The structural performance of the Handrail for the above mentioned project shall be checked using the
following design codes and standards:
The following are the properties of materials, structural performance and serviceability
requirements of the Stainless Steel Handrail
2
LOADINGS
Dead Load
Live Load
kN
Uniform Load LL1 0.75
m
Deflection Limits
Load Combinations
1.0 x Dead Load + 1.0 x Live Load
1.35 x Dead Load + 1.5 x L:ive Load
Anchor Bolts
Hilti anchor system for post fixing anchor.
3
STAAD REPORT
FOR HANDRAIL
4
Job Information
Engineer Checked Approved
Name:
Date: 08-Jul-20
Primary 1 DL
Primary 2 LL1
Primary 3 LL2
Primary 4 LL3
Primary 5 LL4
Primary 6 LL5
Primary 7 LL6
Combination 8 DL + LL1
Combination 9 DL+LL2
Combination 10 DL + LL3
Combination 11 DL + LL4
Combination 12 DL + LL5
Combination 13 DL + LL6
Combination 14 1.35DL + 1.5LL1
Combination 15 1.35DL + 1.5LL2
Combination 16 1.35DL + 1.5LL3
Combination 17 1.35DL + 1.5LL4
Combination 18 1.35DL + 1.5LL5
Combination 19 1.35DL + 1.5LL6
Section Properties
Prop Section Area Iyy Izz J Material
(mm2) (mm4) (mm4) (mm4)
1 Cir 0.79 314.158 7.85E+3 7.85E+3 15.7E+3 STAINLESSST
2 PIPE50.8X2 306.618 91.4E+3 91.4E+3 183E+3 STAINLESSST
Releases
Beam ends not shown in this table are fixed in all directions.
Beam Node x y z rx ry rz
5
Primary Load Cases
Number Name Type
1 DL Dead
2 LL1 Live
3 LL2 Live
4 LL3 Live
5 LL4 Live
6 LL5 Live
7 LL6 Live
8 DL + LL1 1 DL 1.00
2 LL1 1.00
9 DL+LL2 1 DL 1.00
3 LL2 1.00
10 DL + LL3 1 DL 1.00
4 LL3 1.00
11 DL + LL4 1 DL 1.00
5 LL4 1.00
12 DL + LL5 1 DL 1.00
6 LL5 1.00
13 DL + LL6 1 DL 1.00
7 LL6 1.00
14 1.35DL + 1.5LL1 1 DL 1.35
2 LL1 1.50
15 1.35DL + 1.5LL2 1 DL 1.35
3 LL2 1.50
16 1.35DL + 1.5LL3 1 DL 1.35
4 LL3 1.50
17 1.35DL + 1.5LL4 1 DL 1.35
5 LL4 1.50
18 1.35DL + 1.5LL5 1 DL 1.35
6 LL5 1.50
19 1.35DL + 1.5LL6 1 DL 1.35
7 LL6 1.50
6
60.000mm
999.998mm
100.000mm
Y
X
Z Load 19
Structural Model
Y
X
Z Load 1
7
-0.750 kN/m
-0.750 kN/m
Y
X
Z Load 2
0.750 kN/m
0.750 kN/m
Y
X
Z Load 3
8
-0.890 kN
-0.890 kN
-0.890 kN
Y
X
Z Load 4
0.890 kN
0.890 kN
0.890 kN
Y
X
Z Load 5
9
-0.890 kN
-0.890 kN
Y
X
Z Load 6
0.890 kN
0.890 kN
Y
X
Z Load 7
10
Max: 0.268 mm
Max: 0.153 mm
Max: 0.877 mm
Max: 0.385 mm
Max: 0.220 mm
Max: 0.877 mm
Max: 0.268 mm
Max: 0.153 mm
Y
X Load 13 : Displacement
Z Displacement - mm
Y
X Load 18 : Beam Stress
Z Stress - MPa
11
Y = 0.473 kN
Z = -0.008 kN
MX = -0.059 kN-m
Y = 1.803 kN
Z = 0.015 kN
MX = -0.157 kN-m
Y = 0.473 kN
Z = -0.008 kN
MX = -0.059 kN-m
Y
X
Z Load 18
Y = 0.025 kN
Z = -0.458 kN
MX = -0.067 kN-m
Y = 0.029 kN
Z = -1.755 kN
MX = -0.101 kN-m
Y = 0.025 kN
Z = -0.458 kN
MX = -0.067 kN-m
Y
X
Z Load 19
12
STRUCTURAL VERIFICATION
Deflection Check
Maximum deflection of vertical member δmax 0.385mm STAAD Report
Page 7/8
Unsupported length of vertical member Lu 60mm
Lu
Limiting deflection of vertical member δlim 2 mm
30
STAAD Report
Maximum deflection of horizontal member δmax 0.877mm Page 7/8
Unsupported length of horizontal member Lu 1000mm
Lu
Limiting deflection of horizontal member δlim 5 mm
200
Stress Check
STAAD Report
Maximum Stress σmax 200.314MPa Page 7/8
Limiting Stress σlim 205MPa
(Based on EN 10088-3: 2005)
σmax σlim "Therefore OK!"
13
DESIGN OF
CONNECTION
COMPONENTS
Connection 1
Connection 2
14
A. CONNECTION 1
This connection refers to the connection between the Horizontal and Vertiacal members as marked in the sketch above.
15
Maximum Support reactions are extracted from beam end forces table shown above (Extracted from Staad)
Screw Properties
As per AAmA TIR A9-1991
Type of screw to be utilized #10 - 4.8 Diameter Screw
Nominal Thread Diameter d sc 0.19in 4.826 mm
2 2
Tensile stress area AS 0.0175in 11.29 mm
Thread root area 2 2
AR 0.0152in 9.806 mm
Number of Screws n sc 2
2 2
Fx1 Fz1 M y1
Design shear Load per Screw fvmax 1.128 kN
n sc d sc
0.4 Fu AR
Allowable shear load per screw Fvall 1.585 kN
3
16
Bearing Load Check
Thickness of connected stainlesssteel pipe tp 2mm
Constant c 0.80
Limiting stress for bending and overall yielding Py 205MPa
c d sc t p Py
Bending load capacity of connected plate fbsd 9.542 kN
γM
17
B. CONNECTION 2
This connection refers to the connection of the member to the concrete lintel.
Maximum Support reactions are extracted from Staad Report, and the Anchorage is checked using HILTI.
NOTE: a 150mm Concrete Lintel to be added in order for the handrail to be anchored to it
Case 1
Note that these forces are the same as the HILTI Input)
Case 2
Note that these forces are the same as the HILTI Input)
Force along y-axis Fy2 0.029kN
18
Hilti PROFIS Engineering 3.0.62
www.hilti.co.uk
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Handrail Date: 11/07/2020
Fastening Point:
Specifier's comments:
1 Input data
Anchor type and size: HUS-CR 6
Return period (service life in years): 50
Item number: not available
Effective embedment depth: hef = 45.0 mm, hnom = 55.0 mm
Material: A4
Approval No.: ETA 08/0307
Issued I Valid: 23/08/2018 | -
Proof: Engineering judgement SOFA - based on ETAG testing
Stand-off installation: eb = 0.0 mm (no stand-off); t = 8.0 mm
Baseplate :
R lx x ly x t = 80.0 mm x 80.0 mm x 8.0 mm; (Recommended plate thickness: 7.0 mm)
R
- The anchor calculation is based on a rigid baseplate assumption.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
1
19
Hilti PROFIS Engineering 3.0.62
www.hilti.co.uk
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Handrail Date: 11/07/2020
Fastening Point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
2
20
Hilti PROFIS Engineering 3.0.62
www.hilti.co.uk
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Handrail Date: 11/07/2020
Fastening Point:
Group anchor ID
1, 2
Group anchor ID
1, 2
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
21
Hilti PROFIS Engineering 3.0.62
www.hilti.co.uk
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Handrail Date: 11/07/2020
Fastening Point:
Group anchor ID
1-3
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
4
22
Hilti PROFIS Engineering 3.0.62
www.hilti.co.uk
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Handrail Date: 11/07/2020
Fastening Point:
a a
bN + bV ≤ 1.0
Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the baseplate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!
The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
5
23
Hilti PROFIS Engineering 3.0.62
www.hilti.co.uk
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Handrail Date: 11/07/2020
Fastening Point:
7 Warnings
• The anchor design methods in PROFIS Engineering require rigid baseplates per current regulations (AS 5216:2018, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the baseplate are not considered - the
baseplate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering
calculates the minimum required baseplate thickness with CBFEM to limit the stress of the baseplate based on the assumptions explained
above. The proof if the rigid baseplate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be
checked for agreement with the existing conditions and for plausibility!
• In general, the conditions given in ETAG 001, Annex C, section 4.2.2.1 and 4.2.2.3 b) are not fulfilled because the diameter of the clearance
hole in the fixture acc. to Annex 3, Table 3 is greater than the values given in Annex C, Table 4.1 and AS5126 for the corresponding
diameter of the anchor. Therefore the design resistance for anchor groups is limited to twice the steel resistance (of a single anchor) in
accordance with the approval.
• Checking the transfer of loads into the base material is required in accordance with ETAG 001, Annex C(2010)Section 7! The software
considers that the grout is installed under the baseplate without creating air voids and before application of the loads.
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of ETAG 001, Annex C! For larger
diameters of the clearance hole see Chapter 1.1. of ETAG 001, Annex C!
• Your design has selected filled holes. Please ensure that there is a proper method to fill the annular gap between the fixture and HUS-CR
6and contact Hilti in case of any questions.
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• The design method SOFA assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by filling
the gap with mortar of sufficient compressive strength (e.g. by using the HILTI Filling set) or by other suitable means
• The compliance with current standards (e.g. EN 1993, AS 4100:1998, etc.) is the responsibility of the user
• An SLS-check is not performed for SOFA and has to be provided by the user!
• The characteristic bond resistances depend on the return period (service life in years): 50
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
6
24
Hilti PROFIS Engineering 3.0.62
www.hilti.co.uk
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Handrail Date: 11/07/2020
Fastening Point:
(1)
Mallée, R.; Riemann, H. (1990): Ankerplattenbefestigungen mit Hinterschnittdübeln,
Bauingenieur 65 (1990), S. 49 - 57, Springer VDI-Verlag, 1990
Mallée, R.; Burkhardt, F. (1999): Befestigungen von Ankerplatten mit Dübeln, Beton und
Stahlbetonbau 94, Heft 12, S. 502 - 511, Ernst & Sohn Verlag, 1999
8.2 Results
Stress distribution s 11
2
116.32 [N/mm ]
2
-49.34 [N/mm ]
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
7
25
Hilti PROFIS Engineering 3.0.62
www.hilti.co.uk
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Handrail Date: 11/07/2020
Fastening Point:
Stress distribution s 22
2
60.12 [N/mm ]
2
-78.19 [N/mm ]
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
8
26
Hilti PROFIS Engineering 3.0.62
www.hilti.co.uk
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Handrail Date: 11/07/2020
Fastening Point:
Deformations (z-direction)
0.0 [mm]
0.0 [mm]
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
9
27
Hilti PROFIS Engineering 3.0.62
www.hilti.co.uk
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Handrail Date: 11/07/2020
Fastening Point:
9 Installation data
2 2
Baseplate, steel: 1.4401; E = 200,000.00 N/mm ; fyk = 200.00 N/mm Anchor type and size: HUS-CR 6
Profile: Cylinder, ; (L x W x T) = 20.0 mm x 20.0 mm Item number: not available
Hole diameter in the fixture: df = 9.0 mm Installation torque: Hilti SIW 22T-A
Plate thickness (input): 8.0 mm Hole diameter in the base material: 6.0 mm
Recommended plate thickness: 7.0 mm Hole depth in the base material: 65.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 100.0 mm
Cleaning: Manual cleaning of the drilled hole according to instructions for use is
required.
Hilti HUS screw anchor with 55 mm embedment, 6, Stainless steel, installation per ETA 08/0307
y
40.0 40.0
18.0
3
40.0
44.0
x
40.0
1 2
18.0
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
10
28
Hilti PROFIS Engineering 3.0.62
www.hilti.co.uk
Company: Page: 11
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Handrail Date: 11/07/2020
Fastening Point:
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2020 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
11
29
REFERENCES