The external SPD is designed to provide surge protection to hybrid DC and fibre cabling close to the point
where DC cable exits the shelter. It also provides a suitable junction point at the shelter or cabinet for
separation of the DC and fibre and connection of DC power.
VERSION 1.1
ISSUE DATE: 3 APRIL 2018
Incorporating Erico DSD140-3BR-24/48V 3 mode MOV modules, 48V-DC rated circuit breakers and Eriflex
terminals, this product provides protection as used in Telecommunication shelters previously. The unit has
been designed for simplicity and ease of cabling with cable management in mind.
SPECIFICATIONS
Model # DSD1402BR24/48
Item Number for Europe 702750
Nominal Voltage, Un 0 to 48 VDC
Max Cont. Operating Voltage, Uc 060 VAC & 60 VDC
Frequency 0-60 Hz
Max Discharge Current, Imax 40 kA 8/20 µs
Nominal Discharge Current, In 20 kA 8/20 µs
Protection Modes Differential & Common Mode
Technology MOV with thermal disconnect
Short Circuit Current Rating, Isc 25 kA
280 V @ 3 kA L-N
Voltage Protection Level, Up
600 V @ ln + to -
Mechanical flag
Status Change-over contact (Form C Dry) 250 V---/0.5 A,
Max 1.5 mm2 (#14 AWG) connecting wire
Dimensions H x D x W: mm (in) 90 x 68 x 36 (3.54 x 2.68 x 1.42)
Module Width 2M
Weight: kg (lbs) 0.15 (0.33)
Enclosure DIN 43 880, UL® 94V-0 thermoplastic, IP 20 (NEMA®-1)
≤ 25 mm2 (#4AWG) stranded
Connection
≤ 35 mm2 (#2AWG) solid
Mounting 35 mm top hat DIN rail
Back-up Overcurrent Protection 250 Agl if supply > 250 A
Temperature -40°C to 80°C (-40°F to 176°F)
Approvals CE, IEC® 61643-1
ANSI®/IEEE® C62.41.2-2002 Cat A, Cat B, Cat C
ANSI®/IEEE® C62.41.2-2002 Scenario II, Exposure 1, 20 kA 8/20 µs,
Surge Rated to Meet
2 kA 10/350 µs