Professional Documents
Culture Documents
Instruction Manual-Overcurrent
Instruction Manual-Overcurrent
Instruction Manual-Overcurrent
Overcurrent Protection
Instructions Manual
1. License Grant. Licensor hereby grants to you, and your accept, a nonexclusive and non-
transferable license to use the embedded programs and the accompanying documentation, if any
(collectively referred to as the “Software”), only as authorized in this License Agreement.
2. Restrictions. You may not (a) use, copy, modify or transfer the Software except as expressly
provided in this or another Agreement with Licensor, (b) reverse engineer, decompile or
disassemble or separate the components of the Software, or (c) rent, sell or lease the Software or
make the Software available to others to do any of the foregoing.
3. No Assignment. This License is intended for your exclusive use with the purchased equipment.
You agree that you will not assign, sublicense, transfer, pledge, lease, rent or share your rights
under this License Agreement.
4. Licensor’s Rights. You acknowledge and agree that the Software is the proprietary product of
Licensor protected under U.S. copyright law and international treaties.. You further
acknowledge and agree that all right, title and interest in and to the Software, including
associated intellectual property rights, are and shall remain with Licensor. This License
Agreement does not convey to you an ownership interest in or to the Software, but only a
limited right of use revocable in accordance with the terms of this License Agreement.
5. Confidentiality. The Software is confidential and no details or information relating to the same
shall be disclosed to any third party without the prior written consent of Licensor. For the
purposes of this clause, sub-contract staff, employed or retained by the Licensee to perform
computer systems development work, shall not be deemed to be third parties provided such staff
are subject to the disclosure restrictions set forth above. In no event, except with a prior written
authorization duly signed by an officer of Licensor, may you disclose any such confidential
information, even for subcontracted jobs, to persons or entities that may be considered to be
direct competitors of Licensor.
6. Term. The License Agreement is effective upon delivery of the equipment to you and shall
continue until terminated. You may terminate this License Agreement at any time by returning
the equipment to Licensor, or by destroying the equipment. Licensor may terminate this License
Agreement upon your breach of any term hereof. Upon such termination by Licensor, you agree
to return the equipment to Licensor.
7. Warranty and Disclaimer. Licensor warrants, for your benefit only, that the Software, when
and as delivered to you, will conform to the specifications described in the instruction manuals
for the equipment purchased, or any specifications agreed to in writing by Licensor with a
particular customer. This warranty does not cover any minor errors or deviations from the
specifications that do not affect the proper functioning of the equipment. EXCEPT FOR THE
WARRANTIES SET FORTH ABOVE, THE SOFTWARE IS LICENSED “AS IS”, AND
LICENSOR DISCLAIMS ANY AND ALL OTHER WARRANTIES, WHETHER
EXPRESS OR IMPLIED, INCLUDING, WITHOUT LIMITATION, ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE.
8. Licensee’s Remedy. You sole and exclusive remedy for any breach of Licensor’s warranty
shall be the repair or replacement, at Licensor’s sole option, of any Software that does not
conform to stated specifications. Licensor shall not be responsible for any failure arising from
inadequate or improper use of the Software.
9. Limitation of Liability. Licensor’s cumulative liability to you or any other party for any loss or
damages resulting from any claims, demands, or actions arising out of or relating to this
Agreement shall not exceed the purchase price paid to Licensor for the equipment. In no event
shall Licensor be liable for any indirect, incidental, consequential, special, or exemplary
damages or lost profits, even if licensor has been advised of the possibility of such damages.
10. Trademark. All ZIV trademarks (including ZIVERCOM, ZIVERLOG and ZIVERSYS) are
common law trademarks of Licensor. No right, license or interest to such trademarks is granted
hereunder, and you agree that no such right, license or interest shall be asserted by you with
respect to such trademark.
11. Licensee’s Indemnity. You shall defend, indemnify and hold Licensor harmless against any
loss or damage of any kind arising from a breach by you of this License Agreement, or any use
or misuse of the Software by you or your employees, agents or representatives, and from any
other of your conduct or from any claim or action by any of your customers in connection with
the Software or this License Agreement.
12. Governing Law. This License Agreement shall be construed and governed in accordance with
the internal laws of the State of Illinois, U.S.A.
13. No Waiver. The failure of either party to enforce any rights granted hereunder or to take action
against the other party in the event of any breach hereunder shall not be deemed a waiver by that
party as to subsequent enforcement of rights or subsequent actions in the event of future
breaches.
14. Entire Agreement. This License Agreement is the entire agreement between you and Licensor
with respect to the use of the software and supersedes all prior understandings or agreements
between the parties. This License Agreement may be amended only by a writing signed by an
officer of Licensor.
Chapter 1. Description
1.1 Functions ..................................................................................................... 1-2
1.1.1 Non-directional Overcurrent Protection 3-Phase and Ground..................... 1-2
1.1.2 Reclosing ..................................................................................................... 1-2
1.1.3 Breaker Failure Protection ........................................................................... 1-3
1.1.4 Open Phase Protection................................................................................ 1-3
1.1.5 Residual Current Protection ........................................................................ 1-3
1.2 Additional Functions .................................................................................... 1-3
1.3 Model Selection ........................................................................................... 1-5
Chapter 5. Settings
5.1 Configuration Settings ................................................................................. 5-2
5.2 General Settings .......................................................................................... 5-3
5.3 Protection Settings....................................................................................... 5-4
5.4 Recloser Settings......................................................................................... 5-6
5.5 Logic Settings .............................................................................................. 5-8
5.6 Breaker Monitoring Settings ........................................................................ 5-8
5.7 History Record ............................................................................................. 5-9
5.8 Oscillographic Recording (Optional) ............................................................ 5-10
5.9 No Keypad Models Settings ........................................................................ 5-11
I
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Table of Contents
II
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Table of Contents
III
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Table of Contents
F. Product Warranty
IV
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
1. Description
1.1 Functions .................................................................................................................... 1-2
1.1.1 Non-directional Overcurrent Protection 3-Phase and Ground .................................... 1-2
1.1.2 Reclosing .................................................................................................................... 1-2
1.1.3 Breaker Failure Protection .......................................................................................... 1-3
1.1.4 Open Phase Protection ............................................................................................... 1-3
1.1.5 Residual Current Protection........................................................................................ 1-3
1.2 Additional Functions.................................................................................................... 1-3
1.3 Model Selection .......................................................................................................... 1-5
Chapter 1. Description
IRD terminal are applicable in medium voltage lines, power transformers, generators, and
feeders in general, where overcurrent protection (for phase to phase or phase to ground
faults) is required.
This instruction manual covers the IRD-A and IRD-J, and particular characteristics are
specified where are relevant.
1.1 Functions
1.1.1 Non-directional Overcurrent Protection 3-Phase and Ground
Includes four non-directional overcurrent measuring units (three for Phase Overcurrent
protection and one for Ground). At IRD-A’s each unit is comprised of a time element and an
instantaneous element, with additional temporization adjustable.
At IRD-J’s each unit is comprised of a time element and two instantaneous elements, with
additional temporization adjustable.
Time elements can be selected with the following types of characteristics: Definite Time,
Inverse, Very Inverse, Extremely Inverse and User Programmable.
Time and Instantaneous Overcurrent Elements for Phase and Ground can be enabled or
disabled using settings. Three setting groups are provided for selecting alternative pre-
established time and instantaneous overcurrent pickup values and time characteristics (one is
active and two are in reserve).
Phase and ground, timed and instantaneous overcurrent pickup and tripping functions can all be
individually targeted.
1.1.2 Reclosing
Reclosing can be separately coordinated with external protection as well as with the protection
contained in the terminal unit. Reclosing sequences for phase faults and ground faults can be
set independently.
Reclosing is selectable up to a maximum of four attempts with independent settings for recloser
timers (dead or open breaker wait times) and reset times. The reclosing sequence is controlled
by the breaker position and by the reclose initiate signal, which permits reclosing based on the
protective elements which operated to trip the breaker.
The trip elements and reclose attempts enabled during a fault clearing and reclosing sequence
are selectable.
Manual closing can be initiated from the terminal unit using its reclosing output contacts. The
Close Command in this instance is supervised and controlled in the same way as any
permissible automatic reclosing command following a trip from the protection elements.
1-2
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 1. Description
1-3
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 1. Description
Operations:
- Last trip and recloser status (according to model).
- Started Units.
- Activated Units.
- Activated Inputs / Outputs.
Meterings:
- Phase and Ground Currents.
- Maximum Current.
- Positive and Negative Sequence Currents.
Records:
- Event Recording.
- Fault Reports.
- Current History Record.
• Self-Test Program
A continuously running diagnostic self-test program verifies the correct operation of the terminal
unit and alerts the user to potential problems.
1-4
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 1. Description
1 Selection
3 Rack module construction 8 19'' Rack construction
2 Functions
A 3x50/51 + 50N/51N + 79 J 3x(2x50)/51 + (2x50N)/51N + 79
3 Options
1 Basic Model A Control Mimic
2 Oscillographic Register B Control Mimic + Oscillographic Register
7 Oscillographic Register + Digital TOP
4 Rated Current
E 1A N 5A
G 5 A (phases) + 1 A (ground)
5 Auxiliary Voltage
Power Supply Digital Supervision Power Supply Digital Supervision
Inputs Inputs Inputs Inputs
1 24-48 Vdc (±20%) 24-48 Vdc 24-48 Vdc 3 220-250 Vdc (±20%) 48-250 Vdc 250 Vdc
2 110-125 Vdc (±20%) 24-125 Vdc 125 Vdc 6 90-220 Vdc (±20%) 24-125 Vdc 125 Vdc
6 Voltage / Frequency / Language
0 50 Hz / Spanish D 120 & 120 √3 Vac / 60 Hz / Spanish
1 110 & 110√3 Vac / 50 Hz / Spanish E 60 Hz / Portuguese
2 60 Hz / English F 120 & 120 √3 Vac / 60 Hz / Portuguese
3 120 & 120 √3 Vac / 60 Hz / English G 50 Hz / French
A 50 Hz / English H 110 & 110 √3 Vac / 50 Hz / French
B 110 & 110 √3 Vac / 50 Hz / English J 50 Hz / Portuguese
C 60 Hz / Spanish K 110 & 110 √3 Vca / 50 Hz / Portuguese
7 Communications
1 RS232 + RS232 7 RS232 + 2 x RS232
2 RS232 + PFO 1mm 8 RS232 + GFO (con ST)
3 RS232 + GFO (SMA) A RS232 + 2xGFO (con ST)
4 RS232 + GFO (ST) B RS232 + Double Rear Port (GFO*+RS232**)
5 RS232 + RS485 C RS232 + Double Rear Port (RS232*+RS485**)
6 RS232 + PFO 1 mm D RS232 + 2 x PFO 1 mm.
8 Inputs / Outputs Module
0 Standard Inputs / Outputs B 79 Pulses Inputs + Oscillographic with battery
2 Expansion Inputs / Outputs M 79 Level Inputs + Multireclosement
5 Oscillographic with battery Y 79 Pulses Inputs + 79 UEF Logic (v.01)
8 Model 2 + Model 9 Z 79 Pulses Inputs
9 Lockout Function and 79 Pulses Inputs
9 Special Models
00 Standard Model 22 Optional Ground Ratio IN>>(0.04-12 A) x In // IN>(0.04-12 A) x In
11 Without keypad and display + Aux8 without coil supervision 24 Ground Ratio: 0.1 - 6A time // 0.25 - 60A instantaneous for 5A
12 Without keypad and display 30 Special Model 15 + Phases Ratio (0.1 - 30 x In) instantaneous /
14 Directional Ground Ratio (67N): 0.8 - 10 mA / 0.8 - 24 mA (0.2 – 3.2 x In) time + Sensitive ground time: 180 s.
Nominal Voltage N: 1000 Vac 35 Without keypad and display + Aux8 without coil supervision
15 Optional Ground Ratio IN>> (0.1-30) x In // IN>(0.1-1.2) x In Optional Ground Ratio: (0.1 – 1.2) x In
16 Ino = 20mA 40 Phase and Ground Ratio: (0.1 - 30 x In) time / (0.1 - 30 x In) inst.
17 Frequency measurement 50 Sensitive Ground Timers: 0 - 600 ms and 1 - 1800 ms
18 Without keypad and display + Directional Ground Ratio 99 Model 11 + Double Bay [DAN]
(67N): 0.005 – 0.06 A / 0.005 – 0.6 A
1-5
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 1. Description
IRD
1 2 3 4 5 6 7 8 9 10 11
10 Type of Enclosure
A 6 U x 1 19" rack C 6 U x 1/4 19" rack
B 6 U x 1/2 19" rack F 2 U x 1 19" rack
11 Communications Protocol
A Protec. NO PROCOME + Without Ctrl. E Protec. NO PROCOME + Ctrl. DNP3
B Protec. NO PROCOME + Ctrl. PROCOME F Protec. NO PROCOME + Ctrl. MODBUS and PROCOME
D Protec. PROCOME + Ctrl. PROCOME H Special Models
L Special Models
M Special Models
• Functions
1-6
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
2. Technical
Data
2.1 Power Supply Voltage ................................................................................................ 2-2
2.2 Power Supply Burden ................................................................................................. 2-2
2.3 Current Analog Inputs ................................................................................................. 2-2
2.4 Measurement Accuracy .............................................................................................. 2-3
2.5 Accuracy of Time Measurement ................................................................................. 2-3
2.6 Repeatability ............................................................................................................... 2-3
2.7 Transient Overreach ................................................................................................... 2-3
2.8 Status Contact Inputs ................................................................................................. 2-4
2.9 Trip and Close Outputs ............................................................................................... 2-4
2.10 Auxiliary Contact Outputs ........................................................................................... 2-5
2.11 Communications Link.................................................................................................. 2-5
Chapter 2. Technical Data
Note: in case of an auxiliary power supply voltage failure, terminal units can tolerate a maximum interruption of
100ms at 110Vdc.
Quiescent 7W
Maximum 20 W
2-2
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 2. Technical Data
2.6 Repeatability
Expressed as: ST = I −I
A T
x100
I A
<10% for totally inductive lines
<5% for lines with an impedance angle of 70º
2-3
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 2. Technical Data
Rated Voltage
Input IN1 (IN9*) 110 Vac ±20 % or 125 Vdc ±20%
Inputs IN2 to IN8 (IN10 to IN16*) 24 - 125 Vdc ±20 %
(according to model) 48 - 250 Vdc ±20 %
Note: Status Contact Inputs IN5 to IN8 (IN13 to IN16*) will be selectable (according to model) when they are
used in trip and close circuits supervision applications.
2-4
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 2. Technical Data
Electrically separate open and closed contacts and normally open contacts.
2-5
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 2. Technical Data
RS485 Transmission
Signals Used A (B5)
B (B6)
2-6
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
3. Standards and
Type Test
3.1 Insulation ..................................................................................................................... 3-2
3.2 Electromagnetic Compatibility .................................................................................... 3-2
3.3 Environmental Test ..................................................................................................... 3-3
3.4 Power Supply .............................................................................................................. 3-3
3.5 Mechanical Test .......................................................................................................... 3-3
Chapter 3. Standards and Type Tests
The equipment satisfies the requirements of IEC-255 (EN 21-136) at the maximum class for the
values indicated below.
3.1 Insulation
3-2
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 3. Standards and Type Tests
The models comply with the IEC 89/336 standard of electromagnetic compatibility.
3-3
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 3. Standards and Type Tests
3-4
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
4. Physical
Architecture
4.1 General ....................................................................................................................... 4-2
4.2 Dimensions ................................................................................................................. 4-4
4.3 Connection Elements .................................................................................................. 4-4
4.3.1 Terminal Blocks .......................................................................................................... 4-4
4.3.2 Plug-in connectors (Non Self-shorting) ....................................................................... 4-6
4.3.3 Removing of Printed Circuit Boards (Non Self-shorting) ............................................ 4-6
4.3.4 Internal Wiring ............................................................................................................. 4-6
Chapter 4. Physical Architecture
4.1 General
• 8IRD Models
8IRD protection terminal units are supplied with one printed circuit board that provides the
following functions:
Additionally, one or two printed circuit boards can be added to provide more contact inputs and
outputs when the 3IRD enclosure is half of a 19” rack in width.
Depending on the loaded configuration, the available physical inputs and outputs can be fully
used or not.
The physical aspects of the 8IRD equipment are shown in Figure 4.1 and 4.2. Figure 4.2 shown
the physical aspect of an 8IRD without the keypad and alphanumeric display.
4-2
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 4. Physical Architecture
On Figures 4.3 and 4.4 are shown the physical aspects of the 3IRD of ¼ and ½ racks.
Figure 4.3: 3IRD ½ Rack Front View. Figure 4.4: 3IRD ¼ Rack Front
View.
The keypad and the alphanumeric display, the local communications port and LEDs are located
at the front of the equipment. On 3IRDs expansion bus cable connections are located here too.
Connectors of each printed circuit board and the remote communication port are located at the
rear of the equipment. Connector position will depend on the model.
4-3
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 4. Physical Architecture
4.2 Dimensions
Protection terminal units have the following case dimensions according to the model specified:
The equipment is intended to be installed either semi-flush mounted in panels or in 19” racks,
where the smaller cases can be mounted side by side to occupy a full 19” rack width. The 3IRD
comes equipped with a transparent cover, which can be sealed for security purposes. The
enclosure color of both units is graphite.
- One column for current/voltage analog inputs split into a terminal connectors blocks of
10 terminals.
- One column for contact inputs/outputs split into two terminal connectors blocks of 32
terminals each (64 terminals total).
- One column for additional digital inputs/outputs split into two terminals connectors
blocks of 32 terminals each (64 terminals total). (Available in ½ rack case widths only).
For ¼ rack models the connector disposition is shown at Figure 4.5. The disposition for the ½
rack models is shown at Figure 4.6.
• 8IRD Models
Printed circuit boards are arranged horizontally (see Figure 4.7). Terminal connectors/connector
blocks are grouped in rows:
- One row split with 2 connectors blocks of 24 terminals each (48 terminals total) for
digital inputs/outputs and 1 connectors block of 10 terminals for measures of
current/voltage analog inputs.
- One row split, for additional current/voltage digital outputs, with 2 connectors blocks of
24 terminals each (48 terminals total).
The analog current input terminals (10 connectors terminal block) admit wires of a cross section
up to 4 mm2 #11 AWG. The rest of the circuits admit wires of up to 2.5 mm2 #13AWG cross-
section. Pointed terminal are recommended for the connection to the terminal connectors.
4-4
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 4. Physical Architecture
Figure 4.5: 3IRD Rear View (¼ Rack). Figure 4.6: 3IRD Rear View (½
Rack).
4-5
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 4. Physical Architecture
The printed circuit board is attached to the case with self-tapping screws. These screws must
be removed before the board is withdrawn. This operation always requires the protection to be
Not in Service.
4-6
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
5. Settings
5.1 Configuration Settings................................................................................................. 5-2
5.2 General Settings ......................................................................................................... 5-3
5.3 Protection Settings ...................................................................................................... 5-4
5.4 Recloser Settings ........................................................................................................ 5-6
5.5 Logic Settings ............................................................................................................. 5-8
5.6 Breaker Monitoring Settings ....................................................................................... 5-8
5.7 Metering History Log ................................................................................................... 5-9
5.8 Oscillographic Recording (Optional) ......................................................................... 5-10
5.9 No Keypad Models Settings ..................................................................................... 5-11
Chapter 5. Settings
Operation Enable
Setting Range
Breaker / Recloser from
Local Keypad YES / NO
Local Port YES / NO
Remote Port YES / NO
Remote Setting from
Remote Port YES / NO
Digital Inputs YES / NO
5-2
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 5. Settings
Language*
Setting Range
Language Spanish
English
Portuguese
Frequency*
Setting Range
Frequency 50 / 60 Hz
Contrast
Keyboard updating
5-3
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 5. Settings
5-4
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 5. Settings
Note: Pickup ratio for phase and ground elements is in In function (5A or 1A). For example, for 5A the phase
time ratio is (1-12A).
5-5
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 5. Settings
Recloser Timers
Setting Range Step
Phase to Phase Faults (1, 2, 3 and 4 attempts) 0.2 - 300 s 0.01 s
Phase to Ground Faults (1, 2, 3 and 4 attempts) 0.2 - 300 s 0.01 s
5-6
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 5. Settings
5-7
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 5. Settings
(*) Depending on the chosen setting (YES/NO), the position of the internal jumpers on the input/output circuit
board should be modified (see Figures 5.1 and 5.2).
5-8
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 5. Settings
5-9
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 5. Settings
5-10
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 5. Settings
Passwords
There are not necessary because there is no keypad
Operation Enables
Setting By Default
Breaker / Recloser
Frontal Port YES
Remote Port YES
Remote Setting
Remote Port YES
Digital Inputs NO
5-11
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 5. Settings
5-12
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
6. Description of
Operation
6.1 Overcurrent Elements ................................................................................................. 6-2
6.1.1 Time Elements ............................................................................................................ 6-2
6.1.1.a Time/ Current Characteristics ................................................................................ 6-3
6.1.2 Instantaneous Elements ............................................................................................. 6-6
6.1.3 Overcurrent Units Block Diagrams ............................................................................. 6-6
6.1.4 Torque Control (Pickup Blocking Enable) ................................................................... 6-7
6.1.5 Trip Blocking and Time Delay Disable ........................................................................ 6-8
6.2 Breaker Failure ........................................................................................................... 6-8
6.3 Open Phase Element .................................................................................................. 6-9
6.4 Residual Current Element ......................................................................................... 6-10
6.5 General Settings ....................................................................................................... 6-11
6.6 Recloser .................................................................................................................... 6-12
6.6.1 Reclose Sequence .................................................................................................... 6-13
6.6.2 Recloser Lockout ...................................................................................................... 6-16
6.6.3 Manual Close ............................................................................................................ 6-17
6.6.4 Manual and External Blocking .................................................................................. 6-18
6.6.5 Definite Trip............................................................................................................... 6-18
6.6.6 Recloser Not in Service ............................................................................................ 6-18
6.6.7 Reclose Counter ....................................................................................................... 6-19
6.6.8 Recloser and Trip Control Masks ............................................................................. 6-19
6.7 Logic ......................................................................................................................... 6-21
6.7.1 Trip Seal-In ............................................................................................................... 6-21
6.7.2 Breaker Open and Close Failure Time ..................................................................... 6-21
6.7.3 Manual Closing through Recloser............................................................................. 6-21
6.8 Trip and Close Coil Circuit Supervision .................................................................... 6-22
6.8.1 Trip Coil Circuit ......................................................................................................... 6-23
6.8.2 Close Coil Circuit ...................................................................................................... 6-23
6.8.3 Trip/Close Coil Circuit Supervision Input Programming ........................................... 6-24
6.8.4 Trip/Close Output Supervision .................................................................................. 6-24
6.9 Breaker Monitoring.................................................................................................... 6-25
6.9.1 Excessive Number of Trips ....................................................................................... 6-25
6.10 Change Settings Group ............................................................................................ 6-26
6.11 Event Record ............................................................................................................ 6-27
6.12 Fault Reports ............................................................................................................ 6-32
6.13 Metering History Log ................................................................................................. 6-33
6.14 Oscillographic Register (Optional) ............................................................................ 6-34
6.15 Inputs, Outputs and LED Targets ............................................................................. 6-37
6.15.1 Inputs ........................................................................................................................ 6-37
6.15.2 Auxiliary Outputs and Trip Contact Outputs ............................................................. 6-39
6.15.3 LED Targets .............................................................................................................. 6-45
6.16 Communications ....................................................................................................... 6-46
6.16.1 Communications Settings ......................................................................................... 6-46
6.16.2 Communications Types ............................................................................................ 6-46
6.16.3 Communication with the Unit .................................................................................... 6-46
6.17 Alarm Codes ............................................................................................................. 6-47
Chapter 6. Description of Operation
The Time Element integrates a measured value above pickup by incrementing a counter in the
integrator module using an amount proportional to the input current RMS value. When the
counter reaches the operate threshold, the Time Overcurrent Element initiates a trip.
When the measured value drops below the pickup setting, the incrementing value is removed,
causing a rapid reset of the integrator module to its initial condition with the counter at zero. Any
new measured value above pickup must then start the integration interval from zero.
Three inverse time curves (Inverse, Very Inverse and Extremely Inverse), one Definite Time
curve and one User Programmable time curve can be selected. The User Programmable
curve is loaded into the terminal unit front RS232 port through the ZiverCom® communications
program.
Time-current characteristic curves have two independent settings: Curve Family, and Time Dial.
6-2
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
0.14
t =
0.02
IS −1
6-3
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
13.5
t =
IS −1
6-4
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
80
t =
2
IS −1
6-5
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
Filtering out the DC offset component in combination with the application of these two
instantaneous measurement methods results in low transient overreach without adversely
affecting tripping speed.
The combined output of these measuring elements is equipped with an adjustable timer which
enables delay of the instantaneous trip.
The actuation of the Instantaneous 2 (Phase and Ground) elements on IRD-J model, inhibit the
actuation of the Recloser.
6-6
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
• IRD-J Model
To enable Time Overcurrent tripping, this input must remain de-energized during the entire
timing process from pickup to trip. If the input is energized for the Instantaneous Overcurrent
Element, the instantaneous function is blocked via a logic gate after the level detector outputs
that will hold the timer reset.
For each one of the Torque Control inputs, there is an Enable setting within each protection
element menu in the display. To use these Logic Input Signals, Status Contact Inputs must be
programmed for this application.
6-7
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
Another programmable input exists that can turn a given Time Overcurrent element into
instantaneous. Said input is called Timer Disable and is available for all time-delayed elements.
The reset of either the I_FI or P_INT signal causes the T_FI timer to reset and stop the Breaker
Failure process.
The P_INT signal, which indicates the presence of current, is active whenever any of the units
pickup levels are exceeded. These fast reset current level detectors are intended to stop the
timer as soon as the breaker is open and current has disappeared to insure that the FI signal is
not triggered inadvertently.
In order to activate the breaker failure element from an external protection trip input, one of the
terminal unit Status Contact Inputs must be configured as an External Protection Trip Input
(APE). If an input is not assigned as an External Protection Trip Input, the APE signal will
default to a logic “0”.
Additionally, one or more of the Auxiliary Contact Outputs must be configured as a Breaker
Failure Output (FI) to produce a contact output for initiating backup tripping.
6-8
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
Figure 6.7: Open Phase Element Block Diagram (without Minimum Load in the Line Setting).
Open Phase Pickup is initiated when this ratio exceeds the user adjustable setting. Once the
Open Phase element has picked up, output T_FASE_A is initiated. If the T_FASE_A signal is
present for a period of time equal to or greater than the T_FASE_A Time Delay setting, a Open
Phase Trip Output occurs.
The operation of this function is controlled by the element enable setting, the position of the
breaker and the positive sequence current level. If the breaker is open or the positive sequence
current level is less than 100 mA, the element is disabled. This function is also disabled when
any of the Phase or Ground, Time or Instantaneous Overcurrent Elements are picked up.
If this function is disabled, positive and negative sequence current measurement is still provided
for metering display purposes.
6-9
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
Figure 6.8: Open Phase Element Block Diagram (with Minimum Load in the Line Setting)
The current measured by the Residual Current Unit Detection uses the same Current Analog
Input as the Ground Overcurrent Elements. Once this element has picked up, output
A_RESIDUAL is activated. If the A_RESIDUAL signal is present for a period of time equal to or
greater than the Time Delay setting, a Trip Output occurs (S_RESIDUAL). The Residual
Current Unit Detection can be disabled with the element Enable setting but is automatically
disabled when the Ground Time Overcurrent Element picks up.
6-10
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
When the equipment is out of service (NO), its function will be reduced exclusively to metering
operations. The measured values will appear in the display and can be seen through local and
remote communications.
• Transformer Ratio
The transformer ratio settings (phase and/or ground, depending on model) only affect to the
analog values displayed on the HMI.
A transformer ratio setting of 1 will display the secondary values of the CTs. A setting equivalent
to the CT transformation ratio will display the primary values of the system.
• Open Breaker Status
The function of the Open Breaker Status Input controls the state of the breaker and this input
can be defined as contact normally open (with breaker open), which corresponds to the setting
“0”, or as contact normally (with breaker closed), which corresponds to the setting “1”.
The state of the breaker is used by the Recloser to define the state of Block due to Open
Breaker and the beginning of the reclosing cycle. Moreover, it is linked to the Breaker operation,
which occur from the keyboard and via communications. Lastly, the open phase unit will not
pick up if the breaker is open.
• Event Masking
It is possible to mask unneeded events or those events without importance for the study of
protection behavior. Event masking can be done only through ZiverCom® communications
software.
6-11
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
6.6 Recloser
The Recloser function in the IRD IEDs is designed to initiate up to four reclose attempts with
independent settings of the Recloser and security times.
Independent Recloser Timer settings are available for each dead time interval for both phase
and ground faults. The types of controlled Recloser signals are:
- Recloser starts for phase-to-ground faults tripped by the ground time unit.
- Recloser starts for phase-to-ground faults tripped by the ground instantaneous unit.
- Recloser starts for phase-to-phase faults tripped by the instantaneous units (Phase
Time).
- Recloser starts for phase-to-phase faults tripped by the instantaneous units (Phase
Instantaneous).
- Recloser starts for open phase unit trip.
- Recloser starts for residual current unit trip.
- Recloser starts for external protection unit trip.
Figures 6-10 and 6-11 show flow diagrams describing the operation of the Recloser. Reclose
Initiate (IR) signal shown in these diagrams is the logic sum of the following signals:
IR is activated when either IR-P or IR-N is initiated. IR is reset when both IR-P and IR-N are
reset.
6-12
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
If the Recloser Reference Voltage setting is NO, the Reference Voltage Timer logic is
bypassed and the Recloser Timer (Dead Time) state is achieved immediately.
• Recloser Timer (Dead Time)
The Recloser Time (Dead Time) is the time the breaker is allowed to remain open before a
reclose is attempted. This time delay starts when the Recloser Timer (Dead Time) status is
achieved. The Recloser Timer (Dead Time) time delay setting can be different for each reclose
attempt. When this timer has timed out, the Reclose Inhibit (INR) input status is verified. If an
INR input signal is not present, the Reclose Command is activated and the Closing Time
status is achieved.
If an INR signal is present, the Supervision by Reclose Inhibit setting status is checked. If
Supervision by Reclose Inhibit is disabled, the Reclose Command is activated and the
Closing Time status is achieved. If Supervision by Reclose Inhibit is enabled, the Reclose
Inhibit Timer starts. If the Reclose Inhibit (INR) input is removed before the timing is
completed, the Reclose Command is activated and the Closing Time status is achieved. If the
Reclose Inhibit Timer times out and the Reclose Inhibit (INR) input is present, the Recloser
status changes to Recloser Lockout Due To Unsatisfied Reclosing Conditions.
6-13
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
6-14
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
6-15
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
• Closing Time
When the Recloser Closing Time state is achieved, the Reclose Command (OR) output is
activated to send a Close Command to the breaker and an adjustable Breaker Close Failure
Timer is started. If the breaker closes before the Breaker Close Failure Time is completed, the
Recloser Reset Time state is achieved. If the time is completed and the breaker remains open,
the Recloser state switches to Recloser Lockout Due To Breaker Close Failure. In either
case the Reclose Command (OR) output is subsequently de-activated.
• Reset Time
When the Recloser Reset Time state is achieved, an adjustable Reset Time timer is started.
The Reset Time setting corresponds to the closing attempt the Recloser is currently executing
and the type of prior fault. If the Reset Time is completed without a trip being initiated, the
Recloser switches to the Recloser Reset state and the reclose attempt is completed
successfully.
If a trip occurs and Reclose Initiate (IR) is activated before the Reset Time is completed, the
next step in the reclose sequence is determined by the Number of Reclose Attempts setting.
If a trip (IR active) occurs after the last reclose attempt permitted by this setting, the Recloser
switches to Recloser Lockout Due To Permanent Fault, and the reclose sequence ends. If
the Recloser has not reached the last permitted reclose attempt, the trip (IR active) which
occurs before the Reset Time is completed initiates a new reclose attempt and the Recloser
switches to the Sequence Check Time state.
Another condition will produce Recloser Lockout. Recloser Lockout is also achieved when
the breaker is opened without a fault associated with the breaker operation. Under this
circumstance, the Recloser switches to Recloser Lockout Due To Open Breaker Status and
reclosing is disabled.
The Recloser will remain in the Recloser Lockout state until a closed breaker is detected or a
Manual Close Command is initiated through the terminal unit. The Recloser will then reset only
if the breaker remains closed for the Reset Time after Manual Close set by the user.
6-16
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
When this condition is detected, the Recloser leaves the Recloser Lockout state and switches
to the Reset Time after Manual Close state. When this state is achieved the timer for the
Reset Time after Manual Close starts. If timing is completed without a trip initiation, the
Recloser switches to the Recloser Reset state. If there is a trip before timing is completed, the
Recloser switches to the Recloser Lockout Due To Switch-On-To-Fault state.
• Recloser Manual Close
If the Recloser Manual Close Enable setting is YES in the Logic Settings, then reclosing is
initiated when the Recloser receives a Manual Close Command signal from a Status Contact
Input. The subsequent closing sequence is similar to a final programmed reclose attempt except
there is no Sequence Check Time. Also, the following Reclose Sequence settings supersede
those associated with a final programmed reclose attempt:
Near the end of the Recloser Manual Close sequence, at breaker closure, the Reset Time
after Manual Close timer is started. Recloser Lockout results if a mask enabled trip output
occurs during this period of time. If no trip occurs, the Recloser returns to the Recloser Reset
state.
6-17
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
A Recloser Unblock command must be entered from the operator interface to exit the Blocked
status. If the breaker is open when this command is received, the Recloser changes to the
Recloser Lockout state. If the breaker is closed when the Unblock command is received, the
Reset Time after Manual Close timer is started.
• External Blocking
The Recloser External Lockout feature operates the same as Block Reclosing, except that
commands are executed through Status Contact Inputs instead of the operator interface.
The Recloser External Lockout state can be controlled by the status of one single status
contact input or by two separate contact inputs, depending on the model.
Block Reclosing commands override Recloser External Lockout commands. If the Recloser
receives a Recloser Block command while in the Recloser External Lockout state, the
Recloser changes to the Recloser Blocked state which can only be reset by a Recloser
Unblock command.
It is possible too to configure an auxiliary output (DD + DISP*BLQ), also as a definitive trip; so
that when a trip occurs the Recloser will get internally blocked.
This Definitive Trip signal will remain active as long as the unit performing that trip does not
reset. It usually happens when after a trip no reclosing attempt takes place.
6-18
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
For example, where the number of reclose attempts is set to four, and a fault has been
successfully cleared after the fourth trip, the first counter is incremented one count and the
second counter incremented three counts. The counters are reset from the operator interface.
Enabling or disabling of these units for trip generation is subjected to the following status of the
Recloser:
Recloser at Rest
Recloser Counting Security Time Following Closure #1, 2, 3 Or 4
Recloser Counting Security Time Following External Manual Close
Recloser Counting Security Time Following Manual Closure Through Block Reclosing
The action of the trip masks can only take place if the corresponding unit has been activated,
within its own protection settings, given that if the unit has been deactivated, its pickup process
does not initiate.
Trip mask, which corresponds to the NO setting, makes the physical output of the trip contact,
or of an output configured as masked, but it realizes the whole process of the unit from start to
the decision of generating a trip.
6-19
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
• Reclose Enable
Enabling or disabling of reclosing is possible in these faults:
Operatives instantaneous elements on IRD-J are phase 1 and ground 1 element. The
actuation of the Instantaneous 2 (Phase and Ground) elements, lockout the actuation of
the Recloser.
If the Recloser is Out of Service or Blocked, the masks are not operative and all trips are by
default in active status.
Warning: Caution should be exercised when disabling protective trip elements that are
expected to respond to faults, as each of the above settings are independent. Masking of
all the units makes it impossible for the protection to trip. No masking is YES in the
setting. Therefore, you have to make sure that at least one measurement unit is not
masked and is in an enable status.
6-20
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
6.7 Logic
The logic settings include the following functions: Trip Seal-In, Time Delay for Breaker
Opening and Closing Failure, Closing through the Recloser and Coordination Time.
If the Seal-In Enable is set to NO, the trip command resets when the protection trip elements
reset. If the breaker fails to open, and the fault has been cleared by an upstream breaker, the
Trip Output contact will be destroyed attempting to interrupt the breaker trip coil current.
The equipment will maintain the closing or opening order for the time indicated in this setting if
the operation is not executed before that time has elapsed.
6-21
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
The Trip and Close Coil Circuit Supervision functions can be independently disabled. The block
diagram depicting this feature (in the open breaker condition) is shown in Figure 6-12.
6-22
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
If the trip coil opens, the input IN-6 is energized and the SBAIA signal is activated, causing
deactivation of the output of the exclusive OR gate and 5 seconds later the activation of the Trip
Coil Circuit Supervision Failure (FCD) signal.
When the circuit breaker is closed, the status of the 52/a and 52/b contacts will change and
consequently (assuming the trip coil is not open circuited) inputs IN-6 and IN-5 will be inverted
as well as the SSP-1 and SBAIA signals. However, the FCD output will remain deactivated
since both inputs at the exclusive OR gate have different logic values.
The purpose of the 5 second time delay is to compensate for the time gap between the closing
of the 52/a and opening of the 52/b contacts. In general, SSP-1 and SBAIA signals will not
change their states simultaneously and a transient logic “0” will appear at the output of the
exclusive OR. When this disagreement lasts less than 5 seconds this “0” will not modify the
state of FCD.
If the trip coil circuit is opened while the breaker is closed, input IN-5 is energized and SSP-1 is
activated initiating the deactivation of the output of the exclusive OR gate and 5 seconds later,
activation of the Trip Coil Circuit Supervision Failure (FCD) signal.
If a trip occurs while the breaker is closed and the breaker opens reversing the status of the
52/a and 52/b contacts, the FCD signal will not be activated regardless of the time duration of
the trip command. If the breaker did not execute the command, the FCD signal is activated in 5
seconds.
If the DC control voltage disappears, the inputs that are energized reverse their state.
Consequently, the inputs of both exclusive OR gates become inactive, initiating activation of
both Trip and Close Coil Circuit Supervision Failure Outputs (FCD and FCC).
When the supervision function detects an open circuit in the trip circuit and therefore the inability
to initiate a trip, Manual Close breaker operations processed through the terminal unit will not be
permitted.
It is also necessary to take into account that for the Close Coil Circuit the activation time is
about 20 sec, instead of the 5 sec for the Trip Coil Circuit.
6-23
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
The Status Contact Inputs associated with the Trip and Close Coil Circuit Supervision
functions are made using the programmable inputs software menu. The programmable inputs
software menu enables the assignment of IN-6, IN-8, IN-5 and IN-7 to SBAIA, SBCIC, SSP-1
and SSP-3 signals respectively. The association made in Figure 6-12 is:
The Trip and Close Coil Circuit Supervision functions operate separately. If only one coil is
monitored, the other Status Contact Inputs can be used for other functions if the printed circuit
board jumper links are modified.
The close output is monitored in a similar manner. Signal FSP-3 indicates an improper close
operation.
6-24
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
When a trip is initiated, the largest of the three phase primary currents is recorded and then
stored as I2. The current measurement period is between trip initiation and breaker opening.
When the breaker is opened manually, either through the terminal unit or by external means,
the value accumulated is equivalent to the square of the time Overcurrent pickup setting.
Once the value established for the Alarm Level of I2 is reached, the function activates the Σ I2
Alarm Level signal that can be used to activate a programmable Auxiliary Contact Output. When
activated, this output is captured by the sequence of events recorder.
- Σ I 2 Alarm Level.
- Σ I 2 Cumulative Present Value.
The Cumulative Present Value is updated each time a breaker opening operation takes place.
It represents a base to which successive interruption values are added. This setting can be
modified by the user to set an initial value into a newly installed terminal unit to match the
history of an existing breaker. The value may also be reset to zero after major breaker
maintenance has been completed.
This output will disable any further reclose initiation by placing the unit in Recloser Lockout
Due To Open Breaker Status. This condition will reset only after a Manual Close Command
or a loss of auxiliary power.
6-25
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
The Setting Group Control function allows the user to modify the active Setting Group by means
of Status Contact Inputs. This feature enables quick modification of the protection settings when
circumstances require a change. Use of this function requires that the protection setting groups
be pre-programmed.
Change of setting group using the HMI will be explained in Chapter 7, Keypad and
Alphanumeric Display. Using local communications this change is carried out with the setting
Activate table (Settings Menu).
Change of setting group using the communications port or digital input need of a specific
enabling by an option in the Configuration menu (Operations – Remote Setting submenu) of
HMI. Both options are simultaneously incompatible.
The value of E_DIG should be set to “1” (YES) to enable group setting changes to be made
from the status contact inputs. If E_DIG is set to “0”, the terminal unit will remain in the last
setting group selected, independent of the activity of the Status Contact Inputs. When Setting
Group Control by status contact is enabled, no setting changes can be made from the keypad of
the local RS232 communications port. If the Change Settings option on the Main Menu is
selected from the keypad, the display indicates Access Denied.
To use this function, three status contact inputs must be programmed to activate the three
setting group.
Control setting group by status contact inputs (E_DIG set to “1”) and by remote communications
port (P_REM set to “1”) cannot be enabled simultaneously.
6-26
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
6-27
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
6-28
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
6-29
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
6-30
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
- Phase and Ground current and voltage measured at the moment the event was
generated.
- Event date and time.
- Event description.
The organization of the record is such that simultaneous events generated by the same function
will not occupy separate records, and will use only one position of the event memory.
Simultaneous events are those that occur separately within a time interval of 1ms, which is the
resolution time of the recorder.
It is necessary to remember that the possibility exists to mask those events that are not
necessary. The events can be masked by communications, within General Settings.
The communications program ZiverCom®, has an access system for the event record. The
information appears separately for each of the events in the table. If the IED provide
oscillographic register the Event Records consulting only can be effectuated via
communications.
6-31
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
- Pre-fault currents. The 3-phase and ground current values, two cycles before the fault
started.
- Pickup Units (according to model) for Full Fault Duration.
Trip Order Tag corresponds the date and time of the trip order. Also included:
- The 3-phase and ground Current values, 2’5 cycles after unit pickup.
- Tripped Units (according to model).
Fault End Time Tag corresponds at the moment (date and time) when the last element
involved in the fault resets. Also included:
- Open Current by the Breaker: it’s the maximum registered phase current between the
moment of the trip command and the fault end time (by breaker opening or by opening
order failure).
Each Fault Report specified the active group at the trip moment.
• By HMI
All of the above information is stored in memory and available through both communications
ports; however, only the following data is accessible for each fault report from the terminal unit
display:
- Fault Initiation Time Tag. Corresponds with the time when the first element involved in
the fault picked up.
- Trip Order Time Tag.
- Fault End Time Tag. Corresponds to the time when the last element involved in the
fault resets.
- Generating Element of Trip and Elements Picked Up for full fault duration.
Chapter 7 offers the related information to consult the fault report using the HMI. If the IED
provide Oscillographic Register, the Fault Report can’t be effectuated by HMI.
6-32
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
At the end of the recording period, called the Data Record Interval, which is adjustable between
1 minute and 24 hours, the maximum value retained from each Averaging Calculation Time
Interval is entered in the Current History Record.
TM:
Averaging
Calculation
Time
Interval; the
figure shows
the value of
TM to be
equal to one
minute.
TR: Data
Recording
Interval; the
figure shows
TR to have
a value of
15 minutes.
In each TM window, there are two VM values that correspond to the maximum and minimum
averages, considering the three phases. In each TR interval, the maximum and minimum values
of all the computed VM values are taken. The outline of current in Figure 6.14 would give the
following record of values: VR1-Vr1-F1, VR2-Vr2-F2, VR3-Vr3-F3, VR4-Vr4-F4 and VR5-Vr5-
F5.
Note: if during the sample interval, phase or ground units pick up, the recorded value is the average of the
measures taken during the time in which the units have not been picked up. On the contrary, if the units remain
picked up during all the interval, the recorded value is: 0A.
The available memory for the History Record is the typical RAM, with a capacity corresponding
to 168 values (equivalent to 7 days in intervals of 1 hour). With the goal of adapting the memory
use to the application of every user, the Days of the Week and Hours Trip can be enabled
within the defined days (the same interval schedule for all days) in addition to those that do not
register a value.
Access to the information about the Current History Record is available through the following
sequence: Information - Records - Current History. This is explained in Chapter 7,
Alphanumeric Keyboard and Display. It the IED has Oscillographic Register, this information
only will be available through communications.
6-33
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
Depending on the model there is a possibility of storing the oscillographic records in RAM
memory (non volatile) with an additional battery so that the information can be kept up to 1
month with the unit's auxiliary supply turned off. In this type of device there is a procedure that
allows to delete at any time the stored oscillographic records.
• Capture function
An analog record is stored each time a sample is taken. Status Contact Input signals are only
stored by the Event Record function.
• Stored Data
The following data is stored with a resolution time equal to the sampling rate:
Some devices in addition to analogue channels, have the possibility to retrieve the digital
channels (there are as many digital channels as are configurable logic outputs).
Once an Oscillographic Record has been stored in the relay, its retrieval can be done with a
maximum of 72 digital channels. There is a possibility of retrieving the same Oscillographic
Record as many times as one wants, each time setting different digital channels. In this case,
the relay communication program ZiverCom® sends a message to the user indicating that this
Oscillographic Record has already been retrieved so that the user is aware that in his list of
Oscillographic Records there will be various ones with the same time tag corresponding to the
beginning of the record.
6-34
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
• Recording Mode
The following Recording Modes are selectable: Fixed Time YES (Fixed Time Mode) and Fixed
Time NO (Variable Time Mode). In the first mode, Fixed Time YES, recording begins when the
Start function is activated. Recording stops when the pre-determined Record Length set by the
user is reached. In the second Mode, Fixed Time NO, recording begins when the Start
Function is activated. Recording stops when the Start Function is de-activated.
• Start Function
The Start Function consists of a programmable mask which can be applied to permit recording
to start after selected internal logic output signals or the External Oscillographic Start Logic
Input Signal. The External Oscillographic Start signal can be assigned to any of the physical
Status Contact Inputs.
This Start Function Control Mask is connected to each protection element within the relay. Only
connections that are enabled by the mask settings will activate the oscillography Start Function.
The activation occurs when any of the selected protection elements pick up, and de-activation
occurs when all selected elements are reset.
• Start Time (Pre-Fault Time)
Pre-Fault is the storage time before the activation of the Start Function.
• Oscillographic Record Length
It’s defined as the duration time of the store window at the Fixed Time Mode.
• Number of Records
The Number of Records stored in memory varies and depends on the number of channels
recorded and on the length of the fault records.
Once the recording memory is full, the Overwrite setting determines whether or not the next
event that occurs is stored over the oldest stored record (s). If the Overwrite setting has been
set to YES and as the new records vary in length, old records will get canceled depending on
the space required by the new record.
6-35
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
Trip Mode 1: Recorded data is stored in memory only if a trip occurs. For Fixed Time Mode
[Fixed Time (YES)] recorded data is stored in memory only if a trip occurs within the time set for
the Record Length. If a trip occurs after this time has expired, no record is stored. For Variable
Time Mode [Fixed Time (NO)] recorded data whenever the Start Function is active in addition to
the pre-fault data.
Trip Mode 2: For Fixed Time Mode [Fixed Time (YES)] recorded data is stored in memory only
if a trip occurs within the time set for the Record Length. If no trip occurs within the time set for
the Record Length, only 4 cycles of recorded data will be stored after the Start Function is
activated.
For Variable Time Mode [Fixed Time (NO)] if no trip occurs while the Start Function remains
active, only 4 cycles of recorded data will be stored after the Start Function is activated. If a trip
occurs while the Start Function is active, recorded data will be stored during the whole time the
Start Function remains active in addition to the pre-fault data.
Note: For the elements in which reset time can be long, it is recommended to set Fixed Time on YES.
It is reminded that information recorded during the time set as Pre-Fault Time is always stored.
• Overwrite
If the Overwrite setting has been set to NO, no more records will be stored once the
oscillography memory is full. In that situation, set Overwrite on YES so that new records can
get stored.
If the Overwrite setting has been set to YES, once the memory is full, the next record will
replace the oldest record that is erased.
6-36
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
6.15.1 Inputs
The terminal unit metering elements, and logic functions use the Logic Input Signals listed in
Table 6-2 below. Any of these Logic Input Signals can be assigned to one of the eight Status
Contact Inputs of the terminal unit. The closure of a contact will thereby activate those Logic
Input Signals assigned to it. Several different Logic Input Signals can be assigned to one Status
Contact Input, but a given Logic Input Signal can only be assigned to one Status Contact Input.
6-37
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
The status contact inputs leave the factory with an assigned configuration, but can be modified
through the local communications port with ZiverCom®.
6-38
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
The terminal unit protection, reclosing and monitoring functions generate a series of Logic
Output Signals during terminal unit operation. Each of these signals has either a “True” or
“False” value and this status (or its negation by using the “not” input(s) to the “OR” and “AND”
logic gates) can be used as an input to either of the combinational logic gates shown in Figure
6-15. The desired final “AND” or “OR” output from the logic cell can then be connected to any
one of the seven programmable Auxiliary Contact Outputs (AUX-1 through AUX-7) available in
the terminal unit.
Each block has 8 possible input signals. One of them is an OR gate (one activated signal
activates the output) and the other is an AND gate (all signals are needed to activate the
output). Between these two blocks both OR and AND operations can be executed. To the result
of this operation, can be applied the option to produce a pulse signal or not, in the following
manner.
• Without Pulses: setting the pulse timing at “0”, the auxiliary contact output is active while
the signal that has activated it lasts.
• With Pulses: once the auxiliary contact output has been activated, it maintains itself the
set time independently from the fact that the signal which generated it becomes not
longer active or stay active during a longer period.
6-39
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
6-40
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
6-41
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
6-42
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
6-43
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
The outputs are configured at the factory, but can be modified by the user using ZiverCom®
program through the local communications port.
• Breaker Operation
Manual trip and close operations can be performed through the terminal units using the same
Trip and Close Output contacts described above. These operations can be enabled using the
Operation Enable setting (Configuration settings). Manual operation is designed to require
confirmation before trip or close commands are completed.
The terminal unit is designed to confirm that the breaker has changed state. A Breaker Open
and a Breaker Close Failure Time can be programmed for trip and close operations. Open
Command Failure or Close Command Failure alarms are generated if the breaker response
is too slow.
6-44
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
Each indicator can be defined as latched or unlatched. In the case where the LED is latched, it
appears illuminated until reset. By means of the keypad, (see Chapter 7 Alphanumeric Keypad
and Display) the order to reset the LEDs can be executed using the key F2.
The latching function resides in the volatile memory section of the microprocessor. A power
supply loss to the unit will cause any latched LED to reset.
The LEDs can be programmed to any of the available logic outputs indicated in table 6-3. The
programming of the LEDs has been done at the factory, but can be modified by ZiverCom®
through a local communications port.
6-45
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
6.16 Communications
6.16.1 Communications Settings
The communications adjustments are described in detail in Chapter 5 (Settings) and are related
to Terminal Address, Baud Rate, Stop Bits and Parity.
The configuration of the remote communication ports can only be accessed through the HMI. It
is important that the adjustment for the local port is fixed at 4.800 bauds, 1 stop bit, and
adjustable parity, as indicated in Chapter 5.
In the model IRD exist two controllers; one is for the communications port so that several ports
can be established at one time.
6-46
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
Software Alarms
Code Description
01 00 Adjustment loss
04 00 Check-sum in the RAM zone pertaining to the curves
80 00 Protection out of order
Hardware Alarms
Code Description
00 01 E2PROM writing error
00 08 Low battery clock
00 10 Stopped clock
00 20 E2PROM file calibration error
00 40 RAM file calibration error
00 80 Memory test error
In the case of giving more than one alarm at once, the sum of the codes of these alarms is seen
in hexadecimal form. Below are a few examples:
01 and 02 = 03 02 and 08 = 0A
01 and 04 = 05 01 and 02 and 08 = 0B
04 and 08 = 0C
01 and 04 and 08 = 0D
02 and 04 and 08 = 0E
01 and 02 and 04 and 08 = 0F
6-47
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 6. Description of Operation
6-48
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
7. Alphanumeric Keypad
and Display
7.1 Alphanumeric Display and Keypad ............................................................................. 7-2
7.2 Keys, Functions and Operation Modes....................................................................... 7-3
7.3 Access to Functions Using Key F2 ............................................................................. 7-6
7.3.1 Last Trip Indication and Recloser Status .................................................................... 7-6
7.3.2 Screen Sequences Using F2 ...................................................................................... 7-7
7.4 Function Access Using the Keypad ............................................................................ 7-9
Chapter 7. Alphanumeric Keypad and Display
• Default Display
The default display shows the IED model, date and time. It also shows, on the first row left, the
connection mode (if the communication is established) at the following mode:
The access to the functions can be done by two different modes: using a single key (F2) or
using the keypad.
7-2
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 7. Alphanumeric Keypad and Display
Confirmation Key
The ENT key is used to confirm an action: after a selection has been made, after
editing an adjustment or to move forward the list of records. After finishing an
operation (selection, change settings, information, etc.) press ENT again to return
to the previous screen.
Escape Key
The key ESC is used to exit a screen if the user does not wish to make a
modification to the setting or if you merely looked at a screen for information. In
either case pressing this system key returns the user to the previous screen.
The key ↓ is also used to erase numbers within a setting when making
modifications. This function is only needed when changing a setting.
Contrast Key
Pressing this key adjusts the contrast for the display. The selection keys (↓↑)
modify the contrast value: a larger value = less contrast.
Pressing this key from any menu or submenu also returns the system directly to
the default screen.
7-3
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 7. Alphanumeric Keypad and Display
• Function Keys
Pressing F1 confirms settings changes (when the equipment asks for confirmation
of the changes) or activates the default table of settings.
The F3 key is used to display on the screen information about the event record,
and the octets that contain the function codes that the corresponding event has
generated.
The F4 key is used to cancel the changed settings (when the equipment asks for
confirmation of the changes) and to cancel the activation of the default table of
settings. F4 can, also, be used to reset the terminal.
• Options Access
The numeric keys (from 0 to 9) allow direct access to terminal’s settings, information,
measurements, etc. This direct access consists of pushing successively the identification
numbers that are displayed on the screen before each setting, or within a corresponding setting.
Another mode of access consists in going through the menus by the selection keys (↓↑) and
confirm the selection option pressing ENT.
7-4
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 7. Alphanumeric Keypad and Display
• Operation
Change of Settings: Range
The operative value of the setting is at the row of
ACTUAL word. The new value is introduced at the
following row, where there is the NEW word.
7-5
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 7. Alphanumeric Keypad and Display
7-6
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 7. Alphanumeric Keypad and Display
• Recloser Status
The Recloser possible status are: IN SERVICE or NOT IN SERVICE (if this settings is
activated); BLOCKED, if it’s blocked manual or externally (Recloser BLC signal activate);
UNBLOCKED, if it’s locked out (Recloser BLC and IB signal deactivate) or INTERNAL BLC if
it’s at internal blocked (Recloser IB signal activated).
At NO RECL row two values appears: one of them indicates the number of first reclose
attempts; the second one, shows the accumulated number 2nd, 3rd and 4th reclose attempts.
7-7
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 7. Alphanumeric Keypad and Display
Pressing again F2 the cycle can be repeat. The system automatically returns to the default
screen if no keys entries are made after 20 seconds.
7-8
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 7. Alphanumeric Keypad and Display
0 - CONFIGURATION 0 - PASSWORDS
1 - OPERATIONS 1 - OPERATION ENABLE
2 - ACTIVE GROUP 2 - CONFIGURE INPUTS
3 - CHANGE SETTINGS 3 - CONFIGURE OUTPUTS
4 - INFORMATION 4 - COMMUNICATIONS
5 - DATE & TIME
6 - CONTRAST
7 - LANGUAGE
8 - FREQUENCY
7-9
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 7. Alphanumeric Keypad and Display
0 - CONFIGURATION 0 - PASSWORDS
1 - OPERATIONS 1 - OPERATION ENABLE 0 - TERMINAL ADDRESS
2 - ACTIVE GROUP 2 - CONFIGURE INPUTS 1 - AUD RATE
3 - CHANGE SETTINGS 3 - CONFIGURE OUTPUTS 2 - STOP BITS
4 - INFORMATION 4 - COMMUNICATIONS 3 - PARITY
5 - DATE & TIME 4 - PARIDAD FRONTAL P.
6 - CONTRAST 5 - COM TIMEOUT
7 - LANGUAGE
8 - FREQUENCY
0 - CONFIGURATION 0 - PASSWORDS
1 - OPERATIONS 1 - OPERATION ENABLE
2 - ACTIVE GROUP 2 - CONFIGURE INPUTS
3 - CHANGE SETTINGS 3 - CONFIGURE OUTPUTS
4 - INFORMATION 4 - COMMUNICATIONS
5 - DATE & TIME
6 - CONTRAST 0 - SPANISH
7 - LANGUAGE 1 - ENGLISH
8 - FREQUENCY 2 - PORTUGUESE
0 - CONFIGURATION 0 - PASSWORDS
1 - OPERATIONS 1 - OPERATION ENABLE
2 - ACTIVE GROUP 2 - CONFIGURE INPUTS
3 - CHANGE SETTINGS 3 - CONFIGURE OUTPUTS
4 - INFORMATION 4 - COMMUNICATIONS
5 - DATE & TIME
6 - CONTRAST
7 - LANGUAGE 0 - 50 HZ
8 - FREQUENCY 1 - 60 HZ
0 - CONFIGURATION 0 - BREAKER
1 - OPERATIONS 1 - RECLOSER
2 - ACTIVE GROUP
3 - CHANGE SETTINGS
4 - INFORMATION
7-10
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 7. Alphanumeric Keypad and Display
0 - CONFIGURATION 0 - GENERAL
1 - OPERATIONS 1 - PROTECTION
2 - ACTIVE GROUP 2 - RECLOSER
3 - CHANGE SETTINGS 3 - LOGIC
4 - INFORMATION 4 - BREAKER SUPV.
5 - HISTORICAL RECOR
6 - OSCILLOGRAPHY
7-11
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 7. Alphanumeric Keypad and Display
7-12
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 7. Alphanumeric Keypad and Display
7-13
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 7. Alphanumeric Keypad and Display
7-14
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 7. Alphanumeric Keypad and Display
7-15
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 7. Alphanumeric Keypad and Display
7-16
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 7. Alphanumeric Keypad and Display
0 - CONFIGURATION 0 - GENERAL
1 - OPERATIONS 1 - PROTECTION
2 - ACTIVE GROUP 2 - RECLOSER 0 - CALC T INTERVAL
3 - CHANGE SETTINGS 3 - LOGIC 1 - DATA RCRD INTERVAL
4 - INFORMATION 4 - BREAKER SUPV. 2 - DAY CALENDAR MASK
5 - HISTORICAL RECOR 3 - HOUR RANGE
6 - OSCILLOGRAPHY
7-17
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 7. Alphanumeric Keypad and Display
0 - CONFIGURATION 0 - SETTINGS
1 - OPERATIONS 1 - CONFIGURATION
2 - ACTIVE GROUP 2 - TRIPS
3 - CHANGE SETTINGS 3 - RECORDS*
4 - INFORMATION 4 - STATUS
5 - METERING
(*) If the equipment have Oscillographic function, Records will be available only through communications..
This menu is identical to the one of Change Settings, as well as its later development, since it
talks about to the information on these settings.
7-18
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 7. Alphanumeric Keypad and Display
0 - CONFIGURATION 0 - SETTINGS T:
1 - OPERATIONS 1 - CONFIGURATION
2 - ACTIVE GROUP 2 - TRIPS RECL. RESET
3 - CHANGE SETTINGS 3 - RECORDS NO RECL:
4 - INFORMATION 4 - STATUS
5 - METERING
0 - CONFIGURATION 0 - SETTINGS
1 - OPERATIONS 1 - CONFIGURATION
2 - ACTIVE GROUP 2 - TRIPS
3 - CHANGE SETTINGS 3 - RECORDS 0 - CURRENTS
4 - INFORMATION 4 - STATUS 1 - IMAX
5 - METERING 2 - SEQUENCE CURRENTS
7-19
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 7. Alphanumeric Keypad and Display
7-20
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
8. Receiving
Tests
8.1 General ....................................................................................................................... 8-2
8.1.1 Accuracy ..................................................................................................................... 8-2
8.2 Preliminary Inspection ................................................................................................ 8-3
8.3 Isolation Test............................................................................................................... 8-3
8.4 Power Supply Test ...................................................................................................... 8-4
8.5 Metering Tests ............................................................................................................ 8-4
8.6 Phase and Ground Current Test................................................................................. 8-4
8.7 Open Phase Element Test.......................................................................................... 8-6
8.8 Residual Current Element Test................................................................................... 8-6
8.9 Breaker Failure Element Test ..................................................................................... 8-6
8.10 Recloser Test .............................................................................................................. 8-7
8.11 Digital Inputs, Auxiliary Outputs and LEDs Test ......................................................... 8-8
8.12 Communications Test ................................................................................................. 8-8
8.13 Installation ................................................................................................................... 8-9
8.13.1 Location ...................................................................................................................... 8-9
8.13.2 Connection .................................................................................................................. 8-9
Chapter 8. Receiving Tests
8.1 General
Improper handling of electrical equipment is extremely dangerous; therefore, only skilled and
qualified personnel familiar with appropriate safety procedures and precautions should work
with this equipment. Damage to equipment and injury to personnel can result when proper
safety precautions are not followed. The following general safety precautions are provided as a
reminder:
• High magnitude voltages are present in auxiliary supply and metering circuits even after
equipment has been disconnected.
• Equipment should be solidly grounded before handling or operating.
• Under no circumstances should the operating limits of the equipment be exceeded
(auxiliary voltage, current, etc.).
• The auxiliary supply voltage (AC or DC) should be disconnected from the equipment
before extracting or inserting any module, otherwise damage may result.
The number, the type and the specific characteristics of the acceptance tests are model
dependent and are detailed in the following table.
Preliminary Inspection
Power Supply Test
Metering Test
Overcurrent Units Test
Open Phase Test
IRD-A/J
Residual Overcurrent Test
Breaker Failure Test
Recloser Test
Inputs, Outputs and LEDs Supervision Test
Communications Test
8.1.1 Accuracy
The accuracy of the measuring instruments and test source signals (auxiliary power supply
voltage, AC currents and AC voltages) is fundamental in electrical testing. Therefore, the
information specified in the Technical Data section (2.1) of this manual can only be reasonably
verified with test equipment under normal reference conditions and with the tolerances indicated
in the UNE 21-136 and IEC 255 standards in addition to using precision instruments.
It is extremely important that there be little or no distortion (<2%) in the test source signals as
harmonics can affect internal measuring of the equipment. For example, distortions will affect
this IED, made up of non-linear elements, differently from an AC ammeter, because the
measurement is made differently in both cases.
It must be emphasized that the accuracy of the test will depend on the instruments used for
measuring as well as the source signals used. Therefore, tests performed with secondary
equipment should focus on operation verification and not on measuring accuracy.
8-2
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 8. Receiving Tests
• The relay is found in perfect physical condition, all of the parts are securely attached
and no assembly fasteners are missing.
• The model numbers and specifications agree with the equipment order.
CAUTION: Internal capacitors exist that can generate a high voltage if you take away the
isolation test probes without lowering the test voltage.
8-3
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 8. Receiving Tests
Test that when the equipment is found without power, the contacts designated by CON2P in the
table above are closed and the contacts designated by CON1P are open. Apply nominal power
test to see that the state of the contacts for CON1P and CON2P change and that the LED In
Service is on.
Note: Interval for pickup and tripping within lower current ranges can be extended to X ±20 mA.
8-4
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 8. Receiving Tests
• Operating Times
For this test use the trip contacts C7-C8 and C9-C10 (8IRD model) or 21-23 and 25-27 (3IRD
model).
8-5
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 8. Receiving Tests
Set the unit to 0.2 I2/I1 and check that has not pick up. Increase the B phase current and check
that the unit pick up (pick up flag to “1”) with a current value, on the B phase, between 1.35 Aac
and 1.49 Aac. Apply a 1 Aac current to A phase and check that a trip occurred between 10.5 s
and 9.5 s, for a 10 s time setting. Verify that the tripped contact close.
Set the Phase and Ground Instantaneous Overcurrent Pickup to 0.5A and set their Time Delay
to zero. Set Breaker Failure Time Delay to the desired value of current reposition and actuation
time. Produce a trip by applying 1A ac phase to ground to the Phase A and Ground Current
Analog Inputs, and maintain the current after the Phase and Ground elements trip. The Breaker
Failure element should operate between ± (0.025 s. or 5%) of the setting value. The operation
of the Breaker Failure element should activate the Auxiliary Contact Output.
Gradually reduce the current until the Breaker Failure element reaches a stable reset. Verify
that this occurs between ± 5% of the setting value.
8-6
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 8. Receiving Tests
- After manual closing, you must wait for the duration of the security time. If you do not
wait for that time before generating the trip, the Recloser will lockout.
- For the reclose sequence to start, the protection has to detect that the breaker is open,
and that no current flows through the phases before the starting time has concluded
(setting in the group of Recloser – Time Sequence Control).
- If the equipment is giving a fault in the breaker opening circuit, it will not carry out the
reclose, and will lockout.
- For the Recloser to carry out the complete sequence until its permanent fault status, the
trips have to be generated.
- It has to be taken into account if the rated voltage options and inhibition inputs, are
being used. Same remark for the units inhibitors and the trip and reclose masks.
Figure 8.2 shows how to carry out the Recloser test. If the current generator did not cut the
injection before the starting time, the test can be carried out by opening the current circuit (by
opening the breaker itself o by simulating it), or by generating an instantaneous trip, using a
simple pulse. This way of action could be sufficient to cause the Instantaneous Element to trip,
and at the same time, to stop it from seeing the current circulating before starting time.
8-7
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 8. Receiving Tests
Place yourself in the inputs screen of the Information menu (see Chapter 7, Alphanumeric
Keypad and Display) and verify that the inputs are activated (“1”). Switch the voltage off and
verify that the inputs get deactivated (“0”).
Trip and Close Circuits Monitoring Inputs
Once configured to the effect of the corresponding digital inputs, check that, without being
energized, these appear activated on the Information - Status – Digital Inputs screen or on
the ZiverCom® status screen.
The two circuit monitoring inputs, whether opening or closing, should not be at “1” or at “0”. If
this mistake were to happen, both inputs should be in different states.
• Auxiliary Outputs
To test the Auxiliary Outputs, you will have make them trip depending on how they have been
configured. If they do not have any configuration, the outputs can be configured as activation of
the physical inputs. That way at the same time as the inputs are being tested, correct tripping of
the output contacts from AUX1 to AUX7 is verified.
• LEDs
To test the LEDs, press the down arrow key F2 from the screen at rest until the LED targets
reset screen appears. Maintain the key pressed down until all the LEDs have been switched on.
Release the key and check that all the LEDs switch off.
Connect to the terminal unit through the local communications port using a DB9 (9-pin) serial
connection wire. Synchronize time using the ZIVercom© software program. Disconnect the
communications wire and disconnect the terminal unit power supply and wait for two minutes.
Afterwards, connect the power supply and connect to the terminal unit through the remote
communications port. Activate the “cyclical” mode in the ZIVercom© software program and
verify that time actualizes properly.
8-8
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 8. Receiving Tests
8.13 Installation
8.13.1 Location
The location where the Terminal Unit is to be installed should meet the following minimum
conditions to ensure correct operation, long service life, ease of installation and ease of
maintenance:
Mounting should be in accordance with the instructions regarding installations in the dimension
diagram.
8.13.2 Connection
Terminal 83 for the 3IRD or C1 for 8IRD should be solidly grounded to ensure disturbance
filtering circuits operate properly. The wire used for grounding these terminals should be
stranded 14 AWG. Ground wire length should be minimized and should not exceed 12”. The
ground terminal of the enclosure located on the rear panel of the equipment should also be
grounded.
8-9
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Chapter 8. Receiving Tests
8-10
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
A. PROCOME 3.0
Communications
Protocol
A.1 Settings ....................................................................................................................... A-2
A.1.1 Configuration Settings................................................................................................. A-2
A.1.2 Recloser Settings ........................................................................................................ A-2
A.1.3 Logic Settings ............................................................................................................. A-2
A.1.4 Metering History Log Settings..................................................................................... A-2
A.2 Description of Operation ............................................................................................. A-3
A.2.1 General Settings ......................................................................................................... A-3
A.2.2 Logic ........................................................................................................................... A-3
A.2.3 Event Record .............................................................................................................. A-3
A.2.4 Fault Report ................................................................................................................ A-4
A.2.5 Inputs .......................................................................................................................... A-4
A.2.6 Communicating with the Unit ...................................................................................... A-4
A.3 Alphanumeric Keypad and Display ............................................................................. A-5
A.3.1 Configuration............................................................................................................... A-5
A.3.2 Settings ....................................................................................................................... A-6
A.3.3 Accessing the Information .......................................................................................... A-6
Annex A. PROCOME 3.0 Communications Protocol
A.1 Settings
A.1.1 Configuration Settings
Communications (HMI)
Setting Range
Communications Password Enable YES / NO
Communications Password Timeout 1 - 1440 min
Communications Password 8 characters
Logic
Setting Range
Pickup Report YES / NO
A-2
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Annex A. PROCOME 3.0 Communications Protocol
If the directional elements are not in a stable situation they should not be unmasked. In the
specific case of the neutral directional, it should not be unmasked unless it is to analyze some
very specific situation.
A.2.2 Logic
• Pickup Report
The Fault Report is constructed as follows: it commences when a pickup occurs and ends when
the units are reset. The fault report file only makes an annotation if a trip occurs in the course of
the fault.
The Pickup Report setting allows selecting the option to make an annotation in the file without
a trip occurring. When the setting takes the value YES, the corresponding report is registered in
the fault report file without the need of a trip occurring.
If the Directional elements are not in a stable situation they should not be unmasked. In the
particular case of the Neutral Directional, it should not be unmasked unless it is to analyze
some very specific situation.
A-3
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Annex A. PROCOME 3.0 Communications Protocol
Pre-fault Magnitudes
- Currents (magnitude and angle) of the currents of the three phases and of the neutral
two cycles before the initiation of the fault. The angles refer to phase A of pre-fault
voltages.
- Voltages (magnitude and angle) of the three phases two cycles before the initiation of
the fault.
Trip Command Time Tag, presenting the date and time of the trip command. It also presents:
Fault Magnitudes
- Currents (magnitude and angle) two cycles and a half after the initiation of the fault.
The angles refer to phase A of pre-fault voltages.
- Voltages (magnitude and angle) two cycles and a half after the initiation of the fault.
A.2.5 Inputs
There exists the possibility of the physical inputs functioning with inverse logic, assigning one or
a set of them to a digital input or to its negated.
A-4
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Annex A. PROCOME 3.0 Communications Protocol
A-5
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Annex A. PROCOME 3.0 Communications Protocol
A.3.2 Settings
• Logic Settings
From the Change Settings menu, select the option 0 - TRIP SEAL-IN ENABLE
Logic to view the screen for selecting tables. 1 - OPEN FAILURE TIMER
2 - CLS FAILURE TIMER
3 - RECL MNCL ENABLE
4 - COORD TIMER
5- PICKUP REPORT
Pickup Report
The construction of the Fault Report commences when PICKUP REPORT
a pickup occurs and ends when the units are reset. An ACTUAL: YES
annotation is made in the Fault Report file when there NEW:
has been a trip in the course of the fault. When this ( 1 [ YES ] 0 [ NO ] )
setting takes the value YES, annotations will be made in
the report whether there is a trip not.
A-6
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
B. DNP 3.0
Communications
Protocol
B.1 Physical Architecture .................................................................................................. B-2
B.2 Settings ....................................................................................................................... B-2
B.3 Description of Operation ............................................................................................. B-3
B.3.1 DNP 3.0 Protocol ........................................................................................................ B-3
B.3.2 Communications ......................................................................................................... B-8
B.3.2.a Communication with the Equipment ...................................................................... B-8
B.4 Alphanumeric Keypad and Display ............................................................................. B-8
B.4.1 Change Settings ......................................................................................................... B-8
B.4.2 DNP3.0 Protocol ......................................................................................................... B-8
B.4.3 Information Access ..................................................................................................... B-9
Annex B. DNP 3.0 Communications Protocol
B.2 Settings
DNP 3.0 Protocol Settings
Setting Range Step
MTU Address (Master equipment number) 0 - 65519 1
RTU Address (Slave equipment number) 0 - 65519 1
Enable unsolicited report 0-1
Reply Timeout N7 100 - 65535 ms 1 ms
Unsol Retard 100 - 65535 ms 1 ms
N7 Retry Counter 0-3 1
Pre-transmission Time 0 - 65535 ms 1 ms
Echo Control Enable 0-1
N2 Retry Counter 0 - 32 1
Fixed Delay 0 - 32767 1 ms
Max. Random Delay 0 - 32767 1 ms
B-2
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Annex B. DNP 3.0 Communications Protocol
MTU Address
Destination address of the Master device to which the unsolicited responses are to be sent.
Addresses 0xFFF0 to 0xFFFF are reserved as Broadcast Addresses. It is useful only when
Unsolicited Reporting is enabled.
RTU Address
Remote Terminal Unit Address. Addresses 0xFFF0 to 0xFFFF are reserved as Broadcast
Addresses.
Unsol Enable
Enables (YES) or disables (NO) sending spontaneous messages (Unsolicited); it is used in
combination with the MTU Number parameter. For the IRD relay to begin sending spontaneous
messages the master must also enable them with the Function Code FC = 20..
Time out N7
It specifies the time lapse (in milliseconds) from the time the IRD sends a message requesting
the master to confirm the Application layer (Level 7), until this confirmation is considered lost.
The IRV requests confirmation of the Application Layer when it sends spontaneous (Unsolicited)
messages or in response to requests for Class 1 or Class 2 Data. When this time expires, the
message is retransmitted the number of times specified in the N. Retries parameter.
Unsolicited Delay Reporting)
Delay between an event being generated and the subsequent transmission of the unsolicited
message, in order to group several events in one message and to save bandwidth.
N7 Retries
Number of retries of the Application Layer (N7). The default value is 0 (zero), indicating that no
retransmission will be attempted.
Pre-Transmission
Time setting which generates the number of warning characters.
Echo Control
The activation or deactivation of the transmission echo
Note: warning time and echo control settings are used to have various equipments connected to a concentrator
type CCY and working in multi-master mode.
B-3
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Annex B. DNP 3.0 Communications Protocol
• Metering Changes
16 analog metering bands (from 0 to 15) can be set. The setting represents the percentage over
the maximum value of the measure, that will be taken as reference to test if there is an
analogical change to record. In other word, a change will be recorded if the difference in the
analogical measures is greater than the set percentage.
If it is adjusted to 100%, analogical changes in this measure will not be recorded, which is then
understood as being in a deactivated state.
B-4
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Annex B. DNP 3.0 Communications Protocol
• Implementation Table
REQUEST RESPONSE
OBJECT
(IRD will parse) (IRD will respond)
Func Qual Func Qual
Obj Var Codes Codes Codes Codes Notes
Description (dec) (hex) (dec) (hex)
Echo of
12 1 Control Relay Output Block 3,4,5,6 0x17,28 129
request
0x7
50 1 Time and Date 2 129 C
count=1
0x7
52 2 Time Delay Fine 23 129 F,G
count=1
B-5
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Annex B. DNP 3.0 Communications Protocol
REQUEST RESPONSE
OBJECT
(IRD will parse) (IRD will respond)
Func Qual Func Qual
Obj Var Description Codes Codes Codes Codes Notes
(dec) (hex) (dec) (hex)
0x0
80 1 Internal Indications 2 E
index=7
Notes:
A: The unit's level of implementation does not support this group and object variation or, for static objects, it
does not have objects with this group and variation. OBJECT UNKNOWN response (IIN2 bit 1 active).
B: No range of points is specified, and the unit does not have objects of this type. Null response (no IIN bit
active, simply no response is made to any object of the type specified).
C: The unit supports write operations on “time and date” objects. The “Time Synchronization-Required Internal
Indication” bit (IIN1-4) will be set to zero in the response.
D: The unit can be configured for sending or not sending unsolicited responses. There is a configuration option
accessible through the man-machine interface or front-panel user interface. Once the unsolicited option is
enabled, the master can enable or disable unsolicited messages (for classes 1 and 2) by means of requests (FC
20 and 21).
If unsolicited response mode is enabled, then after restarting the unit, it will transmit an initial Null unsolicited
response, requesting confirmation of the application layer. While awaiting the confirmation of the application
layer, the unit will respond to all request functions, including READ requests.
E: The “Restart Internal Indication” bit (IIN1-7) can be explicitly set to zero by the master.
F: The remote station, after receiving a Cold or Warm Start request, will respond by sending a “Time Delay Fine
object” message (which specifies an interval of time until the remote station will be ready for more
communications), reinitiating the process and setting bit DNP IIN1-7 (Device Restart).
G: The unit supports “Delay Measurement” requests (FC = 23). It responds with the “Time Delay Fine object”
(52-2). This object sets the number of milliseconds to transpire between the remote station's reception of the
first bit of the first byte of the request and the
B-6
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Annex B. DNP 3.0 Communications Protocol
Internal Indication IIN1-6 (Device trouble): It activates to indicate a change in the current
DNP configuration of the remote station. It deactivates in the next response. It is used to let the
master station know that the DNP settings have changed in the remote station. Note that some
erroneous configurations could render it impossible to communicate this condition to a master
station.
This "Device Profile Document" also declares the DNP 3.0 settings available in the unit. If the
user changes any of these settings, the “Device Trouble Internal Indication” bit will activate in
the next response sent.
Event Files: the unit can store up to 50 “Binary Input Changes” and 50 “Analog Input Changes.”
If the unit's limits are reached, the “Event Buffers Overflow Internal Indication” bit will be enabled
in the next response sent. It will be disabled when the master reads the changes, making room
for new ones.
The measurements (16-Bit Analog Input) sent by communications depend on each control
model, and their scale readings are:
So that:
B-7
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Annex B. DNP 3.0 Communications Protocol
B.3.2 Communications
B.3.2.a Communication with the Equipment
The IRD models can be fitted with an optional second rear port.
B-8
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Annex B. DNP 3.0 Communications Protocol
B-9
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Annex B. DNP 3.0 Communications Protocol
B-10
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
C. MODBUS RTU
Documentation.
Address Map
C.1 Preliminary Information .............................................................................................. C-2
C.2 Reading of Outputs (Read Coil Status) ..................................................................... C-3
C.3 Reading of Inputs (Read Input Status) ...................................................................... C-4
C.4 Reading of Metering Register (Read Input Registers)............................................... C-5
C.5 Commands (Force Single Coil).................................................................................. C-5
Annex C. MODBUS RTU Documentation. Address Map
Documentation specific to the models with the MODBUS RTU communication profile
This document describes the ModBus map of addresses (inputs, outputs, metering registers
and commands) and their equivalent in the IRD-A/J relay.
Any other function non-included in the table above will be considered illegal and the exception
code 01 (Illegal function) will be returned as a reply.
C-2
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Annex C. MODBUS RTU Documentation. Address Map
Address Description
0200H (*) Breaker Status
0201H (*) Internal Recloser Lockout
0202H (*) Manually Recloser Lockout
0203H (*) Externally Recloser Lockout
0204H (*) Recloser Sequence in Progress
0205H (*) Recloser Reset
0206H (*) Recloser in Service
0207H Aux-1 Status
0208H Aux-2 Status
0209H Aux-3 Status
020AH Aux-4 Status
020BH Aux-5 Status
020CH Aux-6 Status
020DH Aux-7 Status
020EH Aux-1 Status (Virtual)
020FH Aux-2 Status (Virtual)
0210H Aux-3 Status (Virtual)
0211H Aux-4 Status (Virtual)
0212H Aux-5 Status (Virtual)
0213H Aux-6 Status (Virtual)
0214H Aux-7 Status (Virtual)
Assigned addresses are fixed. The content of the addresses indicated with an (*) is also fixed,
the content of the other addresses being variable (it depends on the configuration selected by
the end-user for each relay).
The remaining addresses of the range will be considered as illegal and the exception code 02
(Illegal Data Address) will be returned as a reply.
C-3
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Annex C. MODBUS RTU Documentation. Address Map
Address Description
0000H ENT-1 Status
0001H ENT-2 Status
0002H ENT-3 Status
0003H ENT-4 Status
0004H ENT-5 Status
0005H ENT-6 Status
0006H ENT-7 Status
0007H ENT-8 Status
0008H ENT-9 Status
0009H ENT-10 Status
000AH ENT-11 Status
000BH ENT-12 Status
000CH ENT-13 Status
000DH ENT-14 Status
000EH ENT-15 Status
000FH ENT-16 Status
Assigned addresses are fixed, their content being variable (it depends on the configuration
selected by the end-user for each relay).
The remaining addresses of the range will be considered as illegal and the exception code 02
(Illegal Data Address) will be returned as a reply.
C-4
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Annex C. MODBUS RTU Documentation. Address Map
Address Description
2000H Phase A Current Metering
2001H Phase B Current Metering
2002H Phase C Current Metering
The rest of addresses of the range will be considered as illegal and the exception code 02
(Illegal Data Address) will be returned as a reply.
The rest of addresses of the range will be considered as illegal and the exception code 02
(Illegal Data Address) will be returned as a reply.
Any other value different from 00H or FHH will be considered as illegal and the exception code
03 (Illegal Data Value) will be returned as a reply.
C-5
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Annex C. MODBUS RTU Documentation. Address Map
C-6
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
D. Schemes and
Drawings
3IRD-A >>3RX0101/0051
8IRD-A >>3RX0123/0048
3IRD-J >>3RX0101/0052
8IRD-J/W >>3RX0123/0049
E. List of Illustrations
and Tables
E.1 List of Figures ............................................................................................................. E-2
E.2 List of Tables............................................................................................................... E-3
Annex E. List of Illustrations and Tables
5. Settings
5.1 8IRD Model Internal Jumpers. ..................................................................... 5-8
5.2 3IRD Model Internal Jumpers. ..................................................................... 5-9
6. Description of Operation
6.1 Inverse Time / Current Characteristic. ......................................................... 6-3
6.2 Very Inverse Time / Current Characteristic. ................................................. 6-4
6.3 Extremely Inverse Time/Current Characteristic. .......................................... 6-5
6.4 Overcurrent Unit Block Diagram (IRD-A Model). ......................................... 6-6
6.5 Overcurrent Unit Block Diagram (IRD-J Model)........................................... 6-7
6.6 Breaker Failure Element Block Diagram. ..................................................... 6-8
6.7 Open Phase Element Block Diagram (without Minimum Load in the
Line Setting). ................................................................................................ 6-9
6.8 Open Phase Element Block Diagram (with Minimum Load in the Line
Setting) ......................................................................................................... 6-10
6.9 Residual Current Unit Detection Block Diagram. ......................................... 6-10
6.10 Recloser Flow Diagram (I). .......................................................................... 6-14
6.11 Recloser Flow Diagram (II). ......................................................................... 6-15
6.12 Trip/Close Coil Circuit Supervision Block Diagram. ..................................... 6-22
6.13 Trip/Close Output Supervision Block Diagram. ........................................... 6-24
6.14 Metering History Log Diagram. .................................................................... 6-33
6.15 Auxiliary Contact Output Logic Cell Block Diagram. .................................... 6-39
6.16 LED Target Output Logic Cell Block Diagram. ............................................ 6-45
8. Receiving Tests
8.1 Connection Diagram for the Time Metering Test. ........................................ 8-5
8.2 Recloser Test Setup. ................................................................................... 8-7
E-2
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Annex E. List of Illustrations and Tables
8. Receiving Tests
8-1 Isolation Groups........................................................................................... 8-3
8-2 Power Supply Test....................................................................................... 8-4
8-3 Current Metering Test .................................................................................. 8-4
8-4 Phase and Ground Current Test ................................................................. 8-4
E-3
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
Annex E. List of Illustrations and Tables
E-4
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011
F. Warranty
Annex F. Warranty
All new products sold to customers are warranted against defects in design, materials, and workmanship
for a period of ten (10) years from the time of delivery (at the moment the product leaves ZIV GRID
AUTOMATION premises, as indicated in the shipping documents). Customer is responsible of notifying
ZIV GRID AUTOMATION of any faulty conditions as soon as they are detected. If it is determined that the
new product defect is covered by the warranty, ZIV GRID AUTOMATION will repair, or substitute the
product at its own discretion to the customer at no charge.
ZIV GRID AUTOMATION may, at its own discretion, require the customer to ship the unit back to the
factory for diagnosis before making a determination as to whether it is covered by this warranty. Shipping
costs to the ZIV GRID AUTOMATION factory (including but not limited to, freight, insurance, customs fees
and taxes, and any other expenses) will be the responsibility of the customer. All expenses related to the
shipment of the repaired or replacement units back to the customer will be borne by ZIV GRID
AUTOMATION.
Customers are responsible for all expenses related to the shipment of defective units back to ZIV GRID
AUTOMATION when it is determined that such units are not covered under this warranty or that the fault is
not ZIV GRID AUTOMATION´s responsibility. Units repaired by ZIV GRID AUTOMATION are warranted
against defects in materials, and manufacturing for a period of one (1) year from the time of delivery (at the
moment the product leaves ZIV GRID AUTOMATION premises, as indicated by the shipping documents),
or for the remaining of the original warranty, whichever is greater.
ZIV GRID AUTOMATION warranty does not cover: 1) improper installation, connection, operation,
maintenance, and/or storage, 2) minor defects not interfering with the operation of the product, possible
indemnities, misuse or improper usage, 3) abnormal or unusual operating conditions or application outside
the specifications for the product, 4) application in any way different from that for which the products were
designed, 5) repairs or alterations performed by individuals other than ZIV GRID AUTOMATION
employees or an authorised representative.
Limitations:
1) Equipment or products provided but not manufactured by ZIV GRID AUTOMATION. Such products
may be covered by a warranty issued by the corresponding manufacturer.
2) Software: ZIV GRID AUTOMATION warrants that the licensed Software corresponds with the
specifications included in the instruction manuals provided with the units, or with the specifications
agreed with the end-customer. ZIV GRID AUTOMATION sole and entire liability, and customer
exclusive remedy, with respect to any claims relating to the Software shall be to provide a new set
of diskettes free of charge.
3) In the case that a bank guarantee or similar instrument be required to back up the warranty period,
such warranty period, and only for these purposes, will be of a maximum of twelve (12) months
from the time of delivery (at the moment the product leaves ZIV GRID AUTOMATION premises, as
indicated in the shipping documents).
THIS WARRANTY IS IN LIEU OF ANY OTHER WARRANTIES AND ZIV GRID AUTOMATION HEREBY
DISCLAIMS ANY OTHER WARRANTY, EXPRESS OR IMPLIED, INCLUDING, WITHOUT LIMITATION,
ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. IN NO
EVENT SHALL ZIV GRID AUTOMATION BE LIABLE FOR ANY INDIRECT, INCIDENTAL,
CONSEQUENTIAL, OR SPECIAL DAMAGES OR FOR ANY OTHER LOSS, INJURY, DAMAGE, OR
EXPENSE OF ANY KIND INCLUDING LOST PROFITS OR ANY OTHER PECUNIARY LOSS ARISING
FROM ANY SOURCE.
F-2
BIRD1102A
IRD: Overcurrent Protection
© ZIV GRID AUTOMATION, S. L. Zamudio, 2011