Date: August 2017

Technical Specification :
PVS980-58 2000kVAK+Option Codes
Option Codes :
K475+F296+F263+F304+12H382+F300+F305+G420+G417+G415+G410+G429+Q983+P902+P928+P945

Input (DC side)


Maximum allowed PV-field power (PPV,max) [kWp] 3200
DC range, mpp (UDC, mpp) @ 35 °C (95 °F) [V] 935…1500
(@ Snom) @ 50 °C (122 °F) [V] 935…1100
Maximum operational DC voltage range [V] 935…1500
Maximum DC voltage (Umax (DC)) [V] 1500
Number of MPPT trackers 1
Number of DC inputs 10

Output (AC side)


Max power (PMAX (AC)) @ 35 °C [kW] 2200
Nominal power (SN (AC))@ 50 °C [kW] 2000
Power Factor (CosØ ) 1
Power factor range 0…1 (leading and lagging)
Nominal AC current (IN (AC)) [A] 1750
Maximum AC current (IMAX (AC)) [A] 1925
Nominal AC voltage(UN (AC)) [V] 660 (±10%)
Output frequency [Hz] 50 (±10Hz)
Harmonic distortion, current [%] <3
Distribution network type on inverter terminals 3Phase , 3Wire, IT Type

Efficiency
Maximum efficiency [%] ~98.8
CEC [%] ~98.5
Euro efficiency [%] ~98.6

Power consumption
Own consumption in operation (max) [W] ~ 2500
Own consumption in stand-by [W] ~ 225

Dimensions and weight


Depth [mm] ~ 1519
Width [mm] ~ 3180
Height [mm] ~ 2366
Total weight [kg] ~ 3850

Environmental limits
Degree of protection Outdoor, IP66 / IP56*
Ambient temp. range, nominal ratings [°C] -20 ...+50
Ambient temp. range, storage [°C] -40 ...+70
Max ambient temperature, operational [°C] +60
Relative humidity [%] 5 ... 100
Nominal altitude a.s.l. [m] 1000
Max altitude (with power derating) [m] 4000
Max noise level at Rated Output Power [dB(A)] < 85

* Excluding under-pressure testing, IP56 with under-pressure , Inverter has Internal mechanism that prevent under-pressure inside the cabinet.

Confidential
Technical Specification may be given only to persons that must receive this information in order to perform their duties in
connection with the pv project in which the inverters are installed.
Date: August 2017

Protection & Features ( Including Option Codes selected ) ,


Option Codes :
K475+F296+F263+F304+12H382+F300+F283+F305+G420+G417+G415+G410+G429+Q983+P902+P928+P945
DC Reverse Polarity Protection
PV Insulation & Ground fault monitoring
Negative DC grounding kit ( +F283)
DC Grounding with Grounding Bypass Resistor ( +F304)
DC surge protection (type I+2) )(+F300)
DC Overvoltage Protection
Isolator switch on the DC side (+F305)
10 fused protected DC inputs , 400A Fuse / Input at positive Poles only ( +12H382)
DC input current monitoring (+G417)
Bottom connected cable terminals for DC connection.

Fixed Type Motorized , Remote Control AC breaker (+F296)


AC surge protection , type I+2 (+F263)
Grid Monitoring
Overcurrent Protection
AC & DC Short circuit Protection
Sync Loss Protection
AC Undervoltage & Overvoltage Protection
Over-Temperature Protection.
Anti-Islanding Protection.
Cooling System Failure Protection

Grid Support Functions:


A. Grid monitoring (including anti-islanding)
B. FRT Support ( LVRT , HVRT ,FqRT)
C. Active Power Curtailment ( Based on User set points in % , Frequency Based , Network Voltage Based)
D. Reactive power compensation ( Also at Night)

Bottom connected cable terminals for AC connection

Protected supply for (external) auxiliary power transformer , IEC 32A Fuse ( +G429)
Internal aux. power transformer. (+G415)
1-Phase 2 kW Customer auxiliary output from terminal block (+G410)
Aux. power LVRT capability (buffering)

Communication port for the maintenance tool.


Control panel
Ethernet Adaptor (Ethernet, Modbus/TCP, Profinet) 2Port (+K475)
Smoke Alarm device inside the Inverter (+Q983)
Extended Warranty 60/66 Months (+P928)
Heat Run Test at Factory room temperature ( +P945)

Applicable Standards

EMC Compliance : Yes , CE conformity according to LV and EMC directives


CE Conformity : Yes
IEC Conformity : IEC62109-Part 1& 2 ,IEC61000-6-2,IEC61000-6-4, IEC61727, IEC62116, IEC61683 ,
IEC60068-2 , IEC60529.

Confidential
Technical Specification may be given only to persons that must receive this information in order to perform their duties in
connection with the pv project in which the inverters are installed.
Date: August 2017

Confidential
Technical Specification may be given only to persons that must receive this information in order to perform their duties in
connection with the pv project in which the inverters are installed.

You might also like