Acknowledgements
1
11/13/2018
Objectives :
Systems required to be grounded,
◦ Permitted but not required to be grounded
◦ Systems not permitted to be grounded
Requirements for grounded systems
Installing and sizing grounded service - and
system conductors
System conductors that are required to be
grounded
Objectives :
Function of, and sizing, main and system bonding
jumpers
Grounding requirements for separately derived
systems
Grounding for two or more buildings supplied by
a feeder or branch circuit
Portable and vehicle-mounted generators
High-impedance grounded neutral systems
2
11/13/2018
3
11/13/2018
4
11/13/2018
5
11/13/2018
11
6
11/13/2018
Typical voltages:
208Y/120; 480Y/277;
575Y/332; 600Y/346
Typical voltage is
120/240-volt, 3-phase, 4-
wire
7
11/13/2018
8
11/13/2018
18
9
11/13/2018
19
20
10
11/13/2018
Ungrounded systems
are grounded through
distributed
capacitance when
insulated conductors
are installed in metal
enclosures.
11
11/13/2018
Marking Requirement
250.21(C) Marking. Ungrounded systems shall be
legibly marked “Caution Ungrounded System Operating
__X___ Volts Between Conductors” at the source or
first disconnecting means of the system. The marking shall
be of sufficient durability to withstand the environment
involved.
Additionally -408.3(F)(2) Panelboards -Ungrounded
Systems.
“Caution Ungrounded System Operating _____ Volts
Between Conductors”
24
12
11/13/2018
13
11/13/2018
14
11/13/2018
15
11/13/2018
A premises wiring
system supplied by a
grounded ac service
must have a grounding
electrode conductor
connected to the
grounded service
conductor at each
service per
250.24(A)(1) - (A)(5)
250.24(A)(1) General
16
11/13/2018
17
11/13/2018
A single grounding
electrode connection to
the tie point of dual-fed
services is permitted
18
11/13/2018
37
Feeders
19
11/13/2018
Equipment grounding
conductor connects
to enclosure
EG: If equipment is
grounded to the neutral
past the service, a loose
neutral connection will
result in a shock hazard if
a ground fault occurs
20
11/13/2018
An unspliced main
bonding jumper is
only required in one
section of an assembly
listed for use as
service equipment
Usually furnished by
manufacturer
21
11/13/2018
1000V or less
Run with
ungrounded
conductors.
Not smaller
than 102 C 1
22
11/13/2018
Grounded service
conductor required to
be bonded to each
service disconnecting
means for 1-phase and
3-phase service
disconnects
46
Copyright © Cengage Learning
23
11/13/2018
An Exception to 250.24(C)
Grounded service
conductor only
required to be bonded
to one section of listed
service equipment
consisting of more than
one service
disconnecting means
48
24
11/13/2018
49
50
25
11/13/2018
26
11/13/2018
Example
350 kcmil aluminum service lateral conductors in
each conduit
53
Example
3/0 AWG copper conductors to 200 ampere
service disconnect
54
27
11/13/2018
More Requirements
For service-entrance conductors larger than
1100 kcmil copper or 1750 kcmil aluminum, the
grounded system conductor must be not smaller
than 12½ percent of the area of the largest
service-entrance phase conductor
55
28
11/13/2018
Example
Go to Table 8 of Chapter 9
57
Example
58
29
11/13/2018
Example
For ungrounded conductors larger than 1100 kcmil
copper or 1750 kcmil aluminum
59
30
11/13/2018
61
31
11/13/2018
63
32
11/13/2018
65
33
11/13/2018
Results in “case
ground”
68
34
11/13/2018
Typically 120-volt
systems
2. Single-phase, 3-wire –
the neutral conductor
Typically 120/240 volt,
1-phase, 3-wire
70
Copyright © Cengage Learning
35
11/13/2018
71
Copyright © Cengage Learning
4. Multiphase systems
where one phase is
grounded – one phase
conductor
72
Copyright © Cengage Learning
36
11/13/2018
5. Multiphase systems in
which one phase is used
as in (2) Single phase –
the neutral conductor
73
Copyright © Cengage Learning
Perform identical
functions
37
11/13/2018
250.28(A) Material
Permitted to be of
copper or other
corrosion-resistant
material
Permitted to consist
of a wire, bus, screw
or similar suitable
conductor
76
38
11/13/2018
May be acceptable at
disconnecting means for
separately derived
system
250.28(B) Construction
Where a main
bonding jumper is a
screw only, it is
required to have a
green finish that is
visible with the screw
installed
39
11/13/2018
250.28(C) Attachment
79
80
40
11/13/2018
81
82
41
11/13/2018
42
11/13/2018
85
86
43
11/13/2018
87
44
11/13/2018
89
90
45
11/13/2018
Autotransformers
Autotransformer
has a conductor
that is common to
both primary and
secondary
Cannot be a
separately derived
system
46
11/13/2018
93
47
11/13/2018
If Bonding jumper is
furnished with listed
service equipment -
permitted without
calculation of size
48
11/13/2018
250.30(A)(1) Ex. 2
Bonding jumper at
both source and
first overcurrent
device permitted
where a parallel
path is not
established
49
11/13/2018
99
100
50
11/13/2018
102
51
11/13/2018
103
104
52
11/13/2018
105
10
Copyright © Cengage Learning
6
106
53
11/13/2018
Table 2-3
Wiring NEC
Size Max OCP Length
Method Reference
6 ft 250.118
FMC All 20 A
(1.8 m) (5)
6 ft 250.118
LFMC 3/8 & ½ 20 A
(1.8 m) (6)
¾ thru 6 ft 250.118
LFMC 60 A
1¼ (1.8 m) (6)
Larger Not Not 250.118
LFMC
than 1¼ permitted permitted (6)
107
10
Copyright © Cengage Learning
8
108
54
11/13/2018
Table 250.102C1
110
55
11/13/2018
56
11/13/2018
Primary purpose is
bonding electrical
structures or
equipment that is
likely to become
energized
Connect grounded
conductor of
separately derived
system to grounding
electrode
Connect at same
point where system
bonding jumper is
connected
57
11/13/2018
Example
115
58
11/13/2018
Example
117
Common GEC
Common grounding
electrode and tap conductors
permitted
59
11/13/2018
119
120
60
11/13/2018
250.30(A)(6)(c) Connections
250.30(A)(6)(c) Connections
¼” thick, 2” wide,
Sufficient length for
terminations
61
11/13/2018
123
124
62
11/13/2018
126
63
11/13/2018
64
11/13/2018
65
11/13/2018
Connect in accordance
with 250.32(B) or (C)
If no grounding
electrodes, install per
250.50
66
11/13/2018
Table 2-4
208Y/120 V, 3-
208Y/120** 3 or 4
phase, 4-wire
*Considered a multiwire branch circuit
** See 310.15(B)(5) for the rules on when a neutral is
considered a current-carrying conductor
134
67
11/13/2018
68
11/13/2018
250.32(B)(1) Exception:
Grounded Systems
137
Neutral to
grounding
electrode
69
11/13/2018
139
250.32(B)(2) Supplied by
Separately Derived System
(b) Without Overcurrent Protection. If overcurrent protection
is not provided where the conductors originate, the
installation shall comply with 250.30(A). If installed, the
supply-side bonding jumper shall be connected to the
building or structure disconnecting means and to the
grounding electrode(s).
140
70
11/13/2018
141
Install equipment
grounding conductor
71
11/13/2018
143
72
11/13/2018
145
73
11/13/2018
148
74
11/13/2018
Break to avoid
parallel path
Or do not bond here to avoid
parallel path
Copyright © Cengage Learning
150
75
11/13/2018
76
11/13/2018
153
154
77
11/13/2018
15
Copyright © Cengage Learning
6
156
78
11/13/2018
157
Normal service
conditions
79
11/13/2018
Example:
800 ampere overcurrent device with 2 600kcmil
copper conductors in parallel from generator to
distribution panelboard
160
80
11/13/2018
Permitted where:
1. Qualified persons
service the installation
162
81
11/13/2018
163
System neutral
conductor is not
permitted to be
connected to ground
except through the
grounding impedance
Provides “controlled”
return path
82
11/13/2018
165
Equipment bonding
jumper to be an
unspliced conductor
83
11/13/2018
167
84
11/13/2018
Questions?
169
85