supplies 24VAC to terminal 24VAC" on A3. In turn, indoor blower (B3).
terminal R" of A3 supplies 24VAC to terminal R" of the 7 - When heat demand is satisfied, W1 of the thermostat deĆ
indoor thermostat (not shown). energizes W of the ignition control and the gas valve is
3 - When there is a call for heat, W1 of the thermostat enĆ immediately deĆenergized. The combustion air inducer
ergizes W of the ignition control with 24VAC. immediately stops. The indoor blower runs for a desigĆ
4 - CAB of the ignition control energizes the combustion air nated fan off" period (60-240 seconds) as set by jumper
inducer (B6). When the combustion air inducer on ignition control.
nears full speed, combustion air prove switch (S18)
closes. Switch must close within 2 1/2 minutes or
control goes into 5 minute Watchguard Pressure
Switch delay.
Page 21
80UHG-1 HEATING SEQUENCE OF OPERATION
NORMAL HEATING MODE ABNORMAL HEATING MODE
CONTROL MAIN POWER ON" GAS VALVE OFF. COMB. INDUCER ON. INDOOR
BLOWER ON HEAT SPEED. SEQUENCE HOLDS UNTIL
NO FLAME SENSED OR MAIN POWER IS INTERRUPTED
FLAME OFF? NO
AND RESET. DIAG. CODE: 1- FLASHING; 2-OFF
YES (FLAME SENSED WITHOUT VALVE ENERGIZED)
NO
CONTROL SELF-CHECK OKAY?
YES GAS VALVE, COMB. INDUCER AND INDOOR BLOWER
(WITH DELAY) OFF. REMOVE POWER TO RESET
ROLL-OUT SWITCH CLOSED NO
CONTROL. DIAG. CODE: BOTH ON (CONTROL
YES SELF-CHECK FAILURE OR INCORRECT WIRING)
PRIMARY/SECONDARY LIMITS MONITORED IN NO GAS VALVE OFF. COMB. INDUCER OFF. INDOOR
HEAT CYCLE. ARE SWITCHES CLOSED? BLOWER ON UNTIL LIMIT CLOSES. DIAG.
YES CODE: 1-FLASHING / 2-ON (LIMIT OPEN)
NO IS LIMIT NOW CLOSED?
PRESSURE SWITCH CLOSED?
YES
YES
THERMOSTAT OPENS HAS PRIMARY LIMIT OPENED 5 TIMES DURING
ONE UNSATISFIED HEAT DEMAND. IF YES,
SYSTEM GOES INTO 60 MIN.WATCHGUARD.
LED: SLOW FLASH RATE DIAG. CODE: 1-FLASHING / 2-ON
IF NO, GO TO COMB. AIR BLOWER ON?"
COMB. AIR INDUCER OFF (5 sec. delay) GAS VALVE, COMB. INDUCER AND INDOOR BLOWER
HTG ACC. TERM. DE-ENERGIZED. (WITH DELAY) OFF. DIAG. CODE: 1-OFF / 2-FLASHING NO
(C.A.B. PRESSURE SWITCH OPEN) HAS C.A.B.
PRESSURE SWITCH CLOSED IN 2.5 MINUTES?
INDOOR AIR BLOWER OFF (After selected 60, 90,
YES
120, 180, or 240 delay)?
Page 22
80UHG-1 COOLING SEQUENCE OF OPERATION
LED: Slow flash rate.
REMAINS UNCHANGED THROUGHOUT COOLING CYCLE.
THERMOSTAT OPENS.
COMPRESSOR OFF.
NO YES
Page 23
80UHG-2 MODEL WITH SURELIGHT CONTROL
1 - When there is a call for heat, W1 of the thermostat 5 - Gas valve opens for a 4-second trial for ignition
energizes W of the furnace control with 24VAC. (ignitor will remain energized for the first second).
2 - S10 primary limit switch and S47 rollout switch 6 - Flame is sensed, gas valve remains open for the
are closed. Call for heat can continue. heat call.
3 - SureLight control energizes combustion air blowĆ 7 - After 45-second delay, SureLight control enerĆ
er B6. Combustion air inducer runs until S18 comĆ gizes indoor blower B3.
bustion air prove switch closes (switch must close 8 - When heat demand is satisfied, W1 of the indoor
within 2-1/2 minutes or control goes into 5 minute thermostat de-energizes W of the SureLight conĆ
Watchguard Pressure Switch delay). Once S18 trol which de-energizes the gas valve. CombusĆ
closes, a 15-second pre-purge follows. tion air inducer B6 continues a 5-second post-
4 - SureLight control energizes ignitor. A 20-second purge period, and indoor blower B3 completes a
warm-up period begins. selected OFF time delay.
Page 24
HEATING SEQUENCE OF OPERATION
YES
GAS VALVE OFF. COMBUSTION AIR INDUCER ON.
NO
INDOOR BLOWER ON.
ROLLOUT SWITCH CLOSED? LED #1 -- ON. LED #2 -- SLOW FLASH.
YES SEQUENCE HOLDS UNTIL ROLLOUT SWITCH CLOSES.
Page 25
HEATING SEQUENCE CONTINUED
NORMAL HEATING MODE ABNORMAL HEATING MODE
Page 26
COOLING SEQUENCE OF OPERATION
NORMAL COOLING MODE ABNORMAL COOLING MODE
POWER ON
NO
NO
IS VOLTAGE LED SIGNALS WAITING ON CALL FROM
ABOVE 75 VOLTS? THERMOSTAT. CONTROL WILL NOT RESPOND
UNTIL VOLTAGE RISES ABOVE 75 VOLTS.
YES
THERMOSTAT OPENS.
COMPRESSOR OFF.
Page 27
SURELIGHT CONTROL
CONTINUOUS HEAT SPEED FAN SEQUENCE OF OPERATION
THERMOSTAT OPENS.
THERMOSTAT CALLS FOR COOLING.
YES NO
THERMOSTAT OPENS.
SYSTEM FAN REMAINS ON HEAT-H
HEATING SPEED.
Page 28
VIII-Troubleshooting-SureLight Control
SURELIGHT - TROUBLE SHOOTING GUIDE
UPON INITIAL POWER UP, REMOVE ALL THERMOSTAT DEMANDS TO THE UNIT
PROBLEM: 1 UNIT FAILS TO OPERATE IN THE COOLING, HEATING, OR CONTINUOUS FAN MODE
Condition Possible Cause Corrective Action / Comments
1.1 1.1.1
ACTION 1 - Check 120V main voltage.
- Both diagnostic lights fail to light up. Main voltage 120V not supplied to Determine cause of main power failure.
unit.
1.1.2 ACTION 1 - Check for correct wiring of 120V to
LED#1-Off power make up box and transformer.
LED#2-Off Miswiring of furnace or improper
ACTION 2 - Check 24V wiring to control board.
connections.
1.1.3 ACTION 1 - Replace fuse.
ACTION 2 - If fuse still blows, check for short.
Blown fuse
ACTION 1 - Check that door switch is activated
when door is closed.
1.1.4 ACTION 2 - Check wire connections to switch, reĆ
place loose connectors.
Door interlock switch failure. ACTION 3 - Check continuity of switch in closed
position. Replace if defective.
1.1.5 ACTION 1 - Check that transformer output is
24V. Replace if defective.
Transformer Failure.
1.1.6 ACTION 1 - If all the above items have been
checked, replace board.
Failed control board.
1.2 ACTION 1 - Manually reset the roll-out switch
1.2.1 by pushing the top button.
- Diagnostic lights flash the roll-out Roll-out switch open. ACTION 2 - Determine the cause of the roll-out
switch activation before leaving furnace.
code.
1.2.2 ACTION 1 - Check continuity across roll-out
switch. Replace roll-out switch if switch is reset
Roll-out switch failure. but does not have continuity.
LED#1-On, 1.2.3
LED#2-Slow Flash Miswiring or improper connections at ACTION 1 - Check wiring connections to switch.
switch
roll-out switch.
ACTION 1 - Check 12-pin connector for proper
1.2.4 connection to control board.
ACTION 2 - Check continuity of the multi plug
12 pin connector failure pin.
1.3
- On initial power-up the comb. air inĆ
ducer does not energize.
ACTION 1 - Check the 120V has line and neutral
- Diagnostic lights flash the reverse 1.3.1 correctly input into control.
polarity code. ACTION 2 - Reverse the line and neutral at the
120V main power polarity reversed.
120V field connection.
LED#1-Fast Flash,
LED#2-Slow Flash.
1.4
1.4.1 ACTION 1 - Check for 120V to combustion air
- On initial power up the combustion
Open combustion air inducer motor inducer. If no power, check wire and connecĆ
air inducer does not energize. tions.
- Diagnostic lights flash normal power circuit.
on operation.
Page 29
PROBLEM 1: UNIT FAILS TO OPERATE IN THE COOLING, HEATING, OR CONTINUOUS FAN MODE
PROBLEM 2: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER DOES
NOT ENERGIZE
Condition Possible Cause Corrective Action / Comments
2.1
ACTION 1 - Check continuity across switch(es).
- Unit operates with a cooling or conĆ 2.1.1 Switches reset automatically upon cool down.
tinuous fan demand. ACTION 2 - Check for restrictions on blower inlet
Primary or secondary (if equipped ) air (including filter) and outlet air. Determine
- Combustion air inducer will not start
limit open. cause for limit activation before placing unit back
with a Heating demand. in operation.
- Diagnostic
g lights
g flash the limit failure
mode.
d
2.1.2 ACTION 1 - Check for correct wiring and loose
Miswiring of furnace or improper conĆ connections. Correct wiring and/or replace any
LED#1-Slow Flash, nections at limit switch(es).
loose connections.
LED#2-On
2.2
- Unit operates with a cooling and conĆ 2.2.1 ACTION 1 - Check for correct wiring and loose
tinuous fan demand. Miswiring of furnace or improper conĆ connections. Correct wiring and/or replace any
- Combustion air inducer will not start nections to combustion air inducer. loose connections.
with a Heating demand.
- Diagnostic lights flash the pressure
switch failure code.
2.2.2 ACTION 1 - Check that the pressure switch is
open without the combustion air inducer operatĆ
LED#1-Off, Pressure switch stuck closed. ing. Replace if defective.
LED#2-Slow Flash
Page 30
PROBLEM 2: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR INDUCER DOES
NOT ENERGIZE (CONT.).
Condition Possible Cause Corrective Action/Comments
2.3
- Unit operates with a cooling and conĆ 2.3.1 ACTION 1 - Check for correct wiring and loose
tinuous fan demand. connections. Correct wiring and/or replace any
Miswiring of furnace or improper conĆ
- Combustion air inducer will not start loose connections.
nections to combustion air inducer.
with a Heating demand.
- Diagnostic lights flash the pressure
switch failure code 2.5
2 5 minutes after
heating demand.
2.3.2 ACTION 1 - If there is 120V to combustion air inĆ
ducer and it does not operate, replace combusĆ
Combustion air inducer failure. tion air inducer.
LED#1-Off,
LED#2-Slow Flash
PROBLEM 3: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER
ENERGIZES, IGNITOR IS NOT ENERGIZED.
Condition Possible Cause Corrective Action/Comments
3.1 3.1.1
ACTION 1 - Check that the pressure switch lines
- Unit operates with a cooling and Pressure switch does not close due are correctly routed. Correctly route pressure
continuous fan demand. to incorrect routing of the pressure switch lines.
- Combustion air inducer energizes switch lines.
with a heating demand.
demand
3.1.2
- Diagnostic lights flash the pressure ACTION 1 - Remove any obstructions from the
switch failure code 2.5 minutes after Pressure switch does not close due the pressure lines and/or taps.
heatingg demand. to obstructions in the pressure lines.
3.1.3 ACTION 1 - Check pressure switch lines for
leaks. Replace any broken lines.
LED#1 Off
LED#1-Off Pressure switch lines damaged
LED#2-Slow Flash 3.1.4 ACTION 1 - Check pressure switch lines for conĆ
densate. Remove condensate from lines. Check
Condensate in pressure switch line. that the condensate lines are located correctly.
3.1.6
ACTION 1 - Check that the proper pressure
Wrong pressure switch installed in switch is installed in the unit. Replace pressure
the unit, or pressure switch is out of switch if necessary.
calibration.
3.1.7 ACTION 1 - Check for correct wiring and loose
Miswiring of furnace or improper conĆ connections. Correct wiring and/or replace any
loose connections.
nections at pressure switch.
ACTION 1 - If all the above modes of failure have
3.1.8 been checked, the pressure switch may have
failed. Replace pressure switch and determine if
Pressure switch failure. unit will operate.
Page 31
PROBLEM 4: UNIT FAILS TO FIRE IN THE HEATING MODE, COMBUSTION AIR BLOWER
ENERGIZES, IGNITOR IS ENERGIZED.
Condition Possible Cause Corrective Action/Comments
4.1 4.1.1
ACTION 1 - Check line pressure at the gas
valve. Pressure should not exceed 13" WC for
- Unit operates with a cooling and Check that gas is being supplied to both natural and propane. Line pressure should
read a minimum 4.5" WC for natural and 8.0"WC
continuous fan demand. the unit. for propane.
- Combustion air inducer energizes
4.1.2
with Heating demand. ACTION 1 - Check for correct wiring and loose
- Ignitor is energized but unit fails to Miswiring of gas valve or loose conĆ connections. Correct wiring and/or replace any
nections at multi-pin control amp loose connections.
light. plugs or valve.
ACTION 1 - Check that 24V is supplied to the
gas valve approximately 35 seconds after heat
4.1.3 demand is initiated.
LED#1-Alternating Slow Flash Defective gas valve or ignition conĆ ACTION 2 - Replace the valve if 24V is supplied
LED#2-Alternating Slow Flash but valve does not open.
trol. ACTION 3 - Replace the control board if 24V is
not supplied to valve.
PROBLEM 5: BURNERS LIGHT WITH A HEATING DEMAND BUT UNIT SHUTS DOWN
PREMATURELY
Condition Possible Cause Corrective Action/Comments
5.1
- Burners fire with a heating deĆ
mand.
- Burners light but unit shuts off prior
to satisfying T-stat demand. 5.1.1 ACTION 1 - Check for restricted exhaust vent.
Remove all blockage.
- Diagnostic lights flash the pressure Low pressure differential at the presĆ ACTION 2: Check for proper vent sizing. See
switch code. sure switch. installation instructions.
LED#1-Off
LED#2-Slow Flash
5.2 5.2.1 ACTION 1 - Check that sensor is properly loĆ
- Combustion air inducer energizes Sensor or sensor wire is improperly cated and that the sense wire is properly atĆ
tached to both the sensor and the control.
with a heating demand. installed.
-BBurners
rners light b
butt fail to sta
stay lit
lit. ACTION 1 - Check for a broken sensor.
- After 5 tries the control diagnostics 5.2.2 ACTION 2 - Test continuity across the sense
flash the watchguard burners failed to Sensor or sensor wire is broken. wire. If wire or sensor are damaged replace
ignite code. the component.
ACTION 1 - Check for resistance between the
5.2.3 sensor rod and the unit ground.
Sensor or sensor wire is grounded to ACTION 2 - Check for resistance between the
LED#1-Alternating Slow Flash sensor wire and the unit ground.
LED#2-Alternating Slow Flash the unit. ACTION 3 - Correct any shorts found in circuit.
ACTION 1 - Check the microamp signal from
the burner flame. If the microamp signal is beĆ
low 0.20 microamps, check the sensor rod for
proper location or contamination.
ACTION 2 - Replace, clean, or relocate flame
5.2.4 sensor rod. If rod is to be cleaned, use steel
wool or replace sensor. DO NOT CLEAN ROD
Control does not sense flame. WITH SAND PAPER. SAND PAPER WILL
CONTRIBUTE TO THE CONTAMINATION
PROBLEM. NOTE: Do not attempt to bend
sensor rod.
ACTION 3 - Check that there is proper ground
to burner box. Repair as necessary.
Page 32
PROBLEM 5: BURNERS LIGHT WITH HEATING DEMAND BUT UNIT SHUTS DOWN
PREMATURELY (CONT.)
Condition Possible Cause Corrective Action/Comments
5.3 ACTION 1 - Check that the manifold pressure
matches value listed on nameplate. See installaĆ
- Combustion air inducer energizes 5.3.1 tion instructions for proper procedure.
with a heating demand. ACTION 2 - Verify that the installed orifice size
- Burners light. Unit is firing above 100% of the match the size listed on the nameplate or instalĆ
nameplate input. lation instructions.
- Roll-out switch trips during the ACTION 3 - Check the input rate to verify rate
heating demand. matches value listed on nameplate.
- Diagnostic lights flash roll
roll-out
out fail
failĆ ACTION 1 - Tighten orifice until leak is sealed.
ure. 5.3.2 NOTE: Be careful not to strip orifice threads.
Gas orifices leak at the manifold conĆ ACTION 2 - Check for gas leakage at the
threaded orifice connection. Use approved
nection. method for leak detection (see unit instructions).
LED#1 On
LED#1-On
LED#2-Slow Flash ACTION 1 - Check for sooting deposits or other
5.3.3 restrictions in the heat exchanger assembly.
Clean assembly as outlined in instruction manuĆ
Insufficient flow through the heat exĆ al.
changer caused by a sooted or reĆ ACTION 2 - Check for proper combustion. See
stricted heat exchanger. NO TAG Heating System Service Checks secĆ
tion NO TAG.
LED#1-Alternating Slow Flash 5.4.3 ACTION 1 - Remove gas orifices and inspect.
LED#2-Alternating Slow Flash Remove any burrs that are present or replace
Burrs in gas orifices orifice.
5.5
- Combustion air inducer energizes 5.5.1 ACTION 1 - Check that the sensor is properly loĆ
with a heating demand. cated.
Loose sensor wire connection ACTION 2 - Check that the sense wire is properĆ
- Burners light.
causes intermittent loss of flame sigĆ ly attached to both the sensor and the control.
- Diagnostic lights flash watch guard
nal. Pay extra attention to the pin connectors.
flame failure.
- NOTE" Unit might go into 60 minĆ
ute Watchguard mode depending on
intermittent nature of sensor signal.
5.5.2 ACTION 1 - Check for proper ground and repair
as necessary.
Poor ground to burner box
LED#1-Alternating Slow Flash
LED#2-Alternating Slow Flash
Page 33
PROBLEM 6: CONTROL SIGNALS LOW FLAME SENSE DURING HEATING MODE
Condition Possible Cause Corrective Action/Comments
6.0 6.1.1 ACTION 1 - Check the sensor rod for proper
location on the burner. Properly locate the senĆ
- Unit operates correctly but the Sensor rod is improperly located on sor rod or replace if rod cannot be located corĆ
diagnostic lights flash low flame the burner. rectly.
sense code.
code
ACTION 1 - Check sensor rod for contamination
or coated surface. Clean the sensor rod with
6.1.2 steel wool or replace sensor. DO NOT USE
LED#1-Slow Flash SAND PAPER TO CLEAN ROD. SAND PAPER
LED#2-Fast Flash Sensor rod is contaminated. WILL CONTRIBUTE TO THE CONTAMIĆ
NATION PROBLEM.
Page 34