6/11/2020 Performance Data Sheet

Project Name: IJLDS - HN - CIRAIRE JCI Contract No: Contract #


Location: Coil Version: 7.05b
Consultant/Engineer: Printed Date: 6/11/2020 5:57:23 PM
Contractor: Selection Date: 6/11/2020 4:39:52 PM
Sold To: Last Revision Date: 6/11/2020 4:40:19 PM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty
FL-L0-1, FL-L0-2, FL-L0-15 3 FHP-D06 425 CFM 11,994 Btuh 9,364 Btuh
Unit Data
Model Size : 06 (Fans) Speed : (2) High Filter : 1" Throwaway Coil Tube Dia. [in.] 1/2
Type : Horizontal Low Profile - Series D (Motors) HP : (1) 1/4 Filter (Qty) Size : 31 x 9.25 x 1 Tube Wall [in.] 0.025
Motor FLA : 2 Filter Face Area [ft²] 1.99 Coil Face Area [ft²] 1.62
Motor Type : ECM-B Weight* [lb] 78
Capacity : Std. Capacity
Output Data Options
Altitude [Ft.] 0 Auxiliary Drip Pan- Galvanized Auxiliary Drip Pan
Air Flow Rate [CFM] 425 BC02 24V, Unit S/S Relay / Fan Op. Relay & Transformer
ESP [in.wg] 0.25 Elastomeric Closed Cell Foam Insulation
Chilled Water Coil Data Enclosure Mount- Unit Mounted
EAT DB/WB [°F] 73.4/ 62.0 Galvanized Drain pan
LAT DB/WB [°F] 53.4/ 52.1 Motor Control- 2-10 VDC (Sync)
Total Capacity [Btuh] 11,994 Return Air Options- Return: Bottom No Duct Collar
Sensible Capacity [Btuh] 9,364 Thermostat Location- No Thermostat
EWT/LWT [°F] 42.0/ 53.6 Thermostat- No Thermostat
Fluid Flow [gpm] 2.10 Chilled Water Coil: Field Provided Piping Package Size - 1/2"
Fluid P.D [ft.wg] 3.07 Chilled Water Coil:Galvanized Casing
Fluid Velocity [fps] 2.10 Chilled Water Coil:Left Hand Connection
Rows / FPI / Circuits : 4 Row / 10 FPI / 2 Ckt Chilled Water Coil:Manual Air Vent
Coil Connection Size: [in.] 0.875 Chilled Water Coil:Package Code- Field Provided by Others 1/2" Valve Package
Heating Data
EAT DB [°F] -
LAT DB [°F] -
Sensible Capacity [Btuh] -
Rows / FPI / Circuits : -/-/-
Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data
Motor Voltage [V/P/HZ] 115/1/60 ECM * Unit weight includes unit with wet coil(s) as selected.
Does not include accessories
Total Full Load Amps : 2.00 Unit pressure drop and air flow based upon dry coil as required by AHRI-
MCA / MSCP : 2.50 / 15.00 440.
Fan Power Input [Watts@CFM] 71.00 Sound data tested in accordance with AHRI-260-2012
Sound Data Calculated at 425 CFM and 1309 RPM
Sound Data Calculated at 425 CFM and 1309 RPM Scheduled motor information is for Fan Input Power at High Speed.
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz For 0' altitude the coil selection has been made at Standard Conditions.
Ducted Discharge 58 55 53 53 49 42 33
Casing Radiated Free Inlet 59 61 58 55 49 44 36

https://webselect.johnsoncontrols.com/submittals/perfreport/PerformanceDataSheet.aspx?chnl=JCI&project=4517957&lineid=4517958,4518014,452… 1/16
6/11/2020 Performance Data Sheet
Project Name: IJLDS - HN - CIRAIRE JCI Contract No: Contract #
Location: Coil Version: 7.05b
Consultant/Engineer: Printed Date: 6/11/2020 5:57:23 PM
Contractor: Selection Date: 6/9/2020 11:10:25 AM
Sold To: Last Revision Date: 6/9/2020 11:11:19 AM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty
FC-L0-03, FC-L0-03 2 FHP-D10 600 CFM 17,520 Btuh 13,390 Btuh
Unit Data
Model Size : 10 (Fans) Speed : (4) Medium Filter : 1" Throwaway Coil Tube Dia. [in.] 1/2
Type : Horizontal Low Profile - Series D (Motors) HP : (2) 1/4 Filter (Qty) Size : (2) 26 x 9.25 x 1 Tube Wall [in.] 0.025
Motor FLA : 3.2 Filter Face Area [ft²] 3.34 Coil Face Area [ft²] 2.71
Motor Type : ECM-B Weight* [lb] 129
Capacity : Std. Capacity
Output Data Options
Altitude [Ft.] 0 Auxiliary Drip Pan- Galvanized Auxiliary Drip Pan
Air Flow Rate [CFM] 600 BC02 24V, Unit S/S Relay / Fan Op. Relay & Transformer
ESP [in.wg] 0.25 Elastomeric Closed Cell Foam Insulation
Chilled Water Coil Data Enclosure Mount- Unit Mounted
EAT DB/WB [°F] 73.4/ 62.3 Galvanized Drain pan
LAT DB/WB [°F] 53.2/ 52.1 Motor Control- 2-10 VDC (Sync)
Total Capacity [Btuh] 17,520 Return Air Options- Return: Bottom No Duct Collar
Sensible Capacity [Btuh] 13,390 Thermostat Location- No Thermostat
EWT/LWT [°F] 42.0/ 54.3 Thermostat- No Thermostat
Fluid Flow [gpm] 2.90 Chilled Water Coil: Field Provided Piping Package Size - 1/2"
Fluid P.D [ft.wg] 2.37 Chilled Water Coil:Galvanized Casing
Fluid Velocity [fps] 1.90 Chilled Water Coil:Left Hand Connection
Rows / FPI / Circuits : 4 Row / 10 FPI / 3 Ckt Chilled Water Coil:Manual Air Vent
Coil Connection Size: [in.] 0.875 Chilled Water Coil:Package Code- Field Provided by Others 1/2" Valve Package
Heating Data
EAT DB [°F] -
LAT DB [°F] -
Sensible Capacity [Btuh] -
Rows / FPI / Circuits : -/-/-
Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data
Motor Voltage [V/P/HZ] 115/1/60 ECM * Unit weight includes unit with wet coil(s) as selected.
Does not include accessories
Total Full Load Amps : 3.20 Unit pressure drop and air flow based upon dry coil as required by AHRI-
MCA / MSCP : 3.60 / 15.00 440.
Fan Power Input [Watts@CFM] 84.00 Sound data tested in accordance with AHRI-260-2012
Sound Data Calculated at 600 CFM and 1196 RPM
Sound Data Calculated at 600 CFM and 1196 RPM Scheduled motor information is for Fan Input Power at High Speed.
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz For 0' altitude the coil selection has been made at Standard Conditions.
Ducted Discharge 57 55 54 55 49 39 30
Casing Radiated Free Inlet 58 59 57 54 48 39 32

https://webselect.johnsoncontrols.com/submittals/perfreport/PerformanceDataSheet.aspx?chnl=JCI&project=4517957&lineid=4517958,4518014,452… 2/16
6/11/2020 Performance Data Sheet
Project Name: IJLDS - HN - CIRAIRE JCI Contract No: Contract #
Location: Coil Version: 7.05b
Consultant/Engineer: Printed Date: 6/11/2020 5:57:23 PM
Contractor: Selection Date: 6/11/2020 4:05:46 PM
Sold To: Last Revision Date: 6/11/2020 4:07:00 PM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty
FC-L0-5 1 FHP-D10 770 CFM 22,730 Btuh 16,350 Btuh
Unit Data
Model Size : 10 (Fans) Speed : (4) High Filter : 1" Throwaway Coil Tube Dia. [in.] 3/8
Type : Horizontal Low Profile - Series D (Motors) HP : (2) 1/4 Filter (Qty) Size : (2)26x10.5x1 Coil Face Area [ft²] 2.89
Motor FLA : 3.2 Filter Face Area [ft²] 3.79 Weight* [lb] 109
Motor Type : ECM-B
Capacity : Std. Capacity
Output Data Options
Altitude [Ft.] 0 Auxiliary Drip Pan- Galvanized Auxiliary Drip Pan
Air Flow Rate [CFM] 770 BC02 24V, Unit S/S Relay / Fan Op. Relay & Transformer
ESP [in.wg] 0.25 Elastomeric Closed Cell Foam Insulation
Chilled Water Coil Data Enclosure Mount- Unit Mounted
EAT DB/WB [°F] 73.2/ 62.6 Galvanized Drain pan
LAT DB/WB [°F] 53.8/ 52.2 Motor Control- 2-10 VDC (Sync)
Total Capacity [Btuh] 22,730 Return Air Options- Return: Rear No Duct Collar
Sensible Capacity [Btuh] 16,350 Thermostat Location- No Thermostat
EWT/LWT [°F] 42.0/ 53.5 Thermostat- No Thermostat
Fluid Flow [gpm] 4.00 Chilled Water Coil: Field Provided Piping Package Size - 1/2"
Fluid P.D [ft.wg] 13.62 Chilled Water Coil:Galvanized Casing
Fluid Velocity [fps] 4.00 Chilled Water Coil:Left Hand Connection
Rows / FPI / Circuits : 3 Row / 12 FPI / 3 Ckt Chilled Water Coil:Manual Air Vent
Coil Connection Size: [in.] 0.875 Chilled Water Coil:Package Code- Field Provided by Others 1/2" Valve Package
Heating Data
EAT DB [°F] -
LAT DB [°F] -
Sensible Capacity [Btuh] -
Rows / FPI / Circuits : -/-/-
Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data
Motor Voltage [V/P/HZ] 115/1/60 ECM * Unit weight includes unit with wet coil(s) as selected.
Does not include accessories
Total Full Load Amps : 3.20 Unit pressure drop and air flow based upon dry coil as required by AHRI-
MCA / MSCP : 3.60 / 15.00 440.
Fan Power Input [Watts@CFM] 123.00 Sound data tested in accordance with AHRI-260-2012
Sound Data Calculated at 770 CFM and 1297 RPM
Sound Data Calculated at 770 CFM and 1297 RPM Scheduled motor information is for Fan Input Power at High Speed.
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz For 0' altitude the coil selection has been made at Standard Conditions.
Ducted Discharge 59 58 56 57 52 44 34
Casing Radiated Free Inlet 60 61 59 56 51 44 36

https://webselect.johnsoncontrols.com/submittals/perfreport/PerformanceDataSheet.aspx?chnl=JCI&project=4517957&lineid=4517958,4518014,452… 3/16
6/11/2020 Performance Data Sheet
Project Name: IJLDS - HN - CIRAIRE JCI Contract No: Contract #
Location: Coil Version: 7.05b
Consultant/Engineer: Printed Date: 6/11/2020 5:57:23 PM
Contractor: Selection Date: 6/11/2020 4:10:33 PM
Sold To: Last Revision Date: 6/11/2020 4:11:07 PM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty
FC-L0-6 1 FHP-D09 600 CFM 14,654 Btuh 12,064 Btuh
Unit Data
Model Size : 09 (Fans) Speed : (2) High Filter : 1" Throwaway Coil Tube Dia. [in.] 3/8
Type : Horizontal Low Profile - Series D (Motors) HP : (1) 1/4 Filter (Qty) Size : (1)20x10.5x1 Coil Face Area [ft²] 2.35
Motor FLA : 2.7 (1)22.25x10.5x1 Weight* [lb] 88
Motor Type : ECM-B Filter Face Area [ft²] 3.08
Capacity : Std. Capacity
Output Data Options
Altitude [Ft.] 0 Auxiliary Drip Pan- Galvanized Auxiliary Drip Pan
Air Flow Rate [CFM] 600 BC02 24V, Unit S/S Relay / Fan Op. Relay & Transformer
ESP [in.wg] 0.25 Elastomeric Closed Cell Foam Insulation
Chilled Water Coil Data Enclosure Mount- Unit Mounted
EAT DB/WB [°F] 72.8/ 61.1 Galvanized Drain pan
LAT DB/WB [°F] 54.4/ 52.3 Motor Control- 3 Speed Adjustable (Select)
Total Capacity [Btuh] 14,654 Return Air Options- Return: Rear No Duct Collar
Sensible Capacity [Btuh] 12,064 Thermostat Location- No Thermostat
EWT/LWT [°F] 42.0/ 53.1 Thermostat- No Thermostat
Fluid Flow [gpm] 2.70 Chilled Water Coil: Field Provided Piping Package Size - 1/2"
Fluid P.D [ft.wg] 4.80 Chilled Water Coil:Galvanized Casing
Fluid Velocity [fps] 2.70 Chilled Water Coil:Left Hand Connection
Rows / FPI / Circuits : 3 Row / 12 FPI / 3 Ckt Chilled Water Coil:Manual Air Vent
Coil Connection Size: [in.] 0.875 Chilled Water Coil:Package Code- Field Provided by Others 1/2" Valve Package
Heating Data
EAT DB [°F] -
LAT DB [°F] -
Sensible Capacity [Btuh] -
Rows / FPI / Circuits : -/-/-
Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data
Motor Voltage [V/P/HZ] 115/1/60 ECM * Unit weight includes unit with wet coil(s) as selected.
Does not include accessories
Total Full Load Amps : 2.70 Unit pressure drop and air flow based upon dry coil as required by AHRI-
MCA / MSCP : 3.38 / 15.00 440.
Fan Power Input [Watts@CFM] 94.00 Sound data tested in accordance with AHRI-260-2012
Sound Data Calculated at 600 CFM and 1260 RPM
Sound Data Calculated at 600 CFM and 1260 RPM Scheduled motor information is for Fan Input Power at High Speed.
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz For 0' altitude the coil selection has been made at Standard Conditions.
Ducted Discharge 58 58 55 57 52 46 38
Casing Radiated Free Inlet 61 63 58 54 48 44 37

https://webselect.johnsoncontrols.com/submittals/perfreport/PerformanceDataSheet.aspx?chnl=JCI&project=4517957&lineid=4517958,4518014,452… 4/16
6/11/2020 Performance Data Sheet
Project Name: IJLDS - HN - CIRAIRE JCI Contract No: Contract #
Location: Coil Version: 7.05b
Consultant/Engineer: Printed Date: 6/11/2020 5:57:23 PM
Contractor: Selection Date: 6/11/2020 4:24:43 PM
Sold To: Last Revision Date: 6/11/2020 4:25:17 PM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty
FC-L0-8, FC-L0-9 2 FHP-D08 525 CFM 15,744 Btuh 12,344 Btuh
Unit Data
Model Size : 08 (Fans) Speed : (2) High Filter : 1" Throwaway Coil Tube Dia. [in.] 3/8
Type : Horizontal Low Profile - Series D (Motors) HP : (1) 1/4 Filter (Qty) Size : (2)19x10.5x1 Coil Face Area [ft²] 2.11
Motor FLA : 2 Filter Face Area [ft²] 2.77 Weight* [lb] 84
Motor Type : ECM-B
Capacity : Std. Capacity
Output Data Options
Altitude [Ft.] 0 Auxiliary Drip Pan- Galvanized Auxiliary Drip Pan
Air Flow Rate [CFM] 525 BC02 24V, Unit S/S Relay / Fan Op. Relay & Transformer
ESP [in.wg] 0.25 Elastomeric Closed Cell Foam Insulation
Chilled Water Coil Data Enclosure Mount- Unit Mounted
EAT DB/WB [°F] 73.0/ 61.5 Galvanized Drain pan
LAT DB/WB [°F] 51.5/ 50.7 Motor Control- 2-10 VDC (Sync)
Total Capacity [Btuh] 15,744 Return Air Options- Return: Rear No Duct Collar
Sensible Capacity [Btuh] 12,344 Thermostat Location- No Thermostat
EWT/LWT [°F] 42.0/ 54.7 Thermostat- No Thermostat
Fluid Flow [gpm] 2.50 Chilled Water Coil: Field Provided Piping Package Size - 1/2"
Fluid P.D [ft.wg] 5.09 Chilled Water Coil:Galvanized Casing
Fluid Velocity [fps] 2.50 Chilled Water Coil:Left Hand Connection
Rows / FPI / Circuits : 4 Row / 12 FPI / 3 Ckt Chilled Water Coil:Manual Air Vent
Coil Connection Size: [in.] 0.875 Chilled Water Coil:Package Code- Field Provided by Others 1/2" Valve Package
Heating Data
EAT DB [°F] -
LAT DB [°F] -
Sensible Capacity [Btuh] -
Rows / FPI / Circuits : -/-/-
Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data
Motor Voltage [V/P/HZ] 115/1/60 ECM * Unit weight includes unit with wet coil(s) as selected.
Does not include accessories
Total Full Load Amps : 2.00 Unit pressure drop and air flow based upon dry coil as required by AHRI-
MCA / MSCP : 2.50 / 15.00 440.
Fan Power Input [Watts@CFM] 76.00 Sound data tested in accordance with AHRI-260-2012
Sound Data Calculated at 525 CFM and 1254 RPM
Sound Data Calculated at 525 CFM and 1254 RPM Scheduled motor information is for Fan Input Power at High Speed.
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz For 0' altitude the coil selection has been made at Standard Conditions.
Ducted Discharge 57 57 54 56 51 45 36
Casing Radiated Free Inlet 60 62 56 53 47 42 35

https://webselect.johnsoncontrols.com/submittals/perfreport/PerformanceDataSheet.aspx?chnl=JCI&project=4517957&lineid=4517958,4518014,452… 5/16
6/11/2020 Performance Data Sheet
Project Name: IJLDS - HN - CIRAIRE JCI Contract No: Contract #
Location: Coil Version: 7.05b
Consultant/Engineer: Printed Date: 6/11/2020 5:57:23 PM
Contractor: Selection Date: 6/11/2020 4:30:33 PM
Sold To: Last Revision Date: 6/11/2020 4:31:15 PM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty
FC-L0-10, FC-L0-11 2 FHP-D12 900 CFM 24,071 Btuh 20,061 Btuh
Unit Data
Model Size : 12 (Fans) Speed : (4) High Filter : 1" Throwaway Coil Tube Dia. [in.] 3/8
Type : Horizontal Low Profile - Series D (Motors) HP : (2) 1/4 Filter (Qty) Size : (1)20x10.5x1 (1)40x10.5x1 Coil Face Area [ft²] 3.33
Motor FLA : 3.6 Filter Face Area [ft²] 4.38 Weight* [lb] 129
Motor Type : ECM-B
Capacity : Std. Capacity
Output Data Options
Altitude [Ft.] 0 Auxiliary Drip Pan- Galvanized Auxiliary Drip Pan
Air Flow Rate [CFM] 900 BC02 24V, Unit S/S Relay / Fan Op. Relay & Transformer
ESP [in.wg] 0.25 Elastomeric Closed Cell Foam Insulation
Chilled Water Coil Data Enclosure Mount- Unit Mounted
EAT DB/WB [°F] 73.2/ 61.3 Galvanized Drain pan
LAT DB/WB [°F] 52.8/ 51.7 Motor Control- 2-10 VDC (Sync)
Total Capacity [Btuh] 24,071 Return Air Options- Return: Rear No Duct Collar
Sensible Capacity [Btuh] 20,061 Thermostat Location- No Thermostat
EWT/LWT [°F] 42.0/ 55.6 Thermostat- No Thermostat
Fluid Flow [gpm] 3.60 Chilled Water Coil: Field Provided Piping Package Size - 1/2"
Fluid P.D [ft.wg] 2.94 Chilled Water Coil:Galvanized Casing
Fluid Velocity [fps] 2.20 Chilled Water Coil:Left Hand Connection
Rows / FPI / Circuits : 4 Row / 12 FPI / 5 Ckt Chilled Water Coil:Manual Air Vent
Coil Connection Size: [in.] 0.875 Chilled Water Coil:Package Code- Field Provided by Others 1/2" Valve Package
Heating Data
EAT DB [°F] -
LAT DB [°F] -
Sensible Capacity [Btuh] -
Rows / FPI / Circuits : -/-/-
Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data
Motor Voltage [V/P/HZ] 115/1/60 ECM * Unit weight includes unit with wet coil(s) as selected.
Does not include accessories
Total Full Load Amps : 3.60 Unit pressure drop and air flow based upon dry coil as required by AHRI-
MCA / MSCP : 4.05 / 15.00 440.
Fan Power Input [Watts@CFM] 148.00 Sound data tested in accordance with AHRI-260-2012
Sound Data Calculated at 900 CFM and 1339 RPM
Sound Data Calculated at 900 CFM and 1339 RPM Scheduled motor information is for Fan Input Power at High Speed.
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz For 0' altitude the coil selection has been made at Standard Conditions.
Ducted Discharge 60 60 58 57 52 45 35
Casing Radiated Free Inlet 62 61 60 57 50 45 38

https://webselect.johnsoncontrols.com/submittals/perfreport/PerformanceDataSheet.aspx?chnl=JCI&project=4517957&lineid=4517958,4518014,452… 6/16
6/11/2020 Performance Data Sheet
Project Name: IJLDS - HN - CIRAIRE JCI Contract No: Contract #
Location: Coil Version: 7.05b
Consultant/Engineer: Printed Date: 6/11/2020 5:57:23 PM
Contractor: Selection Date: 6/11/2020 4:37:49 PM
Sold To: Last Revision Date: 6/11/2020 4:38:29 PM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty
FC-L0-14 1 FHP-D03 185 CFM 5,574 Btuh 4,314 Btuh
Unit Data
Model Size : 03 (Fans) Speed : (1) Medium Filter : 1" Throwaway Coil Tube Dia. [in.] 3/8
Type : Horizontal Low Profile - Series D (Motors) HP : (1) 1/4 Filter (Qty) Size : 19x10.5x1 Coil Face Area [ft²] 1.07
Motor FLA : 1.1 Filter Face Area [ft²] 1.39 Weight* [lb] 40
Motor Type : ECM-B
Capacity : Std. Capacity
Output Data Options
Altitude [Ft.] 0 Auxiliary Drip Pan- Galvanized Auxiliary Drip Pan
Air Flow Rate [CFM] 185 BC02 24V, Unit S/S Relay / Fan Op. Relay & Transformer
ESP [in.wg] 0.25 Elastomeric Closed Cell Foam Insulation
Chilled Water Coil Data Enclosure Mount- Unit Mounted
EAT DB/WB [°F] 73.2/ 61.3 Galvanized Drain pan
LAT DB/WB [°F] 51.9/ 50.3 Motor Control- 2-10 VDC (Sync)
Total Capacity [Btuh] 5,574 Return Air Options- Return: Rear No Duct Collar
Sensible Capacity [Btuh] 4,314 Thermostat Location- No Thermostat
EWT/LWT [°F] 42.0/ 53.3 Thermostat- No Thermostat
Fluid Flow [gpm] 1.00 Chilled Water Coil: Field Provided Piping Package Size - 1/2"
Fluid P.D [ft.wg] 11.77 Chilled Water Coil:Galvanized Casing
Fluid Velocity [fps] 3.00 Chilled Water Coil:Left Hand Connection
Rows / FPI / Circuits : 3 Row / 12 FPI / 1 Ckt Chilled Water Coil:Manual Air Vent
Coil Connection Size: [in.] 0.875 Chilled Water Coil:Package Code- Field Provided by Others 1/2" Valve Package
Heating Data
EAT DB [°F] -
LAT DB [°F] -
Sensible Capacity [Btuh] -
Rows / FPI / Circuits : -/-/-
Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data
Motor Voltage [V/P/HZ] 115/1/60 ECM * Unit weight includes unit with wet coil(s) as selected.
Does not include accessories
Total Full Load Amps : 1.10 Unit pressure drop and air flow based upon dry coil as required by AHRI-
MCA / MSCP : 1.38 / 15.00 440.
Fan Power Input [Watts@CFM] 24.00 Sound data tested in accordance with AHRI-260-2012
Sound Data Calculated at 185 CFM and 1113 RPM
Sound Data Calculated at 185 CFM and 1113 RPM Scheduled motor information is for Fan Input Power at High Speed.
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz For 0' altitude the coil selection has been made at Standard Conditions.
Ducted Discharge 52 53 47 47 42 35 27
Casing Radiated Free Inlet 52 53 51 47 40 33 28

https://webselect.johnsoncontrols.com/submittals/perfreport/PerformanceDataSheet.aspx?chnl=JCI&project=4517957&lineid=4517958,4518014,452… 7/16
6/11/2020 Performance Data Sheet
Project Name: IJLDS - HN - CIRAIRE JCI Contract No: Contract #
Location: Coil Version: 7.05b
Consultant/Engineer: Printed Date: 6/11/2020 5:57:23 PM
Contractor: Selection Date: 6/11/2020 4:56:09 PM
Sold To: Last Revision Date: 6/11/2020 4:56:56 PM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty
FC-L0-07 1 FHX-D03 294 CFM 8,034 Btuh 6,654 Btuh
Unit Data
Model Size : 03 (Fans) Speed : (1) High Filter : 1" Throwaway Coil Tube Dia. [in.] 3/8
Type : Horizontal Low Profile - Series D (Motors) HP : (1) 1/4 Filter (Qty) Size : 19 x 9.25 x 1 Coil Face Area [ft²] 1.07
Motor FLA : 1.1 Filter Face Area [ft²] 1.03 Weight* [lb] 82
Motor Type : ECM-B
Capacity : Std. Capacity
Output Data Options
Altitude [Ft.] 0 Access Latches- Standard
Air Flow Rate [CFM] 294 Auxiliary Drip Pan- Galvanized Auxiliary Drip Pan
ESP [in.wg] 0.00 BC02 24V, Unit S/S Relay / Fan Op. Relay & Transformer
Chilled Water Coil Data Elastomeric Closed Cell Foam Insulation
EAT DB/WB [°F] 73.0/ 61.4 Enclosure Mount- Unit Mounted
LAT DB/WB [°F] 52.3/ 51.6 Galvanized Drain pan
Total Capacity [Btuh] 8,034 Motor Control- 2-10 VDC (Sync)
Sensible Capacity [Btuh] 6,654 Paint Options- Pearl White Satin
EWT/LWT [°F] 42.0/ 56.8 Return Air Options- Return: Bottom Stamped Louver Grille
Fluid Flow [gpm] 1.10 Supply Air Options- Supply: Stamped Louver Grille
Fluid P.D [ft.wg] 2.94 Thermostat Location- No Thermostat
Fluid Velocity [fps] 1.60 Thermostat- No Thermostat
Rows / FPI / Circuits : 5 Row / 12 FPI / 2 Ckt Chilled Water Coil: Field Provided Piping Package Size - 1/2"
Coil Connection Size: [in.] 0.875 Chilled Water Coil:Galvanized Casing
Heating Data Chilled Water Coil:Left Hand Connection
EAT DB [°F] - Chilled Water Coil:Manual Air Vent
LAT DB [°F] - Chilled Water Coil:Package Code- Field Provided by Others 1/2" Valve Package
Sensible Capacity [Btuh] -
Rows / FPI / Circuits : -/-/-
Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data
Motor Voltage [V/P/HZ] 115/1/60 ECM * Unit weight includes unit with wet coil(s) as selected.
Does not include accessories
Total Full Load Amps : 1.10 Unit pressure drop and air flow based upon dry coil as required by AHRI-
MCA / MSCP : 1.38 / 15.00 440.
Fan Power Input [Watts@CFM] 42.00 Sound data tested in accordance with AHRI-350-2015
Total sound power level data based on Horizontal Ceiling Exposed Cabinet
Sound at Max, Min Fan Speed **Selected FCU Model with fan air flow at corresponding motor tap with 115/1/60 volt
Speed 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz ECM-B motor, 4 row coil, 1" throwaway filter, unit standard insulation, 0.00
in.wg external static pressure and standard rated internal pressure losses.
High** 55 61 56 54 49 44 37 Scheduled motor information is for Fan Input Power at High Speed.
Total
Medium 52 56 53 50 44 38 30 For 0' altitude the coil selection has been made at Standard Conditions.
Low 47 51 48 45 38 30 25
Max 58 63 59 56 52 47 41
Min 43 47 43 39 30 23 23

https://webselect.johnsoncontrols.com/submittals/perfreport/PerformanceDataSheet.aspx?chnl=JCI&project=4517957&lineid=4517958,4518014,452… 8/16
6/11/2020 Performance Data Sheet
Project Name: IJLDS - HN - CIRAIRE JCI Contract No: Contract #
Location: Coil Version: 7.05b
Consultant/Engineer: Printed Date: 6/11/2020 5:57:23 PM
Contractor: Selection Date: 6/11/2020 5:03:17 PM
Sold To: Last Revision Date: 6/11/2020 5:03:51 PM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty
FC-L0-12, FC-L0-13 2 FHX-D08 600 CFM 10,994 Btuh 10,504 Btuh
Unit Data
Model Size : 08 (Fans) Speed : (2) High Filter : 1" Throwaway Coil Tube Dia. [in.] 3/8
Type : Horizontal Low Profile - Series D (Motors) HP : (1) 1/4 Filter (Qty) Size : (2) 19 x 9.25 x 1 Coil Face Area [ft²] 2.11
Motor FLA : 2 Filter Face Area [ft²] 2.44 Weight* [lb] 134
Motor Type : ECM-B
Capacity : Std. Capacity
Output Data Options
Altitude [Ft.] 0 Access Latches- Standard
Air Flow Rate [CFM] 600 Auxiliary Drip Pan- Galvanized Auxiliary Drip Pan
ESP [in.wg] 0.02 BC02 24V, Unit S/S Relay / Fan Op. Relay & Transformer
Chilled Water Coil Data Elastomeric Closed Cell Foam Insulation
EAT DB/WB [°F] 73.2/ 61.3 Enclosure Mount- Unit Mounted
LAT DB/WB [°F] 57.1/ 54.9 Galvanized Drain pan
Total Capacity [Btuh] 10,994 Motor Control- 2-10 VDC (Sync)
Sensible Capacity [Btuh] 10,504 Paint Options- Pearl White Satin
EWT/LWT [°F] 42.0/ 60.7 Return Air Options- Return: Bottom Stamped Louver Grille
Fluid Flow [gpm] 1.20 Supply Air Options- Supply: Stamped Louver Grille
Fluid P.D [ft.wg] 0.99 Thermostat Location- No Thermostat
Fluid Velocity [fps] 1.20 Thermostat- No Thermostat
Rows / FPI / Circuits : 4 Row / 12 FPI / 3 Ckt Chilled Water Coil: Field Provided Piping Package Size - 1/2"
Coil Connection Size: [in.] 0.875 Chilled Water Coil:Galvanized Casing
Heating Data Chilled Water Coil:Left Hand Connection
EAT DB [°F] - Chilled Water Coil:Manual Air Vent
LAT DB [°F] - Chilled Water Coil:Package Code- Field Provided by Others 1/2" Valve Package
Sensible Capacity [Btuh] -
Rows / FPI / Circuits : -/-/-
Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data
Motor Voltage [V/P/HZ] 115/1/60 ECM * Unit weight includes unit with wet coil(s) as selected.
Does not include accessories
Total Full Load Amps : 2.00 Unit pressure drop and air flow based upon dry coil as required by AHRI-
MCA / MSCP : 2.50 / 15.00 440.
Fan Power Input [Watts@CFM] 80.00 Sound data tested in accordance with AHRI-350-2015
Total sound power level data based on Horizontal Ceiling Exposed Cabinet
Sound at Max, Min Fan Speed **Selected FCU Model with fan air flow at corresponding motor tap with 115/1/60 volt
Speed 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz ECM-B motor, 4 row coil, 1" throwaway filter, unit standard insulation, 0.00
in.wg external static pressure and standard rated internal pressure losses.
High** 60 63 59 58 52 47 39 Scheduled motor information is for Fan Input Power at High Speed.
Medium 56 59 56 53 47 41 32 For 0' altitude the coil selection has been made at Standard Conditions.
Low 51 54 51 46 40 33 26
Max 62 66 62 61 56 51 44
Min 47 48 45 40 32 26 24

https://webselect.johnsoncontrols.com/submittals/perfreport/PerformanceDataSheet.aspx?chnl=JCI&project=4517957&lineid=4517958,4518014,452… 9/16
6/11/2020 Performance Data Sheet
Project Name: IJLDS - HN - CIRAIRE JCI Contract No: Contract #
Location: Coil Version: 7.05b
Consultant/Engineer: Printed Date: 6/11/2020 5:57:23 PM
Contractor: Selection Date: 6/11/2020 5:10:53 PM
Sold To: Last Revision Date: 6/11/2020 5:11:29 PM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty
FC-L1-1 1 FNP12 1020 CFM 27,315 Btuh 22,705 Btuh
Unit Data
Model Size : 12 (Fans) Speed : (2) Medium Filter : 1" Throwaway Coil Tube Dia. [in.] 3/8
Type : Horizontal High Performance (Motors) HP : (1) 1/2 Filter (Qty) Size : (2) 16x16 Coil Face Area [ft²] 2.82
Motor FLA : 7.7 Filter Face Area [ft²] 3.23 Weight* [lb] 178
Motor Type : ECM Inlet Direction : Rear
Capacity : Std. Capacity
Output Data Options
Altitude [Ft.] 0 Auxiliary Drip Pan- Galvanized Auxiliary Drip Pan
Air Flow Rate [CFM] 1020 BC02 24V, Unit S/S Relay / Fan Op. Relay & Transformer
ESP [in.wg] 0.35 Coil Casing- Galvanized Casing
Chilled Water Coil Data Control Enclosure Handing- Opposite of Coil 1
EAT DB/WB [°F] 73.2/ 61.2 Enclosure Mount- Unit Mounted
LAT DB/WB [°F] 52.8/ 51.4 Filter Bottom Access
Total Capacity [Btuh] 27,315 Galvanized Drain pan
Sensible Capacity [Btuh] 22,705 Motor Control- 2-10 VDC (Sync)
EWT/LWT [°F] 42.0/ 52.9 Standard Fiberglass
Fluid Flow [gpm] 5.40 Thermostat Location- No Thermostat
Fluid P.D [ft.wg] 8.16 Thermostat- No Thermostat
Fluid Velocity [fps] 3.20 Chilled Water Coil: Field Provided Piping Package Size - 1/2"
Rows / FPI / Circuits : 4 Row / 10 FPI / 5 Ckt Chilled Water Coil:Manual Air Vent
Coil Connection Size: [in.] 0.875 Chilled Water Coil:Package Code- Field Provided by Others 1/2" Valve Package
Heating Data Chilled Water Coil:Right Hand
EAT DB [°F] -
LAT DB [°F] -
Sensible Capacity [Btuh] -
Rows / FPI / Circuits : -/-/-
Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data
Motor Voltage [V/P/HZ] 115/1/60 ECM * Unit weight includes unit with wet coil(s) as selected.
Does not include accessories
Total Full Load Amps : 7.70 Unit pressure drop and air flow based upon dry coil as required by AHRI-
MCA / MSCP : 9.63 / 15.00 440.
Fan Power Input [Watts@CFM] 258.00 Sound data tested in accordance with AHRI-260-2012
3-Phase Neutral Amps [Amps] 13.30 Sound Data Calculated at 1020 CFM and 1036 RPM
Scheduled motor information is for Fan Input Power at High Speed.
Sound Data Calculated at 1020 CFM and 1036 RPM For 0' altitude the coil selection has been made at Standard Conditions.
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Ducted Discharge 68 65 64 63 60 57 46
Casing Radiated Free Inlet 69 66 65 65 60 56 49

https://webselect.johnsoncontrols.com/submittals/perfreport/PerformanceDataSheet.aspx?chnl=JCI&project=4517957&lineid=4517958,4518014,45… 10/16
6/11/2020 Performance Data Sheet
Project Name: IJLDS - HN - CIRAIRE JCI Contract No: Contract #
Location: Coil Version: 7.05b
Consultant/Engineer: Printed Date: 6/11/2020 5:57:23 PM
Contractor: Selection Date: 6/11/2020 5:22:50 PM
Sold To: Last Revision Date: 6/11/2020 5:23:22 PM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty
FC-L1-2,FC-L1-3 2 FNP10 800 CFM 21,928 Btuh 18,078 Btuh
Unit Data
Model Size : 10 (Fans) Speed : (1) High Filter : 1" Throwaway Coil Tube Dia. [in.] 3/8
Type : Horizontal High Performance (Motors) HP : (1) 1/3 Filter (Qty) Size : (1) 16x25 Coil Face Area [ft²] 2.33
Motor FLA : 5 Filter Face Area [ft²] 2.57 Weight* [lb] 134
Motor Type : ECM Inlet Direction : Rear
Capacity : Std. Capacity
Output Data Options
Altitude [Ft.] 0 Auxiliary Drip Pan- Galvanized Auxiliary Drip Pan
Air Flow Rate [CFM] 800 BC02 24V, Unit S/S Relay / Fan Op. Relay & Transformer
ESP [in.wg] 0.35 Coil Casing- Galvanized Casing
Chilled Water Coil Data Control Enclosure Handing- Opposite of Coil 1
EAT DB/WB [°F] 73.2/ 61.2 Enclosure Mount- Unit Mounted
LAT DB/WB [°F] 52.5/ 51.3 Filter Bottom Access
Total Capacity [Btuh] 21,928 Galvanized Drain pan
Sensible Capacity [Btuh] 18,078 Motor Control- 2-10 VDC (Sync)
EWT/LWT [°F] 42.0/ 53.3 Standard Fiberglass
Fluid Flow [gpm] 4.00 Thermostat Location- No Thermostat
Fluid P.D [ft.wg] 7.93 Thermostat- No Thermostat
Fluid Velocity [fps] 3.00 Chilled Water Coil: Field Provided Piping Package Size - 1/2"
Rows / FPI / Circuits : 4 Row / 10 FPI / 4 Ckt Chilled Water Coil:Manual Air Vent
Coil Connection Size: [in.] 0.875 Chilled Water Coil:Package Code- Field Provided by Others 1/2" Valve Package
Heating Data Chilled Water Coil:Right Hand
EAT DB [°F] -
LAT DB [°F] -
Sensible Capacity [Btuh] -
Rows / FPI / Circuits : -/-/-
Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data
Motor Voltage [V/P/HZ] 115/1/60 ECM * Unit weight includes unit with wet coil(s) as selected.
Does not include accessories
Total Full Load Amps : 5.00 Unit pressure drop and air flow based upon dry coil as required by AHRI-
MCA / MSCP : 6.25 / 15.00 440.
Fan Power Input [Watts@CFM] 322.00 Sound data tested in accordance with AHRI-260-2012
3-Phase Neutral Amps [Amps] 8.70 Sound Data Calculated at 800 CFM and 1190 RPM
Scheduled motor information is for Fan Input Power at High Speed.
Sound Data Calculated at 800 CFM and 1190 RPM For 0' altitude the coil selection has been made at Standard Conditions.
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Ducted Discharge 68 67 66 66 63 61 53
Casing Radiated Free Inlet 70 66 65 67 62 59 55

https://webselect.johnsoncontrols.com/submittals/perfreport/PerformanceDataSheet.aspx?chnl=JCI&project=4517957&lineid=4517958,4518014,45… 11/16
6/11/2020 Performance Data Sheet
Project Name: IJLDS - HN - CIRAIRE JCI Contract No: Contract #
Location: Coil Version: 7.05b
Consultant/Engineer: Printed Date: 6/11/2020 5:57:23 PM
Contractor: Selection Date: 6/11/2020 5:31:26 PM
Sold To: Last Revision Date: 6/11/2020 5:31:55 PM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty
FC-F1-4, FC-F1-5, FC-F1-6 3 FHP-D03 200 CFM 6,044 Btuh 4,684 Btuh
Unit Data
Model Size : 03 (Fans) Speed : (1) High Filter : 1" Throwaway Coil Tube Dia. [in.] 3/8
Type : Horizontal Low Profile - Series D (Motors) HP : (1) 1/4 Filter (Qty) Size : 19x10.5x1 Coil Face Area [ft²] 1.07
Motor FLA : 1.1 Filter Face Area [ft²] 1.39 Weight* [lb] 43
Motor Type : ECM-B
Capacity : Std. Capacity
Output Data Options
Altitude [Ft.] 0 Auxiliary Drip Pan- Galvanized Auxiliary Drip Pan
Air Flow Rate [CFM] 200 BC02 24V, Unit S/S Relay / Fan Op. Relay & Transformer
ESP [in.wg] 0.35 Elastomeric Closed Cell Foam Insulation
Chilled Water Coil Data Enclosure Mount- Unit Mounted
EAT DB/WB [°F] 73.3/ 62.2 Galvanized Drain pan
LAT DB/WB [°F] 51.9/ 51.4 Motor Control- 2-10 VDC (Sync)
Total Capacity [Btuh] 6,044 Return Air Options- Return: Rear No Duct Collar
Sensible Capacity [Btuh] 4,684 Thermostat Location- No Thermostat
EWT/LWT [°F] 42.0/ 54.3 Thermostat- No Thermostat
Fluid Flow [gpm] 1.00 Chilled Water Coil: Field Provided Piping Package Size - 1/2"
Fluid P.D [ft.wg] 1.92 Chilled Water Coil:Galvanized Casing
Fluid Velocity [fps] 1.50 Chilled Water Coil:Left Hand Connection
Rows / FPI / Circuits : 4 Row / 12 FPI / 2 Ckt Chilled Water Coil:Manual Air Vent
Coil Connection Size: [in.] 0.875 Chilled Water Coil:Package Code- Field Provided by Others 1/2" Valve Package
Heating Data
EAT DB [°F] -
LAT DB [°F] -
Sensible Capacity [Btuh] -
Rows / FPI / Circuits : -/-/-
Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data
Motor Voltage [V/P/HZ] 115/1/60 ECM * Unit weight includes unit with wet coil(s) as selected.
Does not include accessories
Total Full Load Amps : 1.10 Unit pressure drop and air flow based upon dry coil as required by AHRI-
MCA / MSCP : 1.38 / 15.00 440.
Fan Power Input [Watts@CFM] 35.00 Sound data tested in accordance with AHRI-260-2012
Sound Data Calculated at 200 CFM and 1309 RPM
Sound Data Calculated at 200 CFM and 1309 RPM Scheduled motor information is for Fan Input Power at High Speed.
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz For 0' altitude the coil selection has been made at Standard Conditions.
Ducted Discharge 55 56 51 50 45 40 31
Casing Radiated Free Inlet 55 57 54 51 45 38 32

https://webselect.johnsoncontrols.com/submittals/perfreport/PerformanceDataSheet.aspx?chnl=JCI&project=4517957&lineid=4517958,4518014,45… 12/16
6/11/2020 Performance Data Sheet
Project Name: IJLDS - HN - CIRAIRE JCI Contract No: Contract #
Location: Coil Version: 7.05b
Consultant/Engineer: Printed Date: 6/11/2020 5:57:23 PM
Contractor: Selection Date: 6/11/2020 5:43:56 PM
Sold To: Last Revision Date: 6/11/2020 5:44:23 PM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty
FC-L1-7 1 FHP-D06 450 CFM 10,504 Btuh 8,794 Btuh
Unit Data
Model Size : 06 (Fans) Speed : (2) High Filter : 1" Throwaway Coil Tube Dia. [in.] 3/8
Type : Horizontal Low Profile - Series D (Motors) HP : (1) 1/4 Filter (Qty) Size : 31x10.5x1 Coil Face Area [ft²] 1.72
Motor FLA : 2 Filter Face Area [ft²] 2.26 Weight* [lb] 64
Motor Type : ECM-B
Capacity : Std. Capacity
Output Data Options
Altitude [Ft.] 0 Auxiliary Drip Pan- Galvanized Auxiliary Drip Pan
Air Flow Rate [CFM] 450 BC02 24V, Unit S/S Relay / Fan Op. Relay & Transformer
ESP [in.wg] 0.35 Elastomeric Closed Cell Foam Insulation
Chilled Water Coil Data Enclosure Mount- Unit Mounted
EAT DB/WB [°F] 73.3/ 61.7 Galvanized Drain pan
LAT DB/WB [°F] 55.4/ 53.5 Motor Control- 2-10 VDC (Sync)
Total Capacity [Btuh] 10,504 Return Air Options- Return: Rear No Duct Collar
Sensible Capacity [Btuh] 8,794 Thermostat Location- No Thermostat
EWT/LWT [°F] 42.0/ 53.3 Thermostat- No Thermostat
Fluid Flow [gpm] 1.90 Chilled Water Coil: Field Provided Piping Package Size - 1/2"
Fluid P.D [ft.wg] 2.00 Chilled Water Coil:Galvanized Casing
Fluid Velocity [fps] 1.90 Chilled Water Coil:Left Hand Connection
Rows / FPI / Circuits : 3 Row / 12 FPI / 3 Ckt Chilled Water Coil:Manual Air Vent
Coil Connection Size: [in.] 0.875 Chilled Water Coil:Package Code- Field Provided by Others 1/2" Valve Package
Heating Data
EAT DB [°F] -
LAT DB [°F] -
Sensible Capacity [Btuh] -
Rows / FPI / Circuits : -/-/-
Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data
Motor Voltage [V/P/HZ] 115/1/60 ECM * Unit weight includes unit with wet coil(s) as selected.
Does not include accessories
Total Full Load Amps : 2.00 Unit pressure drop and air flow based upon dry coil as required by AHRI-
MCA / MSCP : 2.50 / 15.00 440.
Fan Power Input [Watts@CFM] 83.00 Sound data tested in accordance with AHRI-260-2012
Sound Data Calculated at 450 CFM and 1422 RPM
Sound Data Calculated at 450 CFM and 1422 RPM Scheduled motor information is for Fan Input Power at High Speed.
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz For 0' altitude the coil selection has been made at Standard Conditions.
Ducted Discharge 60 57 55 55 51 45 36
Casing Radiated Free Inlet 61 63 59 57 51 46 40

https://webselect.johnsoncontrols.com/submittals/perfreport/PerformanceDataSheet.aspx?chnl=JCI&project=4517957&lineid=4517958,4518014,45… 13/16
6/11/2020 Performance Data Sheet
Project Name: IJLDS - HN - CIRAIRE JCI Contract No: Contract #
Location: Coil Version: 7.05b
Consultant/Engineer: Printed Date: 6/11/2020 5:57:23 PM
Contractor: Selection Date: 6/11/2020 5:47:40 PM
Sold To: Last Revision Date: 6/11/2020 5:48:11 PM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty
FC-L1-8, FC-L1-9 2 FHP-D03 250 CFM 6,864 Btuh 5,594 Btuh
Unit Data
Model Size : 03 (Fans) Speed : (1) High Filter : 1" Throwaway Coil Tube Dia. [in.] 3/8
Type : Horizontal Low Profile - Series D (Motors) HP : (1) 1/4 Filter (Qty) Size : 19x10.5x1 Coil Face Area [ft²] 1.07
Motor FLA : 1.1 Filter Face Area [ft²] 1.39 Weight* [lb] 43
Motor Type : ECM-B
Capacity : Std. Capacity
Output Data Options
Altitude [Ft.] 0 Auxiliary Drip Pan- Galvanized Auxiliary Drip Pan
Air Flow Rate [CFM] 250 BC02 24V, Unit S/S Relay / Fan Op. Relay & Transformer
ESP [in.wg] 0.35 Elastomeric Closed Cell Foam Insulation
Chilled Water Coil Data Enclosure Mount- Unit Mounted
EAT DB/WB [°F] 73.0/ 61.6 Galvanized Drain pan
LAT DB/WB [°F] 52.5/ 51.8 Motor Control- 2-10 VDC (Sync)
Total Capacity [Btuh] 6,864 Return Air Options- Return: Rear No Duct Collar
Sensible Capacity [Btuh] 5,594 Thermostat Location- No Thermostat
EWT/LWT [°F] 42.0/ 54.7 Thermostat- No Thermostat
Fluid Flow [gpm] 1.10 Chilled Water Coil: Field Provided Piping Package Size - 1/2"
Fluid P.D [ft.wg] 2.35 Chilled Water Coil:Galvanized Casing
Fluid Velocity [fps] 1.60 Chilled Water Coil:Left Hand Connection
Rows / FPI / Circuits : 4 Row / 12 FPI / 2 Ckt Chilled Water Coil:Manual Air Vent
Coil Connection Size: [in.] 0.875 Chilled Water Coil:Package Code- Field Provided by Others 1/2" Valve Package
Heating Data
EAT DB [°F] -
LAT DB [°F] -
Sensible Capacity [Btuh] -
Rows / FPI / Circuits : -/-/-
Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data
Motor Voltage [V/P/HZ] 115/1/60 ECM * Unit weight includes unit with wet coil(s) as selected.
Does not include accessories
Total Full Load Amps : 1.10 Unit pressure drop and air flow based upon dry coil as required by AHRI-
MCA / MSCP : 1.38 / 15.00 440.
Fan Power Input [Watts@CFM] 43.00 Sound data tested in accordance with AHRI-260-2012
Sound Data Calculated at 250 CFM and 1387 RPM
Sound Data Calculated at 250 CFM and 1387 RPM Scheduled motor information is for Fan Input Power at High Speed.
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz For 0' altitude the coil selection has been made at Standard Conditions.
Ducted Discharge 57 57 52 52 47 43 34
Casing Radiated Free Inlet 57 59 55 53 47 42 36

https://webselect.johnsoncontrols.com/submittals/perfreport/PerformanceDataSheet.aspx?chnl=JCI&project=4517957&lineid=4517958,4518014,45… 14/16
6/11/2020 Performance Data Sheet
Project Name: IJLDS - HN - CIRAIRE JCI Contract No: Contract #
Location: Coil Version: 7.05b
Consultant/Engineer: Printed Date: 6/11/2020 5:57:23 PM
Contractor: Selection Date: 6/11/2020 5:51:45 PM
Sold To: Last Revision Date: 6/11/2020 5:52:13 PM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty
FC-L1-10, FC-L1-11 2 FHP-D09 550 CFM 10,604 Btuh 9,814 Btuh
Unit Data
Model Size : 09 (Fans) Speed : (2) High Filter : 1" Throwaway Coil Tube Dia. [in.] 3/8
Type : Horizontal Low Profile - Series D (Motors) HP : (1) 1/4 Filter (Qty) Size : (1)20x10.5x1 Coil Face Area [ft²] 2.35
Motor FLA : 2.7 (1)22.25x10.5x1 Weight* [lb] 93
Motor Type : ECM-B Filter Face Area [ft²] 3.08
Capacity : Std. Capacity
Output Data Options
Altitude [Ft.] 0 Auxiliary Drip Pan- Galvanized Auxiliary Drip Pan
Air Flow Rate [CFM] 550 BC02 24V, Unit S/S Relay / Fan Op. Relay & Transformer
ESP [in.wg] 0.35 Elastomeric Closed Cell Foam Insulation
Chilled Water Coil Data Enclosure Mount- Unit Mounted
EAT DB/WB [°F] 73.0/ 61.6 Galvanized Drain pan
LAT DB/WB [°F] 56.6/ 54.9 Motor Control- 2-10 VDC (Sync)
Total Capacity [Btuh] 10,604 Return Air Options- Return: Rear No Duct Collar
Sensible Capacity [Btuh] 9,814 Thermostat Location- No Thermostat
EWT/LWT [°F] 42.0/ 60.3 Thermostat- No Thermostat
Fluid Flow [gpm] 1.20 Chilled Water Coil: Field Provided Piping Package Size - 1/2"
Fluid P.D [ft.wg] 0.99 Chilled Water Coil:Galvanized Casing
Fluid Velocity [fps] 1.20 Chilled Water Coil:Left Hand Connection
Rows / FPI / Circuits : 4 Row / 12 FPI / 3 Ckt Chilled Water Coil:Manual Air Vent
Coil Connection Size: [in.] 0.875 Chilled Water Coil:Package Code- Field Provided by Others 1/2" Valve Package
Heating Data
EAT DB [°F] -
LAT DB [°F] -
Sensible Capacity [Btuh] -
Rows / FPI / Circuits : -/-/-
Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data
Motor Voltage [V/P/HZ] 115/1/60 ECM * Unit weight includes unit with wet coil(s) as selected.
Does not include accessories
Total Full Load Amps : 2.70 Unit pressure drop and air flow based upon dry coil as required by AHRI-
MCA / MSCP : 3.38 / 15.00 440.
Fan Power Input [Watts@CFM] 103.00 Sound data tested in accordance with AHRI-260-2012
Sound Data Calculated at 550 CFM and 1378 RPM
Sound Data Calculated at 550 CFM and 1378 RPM Scheduled motor information is for Fan Input Power at High Speed.
125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz For 0' altitude the coil selection has been made at Standard Conditions.
Ducted Discharge 59 59 56 58 53 47 39
Casing Radiated Free Inlet 62 63 58 54 49 44 38

https://webselect.johnsoncontrols.com/submittals/perfreport/PerformanceDataSheet.aspx?chnl=JCI&project=4517957&lineid=4517958,4518014,45… 15/16
6/11/2020 Performance Data Sheet
Project Name: IJLDS - HN - CIRAIRE JCI Contract No: Contract #
Location: Coil Version: 7.05b
Consultant/Engineer: Printed Date: 6/11/2020 5:57:23 PM
Contractor: Selection Date: 6/11/2020 5:56:15 PM
Sold To: Last Revision Date: 6/11/2020 5:56:44 PM
Performance Data Sheet P.O. No: PO
Unit Tag Qty Model Air Flow Total Duty Sensible Duty
FC-L1-12 1 FHX-D08 608 CFM 11,014 Btuh 10,364 Btuh
Unit Data
Model Size : 08 (Fans) Speed : (2) High Filter : 1" Throwaway Coil Tube Dia. [in.] 3/8
Type : Horizontal Low Profile - Series D (Motors) HP : (1) 1/4 Filter (Qty) Size : (2) 19 x 9.25 x 1 Coil Face Area [ft²] 2.11
Motor FLA : 2 Filter Face Area [ft²] 2.44 Weight* [lb] 134
Motor Type : ECM-B
Capacity : Std. Capacity
Output Data Options
Altitude [Ft.] 0 Access Latches- Standard
Air Flow Rate [CFM] 608 Auxiliary Drip Pan- Galvanized Auxiliary Drip Pan
ESP [in.wg] 0.00 BC02 24V, Unit S/S Relay / Fan Op. Relay & Transformer
Chilled Water Coil Data Elastomeric Closed Cell Foam Insulation
EAT DB/WB [°F] 73.0/ 61.6 Enclosure Mount- Unit Mounted
LAT DB/WB [°F] 57.4/ 55.3 Galvanized Drain pan
Total Capacity [Btuh] 11,014 Motor Control- 2-10 VDC (Sync)
Sensible Capacity [Btuh] 10,364 Paint Options- Pearl White Satin
EWT/LWT [°F] 42.0/ 60.7 Return Air Options- Return: Bottom Stamped Louver Grille
Fluid Flow [gpm] 1.20 Supply Air Options- Supply: Stamped Louver Grille
Fluid P.D [ft.wg] 0.99 Thermostat Location- No Thermostat
Fluid Velocity [fps] 1.20 Thermostat- No Thermostat
Rows / FPI / Circuits : 4 Row / 12 FPI / 3 Ckt Chilled Water Coil: Field Provided Piping Package Size - 1/2"
Coil Connection Size: [in.] 0.875 Chilled Water Coil:Galvanized Casing
Heating Data Chilled Water Coil:Left Hand Connection
EAT DB [°F] - Chilled Water Coil:Manual Air Vent
LAT DB [°F] - Chilled Water Coil:Package Code- Field Provided by Others 1/2" Valve Package
Sensible Capacity [Btuh] -
Rows / FPI / Circuits : -/-/-
Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)# Special Quote (SQ)#
Electrical Data
Motor Voltage [V/P/HZ] 115/1/60 ECM * Unit weight includes unit with wet coil(s) as selected.
Does not include accessories
Total Full Load Amps : 2.00 Unit pressure drop and air flow based upon dry coil as required by AHRI-
MCA / MSCP : 2.50 / 15.00 440.
Fan Power Input [Watts@CFM] 80.00 Sound data tested in accordance with AHRI-350-2015
Total sound power level data based on Horizontal Ceiling Exposed Cabinet
Sound at Max, Min Fan Speed **Selected FCU Model with fan air flow at corresponding motor tap with 115/1/60 volt
Speed 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz ECM-B motor, 4 row coil, 1" throwaway filter, unit standard insulation, 0.00
in.wg external static pressure and standard rated internal pressure losses.
High** 60 63 59 58 52 47 39 Scheduled motor information is for Fan Input Power at High Speed.
Total
Medium 56 59 56 53 47 41 32 For 0' altitude the coil selection has been made at Standard Conditions.
Low 51 54 51 46 40 33 26
Max 62 66 62 61 56 51 44
Min 47 48 45 40 32 26 24

https://webselect.johnsoncontrols.com/submittals/perfreport/PerformanceDataSheet.aspx?chnl=JCI&project=4517957&lineid=4517958,4518014,45… 16/16